RXTH DUAL ROOM SENSOR / SWITCH

Similar documents
RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

RXTP ROOM TEMPERATURE

DXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions

RТTH DUAL ROOM SWITCH

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions

MVS RAIL ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions

CNVT-USB-RS485 MODBUS TO USB CONVERTER. Operating instructions

HPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions

DPOM8-24/20 DIN RAIL POWER OVER MODBUS MODULE. Mounting and operating instructions

STR-3 STANDARD 3-PHASE 230 VAC TRANSFORMER CONTROLLER. Mounting and operating instructions

Operating instructions. Speed monitor D / / 2014

Instruction Manual. T3110 T3110L T3110Ex

Blue ID Power injection module PI60

sensor, which compensates for ageing effects, is highly insensitive to pollution and offers outstanding long term stability.

LLR-MOD Modbus Light Level and Occupancy Sensor

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

Priva Blue ID Digital input module DI4/DI8/DI16

MU110-6U. Analog output module 6 channel. User guide

Priva Blue ID Analogue output module with manual override AO2m/AO4m

Priva Blue ID Relay output module DOR4/DOR8

Blue ID Communication module RS485 SC44

DOR6. Components All functions and indications are on the front of the module. Characteristics

MXIO. Compact I/O module. Summary. Application Compact I/O module for data acquisition and HVAC control systems. Function

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Installation manual CF8-W-Disp-AL

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

ADC7520 SERIES. 1600W Battery Chargers and Power Supplies

RCF-230CAD. Communicating room controller for fan-coil applications with two analogue V DC outputs

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

RTD-W Installation Instructions

RTD-RA. realtime. Installation Instructions. English A B. Installation Instructions Control Systems LEDS ALL DIMENSIONS IN MM

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W

OZONE SWITCH Model OS-6. OS-6 Features

Small distributed I/O module

RCF-230CD. Communicating room thermostat for fan-coil applications with on/off outputs

thanos RS485 Modbus Application Functions Multifunction Room Operating Unit Datasheet

MOD-RI Room Interface Modules with Modbus

1 IF-810 or IF-811 Terminal (Slave) 2 Intended Use. 3 Assembly and Installation _V IF-810/IF-811

Voltage Transducer UMT516 / MT516

Operating instructions. Switching amplifier DN0210 DN / / 2015

TEMPERATURE AND HUMIDITY TRANSDUCER P18 TYPE USER S MANUAL

USER MANUAL VIBRATION CONTROL RMA-POWER-BOX 107/230

Technical data. Safety notes. Product features

Priva Blue ID Communication module RS485 SC44

Output Signal. 22DTM-16 BACnet DC V, DC V. Electrical data Power Supply DC V, ±10%, 0.3 W

RHT-WM-485-LCD Transmitter and RHT-DM-485-LCD Transmitter

RCF-230CAD. Room controller with communication for fancoil applications with two analogue V DC outputs

Procon A1M. INSTALLATION MANUAL Version MITSUBISHI ELECTRIC FOR INSTALLERS

Communicative controller for VAV systems

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

MC 11 EB-2 Power supply cabinet with external bus, AC version

UC102 basic version with display and knob UC102BL version with display, knob and backlight UC102DK version without knob and display

9.5 nominal torque 4.5 W 16 VA. Min. 30 nominal voltage Min. 30 Nm. Reversible with switch By mounting. MIN (minimum position)

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

1 IF-812 or IF-815 Terminal (Slave) 2 Intended Use. 3 Assembly and Installation _V IF-812/IF-815

Room unit with PPS2 interface

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

Overview of types. Technical data

RTD-NET Installation Instructions

Multifunction Transducer MT440

InBin-P Pressure switches from 5 Pa Pa

CDR-RH Room CO 2, Temperature and Humidity Sensors (Controllers)

Operating instructions. Standstill monitor A / / 2011

PSBOC PSBOC 27,6V/5,5A/OC

Warranty. Warning. Copyright. Contact Us

See instructions to download and install the latest version of LinkBoxLON and the user's manual at

USER S GUIDE. EE210 - Humidity and Temperature Transmitter for demanding Climate Control Applications GENERAL

Output Signal. Temperature 22DTH-56M BACnet DC V, DC V. Electrical Data Power Supply DC V, ±10%, 0.7 W

DP2500 DP0250. Differential Pressure Transmitter. Product Bulletin

Page 1 MRK-D-0011, V1.1 Aeroqual SM50 User Guide

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

MOD-IO9 Modbus Input / Output Modules, Wall Mounted

Features and Benefits. Certifications

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3

Product and functional description

Duct humidity and temperature sensor for all HVAC duct applications. Designed for control and monitoring applications.

TRANSDUCER T4311, T4411

Room Temperature Controller

Motor Control and Protection Unit M10x AO Module User Guide

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

Programmable temperature transducer from Pt1000 sensor to current loop 4-20 ma Instruction Manual

The PM1000 series is a universal 4 digit LED plug-on display for transmitters with 4-20mA 2 wire output and fitted with DIN43650 connector.

Priva Blue ID Communication module RS232 SC22

Output signal. 22DTM-16 BACnet DC V, DC V. Electrical data Power supply DC V, ±10%, 0.3 W

Priva Blue ID C-Line Mix input/output module MX34

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1

Page 1 MRK-D-0011, V2.0 Aeroqual SM50 User Guide


CEM M-RS485 INSTRUCTION MANUAL (M014B A)

Model HU-224/225. Technical Information TI.224/ Humidity Transduce r FOR ADDITIONAL INFORMATION SEE HU-224/225 DATA SHEET

Buffered Power Supply PS-30DR v1.0

english S-5EC Potentiometer 5-step Operating Instructions Keep for reference! L-BAL-E265-GB 1608 Index 002

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

POE084824B. PoE 54V/8x0,3A/4x7Ah PoE buffer power supply for up to 8 IP camera. v.1.1 EN* Edition: 7 from

VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide

Transmitters RHT-WM-485-LCD, RHT-DM-485-LCD and RHT-P LCD

QUICK START GUIDE. vau4/3. Frequency converter. operating instructions /12

Transcription:

DUAL ROOM SENSOR / SWITCH FOR TEMPERATURE AND RELATIVE HUMIDITY Mounting and operating instructions

Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 5 MOUNTING & OPERATING INSTRUCTIONS IN STEPS 6 MODBUS REGISTER MAPS 9 VERIFICATION OF INSTALLATION INSTRUCTIONS 10 TRANSPORT AND STOCK KEEPING INFORMATION 10 WARRANTY INFORMATION AND RESTRICTIONS 10 MAINTENANCE 10 MIW--EN-000-27 / 10 / 2015 www.sentera.eu 2-10

SAFETY AND PRECAUTIONS Read all information, the datasheet, mounting instructions and wiring scheme before working with the product. For personal and equipment safety, and for optimum product performance, make sure you entirely understand the contents before installing, using, or maintaining this product. For safety and licensing (CE) reasons, unauthorised conversion and / or modifications to the product are not permitted. The product must not be exposed to abnormal conditions, such as: extreme temperatures, direct sunlight or vibrations. Chemical vapours with high concentration in combination with long exposure times can affect the product performance. Make sure the work environment is as dry as possible; check for condensation spots. All installations shall comply with the local health and safety regulations and local electrical codes. This product can only be installed by an engineer or a technician who has an expert knowledge of the product and safety precautions. Avoid contacts with energised electrical parts; always treat the product as if it is life. Always disconnect the power source before connecting the power cables, servicing or repairing the product. Always verify that you apply appropriate power supply to the product and use wires with appropriate size and characteristics. Make sure that all the screws and nuts are well tightened and fuses (if any) are fitted well. Recycling of equipment and packaging should be taken into consideration and disposed in accordance with local and national legislation / regulations. In case there are any questions that are not answered, please contact your technical support or consult a professional. MIW--EN-000-27 / 10 / 2015 www.sentera.eu 3-10

PRODUCT DESCRIPTION The series are dual room sensors / switches which measure temperature and relative humidity. For each, there are 4 pre-defined s acting as measurement windows plus 1 user definable. These units are equipped with Modbus RTU (RS485) communication and have an analogue and a relay output for each measuring unit. ARTICLE CODES Code Supply Connection G 15 24 VAC ± 10 % 3 - wire 18 34 VDC F 18 34 VDC 4 - wire INTENDED AREA OF USE Monitoring and maintaining temperature and relative humidity in HVAC applications For indoor use only TECHNICAL DATA 2 analogue outputs: 0 10 VDC / 0 20 ma 2 relay outputs, C/O (230 VAC / 2 A) Power consumption: no load: max. 40 ma full load: max. 80 ma Load resistance: 0 10 VDC mode > 500 Ω 0 20 ma mode < 500 Ω Selectable temperature s: 0 30 C / 10 40 C / 20 50 C / 0 50 C Free selectable temperature via Modbus: 0 50 C Selectable rel. humidity s: 20 90 % rh / 0 60 % rh / 0 80 % rh / 0 100 % rh Free selectable rel. humidity via Modbus: 0 100 % rh 2 selectable switching points: by trimmers or via Modbus Fixed temperature hysteresis: 2 C Fixed rel humidity hysteresis: 5 % rh Enclosure: rear lid: plastic ABS, black (RAL9004) front cover: ASA, ivory (RAL9010) Protection standard: IP30 (according to EN 60529) Operating ambient conditions: temperature: 0 50 C rel. humidity: < 100 % rh (non-condensing) Storage temperature: -25 50 C MIW--EN-000-27 / 10 / 2015 www.sentera.eu 4-10

STANDARDS Low Voltage Directive 2006/95/EC EMC Directive 2004/108/EC: EN 61326 WEEE Directive 2012/19/EU RoHs Directive 2011/65/EU OPERATIONAL DIAGRAMS Analogue output 1 [VDC] 10 Relay output 1 rel on rel off 0 SP-hyst SP 50 T, [ C] 0 min. max. 50 T, [ºC] Analogue output 2 [VDC] 10 Relay output 2 rel on rel off 0 SP-hyst SP 100 rh, [%] 0 min. max. 100 rh [%] WIRING AND CONNECTIONS Vin Positive DC voltage / AC ~ GND Ground / AC ~ A Modbus RTU (RS485) signal A /B Modbus RTU (RS485) signal /B Ao1 Analogue output (0 10 VDC / 0 20 ma) GND Ground Ao2 Analogue output (0 10 VDC / 0 20 ma) GND Ground NO1 Normally open contact COM1 Common contact NC1 Normally closed contact NO2 Normally open contact COM2 Common contact NC2 Normally closed contact Connections Cable cross section: max. 1,5 mm 2 MIW--EN-000-27 / 10 / 2015 www.sentera.eu 5-10

MOUNTING & OPERATING INSTRUCTIONS IN STEPS efore you start mounting the dual room sensor / switch, read carefully B Safety and Precautions. Choose a smooth surface for an installation location (a wall, panel and etc.). Follow these steps: 1. O pen the white cover by releasing the locking plates on both sides of the cover and remove it. (See Fig. 1 Locking plates release.) 2. Insert the cables through the cable opening of the enclosure rear lid. (See Fig. 2 Mounting dimensions.) Fig. 1 Locking plates release Fig. 2 Mounting dimensions 59,8 2x Ø 9,8 6 3. D o the wiring according to the wiring diagram (see Fig. 3) using the legend information from section Wiring and connections. Fig. 3 Wiring and connections Analogue output 1 0 10 VDC / 0 20 ma Relay contacts 2 Normally closed Common Normally open Modbus RTU /B Relay contacts 1 A Normally open Common Normally closed Analogue output 2 0 10 VDC / 0 20 ma Power supply 15 24 VAC ± 10% / 18 34 VDC 4. C heck if your unit starts or terminates the network (see Example 1 and Example 2). If it does not, remove the NBT jumper (see Fig. 4). Example 1 Fig. 4 Network bus resistor jumper Example 2 Slave 1 RX RX Master ТX ТX NBT NBT Slave 2 NBT NBT NBT Master MIW--EN-000-27 / 10 / 2015 Slave n Slave 1 Slave 2 www.sentera.eu Slave n 6-10

ATTENTION If an AC power supply is used with any of the units in a Modbus network, the GND terminal should NOT BE CONNECTED to other units on the network or via the CNVT USB-RS485 converter. This may cause permanent damage to the communication semiconductors and / or the computer! 5. Adjust the standalone settings: 5.1 To select the relative humidity analogue output mode, use jumper JP4. To select the temperature analogue output mode, use jumper JP5. (See Fig. 5 Analogue output selection jumpers.) 5.2 To select a temperature, use jumper JP2. To select the relative humidity, use jumper JP3 (see Fig. 6 and the enclosed information). Fig. 5 Analogue output selection jumpers Relative humidity Temperature Fig. 6 Sensor selection jumpers Temperature Relative humidity 0 10 VDC 0 20 ma 5 4 3 2 1 0 30 C 20 90 % rh 5 4 3 2 1 10 40 C 0 60 % rh 5 4 3 2 1 20 50 C 0 80 % rh 5 4 3 2 1 0 50 C 0 100 % rh JP2 JP3 JP2 JP3 JP2 JP3 JP2 JP3 5.3 To reset the Modbus settings, put and hold jumper P1 for 20 seconds. (See Fig. 7 Modbus reset jumper.) 5.4 To select the temperature setpoint for relay 1 switching, use trimmer VR1. To select the relative humidity setpoint for relay 2 switching, use trimmer VR2 (Fig.8). Fig. 7 Modbus reset jumper Fig. 8 Setpoint trimmers Temperature Relative humidity 5 4 3 2 1 Put and hold for 20 seconds 6. Close the enclosure and fix the cover. 7. Switch on the power supply. MIW--EN-000-27 / 10 / 2015 www.sentera.eu 7-10

ATTENTION Do not exceed the maximum power supply rating! Measure before installation! Unregulated 24 VAC supply units provide higher nominal output voltage and activate the integrated fuse protection. ATTENTION If a G-type article is using the same AC power supply source (transformer) as F-type article, a SHORT CIRCUIT may result when the power supply and analogue signal terminals are connected to the same common ground! In this case always connect different article types to separate AC transformers or use the same article version. 8. Customise the factory settings to the desired ones through 3SModbus software (if necessary). For the default factory setting see Table Modbus register maps. MIW--EN-000-27 / 10 / 2015 www.sentera.eu 8-10

MODBUS REGISTER MAPS INPUT REGISTERS Data type Description Data Values 1 Temperature level Actual temperature level 50 50,0 C 2 Relative humidity level un Actual relative humidity level 1.00 100,0 % rh 3 Dew point Calculated dew point 20 20,0 C 4-10 Reserved, returns 0 11 Temperature output value Value of the analogue output for temperature - Ao1 0 1.000 12 Relative humidity output value Value of the analogue output for relative humidity - Ao2 0 1.000 13 Temperature relay status Status of the relay for temperature. When it is On, the contact between COM1 and NO1 is closed. 0 1 14 Relative humidity relay status Status of the relay for relative humidity. When it is On, the contact between COM2 and NO2 is closed. 0 1 15 Temperature Temperature working selected by jumper or a holding register 1 5 16 Relative humidity Relative humidity working selected by jumper or holding register 1 5 1.00 1.00 2 = 3 = 4 = 5 = 0 % 100 % 0 % 100 % Off On Off On 0 30 C 10 40 C 20 50 C 0 50 C Custom 20 90 % rh 2 = 0 60 % rh 3 = 0 80 % rh 4 = 0 100 % rh 5 = Custom 17 Temperature setpoint Temperature setpoint selected by trimmer or holding register 0 500 25 25,0 C 18 Relative humidity setpoint Relative humidity setpoint selected by trimmer or holding register 0 1.000 50 50,0 % rh 19 Temperature hysteresis Hysteresis for temperature relay switching 2 2,0 C 20 Relative humidity hysteresis Hysteresis for relative humidity relay switching 5 5,0 % rh 21 22 Temperature setpoint out of Relative humidity setpoint out of 23-29 Reserved, returns 0 Flag that shows if the temperature setpoint is out of the working 0 1 Flag that shows if the relative humidity setpoint is out of the working 0 1 30 Sensor communication lost un Flag that shows if the communication with the sensor module is lost 0 1 HOLDING REGISTERS Data type Description Data Default Values No Yes No Yes No Yes 1 Device slave address un Modbus device address 1 247 1 2 Modbus baud rate un Modbus communication baud rate 1 4 2 3 Modbus parity mode un Parity check mode 0 2 1 4 Device type un Device type (Read only) X = 1021 5 HW version un Hardware version of the device (Read only) XXXX 0 x 011 HW version 1.10 6 FW version un Firmware version of the device (Read only) XXXX 0x012 FW version 1.20 7 Operating mode un Enables Modbus control and disables the jumpers and trimmers 0 1 0 8 Output overwrite un Enables the direct control over the outputs. Always settable. Active only if holding register 7 is set to 1. 9-10 Reserved, returns 0 11 Temperature 12 Relative humidity 13 14 15 16 Minimum custom temperature Maximum custom temperature Minimum custom relative humidity Maximum custom relative humidity 17 Temperature setpoint 18 Relative humidity setpoint 19-20 Reserved, returns 0 21 22 Temperature output overwrite value Relative humidity output overwrite value Selects the temperature working. Always settable. Active only if holding register 7 is set to 1. Selects the relative humidity working. Always settable. Active only if holding register 7 is set to 1. Minimum value of the custom temperature. Always settable. Active only if holding register 7 is set to 1 and register 11 is set to 5. Maximum value of the custom temperature. Always settable. Active only if holding register 7 is set to 1 and register 11 is set to 5. Minimum value of the custom relative humidity. Always settable. Active only if holding register 7 is set to 1 and register 12 is set to 5. Maximum value of the custom relative humidity. Always settable. Active only if holding register 7 is set to 1 and register 12 is set to 5. Selects the setpoint for the temperature relay switching. Always settable. Active only if holding register 7 is set to 1. Selects the setpoint for the relative humidity relay switching. Always settable. Active only if holding register 7 is set to 1. Overwrite value for the temperature analogue output. Always settable. Active only if holding registers 7 and 8 are set to 1. Overwrite value for the relative humidity analogue output. Always settable. Active only if holding registers 7 and 8 are set to 1. 23-30 Reserved, returns 0 If you want to find out more about Modbus over serial line, please visit: http://www.modbus.org/docs/modbus_over_serial_line_v1_02.pdf 0 1 0 1 5 1 1 5 1 2 = 3 = 4 = 2 = 2 = 3 = 4 = 5 = 2 = 3 = 4 = 5 = 9.600 19.200 38.400 57.600 8N1 8E1 8O1 Standalone mode Modbus mode Disabled Enabled 0 30 C 10 40 C 20 50 C 0 50 C Custom 20 90 % rh 0 60 % rh 0 80 % rh 0 100 % rh Custom 0 Max 0 10 10,0 C Min 500 500 50 50,0 C 0 Max 0 20 20,0 % rh Min 1.000 1.000 1.00 100,0 % rh 0 500 250 25 25,0 C 0 1.000 500 50 50,0 % rh 0 1.000 0 0 1.000 0 1.00 1.00 0 % 100 % 0 % 100 % MIW--EN-000-27 / 10 / 2015 www.sentera.eu 9-10

VERIFICATION OF INSTALLATION INSTRUCTIONS Check the status of the blue ON/OFF LED after you switch on the power supply. (See Fig. 9 Operating indication.) The ON/OFF LED should blink during the initialization period (30 s) at equal intervals of 2 s for 2 s. Then it should give out continuous blue light. If this is not the case, check the connections again. If the LED blinks rapidly: it is possible that: you use improper power supply. Check it. the communication with the sensor module is not detected. Check the status of register 30 and if it is lost, contact authorised technical support or your sales representative. Check if both LEDs (LEDTX and LEDRX) blink after you switch on your unit. (See Fig. 10 Communication detection indication.) If they do, your unit has detected Modbus network. If they blink rapidly, it is possible that: Fig. 9 Operating indication Fig. 10 Communication detection indication ATTENTION The status of both LEDs (LEDTX and LEDRX) can be checked only when the unit is energised. Take the relevant safety measures! ATTENTION In case of lost communication with the sensor module, the analogue outputs will rise to maximum and the relays will switch on. The sensor status can be checked in input register 30! TRANSPORT AND STOCK KEEPING INFORMATION Avoid shocks and extreme conditions; stock in original packing. WARRANTY INFORMATION AND RESTRICTIONS MAINTENANCE Two years from the delivery date against defects in manufacturing. Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities. The manufacturer bears no responsibility for any misprints or mistakes in this data. In normal conditions this product is maintenance-free. If soiled, clean with a dry or dampish cloth. In case of heavy pollution, clean with a non aggressive product. In these circumstances the unit should be disconnected from the supply. Pay attention that no fluids enter the unit. Only reconnect it to the supply when it is completely dry. MIW--EN-000-27 / 10 / 2015 www.sentera.eu 10-10