The Digital Substation: resilient and Cyber Secure Protection and Control

Similar documents
Update on DSE-Based Protection aka: Setting-less Protection Experience with Laboratory Testing

Dynamic State Estimation Based Protection: Laboratory Validation

Setting-less Protection: Basic Building Block for CSP

Dynamic State Estimation Based Protection (a.k.a. setting-less protection)

Integrated Centralized Substation Protection

The Substation of the Future: A Feasibility Study

p. 1 p. 9 p. 26 p. 56 p. 62 p. 68

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements

Substation Automation Products. Line differential protection RED670 Relion 670 series

We will discuss two types of loss-of-potential (LOP) logic during this presentation:

ELG4125: System Protection

Deploying Digital Substations: Experience with a Digital Substation Pilot in North America. Harsh Vardhan, R Ramlachan GE Grid Solutions, USA

Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure

Chapter 2 State Estimation and Visualization

SPECIAL REPORT FOR STUDY COMMITTEE B5 (Protection and Automation)

Redundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc

Commission Testing Methods for Protection Systems

POWER GRIDS. We are bridging the gap. Enabling Digital Substations.

Digital Substation Overview of Technology, Industry

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Failure Diagnosis and Cyber Intrusion Detection in Transmission Protection System Assets Using Synchrophasor Data

Important Considerations in Testing and Commissioning Digital Relays

MiCOM Agile P345 & P348

THE INTEGRATED TESTING SOLUTION

Data Attack Detection and Command Authentication via Cyber Physical Comodeling

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.

Bus Protection Application Challenges

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

PG&E Transmission Interconnection Handbook

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Ali Abur Northeastern University Department of Electrical and Computer Engineering Boston, MA 02115

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation

Digital Substation Unrestricted Siemens AG 2017 siemens.com/digital-substation

Non-conventional instrument transformers Advanced GIS substations with IEC LE process bus

Sensitive and Selective Ground-Fault Protection in Ungrounded MV Networks Using the DPU-2000R with the Directional-Sensitive-Earth Fault Feature

Power System Network Simulator (PSNsim)

An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems

UR Universal Relay Series

SEL Time-Domain Link (TiDL ) Technology

AUTOMATED TESTING OF BUSBAR DIFFERENTIAL PROTECTION USING A SYSTEM-BASED APPROACH. Christopher Pritchard, Florian Fink

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Power Xpert Meter 350 (PXM350) three-phased DIN-rail multifunction meter

Protection Redundancy Main I and Main II Security and Reliability

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection

www. ElectricalPartManuals. com .Basler Electric BE1-878 HIGH IMPEDANCE BUS DIFFERENTIAL RELAY ADVANTAGES ADDITIONAL INFORMATION APPLICATION Page2

Impact of Measurement and Communication Aspects on Protection of MTDC Grids

Distributed bus protection application in a platform for process bus deployment in the SMART SUBSTATION

Process Bus overcoming the complexity of process bus adoption to drive down design, implementation and operation costs

ASPEN Software - Introduction

Smart Distribution Technology

IEC in Digital Substation and Cyber security

Entergy Development and Deployment of IEC Protection and Control Including Process Bus

Bus Bar Protection Applications Seminar

COMMUNICATION NETWORKS. FOX615/612 TEGO1 IEC GOOSE Proxy Gateway interface module.

EE 868: Digital Techniques for Power System Protection. Laboratory Assignment #2 (Feb. 8 (12pm)) Overcurrent Relay Coordination

ABB Digital medium-voltage switchgear

It is the job of the protection system equipment to recognize and remove the fault.

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

ASPEN Software - Introduction

System Protection and Control Subcommittee

MiCOM Agile P746. Grid Solutions. Key Benefits. Numerical Busbar Protection. A Combination of Speed, Security and Selectivity. About MiCOM P40 Agile

Using the Bitronics 70 Series to Improve Local Monitoring and Control

JULIO OLIVEIRA, ABB POWER GRIDS GRID AUTOMATION, DECEMBER 01 ST ABB Ability - Digital Substations. FISE 7a Edición

PRC Coordination of Protection Systems for Performance During Faults

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

Modular Smart Grid Power Systems Simulators (Utilities)

MID approval no. DE-08-MI004-PTB004 Date of release

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

Residual overvoltage relay

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

Landsnet-Icegrid. Requirements for protection and control systems. Principles for the Icelandic power transmission network.

UR Universal Relay Series

IEEE 1588v2 Time Synchronization in Energy Automation Applications Case Studies from China

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

Uses of Operational and Non-Operational Data

Jim McGhee, Utility Market Manager, RuggedCom Inc.

Improving Real-time Fault Analysis and Validating Relay Operations to Prevent or Mitigate Cascading Blackouts

B. System Design and Performance Requirements

SCADA Training - T&D Automation

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters.

A Hybrid Communication Architecture for Internet of Things (IOT) Application in Smart Grid

PROTECTION, AUTOMATION & CONTROL

Smart Power Flow Monitoring and Control

DRTS 33. The new generation of advanced three phase relay test set

Substations go fully digital but stay compatible

BREAKER FAILURE PROTECTION

Level 2, 3 and 4 Interconnection Application for Certified, Inverter Based Generating Facilities Not Greater than 2MW

Electric T&D Capacity, Reliability, UG Asset Bulletin

Earth-fault Relay SPAJ 110 C. Product Guide

Performance considerations in digital substations

IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS

Measures of Value. By Tomo Popovic and Mladen Kezunovic /12/$ IEEE. september/october IEEE power & energy magazine

Today, utilities are focusing on improving or maintaining

Small Generator Interconnection System Impact Study Report. Completed For Q0047

SDG&E s Accomplishments and Future Plans

Protection relays.

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A

Transcription:

The Digital Substation: resilient and Cyber Secure Protection and Control Sakis Meliopoulos Georgia Institute of Technology, Atlanta, Georgia USA PSERC Webinar, November 20, 2018 1

Presentation Outline Protective Relaying Status & Challenges: Performance Statistics Perennial Issues: Data Integrity, Hidden Failures, Complexity and now cyber attack concerns The digital substation concept Relevant Technologies Setting-less relays Error Correction within Merging Units Substation Centralized Protection Scheme Detection of Hidden Failures and cyber attacks Real Time Autonomous Self Healing Concluding Remarks PSERC Webinar, November 20, 2018 2

Performance Statistics Mis-Operations & Protection Gaps PSERC Webinar, November 20, 2018 3

Performance Statistics: DoE Relay Mis-operations: 10% Of These 65% are related to hidden failures PSERC Webinar, November 20, 2018 4

Sample Statistics For the Brazilian National Grid, the ISO collects yearly the data about the performance of protection systems. The following graph shows the percent of success in operation of protection of transmission lines, transformers and buses, for the whole Brazilian grid, in 3 years. Brazil 2008 2009 2010 Line 97.42 96.3 96.8 Transformer 86.3 87.3 91.2 Bus 86.8 86.2 83.0 PSERC Webinar, November 20, 2018 5

Statistics Protection Systems Misoperations Identified as #1 NERC Reliability Issue in 2010 PSERC Webinar, November 20, 2018 6

Causes of Mis-Operation Complexity Relay Settings Coordination Issues Data Integrity Hidden Failures Cyber Attacks Protection Gaps (HIF, Faults near neutrals, etc.) Unusual Events PSERC Webinar, November 20, 2018 7

Relevant Technologies PSERC Webinar, November 20, 2018 8

The Substation of the Future PSERC Project 2007-08 (Meliopoulos, Bose) PSERC Webinar, November 20, 2018 9

Overall Approach From This To This PSERC Webinar, November 20, 2018 10

Present Day Technology Merging Units were Introduced by 2009: Hardfiber by GE. Today many manufacturers offer free standing merging units and NCIT (Non-Conventional Instrument Transformers) Standardization is quite advanced PSERC Webinar, November 20, 2018 11

The Digital Substation Concept PSERC Webinar, November 20, 2018 12

The Digital Substation Concept PSERC Webinar, November 20, 2018 13

Architectural Notes GPS-Synchronized Samples PSERC Webinar, November 20, 2018 14

The Setting-Less Protection Method Complexity and Protection Gaps PSERC Webinar, November 20, 2018 15

DSE Motivation: In Search of Secure Protection Setting-less Protection has been inspired from Differential protection Analytics: Dynamic State Estimation (systematic way to determine observance of physical laws) PSERC Webinar, November 20, 2018 16

The Setting-Less Protection Method (Dynamic State Estimation Based Protection) Protection Zone State x(t): Minimum Number of Variables that Completely Define the Operating Condition of the Protection Zone, i.e. Voltages, Flux, Speed, etc. Measurements z(t): Any Measurement Can be Expressed as a Function of the State x(t), i.e. z(t)=h(x(t)). State Estimation: Compute x(t) that will make the difference: z(t)-h(x(t)) as small as possible. Note z(t) are Sample Values Min J 2 m z i t hi x t i 1 i PSERC Webinar, November 20, 2018 17

The Setting-Less Protection Method (Dynamic State Estimation Based Protection) If Protection Zone is Free of Faults, the distance (z(t)-h(x(t))) is very small comparable to Measurement Error. If Protection Zone is Free of Faults and there are faults outside the protection zone, the distance (z(t)-h(x(t))) is very small comparable to Measurement Error. If Protection Zone experiencing an internal Fault, the distance (z(t)-h(x(t))) becomes large. PSERC Webinar, November 20, 2018 18

Protection V V of Saturable A A Core Transformers FAULT Event: G 1 2 SOURCE LINE XFMRH XFMRL 1-Ph LOAD 14.4/2.2kV, 1000 kva singlephase saturable-core transformer A 800kW load connected to the system, generating transients and inrush currents at 0.72 seconds Followed by a 5% turn-ground fault near neutral terminal of the transformer at 1.52 seconds List of Measurements: Single-phase voltages at two sides Single-phase currents at two sides Internal Turn-Ground Fault Temperature measurements at selected points PSERC Webinar, November 20, 2018 19

Differential Protection for Turn-ground Fault 5% from Neutral 5.870 A -3.673 A 2.968 A 1.728 A 47.79 A 45.85 A 6.211 % 3.768 % 1.000 u -1.000 u Differential_Current (A) Fundamental_I_op (A) Restraint_I_res (A) Diff_Ratio_Index (%) Trip_Decision 2.074 s 4.500 s Differential Current (SV) Operating Current Restraining Current Differential Ratio Index (%) Trip Decision Legacy Differential Protection MISSES the Fault PSERC Webinar, November 20, 2018 20

Setting-less Protection for Turn-ground Fault 5% from Neutral 11.42 kv -11.42 kv 67.55 A -67.51 A 45.57 ma -45.55 ma 34.92 0.266 m 100.00 48.25 u 1.000 0.000 55.98 us 12.60 us Actual_Measurement_Voltage_XFMRH_A (V) Actual_Measurement_Current_XFMRH_A (A) Residual_Actual_Measurement_Current_XFMRH_A (A) Chi_Square Confidence_Level Trip_Decision Execution_time (s) Voltage Measurement CurrentMeasurement DSE Residuals Chi Square Test Confidence Level Trip Decision DSE Execution Time 2.045 s 4.500 s Setting-Less protection detects fault in sub-msec time and trips within a fraction of a cycle. PSERC Webinar, November 20, 2018 21

Major Additional Benefit: Perpetual Model Calibration and Validation A Ubiquitous System for Perpetual Model Validation Protection is Ubiquitous Makes Economic Sense to Use Relays for Distributed Model Data Base Capability of Perpetual Model Validation Component Real Time Model with GPS Time Stamp enables distributed approaches PSERC Webinar, November 20, 2018 22

Data Integrity 1. Instrumentation Channel Errors 2. Hidden Failures 3. Cyber Data Attacks PSERC Webinar, November 20, 2018 23

Effects of Input Data Accuracy Quality of Data is Affected from (a) Instrumentation Channel Errors, (b) Hidden Failures and (c) cyber data attacks. All Affect Performance of Setting-less relays as any other legacy relays. Relays and merging units are becoming more accurate by using higher resolution in data acquisition and higher sampling rates. Errors from instrumentation channels remain practically the same. Instrumentation channel errors have been much higher than the errors introduced by the data acquisition even in earlier generations of sensor less systems. Merging Units offer a unique opportunity to perform error correction within a merging unit MU provides corrected data in primary quantities. PSERC Webinar, November 20, 2018 24

Basic Question Given a measurement at the secondary of an instrumentation channel, can we extract the correct value of the primary quantity? Can it be done on a sample by sample basis? PSERC Webinar, November 20, 2018 25

Basic Approach to Error Correction Construct the mathematical model of the instrumentation channel: Example CT Channel Use actual measurements and augment with: (a) virtual measurements, (b) derived measurements, and Redundant Measurements. (c) pseudo measurements Perform dynamic state estimation Best Estimate Of Primary Current PSERC Webinar, November 20, 2018 26

Dynamic State Estimation CT Channel math Model Measurements Actual: - Voltage or Current at Burden Add: -Virtual, -Derived, and -Pseudo-Measurements Example Virtual Measurement: Example Derived Measurement: Example Pseudo Measurement: 1 0 g e t i t i ( t) i t g L n dil t 1 m m p L1 s1 1 i t i t g L m b L1 s1 1 m 0 v ( t) 4 dt di L 1 dt t States: 15 Actual Measurements: 1 Virtual Measurements: 14 Derived Measurements: 5 Pseudo measurements: 1 21 Equations in 15 unknowns. One of the unknowns is the Primary Current PSERC Webinar, November 20, 2018 27

Example System Example System Parameters 115-kV transmission system. Current transformer on phase A CT ratio is 800:5A Error class: 10C100. CT instrumentation cable: #10 copper Instr. cable length: 96 meters Burden resistance: 0.1 Ω Current Transformer Parameters PSERC Webinar, November 20, 2018 28

Example System Results PSERC Webinar, November 20, 2018 29

Example System Results Mild CT Saturation Simulated CT Secondary Current Waveform CT Secondary Current 118.5 A I_CT_SEC (A) -105.3 A 26.51 ms 77.70 ms Phase A to ground fault at MIDBUS PSERC Webinar, November 20, 2018 30

Example System Results Mild CT Saturation Error Correction Performance Secondary Current x CT Ratio Estimated Primary Current Actual Primary Current Estimated results match actual primary current with less than 1% error PSERC Webinar, November 20, 2018 31

Intelligent Merging Units Provide Corrected Primary Values Error Correction Integrated into Merging Units (alternative: in substation computers) PSERC Webinar, November 20, 2018 32

Data Integrity 1. Instrumentation Channel Errors 2. Hidden Failures 3. Cyber Data Attacks PSERC Webinar, November 20, 2018 33

Impact of Hidden Failures/Cyber Attacks Hidden failures and cyber attacks corrupt the data seen by a relay, legacy relay or setting-less protective relay. Hidden failures/cyber attacks will cause relay mis-operation whether it is a legacy protective relay or a setting-less relay. Need to identify hidden failures/cyber attacks and avert relay mis-operations. Present State of Art: Some legacy relaying schemes can identify some hidden failures and inhibit relay operation. No capability to take corrective action. PSERC Webinar, November 20, 2018 34

Proposed Method for Securing Data PSERC Webinar, November 20, 2018 35

Proposed Method for Securing Data PSERC Webinar, November 20, 2018 36

Dynamic State Estimation Based Centralized Protection Scheme Resilient Centralized Substation Protection (rcsp) PSERC Webinar, November 20, 2018 37

Dynamic State Estimation Based Centralized Protection Scheme (rcsp) Hypothesis Testing: Observations At substation level redundancy is high (over 2000%) System is continuously running. Probability of simultaneous failure events is low Hypothesis Testing: Mechanics Identify suspect measurements from residuals Group suspect data with certain criteria (see paper) Determine faulted devices from setting-less relays output PSERC Webinar, November 20, 2018 38

Dynamic State Estimation Based Centralized Protection Scheme (rcsp) Hypothesis Type 1 (H1): Remove suspect measurements and rerun DSE. If probability high removed measurements are bad identify root cause issue diagnostics replace bad data with estimated values. End hypothesis testing. Otherwise go to H2. Hypothesis Type 2 (H2): (determine if a fault decision is correct). For the reported faulted device, remove all internal device measurements and remove the faulted device model from the substation model. Then rerun DSE. If probability high the device is truly experiencing an internal fault. Allow zone relay to trip the faulted device. End hypothesis testing. Hypothesis Type 3 (H3): This test combines type 1 and type 2 hypothesis testing to cover the case of a simultaneous fault and a hidden failure. PSERC Webinar, November 20, 2018 39

Numerical Example Case Study: 5 Protection Zones: 115 kv Transmission Line 115 kv Bus 115/13.8 kv, 36 MVA Transformer 13.8 kv Bus 13.8 kv Distribution Line (one of the two) PSERC Webinar, November 20, 2018 40

Numerical Example Case1: Primary Fuse Blown Y-Y, PT-4A Hidden Failure 0 Sequence of Events Time (seconds) 1 2 3 4 5 Fuse Blown 6 MW Load Switched On 6MW Load Switched Off PSERC Webinar, November 20, 2018 41

Numerical Example Case1: Primary Fuse Blown Y-Y, PT-4A Setting-less Relay of Transformer Zone: 22.82 kv Transformer_Zone_LV_Side_PhA (V) -11.60 kv 11.61 kv Transformer_Zone_LV_Side_PhB (V) -11.63 kv 11.64 kv Transformer_Zone_LV_Side_PhC (V) -13.29 kv 100.0 Confidence_Level 0.000 1.000 Trip_Decision 0.000 1.500 s 3.121 s PSERC Webinar, November 20, 2018 42

Numerical Example Case1: Primary Fuse Blown Y-Y, PT-4A Centralized Protection Scheme : PSERC Webinar, November 20, 2018 43

Numerical Example Case1: Primary Fuse Blown Y-Y, PT-4A Centralized Protection Scheme : 200.0 Confidence_Level 1.000 PT-4A_Hidden_Failure -200.0 0.000 1.000 Hidden_Failure_ Status 1.000 u PT-4B_Hidden_Failure 0.000-1.000 u 1.000 u Faulty_ Zone_Status 1.000 u PT-4C_Hidden_Failure -1.000 u -1.000 u 0.000 s 4.992 s 0.000 s 4.992 s PSERC Webinar, November 20, 2018 44

Numerical Example Case1: Primary Fuse Blown Y-Y, PT-4A Compromised Data Correction : PSERC Webinar, November 20, 2018 45

Concluding Remarks Centralized Substation Protection innovations: Innovation 1: Setting-less Protective Relay Innovation 2: Merging Units can provide corrected primary values via instrumentation error correction embedded in intelligent Merging Units Innovation 3: Supervision of protection functions (logical nodes) to determine that hidden failures do not exist. In case of hidden failures use real time dynamic model to replace compromised data with estimated data enable resiliency Innovation 4: Supervision of data integrity to determine data attacks. In case of cyber data attack, use real time model to replace false data enable resiliency. PSERC Webinar, November 20, 2018 46

Concluding Remarks IEEE and CIGRE Efforts Move Towards the DIGITAL SUBSTATION. The entire process should be automated with self healing capabilities against data errors, hidden failures and cyber attacks. Automated testing and in-line testing of active substation protection and control systems. The technology exists. We need to continue developments to bring these approaches to a practical level. PSERC Webinar, November 20, 2018 47

Find out why! To accept something the way it has always been done is simply not acceptable. Furthermore, it is boring. Walter A. Elmore, 1925-2010 Τέλος PSERC Webinar, November 20, 2018 48