COMMUNICATION M-BUS PROTOCOL CE4DMID0M (MBus meter)

Similar documents
COMMUNICATION M-BUS PROTOCOL PR 118

SF-586x: M-Bus Extension

M-BUS Standard acc. EN AE.05:04.01: Protocol Specification

M-BUS PROTOCOL for ML 311

GNM1D M-BUS COMMUNICATION PROTOCOL. Revision 0

EM111-EM112 M-BUS COMMUNICATION PROTOCOL. Revision 4.0

GNM3D M-BUS COMMUNICATION PROTOCOL. Revision 1

0xc1 (Mass) 0xc2 (Flow) 0xc3 (Reserved) 0xc4 (BDE) 0xc5 (AMTRON X-50) 0xc6 (AMBILL) 0xc7 (TGR) 0xc8 (BDV) 0xc9 (DTF)

Technical Description. Wired M-Bus. Water Meters flowiq 2101/3100

M-Bus protocol CALEC energy master

OMS Vol.2 Primary Elster Implementation

EEM230-D-M. Energy meters. Electrical Energy Meter with integrated M-Bus interface

EEM230-D-M. Energy meters. Electrical Energy Meter with integrated M-Bus interface

FLOW 38 v8.x. M-Bus communication protocol specification

Heat meter PolluStat M-bus communication protocol description

DRT-205C M-Bus Protocol V1.1

COMMUNICATION MODBUS PROTOCOL

1 ABBREVIATIONS VERSION M-BUS PROTOCOL SUMMARY OF M-BUS DATA TYPES...15

Singlephase Energy meter with M-Bus interface

TS2M-Bus Protocol Converter / User Manual

COMMUNICATION MODBUS PROTOCOL

3-phase energy meters with M-Bus interface

M-Bus Slaves for MULTICAL 601

FALCON PR6/PR7 Operating instructions M-Bus module for Elster water meter with Falcon register

SONOMETER 1100 Communication description MBus ID = 0x2F

CE4DMID01 COMMUNICATION PROTOCOL CONTENTS 1.0 INTRODUCTION

Assembly. Assembly. Connections Main circuit. Connections Control circuit. Insulation properties

SCYLAR INT 7. Communication description. Software Version 01

COMMUNICATION MODBUS PROTOCOL MF96001 / 021 NEMO 96HD

Flex M-Bus for F3/4 1(11) SVM Implementation of M-Bus in F3/4 meter

FALCON MJ Pulse/M-Bus operating instructions M-Bus module for Honeywell / Elster M100i and M120i waters meters

SHARKY BR773. Communication Description. Software Version 28

T230 heat meter or cold meter

M-Bus Pulse Collector Twin-Pulse Instruction Manual

Venstar Thermostat Adapter

GmbH, Stettiner Str. 38, D Paderborn

COMMUNICATION MODBUS PROTOCOL

Conto D2 COMMUNICATION PROTOCOL CONTENTS 1.0 INTRODUCTION

Sommario. COMMUNICATION PROTOCOL PR 150 Rev. A 31/01/2018 Pag 1 Multifunction Firmware NEMO 96 EA ModBus

COMMUNICATION MODBUS PROTOCOL

DMTME Multimeters. Communication protocol. Technical specification V1.2 ABB

Supercom 636. Manual Radio Modem. Issue: Rev Document: Manual Supercom 636 R+W rev

Citect for Windows, Version 5.xx, 6.xx. M-Bus driver, User information

Mounting instruction Gateway M-Bus Master AMB8466-M-GMM Release 1.2

M2M/DMTME Instruments Communication protocol. Technical specification V.2.1 2CSG445011D0201

jmbus User Guide Fraunhofer Institute for Solar Energy Systems ISE openmuc.org

INSTEON Hidden Door Sensor

RelAir R2M PRO / HOME

CLOCKAUDIO. MR88 Automatic Microphone Mixer RS232 Programming Version 4.2

AN-881 APPLICATION NOTE

SwitchLinc 2-Wire Dimmer (RF Only) (2474DWH - Dev 0x01 / Sub 0x24)

Technical Specification. Third Party Control Protocol. AV Revolution

CTT MODBUS-RTU COMMUNICATION PROTOCOL TEMPERATURE MONITOR DEVICE

GmbH, Stettiner Str. 38, D Paderborn. PadPuls M4L. Art.-No. IM002G: (Valid from M-Bus generation: $12)

The RS-485 user manual for B800 series communication

Micro Module Shutter. Micro Module Shutter

GmbH, Stettiner Str. 38, D Paderborn. PadPuls M2. Art.No.: IM003G + IM003GB. (Valid from M-Bus generation: $40)

C1098 JPEG Module User Manual

CMa10,CMa11 Users Manual English ELVACO-CMa10 M-Bus Tempsensor; CMa11 M-Bus Temperatursensor

IF96017 MODBUS COMMUNICATION PROTOCOL

Operating Instructions

JUMO ctron 04/08/16. Compact controller with timer and ramp function. B Interface Description Modbus /

CAN Bus Quick Start Guide

Logosol Joystick Node LS-731

CODA Online Data Formats

GNetPlus Communication Protocol

FN-BC04 MP3 Sound Module with 10W Amplifier. User s Manual

Proposal for future M-Bus Application Layer

Developer Notes for KeypadLinc Line

PROTOCOL COMMUNICATION pag. 1/22 NEMO 96 HD/HD+ Profibus DP Interface. Application manual

Developer Notes INSTEON Thermostat v012. Developer Notes. INSTEON Thermostat. Revision History

M-BUS/MODBUS CONFIGURATION SOFTWARE FOR GINEERS MMCR-64

Modbus Protocol For FTS/FTM 3x&8x

Driver Manual. FS M-Bus

Version Action Author Date

Touch Encoder. Interface Control Document (CANBUS J1939 Protocol)

Input Channels: 4 differential or four single-ended. Address / Baud rate / range configurable by the user

20 Channel MP3 Sound Board. User s Manual. Model: FN-BC20

Technical Documentation 0630

Modbus/TCP is supported on some controllers. See QCI-AN028 Modbus TCP.

JUMO Quantrol LC100/LC200/LC300

Communication protocols description of. Hx4xx and Hx3xx regulators with RS485 and RS232 communication interface

Interface Card, Interface Box, Datalogger & Interface. Bedienungsanleitung. Kommunikationsprotokoll. Operating Instructions. Communications protocol

Application Note: Using Modbus With the Conext CL Series. Important Safety Instructions

MODBUS Protocol. The ecode Encoders contain both single register (16 bit) and double register (32 bit) values.

MODBUS Protocol Specification. MODBUS Protocol Specification V2.0

FieldServer FS M-Bus

EM210 COMMUNICATION PROTOCOL. Version 3 Revision 3

MCW Application Notes 24 th February 2017

B Interface description 12.01/

TKB Description of the Serial Interface 2WR6

Operating Instructions RMx621

Specification E2 Interface

M-Bus Master Manual. M-Bus Master. Manual. Version 2.0 1/10

Planar Simplicity Series

Specifiche generali protocollo MODBUS-RTU Rev. 10 (inglese) REVISIONS

Aeroflex Colorado Springs Application Note

Conto D1 MODBUS COMMUNICATION PROTOCOL

Chapter 2 Number System

PowerKey 1000 J1939 user manual

Transcription:

COMMUNICATION M-BUS PROTOCOL CE4DMID0M (MBus meter) PR144 Rev A Fw. Version 2.00 16/02/2018 Pag. 1/17 1. Standard M-Bus telegrams... 3 1.1 Request for Data (REQ_UD2 )... 3 1.2 Details of telegrams 1,2,3... 7 1.2.1 Telegram 1... 7 1.2.2 Telegram 2... 8 1.2.3 Telegram 3... 9 3. Primary address reading... 10 4. Read the secondary address... 11 5. Application Reset... 12 6. Selection through Secondary Addressing... 13 7. Writing and reading of Baud rate... 14 8. FCB bit management... 16

COMMUNICATION M-BUS PROTOCOL Pag. 2/17 Rev DESCRIPTION Date Sw A First issue 09/01/2018 2.620 BEFORE READING In the setup there is an option that can be used to change the mode accordingly to which the meter answers to demands of data issued by the master. This option is named : SArS : Secondary Address reset Sequence For a detailed description of the FCB management, refer to the chapter of interest.

1. Standard M-Bus telegrams COMMUNICATION M-BUS PROTOCOL Pag. 3/17 1.1 Request for Data (REQ_UD2 ) REQ_UD2 CODE Description 10h Start 5B/7Bh C field : Request for Data PADR A field : device address 0..250 /254 CS CheckSum = (10h+5B/7Bh+PADR) mod 100h 16h Stop

COMMUNICATION M-BUS PROTOCOL Pag. 4/17 Answer to Request for Data (REQ_UD2 ) See in the following table the summary of the 3 basic telegrams. RSP_UD - 1st message Symbol Sequence UNIT DIF DIFE(1) DIFE(2) DIFE(3) VIF VIFE FORMAT LINE Et+ Active positive Energy (primary side total Energy) 0 0x04 0x84 0X3B INT 32 1 P+ ΣP+ 0 0x04 0xAB 0x3B INT 32 2 P- ΣP- 0 0x04 0xAB 0x3C INT 32 3 Er+ Reactive positive energy 1 0x84 0x40 0x84 0X3B INT 32 4 Q+ ΣQ+ 1 0x84 0x40 0xAB 0x3B INT 32 5 Q- ΣQ- 1 0x84 0x40 0xAB 0x3C INT 32 6 Part Et+ Active energy (terminal side base energy) 2 0x84 0x40 0x84 0X3B INT 32 7 Part Er+ Null (RFU) 3 0x84 0xC0 0x40 0x84 0x3B INT 32 8 Et- Null (RFU) 4 0x84 0x80 0x80 0x40 0x84 0X3C INT 32 9 Er- Null (RFU) 5 0x84 0xC0 0x80 0x40 0x84 0x3C INT 32 10 RSP_UD - 2nd message Symbol Sequence UNIT DIF DIFE(1) DIFE(2) DIFE(3) VIF VIFE FORMAT LINE L1-N V1 2 0x84 0x80 0x40 0xFD 0x48 INT 32 11 I1 I1 2 0x84 0x80 0x40 0xFD 0x59 INT 32 12 P1+ P1 2 0x84 0x80 0x40 0xAB 0x3B INT 32 13 P1- P1-negative 2 0x84 0x80 0x40 0xAB 0x3C INT 32 14 L2-N V2 3 0x84 0xC0 0x40 0xFD 0x48 INT 32 15 I2 I2 3 0x84 0xC0 0x40 0xFD 0x59 INT 32 16 P2+ P2 3 0x84 0xC0 0x40 0xAB 0x3B INT 32 17 P2- P2-negative 3 0x84 0xC0 0x40 0xAB 0x3C INT 32 18 L3-N V3 4 0x84 0x80 0x80 0x40 0xFD 0x48 INT 32 19 I3 I3 4 0x84 0x80 0x80 0x40 0xFD 0x59 INT 32 20 P3+ P3 4 0x84 0x80 0x80 0x40 0xAB 0x3B INT 32 21 P3- P3-negative 4 0x84 0x80 0x80 0x40 0xAB 0x3C INT 32 22 L1-L2 V12 5 0x84 0xC0 0x80 0x40 0xFD 0x48 INT 32 23 Q1+ Q1 5 0x84 0xC0 0x80 0x40 0xAB 0x3B INT 32 24 Q1- Q1-negative 5 0x84 0xC0 0x80 0x40 0xAB 0x3C INT 32 25 L2-L3 V23 6 0x84 0x80 0xC0 0x40 0xFD 0x48 INT 32 26 Q2+ Q2 6 0x84 0x80 0xC0 0x40 0xAB 0x3B INT 32 27 Q2- Q2-negative 6 0x84 0x80 0xC0 0x40 0xAB 0x3C INT 32 28 L1-L3 V13 7 0x84 0xC0 0xC0 0x40 0xFD 0x48 INT 32 29 Q3+ Q3 7 0x84 0xC0 0xC0 0x40 0xAB 0x3B INT 32 30 Q3- Q3-negative 7 0x84 0xC0 0xC0 0x40 0xAB 0x3C INT 32 31

COMMUNICATION M-BUS PROTOCOL Pag. 5/17 RSP_UD - 3rd message Symbol Sequence UNIT DIF DIFE(1) DIFE(2) DIFE(3) DIFE(4) VIF VIFE FORMAT LINE PF Power factor 8 0x82 0x80 0x80 0x80 0x40 0xEE 0x3B INT 16 32 PF- Power factor - 8 0x82 0x80 0x80 0x80 0x40 0xEE 0x3C INT 16 33 Fr Frequency 9 0x82 0xC0 0x80 0x80 0x40 0x6E INT 16 34 Current ratio (KTA) 10 0x84 0x80 0xC0 0x80 0x40 0x6E INT 32 35 Voltage ratio (KTV) 11 0x84 0xC0 0xC0 0x80 0x40 0x6E INT 32 36

COMMUNICATION M-BUS PROTOCOL Pag. 6/17 Position Description Byte Data type 1 3-phase Active Positive Energy 4 Type B, Binary Integer 2 3-phse Active Positive Power 4 TELEGRAM 1 3 3-phase Active Negative Power 4 4 3-phase Reactive Positive Energy 4 5 3-phase Reactive Positive Power 4 6 3-phase Reactive Negative Power 4 7 3-phase Active Partial Energy 4 8 3-phase Reactive Partial Energy 4 9 3-phase Active Negative Energy 4 10 3-phase Reactive Negative Energy 4 11 Pad bytes 5 12 Voltage L1 4 Type B, Binary Integer 13 Current I1 4 TELEGRAM 2 14 Active Power L1 4 15 Negative Active Power L1 4 16 Voltage L2 4 17 Current I2 4 18 Active Power L2 4 19 Negative Active Power L2 4 20 Voltage L3 4 21 Current I3 4 22 Active Power L3 4 23 Negative Active Power L3 4 24 Voltage L1-L2 4 25 Reactive Power L1 4 26 Negative Reactive Power L1 4 27 Voltage L2-L3 4 28 Reactive Power L2 4 29 Negative Reactive Power L2 4 30 Voltage L3-L1 4 31 Reactive Power L3 4 32 Negative Reactive Power L3 4 33 Pad bytes 5 34 Power Factor 2 Type B, Binary Integer 35 Negative power factor 2 TELEGRAM 3 36 Frequency 2 37 Current Transform Ratio KTA 4 38 Voltage Transform Ratio KTV 4 39 Power Factor L1 2 40 Negative Power Factor L1 2 41 Power Factor L2 2 42 Negative Power Factor L2 2 43 Power Factor L3 2 44 Negative Power Factor L3 2 45 Pad bytes 5

COMMUNICATION M-BUS PROTOCOL Pag. 7/17 1.2 Details of telegrams 1,2,3 Details of the telegrams (all values are hexadecimal). 1.2.1 Telegram 1 RSP_UD Field Name Byte n. Value Meaning Start 1 68 Start byte L-f 1 LEN Frame number byte L-f 1 LEN Frame number byte Start 1 68 Start byte C-f 1 08 RSP_UD A-f 1 PADR 0..250 CI-f 1 72 Variable structure,lsb is trasmitted first Secondary address 4 IDENT XXXXXXXX (8 BCD digits) Manufacturer code 2 A5 25 IME = 25A5 Device version 1 GEN Version Medium 1 02 Electricity Access number 1 TC incremented by 1 for any aswered telegram Status 1 STAT Status (*) Signature 2 00 00 Not used (**) DIF 1 1F more records will follow in next telegram Value 5 0000000000 PAD bytes Checksum 1 CS Stop 1 16 (**) data in lines 1.. 10 of telegram n.1

COMMUNICATION M-BUS PROTOCOL Pag. 8/17 1.2.2 Telegram 2 RSP_UD Field Name Byte Number Value Meaning Start 1 68 Start byte L-f 1 LEN Frame number byte L-f 1 LEN Frame number byte Start 1 68 Start byte C-f 1 08 RSP_UD A-f 1 PADR 0..250 CI-f 1 72 Variable structure,lsb is trasmitted first Secondary address 4 IDENT XXXXXXXX (8 BCD digits) Manufacturer code 2 A5 25 IME = 25A5 Device version 1 GEN Version Medium 1 02 Electricity Access number 1 TC incremented by 1 for any aswered telegram Status 1 STAT Status (*) Signature 2 00 00 Not used (**) DIF 1 1F More records will follow in next telegram Value 5 0000000000 PAD bytes Checksum 1 CS Stop 1 16 (**) data in lines 11.. 31 of telegram n.2

COMMUNICATION M-BUS PROTOCOL Pag. 9/17 1.2.3 Telegram 3 RSP_UD Field Name Byte Number Value Meaning Start 1 68 Start byte L-f 1 LEN Frame number byte L-f 1 LEN Frame number byte Start 1 68 Start byte C-f 1 08 RSP_UD A-f 1 PADR 0..250 CI-f 1 72 Variable structure, LSB is trasmitted first Secondary address 4 IDENT XXXXXXXX (8 BCD digits) Manufacturer code 2 A5 25 IME = 25A5 Device version 1 GEN Version Medium 1 02 Electricity Access number 1 TC incremented by 1 for any answered telegram Status 1 STAT Status (*) Signature 2 00 00 Not used (**) DIF 1 0F Indicating that this is the last telegram Value 5 0000000000 PAD bytes Checksum 1 CS Stop 1 16 (**) data in lines 32.. 36 of telegram n.3

COMMUNICATION M-BUS PROTOCOL Pag. 10/17 2. Initialization of Slave (SND_NKE) To start or initialize the communication Master sends this telegram to Slave : SND_NKE command Type : short frame CODE Description 10h Start 40h C field : initialization PADR A field : device address 0..250 /254/255 CS CheckSum = (10h+40h+PADR) mod 100h 16h Stop If the Slave receives SND_NKE it resets TC counter of sent telegrams and answers with E5. 3. Primary address reading SND_UD command Type : long frame To read Primary Address send a SND_UD telegram and then REQ_UD2. This command must be sent in a point to point mode to read out the primary address of a device which the user doesn t know the primary address of (so the demand is in broadcast). Field Name Number of byte Value Meaning Start 1 68h Start L-f 1 05h Header L-f 1 05h Start 1 68h C-f 1 53h/73h SND_UD A-f 1 FE Broadcast Address CI-f 1 51h Data send DIF 1 08h Selection for Readout VIF 1 7Ah Check Sum 1 CS Stop 1 16h Stop Answer : 01 7A 01 (in blue) : 01 is the device primary address

4. Read the secondary address Type : long frame COMMUNICATION M-BUS PROTOCOL Pag. 11/17 To read the Secondary Address send a SND_UD telegram and then REQ_UD2 : Command Field Name Number of byte Value Meaning Start 1 68h Start L-f 1 05h Header L-f 1 05h Start 1 68h C-f 1 53h/73h SND_UD A-f 1 PADR Primary Address CI-f 1 51h Data send DIF 1 08h VIF 1 79h Check Sum 1 CS Stop 1 16h Stop Answer SND_UD 68 05 05 68 73 FE 51 08 79 43 16 E5 h Answer REQ_UD2 10 5B FE 59 16 RSP_UD 68 15 15 68 08 01 72 78 56 34 12 A8 15 00 02 0E 00 00 00 0C 79 78 56 34 12 F5 16 Primary address : FE (in this broadcast point to point just for example) Secondary address : 78 56 34 12 (8 BCD digits) but LSB before and MSB at the end so : Real value : 12 34 56 78

COMMUNICATION M-BUS PROTOCOL Pag. 12/17 5. Application Reset Type : control frame The device allows the application reset command After this message the device resets the answer counter, the pending selection frame, the error flags and responds with the ACK character (E5h) : Field Name Byte n. Value Meaning Start 1 68h L-f 1 03h Header L-f 1 03h Start 1 68h C-f 1 53h/73h SND_UD A-f 1 PADR Primary Address CI-f 1 50h Application reset Check Sum 1 CS Stop 1 16h

6. Selection through Secondary Addressing Type : long frame COMMUNICATION M-BUS PROTOCOL Pag. 13/17 In an M-Bus network it is possible to have maximum 250 participants with primary addresses from 1 to 250. The address 0 is used for a not configured device. If there are more than 250 devices, it is mandatory to use the secondary address. Master sends the following SND_UD telegram to a Slave to select it : Field Name Byte n. Value Meaning Start 1 68h L-f 1 0Bh Header L-f 1 0Bh Start 1 68h C-f 1 53h/73h SND_UD A-f 1 FDh Primary Address CI-f 1 52h Value 4 X1X0 X3X2 X5X4 X7X6 Secondary Address Manufacturer code 2 A5 25 IME = 25A5 Device version 1 Binary Version (1.00 => 100 = 64h) Medium 1 02 Electricity Check Sum 1 CS Stop 1 16h The Primary address used is FDh If there is a Slave having the Secondary Address specified X7X6 X5X4 X3X2 X1X0, with the right Manufacturer code, Device version and Medium it will respond with an ACK (0xE5) character otherwise there will be no answer. If the Slave is correctly selected, it changes its state in selected. This means that it will answer with a RSP_UD to all commands REQ_UD2, issued to the Slave. The Slave remains in a selected state until it receives either a selection command to a different Secondary Address or a SND_NKE command to Address 0xFD. In the Selection command it is allowed to use 0xF wild card instead of any digit of Manufacturer code, Device version and Medium. For example 0xFFFF instead of 0xA525, 0xFF instead of 0x1D and 0xFF instead of 0x02. Example Secondary address : SND_UD Answer [68][0b][0b][68][53][fd][52][02][00][00][00][a5][25][14][02][8d][16] E5 h

COMMUNICATION M-BUS PROTOCOL Pag. 14/17 7. Writing and reading of Baud rate Type : long frame Writing To write Baud rate it is necessary to send a SND_UD telegram : Field Name Number of Value Meaning byte Start 1 68h Start L-f 1 03h Header L-f 1 03h Start 1 68h C-f 1 53h/73h SND_UD A-f 1 PADR Primary Address Value 1 XXh Data send Check Sum 1 CS Stop 1 16h Stop Parameter : XX h : B8 h -> 300 b/s B9 h -> 600 b/s BA h -> 1200 b/s BB h -> 2400 b/s BC h -> 4800 b/s BD h -> 9600 b/s NOTE When Slave receives this telegram, before it sends E5h as confirmation at current Baud Rate and then changes its Baud Rate to the new. Writing of a Baud Rare of 2400 SND_UD 68 03 03 68 73 53 00 BB 0E 16 Answer E5 h

COMMUNICATION M-BUS PROTOCOL Pag. 15/17 Reading To read Baud rate it is necessary to send a SND_UD telegram and then a REQ_UD2 : Field Name Number of byte Value Meaning Start 1 68h Start L-f 1 06h Header L-f 1 06h Start 1 68h C-f 1 53h/73h SND_UD A-f 1 PADR Primary Address CI-f 1 51h Data send DIF 1 08h Selection for Readout VIF 1 FFh VIFE 1 42h Baud rate Check Sum 1 CS Stop 1 16h Stop Reading of a Baud Rate of 300 SND_UD 68 06 06 68 53 01 FE 51 08 FF 42 EB 16 Answer E5 h REQ_UD2 10 7B FE 79 16 Answer 68 13 13 68 08 FD 72 01 00 00 00 A8 15 00 02 94 00 00 00 01 FF 42 00 7C 16

8. FCB bit management COMMUNICATION M-BUS PROTOCOL Pag. 16/17 If the option SArS is set on YES, every time the master selects the slave using the secondary address, the telegram (data messages) sequence is restarted from the telegram n. 1 In this case, the FCB bit continues toggling normally. If a FCB bit is received that is equal to the preceding, the meter does not repeat the last telegram (as it should do in other situations) and responds with the toggled FCB bit. Table below shows the coding of the individual bits of the C field: Bit 7 : it is reserved for future functions, and at present is 0 Bit 6 : it is used to specify the direction of data flow (1 = Master to Slave; 0 = Slave to Master). Frame Count Bit FCB : it is toggled when the slave has answered correctly. E.g. master sends FCB=0, slave returns a valid answer, master sends FCB=1 and vice versa (0.. 1.. 0) Frame Count Bit valid FCV : 0 : the toggle management must be ignored 1 : the toggle management must be used Bits F3 F2 F1 F0 : they specify the function that must be performed by the slave. When the meter answers 0x5B that means the FCB bit is = 0 and vice versa when answering 0x7B

COMMUNICATION M-BUS PROTOCOL Pag. 17/17 Example giving Case 1 SArS = NO (Master) Selection command of secondary address (Slave) E5 (Master) REQ_UD2 command with FCB = 0x5B (Slave) Message response telegram n. 1 (Master) REQ_UD2 command with FCB = 0x7B (Slave) Message response telegram n. 2 (Master) REQ_UD2 command with FCB = 0x5B (Slave) Message response telegram n. 3 (Master) Selection command of secondary address (Slave) E5 (Master) REQ_UD2 command with FCB = 0x5B (Slave) Message response telegram n. 3 (The previous telegram is repeated as the FCB bits are the same before and after the selection) Case 2 SArS = YES (Master) Selection command of secondary address (Slave) E5 (Master) REQ_UD2 command with FCB = 0x5B (Slave) Message response telegram n. 1 (Master) REQ_UD2 command with FCB = 0x7B (Slave) Message response telegram n. 2 (Master) REQ_UD2 command with FCB = 0x5B (Slave) Message response telegram n. 3 (Master) Selection command of secondary address (Slave) E5 (Master) REQ_UD2 command with FCB = 0x5B (Slave) Message response telegram n. 1 (The telegram sequence is restarted due to the selection) The Application Reset command has the effect to completely restart the telegram sequence.