PHOENIX CONTACT - 10/2009

Similar documents
FL SWITCH SFNB. Five- and Eight-Port Standard Function Ethernet Switch with Narrow Housing. AUTOMATION Data Sheet 2642_en_H.

PHOENIX CONTACT - 06/2006

PHOENIX CONTACT - 02/2007

FL SWITCH SFN(T) 16-Port Standard Function Ethernet Switches for Normal and Extreme Environments. AUTOMATION Data Sheet 2806_en_C

FL SWITCH LM 8TX(-E) FL SWITCH LM 4TX/2FX(-E) FL SWITCH LM 4TX/2FX SM(-E)

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B

FL MC 2000E (SM40) LC

PHOENIX CONTACT - 11/2008

ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors

FL SWITCH 8TX. Extract from the online catalog. Discontinued item. Order No.:

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

FL SWITCH Factoryline 5- and 8-port managed switches with optional fiber optic ports and wide temperature ratings. Data sheet.

onlinecomponents.com

PHOENIX CONTACT - 07/2006

IBS IL 24 RB-LK-2MBD:

FL SWITCH SFN 5TX. Extract from the online catalog. Order No.:

PHOENIX CONTACT - 04/2008

PHOENIX CONTACT - 11/2007. This data sheet is only valid in association with the IB IL SYS PRO UM E user manual.

PSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1

MINI MCR-SL-PT100-UI(-SP)(-NC)

Stride Industrial Ethernet Switches

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

FL MC EF 1300 SM SC. FO converter with SC duplex fiber optic connection (1300 nm), for converting 10/100Base-T(X) to single-mode fiberglass (9/125 μm)

PHOENIX CONTACT - 05/2007

VL BPC MINI. A configurable industrial computer platform. Data sheet 2930_en_F. 1 Description. 2 Features

VL BPC MINI. A configurable industrial computer platform Intel Atom Z510PT CMAT IPC Module Option [I28] AUTOMATION Data Sheet 2930_en_A.

MINI MCR-SL-UI-2I(-SP)(-NC)

FLM DI 8 M12. Function. Fieldline Modular Device With Eight Digital Inputs. Data Sheet

IES User Manual. 8 FE + 1 MM SC Unmanaged Switch -40 to 75, DIN-rail. v

This data sheet is only valid in association with the IL SYS INST UM E user manual.

FL MC EF 1300 MM ST. FO converter with B-FOC (ST ) connection (1300 nm), for converting 10/100Base-T(X) to multi-mode fiberglass (50/125 µm)

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

FL MC 10/100BASE-T/FO-660

Stride SE2 Series Unmanaged Industrial Ethernet Switches and Media Converters

onlinecomponents.com

MINI-PS AC/10-15DC/8

1 10/100TX FX w/ 1 PoE Injector Industrial Switch. User Manual

Ha-VIS econ 2000 Fast and Full Gigabit Ethernet Basic. Features

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

Hardened Media Converter

Hardened PoE Ethernet Switch

PSI-MODEM-SHDSL/PB. Broadband PROFIBUS extender, SHDSL PROFIBUS leased line modem. Data sheet _en_03. 1 Description. 1.

AXL BK PN (-ME) Axioline bus coupler for PROFINET IO. Data sheet. 1 Description

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B

Industrial Ethernet Switch

XPress-Pro SW Series Hardened Ethernet Switches Enabling Communication for the Demanding Industrial Environment

PSI-MODEM-SHDSL/SERIAL

PHOENIX CONTACT

Valueline Industrial PC

QUINT-PS-3x AC/24DC/10

Power Input Assignment Power1 12VDC DC Jack VDC Power2 - Power Ground

PHOENIX CONTACT - 12/2007

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

PI-EX-ME-2NAM/COC-120VAC

VL BPC 100. Valueline configurable box PC. Data sheet 3063_en_E. 1 Description. 2 Features

TRIO-DIODE/12-24DC/2X10/1X20

PI-EX-ME-2NAM/COC-24VDC

ETD-BL-1T-230(-PT) Multifunctional time relay with various functions and adjustable times. Data sheet. 1 Description

PSI-MOS-RS422/FO 850 T

Industrial 3-Port Fast Ethernet Media Converter Switches

Quick Start Guide Elinx ESW200 Series. 5 and 8 port Unmanaged Ethernet Switch

MINI MCR-SL-PT100-UI. Active resistance thermometer measuring transducer. Data sheet. 1 Description

User Manual Entry Line Industrial Fast Ethernet Switch 5x 10/100Base-TX

Redundancy Module QUINT-DIODE/40

10/100TX to 100FX w/ 1 PoE Injector Industrial Media Converter User Manual

Industrial Switches Industrial Switches

MINI MCR-SL-PT100-UI-200

Quick Start Guide. Physical Description.

AXL E IOL AO1 U M12 R

PHOENIX CONTACT Features

PSR-PS21. SIL coupling relay. Data sheet. 1 Description

Industrial Ethernet Switch. Signamax Connectivity Systems. Industrial Ethernet Switch. Model A Series. User s Guide

IB IL 24 DI 16 IB IL 24 DI 16-PAC

Power Input Assignment Power1 12VDC DC Jack VDC Power2 - Power Ground

ILB DN 24 DI16 DO16. Inline Block IO Module for DeviceNet With 16 Digital Inputs and 16 Digital Outputs. AUTOMATIONWORX Data Sheet 6885_en_05

Quick Start Guide Elinx ESW100 Series. 5 and 8 port Unmanaged Ethernet Switch

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

Quick Start Guide. Physical Description. The Port Status LEDs

MINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description

KSD-800 Series. Installation Guide. Industrial 8-Port Fast Ethernet Switches with Fiber Connectivity DOC A -1-

QUINT-BUFFER/24DC/24DC/40

IBS IL 24 BK RB-T-2MBD

FL MC EF WDM... Ethernet FO converter for bidirectional data transmission via a single optical fiber (SC simplex) Data sheet.

Quick Start Guide. Installation. User s Manual 1

General. 5 and 8 port Fast Ethernet switches. 6 and 8 Port Gigabit Ethernet switches. Switches with fiber uplink

MINI MCR-SL-CVS NC

Ethernet. RJ45 Copper Ports

PSR-PC20. SIL coupling relay. Data sheet. 1 Description

Device Server for the conversion of serial interfaces (RS-232/422/485) to IP.

8-port 10/100TX + 2-Port 10/100/1000T/100/1000 SFP Combo with 8 PoE Injectors Industrial Ethernet Switch User Manual

PHOENIX CONTACT - 07/2005

Hardened 10/100Base-TX IEEE802.3at PoE PSE Ethernet Extender

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

PTC-101-M12 Hardware Installation Guide

Hardened Web-Smart PoE & High Power PoE Ethernet Switch

EL1142 Series. IEC / IEEE 1613 Hardened 2-Port 10/100BASE-TX to 2-Port 100BASE-FX Media Converter. User s Guide

LNP-0602 series. 6-port Industrial PoE+ Unmanaged Ethernet Switches 4*10/100Tx (30W/Port) + 2*100Fx. User Manual

10/100/1000T to Mini-GBIC Industrial Switch Converter 10/100/1000T to 1000SX/LX Industrial Switch Converter. AMG9011G-H (-40 to 75C) User Manual

ETD-BL-1T-OFF-CC- 10S

Transcription:

Factory Line Switches With Standard Functions AUTOMATIONWORX Data Sheet PHOENIX CONTACT - 10/2009 Description The range of Factory Line switches with standard functions in numerous versions can be used for quick and cost-effective Ethernet network expansion. The switches have 8 or 16 ports, up to two of which are multimode glass fiber ports provided in the SC or ST format. The twisted pair ports of the switches support both Ethernet with a transmission speed of 10 Mbps and Fast Ethernet with a transmission speed of Mbps. The glass fiber ports only support Mbps. The switches regenerate received data telegrams and send them to the port to which the device is connected with the corresponding target address. Features and Fields of Application Increased network performance by filtering the data traffic. - Local data traffic remains local. - The data volume in the network segments is reduced. Easy network expansion without configuration of the switch. Coupling copper network segments with different bit rates. - Automatic detection of the data transmission speed of 10 or Mbps. Auto negotiation: Each copper port establishes a half or full duplex connection with 10 or Mbps. Auto crossing: It is not necessary to make a distinction between 1:1 or crossover Ethernet copper cables. Electrical isolation of network segments using up to two fiber optic ports. Increasing the maximum cable length to 10,000 m (62.5/125 μm) or to 6400 m (50/125 μm) using a fiber optic port. Floating alarm output: The alarm output can be used to monitor the redundant voltage supply. Please note the different connection directions of the transmission media: Copper cables are connected at the front, glass fiber cables at the bottom. Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at www.download.phoenixcontact.com/general/7000_en_00.pdf. This data sheet is valid for the products listed on page 12 under "Ordering Data". 7009_en_06 PHOENIX CONTACT GmbH & Co. KG Flachsmarktstraße 8 32825 Blomberg Germany 1 Phone: +49-(0) 5235-3-00 Fax: +49-(0) 5235-3-4 12 00 www.phoenixcontact.com www.phoenixcontact.com/salesnetwork

Housing Versions and Position of the Fiber Optic Connections The housings of the 8-port versions are identical. On the fiber optic versions, the connections for the fiber optic ports are at the bottom (see also Figure 2). US1 GND US2 GND R1 R2 NC US1 GND US2 GND R1 R2 NC X7 X8 US1 US2 X9 X7 US1 US2 X9 X5 X6 X5 X6 FL SWITCH SF 7TX/FX ST Ord. No.2832577 X3 X1 X4 X2 X3 X1 X4 X2 X8 FL SWITCH SF 8TX Ord.-No.: 2832771 TD RD 700900 Figure 1 Housing examples for 8-port switches - FL SWITCH SF 8TX (left) / FL SWITCH 7TX/FX ST (right) The housings of the 16-port versions are identical. On the fiber optic versions, the connections for the fiber optic ports are at the bottom. X7 US1 US2 X17 X15 X16 X5 X6 FL SWITCH SF 14TX/2FX Ord.-No.: 2832593 X13 X14 X8 X9 X3 X4 X11 X12 X1 X2 X10 Figure 2 Housing example for 16-port switches (FL SWITCH 14TX/2FX) 7009_en_06 PHOENIX CONTACT 2

Local Diagnostic and Status Indicators Des. Color Status Meaning US1 Green ON Supply voltage US1 in the tolerance zone OFF Supply voltage US1 too low US2 Green ON Supply voltage US2 in the tolerance zone OFF Supply voltage US2 too low One LED per port Green ON Link active Flashing Active telegram OFF Link not active Yellow ON Data transmission speed Mbps OFF Data transmission speed not Mbps General Information Warning Disregarding this warning may result in damage to equipment and/or serious personal injury. Only qualified personnel may start up and operate this device. According to the safety instructions in this text, qualified personnel are persons who are authorized to start up, to ground, and to mark devices, systems, and equipment according to the standards of safety technology. In addition, these persons must be familiar with all warning instructions and maintenance measures in this text. Warning The module is designed exclusively for SELV operation according to IEC 950 / EN 60950 / VDE 0805. Warning A.) THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I, ZONE 2, GROUPS A,B,C, AND D OR NON- HAZARDOUS LOCATIONS ONLY. B.) WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, ZONE 2. C.) WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS. 7009_en_06 PHOENIX CONTACT 3

Installation and Mounting/Removal Install the module on a clean DIN rail. To avoid contact resistance only use clean, corrosion-free DIN rails. End clamps can be mounted on both sides of the module to stop the modules from slipping on the DIN rail. Connect the DIN rail to protective earth ground using a grounding terminal block. The modules are grounded when they are snapped onto the DIN rail. Connect protective earth ground with low impedance. Mounting: 1. Place the module onto the DIN rail from above. The upper holding keyway of the module must be hooked onto the top edge of the DIN rail. 2. Push the module from the front towards the mounting surface. 3. Once the module has been snapped on properly, check that it is fixed securely on the DIN rail. Removal: 1. Insert a suitable tool (e.g., needle-nose pliers) into the arresting latch and pull it down. 2. Pull the module slightly away from the mounting surface. 3. Lift the module from the DIN rail. Terminal Assignment 7 5 /, 7 5 /, 4 4 +! " # $ % & % ' # Terminal Meaning 1 Supply voltage +US1 2 GND US1 3 Supply voltage +US2 4 GND US2 5 Alarm contact 1 (R1) 6 Alarm contact 2 (R2) 7 Functional earth ground 8 n. c. Figure 3 Terminal assignment 7009_en_06 PHOENIX CONTACT 4

Connecting the Supply Voltage The module is operated using a +24 V DC SELV. The module is fully operational even with only one supply voltage (without jumpering it to other supply voltage terminal blocks) and/or without wiring the alarm contact. " 8, + " 8, + 7 5 /, 7 5 /, 4 4 +! " # $ % & 7 5 /, 7 5 /, 4 4 +! " # $ % & % ' $ Figure 4 Typical supply of the module from one or two voltage sources Supplying the Module From One Voltage Source The alarm contact is open if voltage is present at both supply voltage terminal blocks US1 and US2. In the event of an error at one of the two voltage sources, the contact is closed. If the voltage is not supplied redundantly, terminal blocks US1 and US2 must be jumpered (see Figure 4, version 1), so that the voltage can be monitored via the alarm contact. Option: In addition, noise immunity can be increased in environments subject to high EMI by a low-impedance connection to functional earth ground via terminal block 7. 7009_en_06 PHOENIX CONTACT 5

Ethernet Interface The module has up to 16 Ethernet ports on the front in RJ45 format, to which only twisted pair cables with an impedance of Ω can be connected. The data transmission speed is 10 Mbps or Mbps. In addition, each port has an auto crossing function: It is not necessary to make a distinction between 1:1 or crossover Ethernet cables.?? 6,?? 6, 4, 4, 2 E & 2 E % 2 E $ 2 E # 2 E " 2 E! 2 E 2 E 4 " # Figure 5 Pin assignment of the Ethernet ports in RJ45 format Switching Features of the Module Store and Forward All data telegrams received by the switch are stored and checked for validity. Invalid or faulty data packets (> 1522 bytes or CRC errors) and fragments (< 64 bytes) are rejected. Valid data telegrams are forwarded by the switch. The switch always forwards the data using the data transmission speed used in the target network segment. Multi-Address Function The switch automatically learns the addresses of termination devices, which are connected via the port, by evaluating the source addresses in the data telegrams. Only packets with unknown addresses, with a source address of this port or with a multicast/broadcast address in the target address field are forwarded via the corresponding port. The switch can store up to 2k (8-port version) or 8k (16-port version) addresses in its address table with an aging time of 5 minutes. This is important when more than one termination device is connected to one or more ports. In this way, several independent subnetworks can be connected to one switch. A restart deletes the entire address table. 7009_en_06 PHOENIX CONTACT 6

Housing Dimensions X9 X7 X8 US1 US2 X5 X6 X3 X4 X1 X2 FL SWITCH SF 8TX Ord.-No.: 2832771 X17 X7 US1 US2 X15 X16 X5 X6 FL SWITCH SF 14TX/2FX Ord.-No.: 2832593 X13 X14 X8 X9 X3 X4 X11 X12 X1 X2 X10 Figure 6 Housing dimensions of the module The housing depth and housing height is identical for all six housing versions. 7009_en_06 PHOENIX CONTACT 7

Mounting Option Using the FL RA SF8 rail adapter the 8-port SF switches can also be mounted on the DIN rail at an angle of 90. In addition, the switch can be fixed on the DIN rail using the E/NS 35 universal end clamp. X7 X5 X3 X1 X8 X6 X4 X2 US1 US2 X9 FL SWITCH SF 8TX Ord.-No.: 2832771 Figure 7 Mounting of the FL SWITCH SF 8TX turned by 90 7009_en_06 PHOENIX CONTACT 8

Technical Data General Data Function Switch/repeater; conforms to standard IEEE 802.3 Latency of the communication processor 6 μs plus frame time (16-port version) 8 μs plus frame time (8-port version) Housing dimensions (width x height x depth) in mm 8-port switch (RJ45) 135 x 80 x 30 (without COMBICON) 135 x 94 x 30 (with COMBICON) 8-port switch (fiber optics) 135 x 89 x 30 (without COMBICON) 135 x 103 x 30 (with COMBICON) 16-port switch (RJ45) 200 x 80 x 30 (without COMBICON) 200 x 94 x 30 (with COMBICON) 16-port switch (fiber optics) 200 x 80 x 30 (without COMBICON) 200 x 103 x 30 (with COMBICON) Permissible operating temperature 0 C to 55 C Permitted storage temperature -20 C to 70 C Degree of protection IP20, DIN 40050, IEC 60529 Class of protection Class 3 VDE 0106; IEC 60536 Humidity (operation) 5% to 95%, no condensation Humidity (storage) 5% to 95%, no condensation Air pressure (operation) 86 kpa to 108 kpa, 1500 m above sea level Air pressure (operation) 66 kpa to 108 kpa, 3500 m above sea level Preferred mounting position Perpendicular to a standard DIN rail Connection to protective earth ground Snapped onto a grounded DIN rail Weight 8-port switch 260 g, typical 16-port switch 380 g, typical Supply Voltage (US) Connection Nominal value Permissible ripple Permissible voltage range Current consumption at US Inrush current Protection against polarity reversal Test voltage Power consumption Via COMBICON; conductor cross-section 2.5 mm 2, maximum 24 V DC 3.6 V pp within the permissible voltage range 18.5 V DC to 30.2 V DC Depends on the device - see the following table 9 A None 500 V DC for 1 minute Depends on the device - see the following table 7009_en_06 PHOENIX CONTACT 9

Module Current Consumption Power Consumption FL SWITCH SF 8TX 200 ma 4.8 W FL SWITCH SF 7TX/FX (ST) 220 ma 5.28 W FL SWITCH SF 6TX/2FX (ST) 240 ma 5.76 W FL SWITCH SF 16TX 300 ma 7.2 W FL SWITCH SF 15TX/FX 330 ma 7.92 W FL SWITCH SF 14TX/2FX 360 ma 8.64 W Interfaces Total number of Ethernet interfaces 8/16 Properties of RJ-45 Ports Number 6, 7, 8, 14, 15 or 16 depending on the device version Connection format 8-pos. RJ45 socket on the switch Connection medium Twisted pair cable with a conductor cross-section of 0.14 mm 2 to 0.22 mm 2 Cable impedance Ω Transmission speed 10/ Mbps Maximum network segment expansion m Properties of Fiber Optic Ports Number 0, 1 or 2 depending on the device version Connection format SC duplex socket or ST socket on the switch Wavelength 1300 nm Laser protection Class 1 according to DIN EN 60825-1:2001-11 Minimum transmission length, including 3 db system reserve 6.4 km glass fiber with F-G 50/125 0.7 db/km F1200 2.8 km glass fiber with F-G 50/125 1.6 db/km F800 10 km glass fiber with F-G 62.5/125 0.7 db/km F0 3 km glass fiber with F-G 62.5/125 2.6 db/km F600 Dynamic (average) transmission power (fiber type) in link mode Minimum -24 dbm (50/125 μm) / -19 dbm (62.5/125 μm) Maximum Minimum receiver responsivity Maximum overrange Transmission speed Alarm contact Voltage Current carrying capacity Mechanical Tests Shock test according to IEC 60068-2-27-14 dbm (50/125 μm) / -14 dbm (62.5/125 μm) -32 dbm (dynamic) -14 dbm (dynamic) Mbps 24 V DC, typical ma, typical Operation: 25g, 11 ms period, half-sine shockpulse Storage/transport: 50g, 11 ms period, half-sine shock pulse Vibration resistance according to IEC 60068-2-6 Operation/storage/transport: 5g, 150 Hz, Criterion 3 Free fall according to IEC 60068-2-32 1 m 7009_en_06 PHOENIX CONTACT 10

Conformance With EMC Directives Developed according to IEC 60-6-2 IEC 60-4-2 (ESD) IEC 60-4-3 (radiated-noise immunity) IEC 60-4-4 (burst) IEC 60-4-5 (surge) IEC 60-4-6 (conducted noise immunity) IEC 60-4-8 (noise immunity against magnetic fields) EN 55022 (noise emission) Criterion B Criterion A Criterion A Criterion B Criterion A Criterion A Class A Approvals CE, curus (File: E140324), culus (Class I Div 2 File: E199827) ROHS EEE 2002/95/EC, WEEE 2002/96/EC Differences to Previous Versions Rev. 00 - First version Rev. 01 - Technical data modified and module marking updated Rev. 02 - Fiber optic technical data and alarm contact wiring modified Rev. 03 - Approvals added Rev. 04 - Port numbering and rail adapter added Rev. 05 - ST versions added Rev. 06 - Values for humidity changed, approval added 7009_en_06 PHOENIX CONTACT 11

Ordering Data Description Type Order No. Pcs./Pkt. Ethernet switch with 8 RJ45 ports FL SWITCH SF 8TX 28 32 77 1 1 Ethernet switch with 7 RJ45 ports and FL SWITCH SF 7TX/FX 28 32 72 6 1 1 fiber optic port in SC format Ethernet switch with 6 RJ45 ports and 2 fiber optic ports in SC format FL SWITCH SF 6TX/2FX 28 32 93 3 1 Ethernet switch with 16 RJ-45 ports FL SWITCH SF 16TX 28 32 84 9 1 Ethernet switch with 15 RJ45 ports and FL SWITCH SF 15TX/FX 28 32 66 1 1 1 fiber optic port in SC format Ethernet switch with 14 RJ45 ports and 2 fiber optic ports in SC format Ethernet switch with 7 RJ45 ports and 1 fiber optic port in ST format Ethernet switch with 6 RJ45 ports and 2 fiber optic ports in ST format Rail adapter for mounting the 8-port switch at an angle of 90 FL SWITCH SF 14TX/2FX 28 32 59 3 1 FL SWITCH SF 7TX/FX ST 28 32 57 7 1 FL SWITCH SF 6TX/2FX ST 28 32 67 4 1 FL RA SF8 28 32 51 9 1 Universal end clamp E/NS 35 N 08 00 88 6 50 RJ45 connector set gray for 1:1 cables (pack of 2) FL PLUG RJ45 GR/2 27 44 85 6 1 RJ45 connector set green for crossover cables (pack of 2) FL PLUG RJ45 GN/2 27 44 57 1 1 Double sheathed Ethernet cable FL CAT5 HEAVY 27 44 81 4 - Flexible Ethernet cable FL CAT5 FLEX 27 44 83 0 - Assembly tool for RJ45 connector FL CRIMPTOOL 27 44 86 9 1 Patchbox 8 x RJ45 CAT5e, pre-assembled, can be FL PBX 8TX 28 32 49 6 1 retrofitted Patchbox 6 x RJ45 CAT5e and 4 SC-RJ, glass preassembled, can be retrofitted FL PBX 6TX/4FX 28 32 50 6 1 Patch cable, CAT 5, pre-assembled, 0.3 m long FL CAT5 PATCH 0,3 28 32 25 0 10 Patch cable, CAT 5, pre-assembled, 0.5 m long FL CAT5 PATCH 0,5 28 32 26 3 10 Patch cable, CAT 5, pre-assembled, 1.0 m long FL CAT5 PATCH 1,0 28 32 27 6 10 Patch cable, CAT 5, pre-assembled, 1.5 m long FL CAT5 PATCH 1,5 28 32 22 1 10 Patch cable, CAT 5, pre-assembled, 2.0 m long FL CAT5 PATCH 2,0 28 32 28 9 10 Patch cable, CAT 5, pre-assembled, 3.0 m long FL CAT5 PATCH 3,0 28 32 29 2 10 Patch cable, CAT 5, pre-assembled, 5.0 m long FL CAT5 PATCH 5,0 28 32 58 0 10 Patch cable, CAT 5, pre-assembled, 7.5 m long FL CAT5 PATCH 7,5 28 32 61 6 10 Patch cable, CAT 5, pre-assembled, 10.0 m long FL CAT5 PATCH 10 28 32 62 9 10 Dust protection caps for RJ45 sockets FL RJ45 PROTECT CAP 28 32 99 1 10 PHOENIX CONTACT 10/2009 7009_en_06 PHOENIX CONTACT 12