sensor, which compensates for ageing effects, is highly insensitive to pollution and offers outstanding long term stability.

Similar documents
USER S GUIDE. EE210 - Humidity and Temperature Transmitter for demanding Climate Control Applications GENERAL

EE160 - Humidity and Temperature Transmitter for HVAC Applications

USER S GUIDE. EE211 - Heatead Humidity and Temperature Transmitter for High Humidity Applications GENERAL ASSEMBLY SCOPE OF SUPPLY CAUTION

EE671 - Miniature Air Flow Transmitter

EE210. Humidity and Temperature Transmitter for Demanding Climate Control. Applications. Features. 36 v2.5 / Modification rights reserved EE210

EE211. Humidity and Temperature Transmitter for Continuous High Humidity. Features. 42 v1.3 / Modification rights reserved EE211 EE211

In order to minimize the impact of rain, snow, ice and solar radiation on the measurement the EE33-M must be mounted inside a radiation shield.

EE310. High-End Humidity and Temperature Transmitter for Demanding Process Control. Typical applications. Features EE310 EE310

EE310. High-End Humidity and Temperature Transmitter for Demanding Process Control. Typical applications. Features EE310 EE310

EE870 Modular CO 2 Transmitter

EE80 Series. HVAC Room Transmitter and Switches for CO 2, Relative Humidity and Temperature EE80. Applications. Typical

HLX31 Series. Multifunctional Industrial Transmitter for Humidity / Temperature / Dew Point / Absolute Humidity... Model A. Model B.

EE360. High-End Moisture in Oil Transmitter. Typical applications. Features EE360 EE360. (+34)

EE32/33 Series. Humidity / Temperature Transmitter for High Humidity and Chemical Applications. Typical Applications. Features

Carbon Monoxide Sensor - ModBus

TPM 80. Dew Point Transmitter. Manual. BA_TPM80_e // V1.0 // technical data are subject to change

EE210. Humidity and Temperature Transmitter for Demanding Climate Control Applications. Features. Applications

CAEL-DP Series Dew Point Transmitter for Industrial Control

Environmental Conditions C - remote sensing probe up to 120 C (248 F)

Manual EE355. Dew Point Transmitter down to -60 C Td. BA_EE355_e // V1.3 // technical data are subject to change

COMMERCIAL. VAM24-90-(A) Series Installation Instructions

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

RXTH DUAL ROOM SENSOR / SWITCH

Output signal. 22DTM-16 BACnet DC V, DC V. Electrical data Power supply DC V, ±10%, 0.3 W

EE35. Industrial Transmitter for Dew Point Measurement. Autocalibration. Installation. Alarm Output. Integrated power supply. Typical Applications

Manual EE371. Dew Point Transmitter / Switch down to -60 C Td. BA_EE371_e // V2.0 // technical data are subject to change

Instruction Manual. T3110 T3110L T3110Ex

EasyIO FW 08VUser Reference

MF RD700. PEGODA Contactless Smart Card Reader READER COMPONENTS. Preliminary Product Specification Revision 2.0 PUBLIC. July2002

Programmable transmitter of temperature, relative humidity and other derived humidity values with RS485 serial output Instruction Manual

Operation manual EE310. Humidity/Temperature Transmitter. BA_EE310_e // V2.1 // Technical data subject to change //

Programmable transmitter of temperature, relative humidity and other derived humidity values with 0 to 10 V outputs Instruction Manual

PACKAGE CONTENTS SPECIFICATIONS

HARDWARE GUIDE. Water Loop Controller C1000 Series. Specifications and Operational Guide

Output Signal. Temperature 22DTH-56M BACnet DC V, DC V. Electrical Data Power Supply DC V, ±10%, 0.7 W

T3311, T3313, T3411 T7310, T7410. Instruction Manual

ALTA Serial Modbus (RTU/ASCII) Gateway Quick Start Guide

IEC-0101FT Industrial 10/100TX to 100M-FX Slim Type Converter User Manual

Operation Manual for Cloud 3700F Version 0

Hypercable injecteur HPOE - Industrial IEEE 802.3at Gigabit PoE Injector. User Manual. v.1.0 Jun Mail :

RXTP ROOM TEMPERATURE

6 10/100/1000TX + 2G Fiber Industrial Ethernet Switch User Manual

Mini Speaker. CWA BT300 Product Information Guide

D Series Sensors for Humidity and Temperature Measurement With calibrated dmodul

4-port 10/100TX + 1 or 2-port 100FX Industrial Switch. User Manual

Dual differential pressure sensor For ventilation and air-conditioning Model A2G-52

DXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions

Lantech. IPES /100TX with 4 PoE Injectors 24~48VDC Industrial Switch. User Manual

The Solution. Multi-Input Module IMPORTANT: READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION

3G Cell Modem Upgrade

Hardened Ethernet to VDSL2 Extender. User Guide. Revision History. Industrial Ethernet to VDSL2 Extender with Wide Operating Temp. Rev.1.

AT-VLI-102DRS. Manual. ATAL B.V. Ampèrestraat NL-1446 TR PURMEREND. Postbus 783 NL-1440 AT PURMEREND T (+31) F (+31)

10/100TX to 100FX w/ 1 PoE Injector Industrial Media Converter User Manual

Blackwire C610 Blackwire C620

TEMPERATURE AND HUMIDITY TRANSDUCER P18 TYPE USER S MANUAL

Output Signal. 22DTM-16 BACnet DC V, DC V. Electrical data Power Supply DC V, ±10%, 0.3 W

User's Guide. Video Borescope Inspection Camera. Model BR70

& I CODE CL RD701. PEGODA Contactless Smart Card Reader READER COMPONENTS. Product Specification Revision 3.1 PUBLIC.

2012 Dealer Price List

Charging Pad / Charging Stand

Control different load types with one device

HARDWARE MANUAL ENGLISH

This simple chassis houses one media-converter module and features an external AC power supply and also a terminal block for DC power input.

IEEE BASE-T IEEE 802.3u 100BASE-TX. ITU-T -G.993.1(VDSL) -G compatible

LNP-0602 series. 6-port Industrial PoE+ Unmanaged Ethernet Switches 4*10/100Tx (30W/Port) + 2*100Fx. User Manual

EE210. Humidity and Temperature Transmitter for Demanding Climate Control Applications. Features. Applications

4 10/100/1000T Mini-GBIC with 4 IEEE 802.3at High Power PoE Industrial Wide Temperature Switch. User Manual SISTP LRT

PWRguard PLUS Spring City Drive Waukesha, WI

IWMR-3002 Industrial Multifunction VPN Router w/up to 2x WiFi 11ac + up to 2 LTE 4G + 2/4 serial ports + 2 Gigabit Ethernet Switch

MONOPRICE. Blackbird 4K Pro 1x2 Ultra Slim HDMI Splitter. User's Manual P/N 21612

HD40H(X) Performance Series Camera. User Guide

Wireless Sensor Adapter (WSA10) Installation Instructions

Cube Camera with Fixed Lens Hardware Manual D11, D12. Ver. 2013/05/17

RS-FS-N01 Wind speed transmitter user's Guide (485type)

USER MANUAL. Model NAME : Anker USB 2.4G Wireless Vertical Mouse MODEL NO. : A VERSION : 0.1 DATE : A User Manual VER: 0.

Thermal-Sensing Security Cameras

TRANSDUCER T4311, T4411

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W

LNP series. 5-port Industrial PoE+ Unmanaged Ethernet Switches 4*10/100Tx (30W/Port) + 1*10/100Tx, 12~36VDC Input.

Mounting and Operating Instructions (Simple Programming) Art.No..: , published: 10/2003

8-port 10/100TX + 2-Port 10/100/1000T/100/1000 SFP Combo with 8 PoE Injectors Industrial Ethernet Switch User Manual

T2314, T2414. Instruction Manual

1101 Universal Transmitter

Serial Port Plug - F2M01SXA Brief Datasheet. Features. Applications. General Description. Provides transparent RS-232 serial cable replacement.

KCD-HP. KCD-HP200x, 300X. [Figures] Top : 1% Sensor probe Bottom left : 10% / 20% Sensor probe Bottom right : Holding bracket(optional) Measurement

DMT345 and DMT346 Dewpoint Transmitters

NV-CTP36-V2 Color Touch Screen Installation Guide

T2314, T2414. Instruction Manual

10/100/1000T to Mini-GBIC Industrial Switch Converter 10/100/1000T to 1000SX/LX Industrial Switch Converter. AMG9011G-H (-40 to 75C) User Manual

Optoma NuForce NuForce STA200 STA200 Stereo Amplifier Power Amplifier UserUser s Manual s Manual ALSTANZZ

CDD ModBus Carbon Dioxide Detector

Humidity goes Digital

5/8 Port Gigabit Ethernet Switch

PACKAGE CONTENTS SPECIFICATIONS PRODUCT DIAGRAM

PICS_EE800D // v1.2 / Technical data subject to change. PICS EE800D BACnet Protocol Implementation Conformance Statement

UPort TM 200/400 Series Quick Installation Guide

InnoMedia ipbx-400. Quick Install Guide.

Please Read Instruction Carefully Before Installation! Figure 1: A/CO2-DUCT

INSTALLATION GUIDE DM-20 English Version 1.10 EN DM20 V1.10A

Temperature, humidity and pressure regulator. with RS485 serial output H0430 H3430 H3431 H3433 H3437 H4431 H7430 H7431. Instruction Manual

Transcription:

USER S GUIDE EE800 - HVAC Room Transmitter for CO 2, Temperature and Relative Humidity GENERAL EE800 combines CO 2, temperature (T) and relative humidity (RH) measurement in one device with modern design. Additionally, it calculates the dewpoint temperature (Td). EE800 with analogue outputs features an optional passive T sensor, while at EE800 with RS485 additional physical quantities are available on the Modbus RTU and BACnet MS/TP interface: absolute humidity (dv), mixing ratio (r), enthalpy (h), frost point temperature (Tf) and water vapor partial pressure (e). It incorporates the E+E dual wavelength NDIR CO 2 sensor, which compensates for ageing effects, is highly insensitive to pollution and offers outstanding long term stability. EE800 is available with: Three voltage outputs (0-5 V or 0-10 V) for CO 2, T and RH or Td, with an optional passive T output, or Two analogue outputs (0-5 V, 0-10 V or 4-20 ma ) for CO 2 and T, with an optional passive T output, or Modbus RTU or BACnet MS/TP interface, where all physical quantities, as above, are available according to the model ordered. CAution The device shall not be exposed to extreme mechanical or thermal stress. The sensing cell shall not be exposed to any mechanical stess. CO 2 Sensing Cell The electronics board is an ESD sensitive device, please handle it accordingly and avoid touching it during installation. Please allow min. 5 minutes warm up time for the device to reach the specified measurement performance. DIMENSIONS / MOUNTING The electronics of EE800 are located in the front cover, which can be easily snapped on/off once the back cover is fixed onto the wall ( D = mounting holes) and wired. B Opening the enclosure Press to release the latch A till the enclosure can be opened. Use a screwdriver or a pen. Closing the enclosure Set the front cover into flute B, rotate it like C and press it onto the back cover till the latch A snaps in. A D Important In order to protect the front cover and the electronics from typical construction site pollution (such as painting of the walls) the front cover should be snapped on only after the construction works are completed. C As EE800 is generally mounted onto a conduit box, for accurate measurement results it is important to tighten the conduit box for avoiding false air ingress (along the electrical tubes inside the wall) into the EE800 enclosure.

Connection diagram EE800 Voltage Output configuration connector Output: 0-5 V 0-10 V EE800 Current Output configuration connector Output: 4-20 ma EE800 Digital Interface Connection on the electronics board. Screw terminals appropriate for daisy-chain wiring configuration connector termination resistor MODBUS AND BACNET HARDWARE The bus termination shall be realized with 120 Ohm resistor, switch on the board. Very important: For proper function the power supply must be strong enough to ensure supply voltage within the specified range (see technical data) at any time and at all devices in the bus. This is particularly relevant when using long and thin cables which can cause high voltage drop; please note that a single EE800 requires peak current of 150mA. ADDRESS SETTINGS Address Switch 1 0 Slave setting via EE-PCS Product Configuration Software: All switches at position 0 has to be set via configuration software (factory setting: 241...Modbus / 3...BACnet). Example: Slave is set via configuration software. Address Switch 1 0 Slave setting via Dip-Switch: Setting the Dip-Switch to any other than 0 overwrites the slave set via configuration software. Example: Slave set to 11 (=00001011 binary).

BACNET INFOS Please see PICS (Product Implementation Conformance Statement) - available on www.epluse.com/ee800) MODBUS-MAP The measured values are saved as a 32Bit float value from 0x19 to 0x2F. The factory setting for the Slave-ID is 241 as an integer 16Bit value. This ID can be customised in the register 60001 (0x00) (value margin 1-247 permitted). The serial number as ASCII-code is located at register 30001-30008. The firmwareversion is located at register 30009. The required units (metric or non-metric) must be selected in the Ordering guide, see EE800 data sheet. FLOAT (read register): 30026 0x19 temperature [ C], [ F] 30028 0x1B relative humidity [%] 30030 0x1D water vapour partial pressure [ C], [ F] 30032 0x1F dew point temperature [ C], [ F] 30036 0x23 absolute humidity [g/m³], [g/ft³] 30038 0x25 maxing ratio [g/kg], [gr/lb] 30040 0x27 specific enthalpy [kj/kg], [BTU/lb] 30042 0x29 frost point temperature [ C], [ F] 30046 0x2D CO 2 Raw* [ppm] 30048 0x2F CO 2 [ppm] * Please Note: Only for special applications where faster response time is necessary. Please contact your E+E Sales representative. Protocol setting: Address, baudrate, parity and stop bits can be set via: 1. Configurator software (available on www.epluse.com/) 2. Modbus protocol (please see Application Note Modbus (available on www.epluse.com) INFO (read register): INTEGER (write register):* 30001 0x00 Serial number 30009 0x08 Firmware version 60001 0x00 Slave-ID (modbus e) 60002 0x01 Modbus protocol settings* *For Modbus protocol setting please see Application Note Modbus (www.epluse.com) SETUP and ADJUSTMENT The EE800 transmitter is ready to use and does not require any configuration by the user. The factory setup of EE800 corresponds to the type number ordered. For ordering guide please see data sheet at www.epluse.com/ee800. If need, the user can change the factory setup by using the optional Configuration Adapter Cable HA011066 and the E+E Product Configuration Software (EE-PCS). The user can assign physical quantities to the analogue outputs, set the scaling of the outputs, change the display settings and perform one or two point adjustment for CO 2, RH and T. The free E+E Product Configuration Software (EE-PCS) and can be downloaded from www.epluse.com/configurator. Configuration Adapter Cable HA011066

TECHNICAL DATA (Modification rights reserved) Measured values CO 2 Measurement principle Dual Wavelength Non-Dispersive Infrared Technology (NDIR) 0...2000 / 5000 ppm Accuracy at 25 C (77 F) 0...2000 ppm: < ± (50 ppm +2 % of measuring value) and 1013 mbar 0...5000 ppm: < ± (50 ppm +3 % of measuring value) Response time τ 63 typ. 110 s Temperature dependence typ. 1 ppm CO 2 / C (-20...45 C) (-4...113 F) Calibration interval 1) >5 years Temperature Accuracy 2) at 20 C (68 F) Relative Humidity Accuracy at 20 C (68 F) Calculated values Dewpoint temperature 3) Accuracy ±0.3 C (±0.54 F) RS485 digital interface; ±0.3 C (±0.54 F) voltage output / ±0.7 C (±1.26 F) current output 10...90 % rh ±3 % RH (30...70 % RH) ±5 % (10...90 % RH) -30...55 C (-22...131 F) < ±2 C (3.6 F) for T - Td < 25 C (45 F) < ±3 C (5.4 F) for T - Td < 30 C (54 F) Outputs Analogue 0...2000 / 5000 ppm 0-5 V / 0-10 V -1 ma < IL < 1 ma 4-20 ma R L < 500 Ohm Digital Interface RS485 with max. 32 devices on one bus Protocol Modbus RTU or BACnet MS/TP Temperature passive please see ordering guide (only in combination with analogue outputs) General Supply voltage 24 V AC ±20 % 15-35 V DC Current consumption Analogue typ. 14 ma + output current; peak 0.3 A for 0.3 s Digital bias: typ. 11 ma at 15 35 V DC typ. 30 ma at 24 V AC ±20 % peak: 150mA at 15 35 V DC, 24 V AC ±20 % Housing (polycarbonate) US Version: UL94V-0 approved / EU Version: UL94HB approved Protection class IP30 Display 4) LC display: alternating CO 2 / T / RH or Td Electrical connection screw terminals max. 1.5 mm 2 (AWG16) Electromagnetic compatibility EN61326-1 EN61326-2-3 FCC Part 15 ICES-003 ClassB Working / Storage T-range 0...90 % RH (non condensing) / -20...60 C (-4...140 F) 1 Under normal operating conditions. 2 U V = 24 V DC and R L = 250 Ω for version with current output 3 Additional calculated physical quantities available only on the Modbus and BACnet interface: absolute humidity, mixing ratio, enthalpy, frost point temperature and water vapor partial pressure. 4 Analogue outputs: The display shows the physical quantities selected for the outputs. Digital interface: The display shows CO2 and T for Model M11 and CO2, T, and RH for Model M12 ACCESSORIES USB configuration adapter Product configuration software HA011066 EE-PCS (free download: www.epluse.com/configurator)

SCOPE OF SUPPLY Model EE800 EE800 with RS485 interface EE800 Transmitter according ordering guide Mounting kit Test report according to DIN EN10204-2.2 Quick Guide - EE800 with digital interface USA FCC notice: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the installation manual, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: - Reorient or relocate the receiving antenna. - Increase the separation between the equipment and receiver. - Connect the equipment into an outlet on a circuit different from that to which thereceiver is connected. - Consult the dealer or an experienced radio/tv technician for help. CANADIAN ICES-003 Issue 5: CAN ICES-3 B / NMB-3 B Informationen +43 7235 605 0 / info@epluse.com Langwiesen 7 A-4209 Engerwitzdorf Tel: +43 7235 605-0 Fax: +43 7235 605-8 info@epluse.com www.epluse.com LG Linz Fn 165761 t UID-Nr. ATU44043101 Place of Jurisdiction: A-4020 Linz DVR0962759 BA_EE800_e // v1.1 // Modification rights reserved