IntesisBox SMS - Mitsubishi Electric air conditioners

Similar documents
IntesisBox KNX. User Manual v10 r10 eng. Mitsubishi Electric air conditioners (Domestic & Mr.Slim lines) Release V.0.2

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN

Modbus Server - Mitsubishi Electric G50

IntesisBox. KNX - Mitsubishi Electric G50. Gateway for integration of Mitsubishi Electric City Multi air conditioners into KNX control systems.

IntesisBox KNX - Mitsubishi Electric G50

IntesisBox PA-AC-MBS-1

IntesisBox KNX - AIRZONE

IntesisBox PA-AW-MBS-1 v.2.0

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

Modbus Server - Mitsubishi Electric G50

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

USER'S MANUAL. IntesisBox KNX K01-KNX-1B/16/64 v1.0. r1 eng Issue Date: 2014/06

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

See instructions to download and install the latest version of LinkBoxLON and the user's manual at

IntesisBox Modbus Server - LON

IntesisBox. v.2.5. User Manual Issue Date: 12/2017 r1.9 EN. Modbus RTU (EIA-485) Interface for Fujitsu air conditioners.

IntesisBox Modbus Server Panasonic

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at


Modbus Server - Mitsubishi Electric G50

IntesisBox KNX SAMSUNG NASA Air Conditioners

IntesisBox ModBus RTU Fujitsu Air Conditioning

IntesisBox BACnet/IP Server DALI

IntesisBox Modbus Server - BACnet/IP Client

IntesisBox TO-RC-MBS-1

IntesisBox Modbus Server Fidelio IP


Modbus Server SIEMENS Algorex (printer port)

IntesisBox KNX - BACnet/IP Client

IntesisBox Modbus Server LG Air Conditioning. User s Manual Issue Date: 06/2016 r1 eng

IntesisBox Modbus Server Siemens Synova FC330A

ASCII Server - BACnet/IP Client. Gateway for integration of BACnet IP devices into ASCII enabled control systems.

IntesisBox. v.1.3. User Manual Issue Date: 04/2016. IntesisBox PA-RC2-MBS-4

MXM-50. Modbus Interface for Mitsubishi Air-Conditioning. Installation and User Guide.

Millenium II +: general characteristics

RCF-230CAD. Room controller with communication for fancoil applications with two analogue V DC outputs

IntesisBox DK-RC-MBS-1 v.0.8

Modbus RTU (EIA-485) Interface for Panasonic and Sanyo air conditioners. Compatible with ECOi and PACi line models.

Modbus Server - M-Bus (EN ) Gateway for the integration of M-BUS meters with Modbus RTU and TCP based control systems.

Smart heating system. with wireless thermostats & smartphone control for every room. Get the most out of any water based underfloor heating

IntesisBox Modbus Server - Honeywell XLS 80

MM-A20 BMS Interface for Mitsubishi Electric Split Air-Conditioning

DKG-210 UNIVERSAL INTERNET GATEWAY UNIT

OP10. Pre-programmed, configurable controller for simple applications

IntesisBox Modbus Server KILSEN KSA-7xx. User s Manual 08/2013 r1.2 eng

OPERATION INSTRUCTIONS

IntesisBox DK-RC-MBS-1 v.0.2

RCF-230CAD. Communicating room controller for fan-coil applications with two analogue V DC outputs

DK-AC-KNX-1. Specifications. Main features. Info

RCF-230CD. Communicating room thermostat for fan-coil applications with on/off outputs

The PanasonicVRF Driver

RCF-230CTD. Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater

IntesisBox KNX - BACnet/IP Client

Gateway for integration of Modbus RTU slave devices into BACnet IP based systems.

INTERFACE SPECIFICATION

Wall mounted units. Please read carefully and thoroughly this manual before operating this unit and save it in a safe place for future reference.

WavePRO Wireless Programmable T2500 Thermostat & R2500 Receiver OPERATING MANUAL. Model K

IntesisBox BACnet IP Server - M-Bus

1/7. Field settings table [6.8.2] =... ID66F2 / ID66F3. Applicable indoor units. *GSQH10S18AA9W ThermaliaC12* Notes 4P E

RTD-W Installation Instructions

IS-IR-WIFI-1 User Manual

RTD-NET Installation Instructions

Andover ContinuumTM. b3850 Series Terminal Controllers

Andover ContinuumTM Infinet II

IntesisBox Modbus Server Hitachi VRF Air Conditioning. User Manual Issu Date: 11/2018 r1.0 EN

Andover ContinuumTM Infinet II

Andover Continuum Infinet II i2865/866 VAV Controllers with Built-in Actuator

STRA-17 Room controller. Installation and maintenance manual. Content

IntesisBox ME-AC-BAC-1

DS BAS 08/99 UNC 532

Temperature controller Ducted systems

IntesisBox HI-AW-KNX-1

BACnet. b3810 Series Local Controllers

M1000 INTELLIGENT ZONE CONTROL SYSTEM

IntesisBox ASCII Server - KNX

USER MANUAL Mobeye CM-Guard CM2000

COMFORT CONTROL CENTER SERVICE INSTRUCTIONS

Semi flush-mounted room temperature controllers with LCD

Andover ContinuumTM Infinet II

Pre-programmed room controller with display and communication

BACnet. b3867 Terminal Controllers

7-day room temperature controller

IntesisBox Modbus Server Mitsubishi Electric Centralized Controller TCP/IP XML. User Manual Issue Date: 01/2018 r1.0 EN

REMOTE CONTROLLER CS244-R OWNER S MANUAL

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions

GSM Controller BR160SM-Sd BR161SM-Sd V1.2

Andover ContinuumTM b3865/866 VAV Controllers with Built-in Actuator

Technical Manual Nova: Cabinet Security Management System (CSMS)

Alternative B Type Mid-Span Power Sourcing Equipment. User s Guide

IntesisBox KNX. Mitsubishi Electric G-50A/GB-50A/GB-50ADA/AG-150A. User's Manual Issue date: 03/08/2012 r21 eng

Weekday / weekend room temperature controller

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification

Data sheet MK 20 GR. Customized solution or off-the-shelf: The choice is yours!

USER MANUAL Mobeye Smoke Detector CM2400 Mobeye Heat Detector CM2400H. SW version 3.n

Installation Manual. DZK BACnet

IntesisBox. Making Building Automation go further. LON Products

ON/OFF HUMIDIFIER CONTROL (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET OVERVIEW WALL CONTROLLER INSTALLATION (TCY-BH-T-U)

Transcription:

Order code ME-AC-SMS-32 IntesisBox SMS - Mitsubishi Electric air conditioners Controller with SMS interface for monitoring and control Mitsubishi Electric air conditioners. Control your Mitsubishi Electric air conditioning system from your mobile phone by means of sending/receiving simple SMS messages. Up to 32 AC indoor units ME-AC-MBS-1 IntesisBox ME-AC-SMS-32 SMS ME-AC-MBS-1 Bus RS485 IntesisBox ME-AC-SMS-32 has been designed to monitoring and control Mitsubishi Electric AC indoor units by means of sending and receiving simple SMS messages from any mobile phone or PDA. It is compatible with all models of Domestic & Mr.Slim lines. Requires the installation of one ME-AC- MBS-1 interface in each AC indoor unit to control. The communication with the AC indoor units is over standard RS485 bus, allowing a bus distance of up to 1.200 meters. ME-AC-SMS-32 performs a continuous monitoring of internal operation parameters and alarm status of the AC units, allowing to immediately send an SMS, to one or more recipients, after detection of an alarm in any AC unit. Security in front of unwanted access: Allows configuring a list of phone numbers with permitted access to the system, any phone that is not in the list can not access the system. Alarms notification fully configurable: Allows configuring one or more phone numbers (recipients) to notify the alarms, notification of alarms restoration (back to normal), and a maximum quota of alarms to notify per day. Automatic control of A.C. units: Powerful and flexible automatic management of the A.C. units (Start/Stop, Set Temp and Mode) based on calendar. Different languages: Language for SMS messages is selectable. Simple configuration and setup: The interface comes pre-configured from factory; just the number of A.C. units to control must be configured for a simple operation. The entire configuration is done through simple SMS messages.

Description IntesisBox ME-AC-SMS-32 is an interface that will allow you to monitor and control your Mitsubishi Electric air conditioning installation by means of sending and receiving simple SMS massages. IntesisBox ME-AC-SMS-32 can only control the indoor units of your installation, and is compatible with all models of Domestic and Mr.Slim series. IntesisBox ME-AC-SMS-32 communicates with the AC indoor units through RS485 bus, and allows connection to up to 32 AC indoor units and a maximum bus distance of 1200 meters. It is necessary to install an ME-AC-MBS-1 interface in each AC indoor unit to be controlled, and to configure all these interfaces with a unique address inside the bus (1, 2, 3, from 1 ascending and consecutively). Consult your IntesisBox provider for details on how to acquire and configure the ME-AC-MBS-1 interfaces. IntesisBox ME-AC-SMS-32 will allow you to: Monitor the status of one, some or all the AC indoor units in any moment by simply sending an SMS message from your mobile phone. Command, i.e. start/stop, change operation mode or set temperature, one, some or all the AC indoor units in any moment by simply sending an SMS message from your mobile phone. Notify any alarm occurred in the installation to one or various recipients by means of an SMS message sent by the interface, and also the alarm restorations. Configure a powerful and flexible automatic management of the AC indoor units. ME-AC-SMS-32 can start/stop, change the operation mode and the setpoint temperature of the AC indoor units automatically based on calendar, in a "day of the week" basis (Monday to Sunday), and also in a specific-day-profile basis that can be freely assigned to any period of time (between two dates). Restrict access to unauthorized users. All trademarks,tradenames and logotypes used in this document are the property of their respective owners. Intesis Software S.L. - All rights reserved IntesisBox is a registered trademark of Intesis Software SL 2

Contents IntesisBox ME-AC-SMS-32 includes the following components: 1. Modem GSM. 2. RS232/RS485 converter. 3. Antenna, with magnetic support and interchangeable rod, incorporating a 3 meters long cable with connector. 4. Power supply 110-230Vac / 50-60Hz. 1 4 3 2

Installation Dimensions: 88 mm 80 mm 68 mm 136 mm 9 mm 37,2 mm Minimum space recommended for installation of the interface, with space enough for external connections: Holes for wall mounting using long screws. Template for drills: 170 mm 45,3 mm 55,3 mm Ø 3,5 mm (x2) 170 mm

Connections MODEM SIM card holder Antenna connection Power supply 12Vdc Use the power supply for mains 110-240Vac / 50-60Hz provided with the interface. RS232/RS485 converter RS485 connection with ME-AC-MBS-1 interfaces Set the internal bus termination resistor in the ME-AC-MBS-1 at the end of the bus. See ME-AC-MBS-1 user's manual for details. Use twisted pair screened cable. Connections: A - B: Earth: Twisted pair Screen Maximum 32 interfaces ME-AC-MBS-1 Maximum 1200 meters

Basic Configuration The interface is configured through SMS messages sent from any mobile phone, messages must be sent to the phone number assigned to the SIM card into the interface. It is only necessary to configure in the interface the number of AC units to be controlled, the rest of basic configuration comes preset from factory. To configure in the interface the number of AC units, just send to it an SMS with the following command: # CONF_DISP x Where x is the number of AC units of the installation (1 to 32). As commented before, do not forget to set appropriately the bus addresses of the ME-AC-MBS-1 interfaces, from 1, ascending, consecutively, and uniquely. The interface comes from factory configured in Spanish language, to change the language use the command: # CONF_LNG x Where X is: 0 for English, 1 for Spanish, 2 for Catalan.

Basic Functionality 1) To consult the status of one, some or all the AC units, send to the interface an SMS with the command: # Aa Where a is the AC unit number (1 to 32). The interface allows to consult the status of some AC units by sending a single SMS, for example send the command # A1 A5 A10 if you want to consult AC units 1, 5 and 10, or send # A0 if you want to consult the status of all the AC units. In response to this command the interface will answer (in one or various SMS depending on the volume of information to send) the required information. The number of parameters per AC unit sent in response to this command is configurable, by default are the following: Parameter Values Description Example OnOff On Off State (On/Off) On Mode Cool..Heat Fan Mode (Cool, Heat, Dry, Auto, Fan) Cool Auto Set Temp. 18..30 ºC Set Temperature 22ºC Ambient Temp. 0..60 ºC Ambient Temperature 22ºC Fan speed 0..3 Fan Speed High Func.Hours 0..65535 Functioning Hours of the AC unit 0 OnOff Calendar Yes..No control by calendar activated No Error None 65535 Error code of the AC unit None 2) To execute orders in one, some, or all the AC units, send an SMS with the command: # Aa Dd Mm Ttt Where: a is the AC unit number (1 to 32). The interface can execute orders in more than one AC unit by sending a single SMS, for example specify A1 A5 A10 if you want to execute the order in AC units 1, 5 and 10, or specify A0 to execute the order in all the AC units. d is the State of the unit (0=Off, 1=On). This parameter is optional, if it is not specified then the state of the AC unit will not be modified. m is the Operation Mode (0 or A => Auto, 1 or H => Heat, 2 or D => Dry, 3 or F => Fan, 4 or C => Cool). This parameter is optional, if it is not specified then the operation mode of the AC unit will not be modified. tt is the Set Temperature in ºC (18..30). This parameter is optional, if it is not specified then the setpoint temperature of the AC unit will not be modified. In response to this command the interface will answer (in one or various SMS depending on the volume of information to send) with the current status of the units after the execution of the order (if it is an order for all the units then there will be no response of the interface). These are some examples of SMS messages with commands of orders: Command Description # D1 M4 T20 A1 On AC unit 1 in Cool Mode and Set Temp=20ºC # D1 MC T20 A1 The same as above # d1 m4 t20 a1 The same as above # D0 A1 A3 Off AC units 1 and 3 # T22 A0 22 ºC to all AC units # A0 D0 Off all AC units # D0 A1 Off AC unit 1 # A1 D1 A2 On AC units 1 and 2

3) To enable the interface to notify the alarms occurred in the system, one or more recipients must be configured, to do so send an SMS with the command: # CONF_NALAR x x Where: x x is the phone number recipient of the alarms. The interface can send the alarms to more than one recipient, just specify all the desired recipient's phone numbers separated by space in the command, for example # CONF_NALAR 609010203 609010204, the format of the phone numbers can be national (i.e. 609010203), international (i.e. +34609010203), or short numbers of GSM Corporative Telephony Service provided by some GSM network providers (i.e. Movistar Corporativo in Spain). Later you can: Add a number to the list of recipients, use the command with the modifier +, i.e. # CONF_NALAR + 609010205 Delete a number from the list, use the command with the modifier -, i.e. # CONF_NALAR - 609010205 Consult the numbers currently in the list, use the command # CONF_NALAR?

Full Functionality Monitoring and controlling the air conditioning system Function Related Commands Description Consult the status of AC #A Command to consult the status of the units AC units, of one, some or all the units. Execute orders in the AC units Automatic management of the AC units based on calendar Reception of the system alarms # A D M T Command to execute orders in the AC units, i.e. On/Off, selection of the operation mode, and change of the setpoint temperature, in one, some or all the units. The interface allows configuring an automatic management of the AC units based on calendar (On/Off, select the operation mode and the setpoint temperature). This management can be in a day-of-the-week basis (the same management for all Mondays, Tuesdays, etc.) or in a special-day-profile basis that can be later assigned to any period between two dates. This functionality comes disabled from factory. See below the commands related to enable and configure it. The interface can notify the alarms occurred in the AC units to one or more recipients, and also can notify the restoration of alarms. A maximum number of notifications per day can also be configured. This functionality comes disabled from factory. See below the commands related to enable and configure it. Configuration of the interface Function Related Commands Description Consult the commands # HELP Returns the list of commands accepted accepted by the interface by the interface Selection of language # CONF_LNG Configuration of the language used by the interface Number of AC units to be # CONF_DISP Configuration of the number of AC units controlled connected to the RS485 bus, to be Internal parameters per AC unit offered by the interface Automatic management of the AC units based on timetable and calendar List of phone numbers with access to the interface Alarms notification controlled by the interface # CONF_PAR Configuration and consultation of the internal parameters per AC unit offered by the interface in response to a consult of status command. # CONF_HOR # CONF_ASG # CONF_NUM # CONF_ACCESS # SPC_CLRLIST # CONF_NALAR # CONF_RALAR # CONF_MAXALAR Configuration of the automatic management of AC units based on timetable and calendar. This management can be in a day-of-theweek basis (the same management for all Mondays, Tuesdays, etc.) or in a special-day-profile basis that can be later assigned to any period between two dates Configuration and consultation of the list of phone numbers with access to the interface functions Configuration of the alarms notification, recipients, and alarms restorations, as well as the maximum number of notifications allowed per day Examples # A1 # A2 A10 # A0 # A1 D1 MC T22 # A1 A2 D1 # A0 D0 Examples # HELP # CONF_LNG 0 # CONF_DISP 10 # CONF_PAR P1 P2 P5 # CONF_PAR P0 # CONF_PAR? # CONF_HOR 1 # CONF_HOR + WD10 M0 T24 A1 ON08:00:00 OFF19:00:00 # CONF_ASG + SA01/06/2008 EA30/09/2008 WD10 # CONF_NUM 609010203 # CONF_ACCESS 609010203 # CONF_ACCESS - 609010204 # CONF_ACCESS? # SPC_CLRLIST # CONF_NALAR 609100203 609100204 # CONF_RALAR 1 # CONF_MAXALAR 20

Alarm Codes These are the possible alarm codes, referent to the AC units, offered by the interface. Code Description 8000 No error active 8001 Communication error between ME-AC-MBS-1 and the AC indoor unit. Revise connection. 1102 Discharge Temperature high 1108 Internal thermostat detector working (49C) 1110 Outdoor unit fail 1300 Pressure low 1302 Pressure high (High pressure probe working 63H) 1503 Protection against freeze or battery high temperature 1504 Protection against freeze or battery high temperature 1504 Over heating protection 1509 High pressure error (ball valve closed) 1520 Super heating anomaly due to low temp. of discharge. (TH4) 2500 Erroneous operation of drain pump 2502 Erroneous operation of drain pump 2503 Drain sensor anomaly (DS) 4030 Serial transmission error 4100 Compressor pause due to excess of current (initial block) 4101 Compressor pause due to excess of current (overload) 4102 Phase detection opened 4103 Anti-phase detection 4108 Phase opened in phase L2 or connector 51CM opened 4118 Error in the anti-phase detector (electronic board) 4124 Connector 49L opened 4210 Cut due to over-current of compressor 4220 Voltage anomaly 4230 Radiator panel temperature anomaly (TH8) 5101 Ambient temperature probe anomaly (TH1), indoor unit 5102 Liquid probe anomaly (TH2) 5102 Cond/Evap probe anomaly (TH5) 5104 Error detection in discharge temperature 5105 Outdoor probe error TH3 5106 Outdoor probe errorth7 5107 Outdoor probe errorth6 5110 Outdoor probe errorth8 5202 Connector 63L opened 5300 Current probe error 6600 MNET duplicated address definition 6602 MNET Line transmission hardware error 6603 MNET BUS busy 6606 MNET Line transmission error 6607 MNET transmission error 6607 MNET without ack 6608 MNET transmission error 6608 MNET without response 6831 IR remote control transmission error (reception error) 6832 IR remote control transmission error (transmission error) 6840 Transmission error with the indoor/outdoor unit (reception error) 6841 Transmission error with the indoor/outdoor unit (transmission error) 6844 Error in inter-connection cable in the indoor/outdoor unit, indoor unit number deactivated (5 min or more) 6845 Error in inter-connection cable in the indoor/outdoor unit (cabling error, disconnection) 6846 Initial timer deactivated 8010 Communication error between ME-AC-SMS-32 and ME-AC-MBS-1. Revise connection. 8011 CRC error in communication between ME-AC-SMS-32 and ME-AC-MBS-1. Revise connection. 8012 Frame too short in communication between ME-AC-SMS-32 and ME-AC-MBS-1. Revise connection. 8013 Frame too long in communication between ME-AC-SMS-32 and ME-AC-MBS-1. Revise connection. 8100 Internal error in ME-AC-SMS-32, in the communication objects. Reset the device.

Technical data Envelope Colour Power supply Mounting RS485 port LED indicators GSM networks compatibility GSM output power SIM card compatibility Console port Configuration Firmware Operational temperature range Operational relative humidity range Protection RoHS conformity Certifications Plastic. Dimensions: 88 x 136 x 37,2 mm. Grey. External power supply for 110-230Vac / 50-60Hz 15W (euro plug) is supplied. Wall 1 x Standard RS485 bus (master) with bus fail safe biasing. 1 x Operating status. Quad-Band GSM 850/900/1800/1900 MHz. - Class 4 (2 W) for EGSM850 & EGSM900. - Class 1 (1 W) for GSM1800 & GSM1900. SIM card interface 3 V, 1.8 V. RS232(DCE). DB9 female. Only used for operation monitoring and maintenance under the indications of Intesis Software. Via SMS messages. Allows firmware upgrades "over-the-air". -30 C to +75 C. 5% to 95%, non condensation. IP20 (IEC60529). Conforms to RoHS directive (2002/95/CE). CE