Rhino Redundancy Module PSM24-REM360S. Operating Instructions

Similar documents
Rhino Buffer Module PSM24-BFM600S. Operating Instructions

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

Rhino PSM Power Supplies. Operating Instructions

TSP-BCM48, TSP-BCM48A. Operating Instruction Manual. Page 1 of 13

Output Voltage* (nom.)(adjustable)

Output Voltage* (nom.)(adjustable)

Power supply CP-C 24/5.0

MINI-PS AC/10-15DC/8

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

Redundancy unit CP-A RU

RTU500 series Data Sheet Power Supply CP-E 24/2.5

Industrial Power Supplies

Industrial Power Supplies

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

TRIO-DIODE/12-24DC/2X10/1X20

QUINT-BUFFER/24DC/24DC/40

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

PHOENIX CONTACT - 07/2006

Power supply CP-E 48/1.25 Primary switch mode power supply

STEP-PS/1AC/24DC/1.75

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Industrial Power Supplies

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Power supply CP-E 24/0.75 Primary switch mode power supply

Power supply CP-E 24/10.0 Primary switch mode power supply

Power supply CP-D 12/2.1 Primary switch mode power supply

QUINT-PS-3x AC/24DC/10

PHOENIX CONTACT - 01/2007

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1

Industrial Power Supplies

Industrial Power Supplies

Redundancy Module QUINT-DIODE/40

QUINT-PS AC/24DC/10

QUINT-PS/24DC/48DC/ 5

Power supply CP-C 24/5.0

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Industrial Power Supplies

Buffer module CP-B 24/20.0, ultra-capacitor based Accessory for power supplies (e.g. switch mode power supplies CP range)

Universal Power Supplies

Simple but elegant look and ease of installation make it ideal for various industrial applications.

TRIO-PS/1AC/24DC/20. Extract from the online catalog. Order No.:

Redundancy unit CP-D RU Accessory for CP range power supplies (e.g. switch mode power supplies CP-D range)

MINI-DC-UPS/12DC/4. Extract from the online catalog. Order No.:

User Manual Entry Line Industrial Fast Ethernet Switch 5x 10/100Base-TX

Power Supply. Users Guide PRODUCT MANUAL. WESTELL.COM Westell Technologies MNL rd

Enclosed Power Supplies

PMT. Safety Standards. Model Number:

1-Phase Power Supply, Primary Switch Mode for Use in Potentially Explosive Areas QUINT-PS AC/24DC/5/EX

PHOENIX CONTACT - 05/2007

UNO-PS/1AC/12DC/30W. Primary-switched power supply unit. Data sheet. 1 Description

ABL8BBU24200 battery control module V DC - 24 V - 20 A - for regulated SMPS

XPSMF40. Main. Safety module name. Monitoring safety detection discrete input Monitoring safety dialogue discrete output

Chrome DIN Rail Power Supply 5V 7.5W 1 Phase (Class II & NEC Class 2) / DRC-5V10W1AZ

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3

QUINT-PS/ 1AC/24DC/ 5

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

ETD-BL-1T-OFF-CC- 10S

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

TRC-190 User s Manual

Analog Voltage Combination Module

PMT. Model Number: Model Number Input Voltage Range Output Voltage Output Current PMT-5V350W1A (Selectable by Switch)

MPU-120S Series. Single Output, 180W Compact, U-Channel AC/DC Power Supplies. Key Features:

MC 11 EB-2 Power supply cabinet with external bus, AC version

PNOZ m ES RS232. Configurable Control System PNOZmulti. Operating Manual EN-01

User Manual Entry Line Industrial Gigabit Ethernet High Power 60/95 W PoE Injector

Electronic timer CT-ERD.12

Series AMES40-MAZ 40 Watt AC-DC / DC-DC Converter

ATS22D75S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

QUINT-PS/ 1AC/24DC/20/CO

BUFFER MODULE SHORT-FORM DATA MARKINGS

CliQ II DC-UPS Module 24V 40A / DRU-24V40ABN

Operating instructions. Switching amplifier DN0210 DN / / 2015

Switch Mode Power Supply S8VT 120/240/480/960 W Models

PMT. Safety Standards. Model Number:

Chrome DC-UPS Module 24V 10A / DRU-24V10ACZ

MSR 2400R. Rugged Power System for Military and Heavy Duty Applications

PMT. Model Number: CC Code PM 24V 150W 1 A Panel Mount Product Type T Enclosed L L Frame*

Electronic timer CT-AHD.22

See instructions to download and install the latest version of LinkBoxLON and the user's manual at

Chrome DIN Rail Power Supply 12V 9.96W 1 Phase (Class II & NEC Class 2) / DRC-12V10W1A

Series AMEL10-MJZ 10 Watt AC-DC / DC-DC Converter

PMC. Safety Standards. Model Number:

12-15VDC (12V±5%) 24-28VDC (24V±5%)

Chrome DIN Rail Power Supply 24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1A

Installation Instructions

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

PMT. Model Number: CC Code PM 24V 200W 1 A Panel Mount Product Type T Enclosed L L Frame*

Voltage Current Front-mounting bracket

TEP 100WIR Series, 100 Watt

ATV12H075M3 variable speed drive ATV kW - 1hp V - 3ph - with heat sink

SAFETY RELAY YRB-4EML-31S MAIN FEATURES

ATSU01N209LT soft starter for asynchronous motor - ATSU01-9 A V KW

2U/3U Redundant Power Supply. 400W for IPC-Computer

ATS22D47S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

MPV1060RI4. Ultra Wide Input, Compact Industrial Grade, PV Power DC/DC Con vert ers. Key Features:

ATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW)

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

TEP160-WIRCM SERIES 160 Watt High Density Brick DC-DC Converter Measures: 2.40 x 2.28 x 0.50

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW)

Transcription:

Rhino Redundancy Module PSM4-REM360S Operating Instructions

RHINO REDUNDANCY MODULE PSM4-REM360S Description With this module and two power supplies of the PSM series (78, 90, 56, 80 and 360 watt models), a highly reliable, truly redundant power system can be configured without any additional components. This module forces each power supply to share the output current equally. The system is fully redundant and provides power to the output even if one power supply has completely failed (e.g,. by short circuit on the output). If one power supply fails or is disconnected, the second device will automatically supply the full current to the load. The redundancy of the system is monitored, and, if lost, indicated by an alarm output. The inputs are hot-swappable and can be loaded up to 5 A each. The output of the PSM4-REM360S should not be overloaded to provide a proper n+ redundancy system. The maximum output current is also 5 A. Both PSM power supplies have to be adjusted to Vout = 4.00 to 4.05 VDC before connecting them to the PSM4-REM360S. Afterward, the connection between the PSM power supplies and Input (+Vin and Vin; J pin & pin ) as well as Input (+Vin and Vin; J pin 3 & pin 4) and the remote sensing (J3 & J4) between these two devices and the PSM4-REM360S using the wire supplied with the PSM4-REM360S module can be made. Now the load can be connected to DC-Out (J pin, pin, pin 3 & pin 4). The output voltage on the PSM4-REM360S can be adjusted between 4 and 7 VDC using the potentiometer on the module. The PSM4-REM360S is a built-in device. The mounting position must fulfill the requirements for fireproof enclosure according to UL60950, IEC/EN 60950 or other appropriate national standard. The relevant UL regulations or equivalent national regulations must be observed during installation.the PSM4-REM360S is designed for mounting on a DIN rail (DIN EN 500-35x5/7.5). The output voltage of the PSM4-REM360S is protected against short circuit and open circuit conditions. Warning The PSM4-REM360S built-in module is designed especially for use in process automation and other industrial applications. Components with dangerously high voltage and high stored energy are located in the device; however, these are inaccessible. Failure to properly maintain the PSM4-REM360S can result in death, severe personal injury or substantial property damage. The PSM4-REM360S should be installed and put into operation by qualified personnel only. The corresponding national regulations (e.g. UL, ANSI, VDE, DIN) must be observed. The successful and safe operation of this module is dependent on proper storage, handling, installation and operation. The potentiometer to adjust the output voltage must be actuated using only an insulated screwdriver, because accidental contact may be made with parts inside the power supply carrying dangerous voltages. Caution: Risk of electrical shock and electrical discharge. Only qualified and trained personnel should open the PSM4-REM360S or the power supply. Do not open the PSM4-REM360S or the power supply until at least 5 minutes after complete disconnection of the main power. Electrostatic sensitive device. In case of non-observance or exceeding the limiting value mentioned in these instructions, the function and electrical safety can be impaired and can destroy the PSM4-REM360S and/or the power supply. Danger: Never work on the PSM4-REM360S or power supplies if power is applied! Before installation ensure that the main switch is switched off and locked out. Touching of any live components or improper usage of PSM4-REM360S or power supply can result in severe injury or death. Warning: To minimize the risk of potential safety problems, follow all applicable local and national codes regulating the installation and operation of this equipment. These codes vary from area to area and it is your responsibility to determine which codes should be followed, and to verify that the equipment, installation, and operation are in compliance with the latest revision of these codes. Failure to follow all applicable codes, or exceeding the limiting value can impair the function and electrical safety and destroy the power supply. Serious injury to personnel can result from the failure to follow all applicable codes and standards. We do not guarantee the products described in this publication to be suitable for your particular application, nor do we assume any responsibility for your product design, installation or operations. Before operating Read these operating instructions carefully and completely. Check that the input wiring is sufficiently protected and is the correct size. Check that the output wiring is rated for the maximum output current, and connected with the correct polarity. Verify that sufficient cooling is assured. Caution: The temperature of the housing can become very high, depending on the ambient temperature and load. Installation Assembly A sufficiently strong DIN rail, such as DN-R35S, must be used. Observe the correct mounting position for optimal cooling performance. A minimum free space of 80 mm [3.5 in.] is required above and below the PSM4-REM360S; leave a minimum space of 50 mm [.97 in.] (which allows air convection) on each side. The air temperature, as measured 0 mm [0.39 in.] below the device, must not exceed the specified values in these instructions. The power derating above ambient temperatures of 40 C is the same as specified for the PSM power supplies. To attach the module to the DIN rail, hook top part of clip on DIN rail, then push down and inward until you hear a clipping sound. To remove the device, pull the latch of the clip using an insulated flathead screwdriver. When clip has cleared the bottom DIN rail, remove the screwdriver from the recess. Lift the module off DIN rail. Wall mounting or chassis mounting can be achieved by use of optional mounting bracket, PSM-PANEL. Remove the DIN-clips by removing the screw and place the -800-633-0405

mounting brackets in the same place as the DIN-clips. Use the countersink screws included with the wall mounting kit to attach the mounting brackets to the PSM4-REM360S (tightening torque 0.8-0.9Nm). Connecting cable Allow only qualified personnel to install the module. The device is equipped with a COMBICON connector. This reliable and easyto-assemble connection method provides a fast connection of the device. Input and Input Connector (J, pin, pin, pin 3 & pin 4) The connection is made by using the Vin and +Vin connections at Input as well as at Input and must be done in accordance with the local codes and regulations. Choose correct wiring size from the Connectinons and Terminal Assignment table below. To achieve a reliable and shockproof connection, strip the connecting ends as listed in the following table. If flexible wires are used, terminate them using ferrules. Connections and Terminal Assignments Device Terminals Function PSM4-090S PSM4-80S PSM4-360S Output (Connector J, pin, pin, pin 3 & pin 4) The 4 VDC connection is made using the +Vout and -Vout terminals. All output terminals should be connected to the load. Make sure that all output lines are sized according to the maximum output current (see Connections and Terminal Assignments table above) or are separately protected. The wires on the secondary side should have large cross sections in order to keep the voltage drops on these lines as low as possible. To achieve a reliable and shockproof connection strip the connecting ends according to the above Connections and Terminal Assignments table.if flexible wires are used, terminate them using ferrules. At delivery, the output voltage is 4 VDC. The output voltage can be set (using an insulated screwdriver) from 4 to 7 VDC on the potentiometer. The device is protected against overload and short circuit. Signaling (Connector J5, pin & pin ) The DC OK outputs facilitate monitoring of the functions of the two PSM power supplies. The Alarm signal contacts (connector J5, pin & pin ) are monitoring if the output voltage is present in both of the PSM power supplies, which are connected to the PSM4-REM360S Input and Input. If one of the devices is disconnected or damaged (e.g., in the event of a power supply s internal short circuit), the alarm is generated. The contact on the relay will switch off (relay contact = open). If both PSM power supplies provide at least an output voltage of.5 VDC, the relay contact is closed and signals that both power supplies are in operation. If the output voltage of the PSM4-REM360S is present, the relay contact (30 VDC / A) is closed. It is detected by measuring the PSM4-REM360S input voltage at Input as well as at Input. Inputs-ON LED The Inputs-ON LED is a green LED that indicates the status of the PSM4-REM360S inputs and enables visual evaluation of the function locally in the control cabinet. Solid or Stranded Wires Torque Stripping Length mm mm AWG Nm -Vin & + Vin Input Input voltage (4 VDC) 0.5 to..5 4 to 0.5 to 0.6 7.0 -Vin & + Vin Input Input voltage (4 VDC) 0.5 to..5 4 to 0.5 to 0.6 7.0 +Vout & - Vout Output voltage (4 VDC) 0.5 to..5 4 to 0.5 to 0.6 7.0 Signal Relay inputs and relay outputs 0. to.5 3 to 0.5 to 0.6 7.0 -Vin & + Vin Input input voltage (4 VDC).0 to-.5 8 to 0.5 to 0.6 7.0 -Vin & + Vin Input input voltage (4 VDC).0 to-.5 8 to 0.5 to 0.6 7.0 +Vout & - Vout Output Voltage (4 VDC).0 to-.5 8 to 0.5 to 0.6 7.0 Signal Relay inputs and relay outputs 0. to.5 3 to 0.5 to 0.6 7.0 Inputs-ON LED Green ON Inputs-ON LED Green OFF Status LED Function Both power supplies are supplying the PSM4-REM360S with 4 VDC One or both power supplies failed Remote ON/OFF Function : The PSM4-REM360S device provides an external remote on/off function by use of pin 3 & pin 4 at connector J5. To switch off the power supply and PSM4-REM360S a connection between connector J5 pin 3 and connector J5, pin 4 by use of a switch or similar has to be made. At open connection between J5 pin 3 and J5 pin 4 the device is providing the adjusted output voltage. www.automationdirect.com 3

Compliance to UL 508C The PSM4-REM360S is a built-in device. To comply with UL508C, the device must be installed in a cabinet with minimum dimensions of: 400 mm (width) x 500 mm (height) x 00 mm (depth) Operating Temperature Ranges and load derating: Operating temperature ranges and load derating depend on the PSM power supplies connected to the PSM4-REM360S. Please see operating temperature ranges and load derating values listed in the datasheet or PSM operating instructions for the applicable PSM power supplies, available on our website at www.automationdirect.com. Technical Specifications Part Number PSM4-REM360S *Output voltage adjustable Input Input Specifications x 4 VDC x control input Max. Input Power * Output Voltage **Max. Output Current x 360 Watt 4 VDC 360 W (5.0 A) **Maximum current at Vout nom. Output Specifications Output Voltage Adjustable Range with Potentiometer Ripple and Noise (0MHz Bandwidth) Maximum Capacitive Load *Outputs are short-circuit protected. At V in nom and I out max 4 to 7 VDC 30 mv peak-topeak max unlimited Redundancy Module Function Diagram Redundancy Module Connector Positions 3 4 J. J.3 J.4 J- - + + PSM J. J3. J3. J. J. Output J Remote Link Remote Link J4 J3 J.4 J.3 J4. PSM J4. DC IN DC IN J5 3 4 J J5. J5. J5.3 J5.4 J- + - + 3 4 J J J3 J4 Voltage control Voltage control J5 for Input for Input Pin Input -Vin GND (-) S+ S+ DC-OK Signal Pin Input +Vin GND (-) S- S- DC-OK Relay contact Pin 3 Input -Vin Vout (+) Remote ON/OFF Pin 4 Input +Vin Vout (+) Remote ON/OFF 4-800-633-0405

General Specifications Specification Description Input x 4 VDC, x Control Input Max Power per Input x 360 W Output Voltage Adjust 4 VDC (4 to 7 VDC) Output Power Max 360 W (5 A) Operating Temperature (ambient): -5 C to + 70 C max (-3 F to 58 F). Above +40 C(04 F) load derating Storage Temperature (non-operating): -5 C to + 85 C max (-3 F to 85 F). Temperature Temperature drift: 0.0%/K. Cooling: convection, no internal fan Reliability, Calculated MTBF In accordance with IEC 6709 350,000 hours Electromagnetic Compatibility In correspondence to connected units (no internal switching device) Redundancy Alarm Signal Trigger threshold at 8 to VDC. Contact closed if one or both inputs failed Dimensions WxHxD 35.0 mm (.30 in) x 0.0 mm (4.33 in) x 0.0 mm (4.33 in) Remote Link Wire 0.5m Two cables included with PSM4-REM360S module Alarm Contact Rating 30 VDC/.0 A max Humidity 95% (non-condensing) relative humidity maximum Isolation According to IEC/EN 60950, UL 60950, UL 508C, EN5078, EN6558--8, EN6004 Green LED: Green On: both PSM power supplies working Status Indicator Green Off: one or two power supplies failed, or Off By external contact: OFF - J5, Pin 3 and Pin 4 shorted Remote ON/OFF ON - J5, Pin 3 and Pin 4 open Maximum Capacitive Load Unlimited Vibration IEC 60068--6: 3 axis, sine sweep, 0-55 Hz, g, oct/min Shock IEC 60068--7: 3 axis, 5g half sine, ms Enclosure Rating IP0 (IEC 59) Enclosure Material Aluminum (chassis) / zinc plated steel (cover) Mounting Snap-on with self-locking spring for 35mm DIN rails per EN 500-35x5/75, or wall mount with bracket Connection Pluggable screw terminals (plugs included) Note: Unless otherwise stated, all specifications are valid at nominal input voltage, full load and +5 C after warmup time. General Specifications Safety Standards Specification Standard Document Number Harmonic Limits Harmonic Current Limits: EN 6000-3-, Class A for limited output power Safety Class Degree of electrical protection Class IEC 536 Electromagnetic Compatibility (EMC), Emissions EMC, Emissions Corresponds to connected units ( no internal switching device) Electromagnetic Compatibility (EMC), Immunity EMC, Immunity Corresponds to connected units ( no internal switching device) Pollution Degree Tbfdeq7. +-i_ Dbt f`eq7-+hd www.automationdirect.com 5