PSR-PS21. SIL coupling relay. Data sheet. 1 Description

Similar documents
PSR-PC20. SIL coupling relay. Data sheet. 1 Description

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

PSR DC/ESP4/2X1/1X2

PSR UC/ESAM4/3X1/1X2/B

SAFETY RELAY YRB-4EML-31S MAIN FEATURES

ETD-BL-1T-OFF-CC- 10S

MINI MCR-SL-CVS NC

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description

MINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

MINI MCR-SL-PT100-UI. Active resistance thermometer measuring transducer. Data sheet. 1 Description

PSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

MACX MCR-SL-(2)I-2)I-ILP(-SP)

MINI MCR-SL-PT100-UI-200

ETD-BL-1T-230(-PT) Multifunctional time relay with various functions and adjustable times. Data sheet. 1 Description

MINI-PS AC/10-15DC/8

MACX MCR-EX-SD LP(-SP)

MINI MCR-2-U-I4(-PT) 3-way signal conditioner. Data sheet. 1 Description

Redundancy Module QUINT-DIODE/40

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B

QUINT-PS-3x AC/24DC/10

QUINT-BUFFER/24DC/24DC/40

MACX MCR-EX-SL-NAM-R(-SP)

TRIO-DIODE/12-24DC/2X10/1X20

MACX MCR-EX-SL-NAM-2RO(-SP)

ELR H3-IES-PT- 24DC/500AC-...

QUINT-PS/ 1AC/24DC/ 5

MACX MCR-EX-SL-2NAM-T(-SP)

PHOENIX CONTACT - 05/2007

RAD-DAIO6-IFS. I/O extension module, 1 analog input/output, 2 digital wide-range inputs/outputs. INTERFACE Data sheet.

PHOENIX CONTACT - 07/2006

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

QUINT-PS/ 1AC/24DC/20/CO

MACX MCR-EX-SL-RPSSI-I(-SP)

QUINT-PS AC/24DC/10

PHOENIX CONTACT Features

STEP-PS/1AC/24DC/1.75

1-Phase Power Supply, Primary Switch Mode for Use in Potentially Explosive Areas QUINT-PS AC/24DC/5/EX

UNO-PS/1AC/12DC/30W. Primary-switched power supply unit. Data sheet. 1 Description

IB IL 24/48 DOR 2/W-XC-PAC

PHOENIX CONTACT - 12/2007

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

Safety module - PSR-SCP- 24DC/TS/S

PI-EX-ME-2NAM/COC-24VDC

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PHOENIX CONTACT - 02/2008

MINI MCR-SL-MUX-V8-FLK 16

PI-EX-ME-2NAM/COC-120VAC

Safety relay emergency stop/protective door, 24VDC/AC, 4 enabling paths

MACX MCR-EX-SL-RPSS-2I-2I

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1

TRIO-PS/1AC/24DC/20. Extract from the online catalog. Order No.:

QUINT-DC-UPS/24DC/40. Extract from the online catalog. Order No.:

STEP-PS/1AC/24DC/2.5. Extract from the online catalog. Order No.: DIN rail power supply of 24 V DC/2.5 A, primary switched, single phase.

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

FL MC 2000E (SM40) LC

QUINT-DC-UPS/24DC/10. Extract from the online catalog. Order No.:

MINI-DC-UPS/12DC/4. Extract from the online catalog. Order No.:

ASI QUINT /2.4 EFD

QUINT-PS/24DC/48DC/ 5

ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors

EMD-SL-LL-230. Electronic monitoring relay for level monitoring of conductive liquids. INTERFACE Data sheet _en_04. 1 Description.

QUINT-DC-UPS/24DC/10. Extract from the online catalog. Order No.:

DeltaV Bulk Power Supplies

Extract from the online catalog

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Operating instructions. Speed monitor D / / 2014

DeltaV Bulk Power Supplies

PHOENIX CONTACT Pin. SUBCON-PLUS M ARCNET, MULTI/MININET (B&R), SYSTEM 2003 (B&R), P-NET SUCONET K1, K2 (EATON/Moeller),

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

Power supply CP-C 24/5.0

MINI MCR-SL-UI-2I-NC. Extract from the online catalog. Order No.:

PHOENIX CONTACT - 01/2007

ABL1REM24025 regulated SMPS - single phase V input - 24 V output - 60 W

PSM-ME-RS485/RS485-P. Repeater for RS wire bus systems. Data sheet. 1 Description

MINI MCR-SL-PT100-UI(-SP)(-NC)

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

SUBCON-PLUS-PROFIB...

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

Power Supply HARTING pcon

Easy Analog RNB130. Technical Information. Primary switched-mode power supply

Safety relay emergency stop/protective door, 230VAC, 3 enabling paths

Uninterruptible power supply - TRIO-UPS/1AC/24DC/

Uninterruptible Power Supply Unit for Universal Use QUINT-DC-UPS/24DC/40

Safety relay emergency stop/protective door, 24VDC/AC, 3 enabling paths

onlinecomponents.com

PHOENIX CONTACT - 10/2009

RTU500 series Data Sheet Power Supply CP-E 24/2.5

Operating instructions. Standstill monitor A / / 2011

PHOENIX CONTACT - 01/2008

Electronic timer CT-ARS.11

PHOENIX CONTACT - 11/2007. This data sheet is only valid in association with the IB IL SYS PRO UM E user manual.

Transcription:

SIL coupling relay Data sheet 106253_en_00 PHOENIX CONTACT 2015-03-13 1 Description Intended Use The SIL coupling relay can be used for power adaptation and electrical isolation in high and low-demand applications up to SIL 2 according to IEC 61508 as well as EN 61511. Using this module, circuits are interrupted in a safety-oriented manner. The category 3 device is designed for installation in zone 2 potentially explosive areas. The safety relay is equipped with an enabling current path and a confirmation current path that drop out without delay according to stop category 0 in accordance with EN 60204-1. By filtering the controller test pulses, premature failure of the safety relays is prevented. If an error occurs inside the module, the internal device input impedance is affected. As such with compatible, safe systems, the test pulses sent from the controller may be disrupted and the error can be reported back to the corresponding digital output without any additional wiring effort. Features SIL 2 coupling relay for safety-related switching off Can be used in high and low-demand applications Approved for Class I, Zone 2 applications Easy proof test: - Active error acknowledgment via A1 - Visually on the device - Evaluation of the force-guided N/C contact Integrated DCS test pulse filter Low inrush current 1 undelayed enabling current path 1 undelayed confirmation current path 1 digital signal output Fixed screw connection 6.8 mm housing width Controller-specific Termination Carrier available on request WARNING: Risk of electric shock Observe the safety instructions in the corresponding section! Make sure you always use the latest documentation. It can be downloaded from the product at phoenixcontact.net/products. This data sheet is valid for all products listed on the following pages.

2 Table of contents 1 Description... 1 2 Table of contents... 2 3 Ordering data... 3 4 Technical data... 3 5 Safety notes... 6 5.1 Installation in the Ex area (zone 2)... 7 5.2 Installation in areas with a danger of dust explosions... 7 6 Basic circuit diagram... 8 7 Derating... 8 7.1 Vertical mounting position... 8 7.2 Horizontal mounting position... 8 7.3 Mounting position with module front at the top... 9 8 Load curve... 9 8.1 Ohmic load... 9 9 Operating and indication elements... 10 9.1 Connection versions... 10 9.2 Connection assignment... 10 10 Mounting and connection... 11 11 Startup... 11 12 Proof test... 11 13 Calculating the power dissipation... 12 14 Application examples... 13 14.1 Application example 1 - SIL 2... 13 15 Revision history... 14 106253_en_00 PHOENIX CONTACT 2

3 Ordering data Description Type Order No. Pcs. / Pkt. Coupling relay for SIL 2 high- and low-demand applications, couples digital output signals to the I/O, 1 enabling current path, 1 confirmation current path, 1 digital signal output, safe state off applications, test pulse filter, fixed screw terminal block -1NO-1NC-24DC-SC 2700357 1 4 Technical data Hardware/firmware version HW/FW 00/-- (The technical data and safety characteristics are valid as of the specified HW/FW version.) Input data Rated control supply voltage U S 24 V DC -15 % / +10 % Rated control supply current I S typ. 45 ma Supply voltage 24 V DC -15 % / +10 % (Diagnostic supply voltage U D ) Input current 6 ma (at 21-A2 for U D ; depending on load + 100 ma at M1 and 22) Typical inrush current 400 ma ( t < 10 s at U s ) 2.5 A ( t < 20 s at U D ) Power consumption at U S Filter time typ. 1.08 W max. 2 ms (at A1-A2; test pulse width) 100 ms (at A1-A2; test pulse rate) Typical starting time with U s < 100 ms (when controlled via A1) Typical release time with U s < 35 ms (when controlled via A1) Recovery time 500 ms Maximum switching frequency 1 Hz Operating voltage display 1 x yellow LED Status display 2 x green LEDs Indication 1 x red LED Protective circuit Surge protection Suppressor diode Polarity reversal protection for rated control supply voltage and diagnostic supply voltage Output data Contact type Contact material Minimum switching voltage Maximum switching voltage Nominal current Limiting continuous current Maximum inrush current Inrush current, minimum Sq. Total current 1 enabling current path 1 confirmation current path AgSnO 2 (enabling current path) AgCuNi, + Au (confirmation current path) 10 V AC/DC (N/O contact) 20.4 V DC (N/C contact) 250 V AC/DC (N/O contact) 26.4 V DC (N/C contact) 6 A (N/O contact) 6 A (N/O contact) 100 ma (N/C contact) 6 A (N/O contact) 100 ma (N/C contact) 3 ma (N/O contact) 1 ma (N/C contact) 36 A 2 (see to derating) 106253_en_00 PHOENIX CONTACT 3

Output data Switching capacity min. Mechanical service life Output fuse 30 mw 10 x 10 6 cycles 6 A gl/gg (N/O contact) 4 A gl/gg (for low-demand applications) 150 ma fast blow (Confirmation current path) Alarm outputs Number of outputs 1 (digital, PNP) Voltage 22 V DC (U D - 2 V) Current max. 100 ma Maximum inrush current 500 ma ( t = 1 ms at U s ) Short-circuit protection no General data Relay type Electromechanically forcibly guided, dust-proof relay. Nominal operating mode 100% operating factor Degree of protection IP20 Min. degree of protection of inst. location IP54 Mounting type DIN rail mounting Mounting position vertical, horizontal, with front of module upward Assembly instructions See derating curve Dimensions (W/H/D) 6.8 x 93.1 x 102.5 mm Type of housing PBT yellow Clearances and creepage distances between the power circuits DIN EN 50178, EN 60079-15 Rated insulation voltage 250 V AC Rated surge voltage/insulation Safe isolation, 6 kv reinforced insulation from control circuit, start circuit, confirmation current path, signal output to the enabling current path; 4 kv/basic insulation between all current paths and housing Pollution degree 2 Surge voltage category III Connection data Connection method Screw connection Conductor cross section, solid 0.2 mm²... 2.5 mm² Conductor cross section, stranded 0.2 mm²... 2.5 mm² Conductor cross section AWG/kcmil 26... 12 Stripping length 12 mm Screw thread M3 Ambient conditions Ambient temperature (operation) -40 C... 65 C (observe derating) Ambient temperature (storage/transport) -40 C... 85 C Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing) Max. permissible humidity (storage/transport) Maximum altitude Shock Vibration (operation) 75 % (on average, 85% infrequently, non-condensing) max. 2000 m (Above sea level) 15g 2g Conformance / approvals Conformance Approvals UL, USA / Canada ( E140324 ) CE-compliant culus 106253_en_00 PHOENIX CONTACT 4

Conformance / approvals UL, USA / Canada ( E360692 ) Class I, Zone 2, AEx na nc IIC T4 / Ex na nc IIC Gc T4 X Shipbuilding GL applied for Functional Safety in accordance with IEC 61508 to SIL 2 Safety data Stop category according to IEC 60204 0 Safety parameters for IEC 61508 - High demand Equipment type Type A HFT 0 SIL 2 (< 15% of the overall SIL) PFH d 8.8 x 10-9 (4 A DC13; 5 A AC15; 8760 switching cycles/year) Demand rate < 12 Months Proof test interval 240 Months Duration of use 240 Months For use in high-demand applications, the diagnostics function must be implemented via the confirmation current path. Alternative illustration of the device as 1001 structure for process customers Equipment type Type A HFT 0 SIL 2 (< 15% of the overall SIL) Safe Failure Fraction (SFF) 99.18 % SD 494.66 FIT SU 79.10 FIT DD 494.66 FIT DU 8.80 FIT Total 1077.22 FIT MTBF 91.65 Years PFH 8.8 x 10-9 (4 A DC13; 5 A AC15; 8760 switching cycles/year) Safety parameters for IEC 61508 - Low demand Equipment type Type A HFT 0 SIL 2 (< 15% of the overall SIL) PFD avg 1.34 x 10-3 Proof test interval 20 Months Duration of use 240 Months Alternative illustration of the device as 1001 structure for process customers Equipment type Type A HFT 0 SIL 2 (< 15% of the overall SIL) Safe Failure Fraction (SFF) 81.2 % SD 0 FIT SU 794.1 FIT DD 0 FIT DU 183.8 FIT Total 977.9 FIT MTBF 99 Years PFD avg 8.06 x 10-4 (For T1 = 1 year) 106253_en_00 PHOENIX CONTACT 5

5 Safety notes WARNING: Risk of electric shock During operation, parts of electrical switching devices carry hazardous voltages. Before working on the switching device, disconnect the power. Please observe the safety regulations of electrical engineering and industrial safety and liability associations! Disregarding these safety regulations may result in death, serious personal injury or damage to equipment. Startup, mounting, modifications, and upgrades should only be carried out by a skilled electrical engineer! WARNING: Risk of automatic machine restart! For emergency stop applications, the machine must be prevented from restarting automatically by a higher-level control system. Protective covers must not be removed when operating electrical switching devices. WARNING: Danger due to faulty devices! The devices may be damaged following an error and correct operation can no longer be ensured. In the event of an error, replace the device immediately. Repairs to the device, especially if the housing must be opened, may only be carried out by the manufacturer or authorized persons. Otherwise the warranty is invalidated. WARNING: danger due to magnetic interference! Do not use the device in the vicinity of strong magnetic fields (e.g., caused by transformers or magnetic iron). The magnetic field strength of the environment must not exceed 30 A/m. NOTE: Risk of damage to equipment due to noise emissions When operating relay modules the operator must meet the requirements for noise emission for electrical and electronic equipment (EN 61000-6-4) on the contact side and, if required, take appropriate measures. NOTE: Risk of damage to equipment due to noise emissions This is a Class A product. In a domestic environment it may cause radion inteference, in which case the user may be required to take adequate measures. Only use power supply units with safe isolation and SELV / PELV in accordance with EN 50178/VDE 0160 (SELV / PELV). NOTE: Electrostatic discharge! The device contains components that can be damaged or destroyed by electrostatic discharge. When handling the device, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN 61340-5-1 and EN 61340-5-2. WARNING: Risk due to incorrect installation For reliable operation, the safety relay must be installed in housing protected from dust and humidity (IP54). Carry out wiring according to the application. Refer to the Application examples section for this. WARNING: Risk due to welded relay contacts A suitable and effective protective circuit is to be provided for inductive loads. This is to be implemented parallel to the load and not parallel to the switch contact. 106253_en_00 PHOENIX CONTACT 6

5.1 Installation in the Ex area (zone 2) Ambient temperature in hazardous areas (zone 2) WARNING: Explosion hazard The category 3 device is suitable for installation in the zone 2 potentially explosive area. It fulfills the requirements of EN 60079-0:2012+A11:2013 (IEC 60079-0:2011 6th ED.) and EN 60079-15:2010 (IEC 60079-15:2010 4th ED.). WARNING: Explosion hazard The device should be installed in a housing (control or distributor box) that fulfills the requirements of EN 60079-15:2010 (IEC 60079-15:2010 4th ED.) and at least IP54 (EN/ IEC 60529) degree of protection. WARNING: Explosion hazard The device must be used in no more than a pollution degree 2 environment as defined by EN/ IEC 60664-1. Observe the derating curves. Observe the special temperature conditions according to the rating plate. Output Ambient Temperature NO-contact 250 V AC / 24 V DC 6 A, Resistive B300, R300-20 C to 65 C DO-contact 24 V DC 100 ma Resistive 5.2 Installation in areas with a danger of dust explosions WARNING: Explosion hazard The device is not designed for use in atmospheres with a danger of dust explosions. WARNING: Explosion hazard When installing and connecting the supply and signal circuits observe the requirements of EN/ IEC 60079-14. Only devices suitable for operation in Ex zone 2 and the conditions at the application site may be connected to the circuits in zone 2. In potentially explosive areas, only connect and disconnect cables when the power is disconnected. WARNING: Explosion hazard The device must be stopped and immediately removed from the Ex area if it is damaged or was subject to an impermissible load or stored incorrectly or if it malfunctions. Only use category 3G devices (ATEX 94/9/ EC). 106253_en_00 PHOENIX CONTACT 7

6 Basic circuit diagram 7 Derating A1 21 13 7.1 Vertical mounting position PWR ERR DGN K1 K1 I TH² [A ² ] 40 36 30 24V DC 20 16 A2 M1 22 14 10 Figure 1 Block diagram 0 0,09 10 20 30 40 50 55 60 70 Key: Designation A1 A2 M1 Explanation +24 V control input with active error acknowledgment 0 V (GND) Signal output (PNP) 21 +24 V diagnostics input 22 Diagnostic output +24 V 13/14 Enabling current path, undelayed Confirmation current path 21/22 (N/C contact) is not an electrically isolated current path and may only be connected to a maximum voltage of 26.4 V in relation to A2. Figure 2 Derating curve - vertical mounting position with connected modules Expanded ambient temperature range (with no distance): up to +65 C Conditions: Max. rated control supply voltage 24 V DC Max. total current of the enabling current path 1 A 2 7.2 Horizontal mounting position I TH² [A ² ] 40 36 30 T [ C] A 20 10 4 0 Figure 3 10 20 30 40 50 60 70 T A [ C] Derating curve - horizontal mounting position with connected modules Expanded ambient temperature range (with no distance): up to +65 C Conditions: Max. rated control supply voltage 24 V DC Max. total current of the enabling current path 250 ma 2 106253_en_00 PHOENIX CONTACT 8

7.3 Mounting position with module front at the top 8 Load curve I [A ] 2 2 TH² 40 36 30 20 10 25 8.1 Ohmic load 0 0,16 10 20 30 40 50 55 60 70 Figure 4 T A [ C] Derating curve - mounting position with module front at the top and aligned modules Expanded ambient temperature range (with no distance): up to +65 C Conditions: Max. rated control supply voltage 24 V DC Max. total current of the enabling current path 250 ma 2 Figure 5 Relay load curve - ohmic load 106253_en_00 PHOENIX CONTACT 9

9 Operating and indication elements 9.1 Connection versions 1 Fixed screw connection 2 Snap-on foot for DIN rail mounting 1 The year the device was constructed can be found underneath the CE designation on the housing. APPROVALS HW/FW: 00/-- HW/FW: 00/-- Serial Serial No. No. xxxxxxxxxx xxxxxxxxxx 2 Warning Warning -- Do Do not not seperate seperate when when energized! energized! PWR AWG 26-12 0,2-2,5 mm 2 PHOENIX CONTACT GmbH & CO.KG Flachsmarktstrasse 8 32825 Blomberg, Germany 14 12 mm 0,5-0,6 Nm 5-7 lb In PWR Figure 6 Connection versions Figure 7 Year of manufacture of the device 9.2 Connection assignment Figure Designation Explanation 22 Diagnostic output +24 V 2 2 21 +24 V diagnostics input 2 1 A 2 A2 0 V (GND) A 1 A1 +24 V control input with active error acknowledgment PWR K1 ERR DGN PWR K1 ERR DGN Power LED (yellow) Status indicator safety circuit; LED (green) Error LED (red) Diagnostics LED (green) PS 21 1 3 1 4 M 1 13/14 Enabling current path, undelayed M1 Signal output (PNP) 106253_en_00 PHOENIX CONTACT 10

10 Mounting and connection Mount the module on a 35 mm DIN rail according to EN 60715. 12 Proof test In the proof test, you check the individual relay channels. 1. Activate A1/A2. 2. Apply the 24 V DC diagnosis power supply to contact 21. If the green DGN-LED lights up, the module is functional. (Apply 24 V DC to signal output M1.) Figure 8 Mounting and removing Connect the cables to the connection terminal blocks using a screwdriver. B If the red ERR LED lights up, replace the module. (Apply 0 V DC to signal output M1. Error acknowledgment via A1 is inactive.) If the diagnostic voltage supply is present and the green DGN LED and the red ERR LED are on, replace the module. If the diagnostic voltage supply is present but neither of the LEDs specified is on, replace the module. AWG 26-12 0,2-2,5 mm 2 Replace the device in the event of an error. A 12 mm 0,5-0,6 Nm 5-7 lb In Figure 9 Connection of the cables For compliance with UL approval, use copper wire that is approved up to 60 C/75 C. 11 Startup Apply the rated control supply voltage at terminal blocks A1/ A2. The PWR LED and K1 LED light up. Enabling current path 13/14 closes, and confirmation current path 21/22 opens. 106253_en_00 PHOENIX CONTACT 11

13 Calculating the power dissipation The total power dissipation of the safety relay is based on the input power dissipation and the contact power dissipation for the same and for different load currents. Input power dissipation P Input = U ² B / (U S /I S ) Contact power dissipation With the same load currents: P Contact = n I ² L 25 mω With different load currents: P Contact = (I ² L1 + I ² L2 +... + I ² Ln ) 25 mω Total power dissipation P Total =P Input + P Contact therefore P Total = U ² B / (U S /I S ) + n I ² L 25 mω or P Total = U ² B / (U S /I S ) + (I ² L1 + I ² L2 +... + I ² Ln ) 25 mω Key: Designation P U B U S I S n I L Explanation Power dissipation in mw Applied operating voltage Rated control supply voltage Rated control supply current Number of enabling current paths used Contact load current 106253_en_00 PHOENIX CONTACT 12

14 Application examples Key: SIS = Safety Instrumented System (safe control) DC = Diagnostic Coverage according to IEC 61508 (line/load diagnostics at DO) DI = Digital input DO = Digital output Applications with the 14.1 Application example 1 - SIL 2 Low-demand application Single-channel control Diagnostic supply voltage is present Data for the application example as 1001 structure Equipment type A HFT 0 SIL 2 SFF 81.20 % SD 0 FIT SU 794.1 FIT DD 0 FIT DU 183.8 FIT Total 977.9 FIT MTBF 99 years PFD avg 8.06 x 10-04 (for T1 = 1 year) A fault e.g., open circuit or short circuit of the load is reported by detuning the test pulse of the safe controller. SIS DC 90% DO DO DI L 24V A1 13 ( ) 21 A2 14 ( )22 ( ) M1 K1 K1 M M (N) Figure 10 Application example 1 - SIL 3 106253_en_00 PHOENIX CONTACT 13

15 Revision history Version Date Contents 00 2015-03-10 First publication 106253_en_00 PHOENIX CONTACT GmbH & Co. KG 32823 Blomberg Germany 14 phoenixcontact.com