Installation Instructions

Similar documents
Installation Instructions

Installation Instructions

Installation Instructions

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

INSTALLATION INSTRUCTIONS

Installation Instructions

Software Installation Guide

Installation, Start-up and Operating Instructions

Installation Instructions

SAVE THESE INSTRUCTIONS

Software Installation Guide

Installation Instructions

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

INSTALLATION INSTRUCTIONS

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.

PowerLogic High Density Metering System 1-Meter Enclosure

User s Manual. ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

Installation Instructions

dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2

MFA-0801 & MFA-1201 D-M-E Smart Series Low Voltage Temperature Control System. User s Manual. D-M-E Company

ELECTRICAL SUPPLY TROUBLESHOOTING QUICK GUIDE SAFETY PRECAUTIONS

SINAMICS. SINAMICS G120P dv/dt filter plus Voltage Peak Limiter. Safety information 1. General. Mechanical installation. Electrical installation 4

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

OWNER S MANUAL TABLE OF CONTENTS

M250 (M LL) Safety

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

Installation Instructions

Model 2657A-LIM-3 LO Interconnect Module

Wiring Diagrams UNITS WITH STARTING SERIAL NUMBER 3507Q

Enphase S-Series Microinverter and Engage Cable Safety

Model 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1

MFP5G, MFP8G, & MFP12G D-M-E Smart Series Mainframes

Siemens Industrial s

SAVE THESE INSTRUCTIONS

Replacing the Power Supply

Model 2380 Rack-Mount Kit

M215 (M215-60) Safety

Installation Instructions

Installation Instructions

Installation NOTICE. S&C IntelliCap Automatic Capacitor Control. Table of Contents. Instruction Sheet

Model 2380 Rack-Mount Kit

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1

PV Rapid Shutdown device

Model 7705 Control Module

COMFORT CONTROL CENTER SERVICE INSTRUCTIONS

Specifications, Installation, and Operating Instructions

SmartVFD Disconnect Panel Assemblies

COOPER POWER SERIES. Input/Output (I/O) module installation instructions. Voltage Regulators MN225067EN

MODELS DSH/DSV R-410A AIR SIDE ECONOMIZER KIT

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating instructions 03/2011 SINAMICS

Overview These instructions are presented as a guideline for installing and setting up the LX Series Breaker Control Panel.

PS/IO Circuit Board Retrofit

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English

Model 2600B-PM V Protection Module with 1 A Clamp. Description / April 2015 *PPA * 1

MODELS DSH/DSV R-410A AIR SIDE ECONOMIZER KIT

M215-Z Safety Information (M LL-IG-ZC)

Models beginning with 2M, 2L or 2X. Product Description. Technical Specifications. Installation Instructions. Series 2000 Multiple Meter Units (MMUs)

INSTALLATION INSTRUCTIONS ECONOMIZER WITH EXHAUST

COOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN

Warning. Important. Always follow all local building electrical codes. PECCSUN3672DB46M PECCSUN3672EN46M

User s Manual. ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

Table of Contents Product Overview Before using the product Installation Procedure... 5

HV-CS kv Edge Mount Triaxial Jack

72In LED Lit Nutcracker Item # CAUTION: IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL SAFETY INSTRUCTIONS

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating Instructions 05/2010 SINAMICS

FDS / FDS-R / FDS-PS

PTB 01 ATEX 2064 U, IECEx PTB U. Example / Beispiel / Exemple: Type Operating Instructions

Quick Start Guide TS A

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Operating Instructions

Models 2601B, 2602B, and 2604B System SourceMeter Instruments Quick Start Guide

Control. Part B, Section 2. This section covers the following unit configurations. 3400V 3500V Voltage 1, 2, 3 Pump Piston (D, E, F, G)

Install Motor Controller User Manual

M215 Safety (M LL-S22-IG / S23-IG / S24-IG)

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

Model 8101-PIV Test Fixture User s Guide. Overview. SMU Device holder (near latch) Two Leaded Part Plungers. PIV Device holder (near hinge)

PanelView Plus/VersaView CE Terminals and Display Modules

High Power Electronic Gear Installation and operation Guide

S Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions. Contents

AutoScan to MultiScan Replacement Kit

Vista SD Portable Remote Control Pendant

EC Series. Safety Guide

SAVE THESE INSTRUCTIONS

Temperature. Power requirements. Weight. Dimensions

Instruction Manual. M Pump Motor Controller. For file reference, please record the following data:

SAVE THESE INSTRUCTIONS

Model 8010 High Power Device Test Fixture Interconnection Reference Guide

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

IM /2016 REV01 LACI Production Monitoring Module

Installing the Cisco AS5400XM Universal Gateway

MicroTech II TM Remote I/O Panel Installation Manual

Installation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2

2260B-RMK-Series Rack Mount Kit

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual

Scanner 2000 Steam Mass Flow Transmitter

READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION IMPORTANT SAFETY INSTRUCTIONS

COOPER POWER SERIES. Form 4C microprocessor-based recloser control standard and automation power supply kit installation and operation instructions

810D Series FAA L-810 Double Obstruction Light Installation Manual

ASCO 920 Remote Control (RC) Switches

Transcription:

50ES, 50EZ, 50GL, 50GS, 50GX, 50JS, 50JX, 50JZ, 50SD, 50SZ, 50VL, 50VT, 50XP, 50XZ 601A, 602A, 602B, 604A, 604B, 604D, 607C, 701A, 702A, 702B, 704A, 704B, 704D, 707C PA1P, PA2P, PA3P, PH1P, PH2P, PH3P SMALL PACKAGED PRODUCTS Electric Heaters 5---20kW 50 Hz and 60 Hz Product Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Installation and servicing of this equipment can be hazardous due to mechanical and electrical components. Only trained and qualified personnel should install, repair, or service this equipment. Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on this equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply. Follow all safety codes. Installation must be in compliance with local and national building codes. Wear safety glasses, protective clothing, and work gloves. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Recognize safety information. This is the safety -alert symbol. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety -alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. Follow all safety codes. Wear safety glasses and work gloves. Have a fire extinguisher available. Before proceeding with heater installation, inspect thoroughly for shipping damage. Notify shipper immediately if any damage is found. Clean all dirt, dust and moisture from heater package. Check for proper clearances of live parts, between phases and to ground. Make sure that all required barriers are in place. Check conductors run in multiple to insure that they are properly wired. Refer to unit installation instructions for complete unit installation details. The maximum duct static for safe electric heater operation isshownintable1or2.! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Before performing installation, service or maintenance operations on this system, turn off all main power to system. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable. Lockout and tag switch with a suitable warning label.! CAUTION CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts. DESCRIPTION AND USAGE This electric heater series is engineered, designed and listed to be installed only in the models shown in Table 3. Before proceeding, verify the heater label for correct voltage and kw requirements. INSTALLATION HEATER INSTALLATION NOTE: Thermostat used must be capable of energizing G (indoor fan) on a call for W (heating). If G is not energized system malfunction will occur. 1. Open all electrical disconnects and install lockout tag before beginning any installation or service work. 2. Check for proper equipment model number from list. 3. Verify that unit ductwork is installed per base unit instructions. 4. Remove unit access panel to access unit (See Fig. 1). 5. Locate and remove the heater access cover plate inside unit access panel (See Fig. 2). Save screws. 6. Remove electric heater from the packaging. 7. Install heater, sliding assembly carefully through access hole. Ensure that mounting holes of heater align with mounting holes on the unit. Secure heater assembly with screws provided. 8. Dress wires with wire ties provided. 1

ELECTRICAL CONNECTION 1. Open all electrical disconnects and install lockout tag before beginning any installation or service work. 2. All electrical connections, wire sizes and type of conduit shall meet the National Electric Code (NEC) and state and local codes (or International Electric Code) as applicable. Main power supply, minimum wire sizes, circuits, fusing, etc. are shown on schematic wiring diagrams. NOTE: Use minimum 75 C copper wire only. 3. Refer to base unit instructions for recommended wiring procedures. 4. Connect low voltage wires as shown in unit schematic diagrams. These connections must be made in the 24v barrier section inside the unit panel (See Fig. 2). 5. Connect field power wiring as shown in heater wiring diagram. All connections should be made inside the unit and comply with the NEC and International Electric Code and state and local codes. Heaters with factory installed fuses may be installed on a branch circuit protected by either a fuse or circuit breaker. For all other heaters, the branch circuit must be protected by a fuse or circuit breaker supplied by others. 6. Make all high voltage wire splice connections inside the unit control box. Use splice connectors provided. Properly insulate connectors. Separate all wires from incoming power leads. 7. For fused heaters, incoming power leads should be strain relieved. After attaching field power wires to the fuse block lugs, use the pre-mounted wire tie on the inside of the control box cover to secure and strain relieve these wires. NOTE: The adjacent heater compressor contactor and low voltage wiring are factory strain relieved in a similar manner. 8. Be sure that all electrical terminal connections, clamps, screws, etc. are tight before proceeding. 9. Check wiring diagram supplied with heater for specific connections and information. 10. Check operation as described in Start -Up section.! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Before performing installation, service or maintenance operations on this system, turn off all main power to system. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable. Lockout and tag switch with a suitable warning label. START -UP! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Before proceeding, verify that all wiring is correct per factory approved schematic. Notify factory immediately of any discrepancies. 1. Refer to base unit installation instructions as required. 2. Check for loose terminal connections. 3. Check that all fuse and circuit breaker short circuit interrupting ratings are adequate. 4. Turn on unit and heater power. 5. Set thermostat to call for heat. 6. Check operation of heater. 7. Check that airflow across the heater is at or above the minimum recommended CFM requirement (See unit installation instructions). Adjust indoor blower heat speed as required. Check that duct system conforms to static pressure limits in Table 1 or 2. NOTE: See Table 1 for Non -Export units (with -3, -5 or -6 as electrical option -see product data). See Table 2 for Export units (with -9 as electrical option -see product data). 8. Any modifications or repairs to this equipment without written permission from the factory will be done at the installer s own risk and expense. TROUBLESHOOTING 1. Fuses - Malfunction will interrupt power to the unit. Check for cause of failure, replace fuses. 2. Limit Switch - Malfunction prevents heating element(s) from being energized. Replace switch if malfunction occurs. 3. Contactor - Malfunction will not allow heater to energize. Replace faulty contactor. Do not attempt to replace coil or dress contacts. PACKAGE CONTENTS Electric Heater Package Contents 1. Heater assembly 2. UPC heater label 3. Installation instructions 4. Identification label 5. Schematic on lid door for all fused units 6. Schematic on sticker to be placed inside unit panel for non -fused units 7. Wire connectors (3) 8. Wire ties -6 -in. (5) 9. Screws #10A (5) 2

UNIT (60 HZ UNITS) Table 1 Maximum Duct Static Pressure for Non -Export Units (IN. W.C.) (pa) MAXIMUM STATIC PRESSURE UNIT SIZE 018 024 030 036 042 048 060 Heat Pump.30 (75).30 (75).30* (75).30 (75).50 (125).50 (125).50 (125) Electric Cooling.30 (75).30 (75).30 (75).30 (75).50 (125).50 (125).50 (125) *15kW size 030 heat pump must be used with medium speed only. All others can be run at low speed. Table 2 Maximum Duct Static Pressure for 50 HZ Export Units (IN. W.C.) (pa) MAXIMUM STATIC PRESSURE 50 HZ UNITS UNIT SIZE 024 030 036 048 060 Max Static (pa) 150 250 250 225 225 Min Airflow (L/s) 354 378 472 708 826 Table 3 Electric Heater Usage Chart-Export Units 50GS (PAC) 50GL (PAC) 50JS (PHP) 50JZ (PHP) Code kw V PH 18 24 30 36 42 48 60 18 24 30 36 42 48 60 071 na 5.2 400 3 x x x x x 072 na 6.9 400 3 x x x x x 073 na 10.4 400 3 x x x x 074 na 13.8 400 3 x x 076 CE 6.5 400 3 x x x x 077 CE 8.7 400 3 x x x x x 078 CE 13.0 400 3 x x x x x 079 CE 17.4 400 3 x x x Table 3 Electric Heater Usage Chart Non -Export Units 50GS, 701A, PA1P (PAC) 50GX, 702A, PA2P (PAC) 50GL, 702B (PAC) Code kw V PH Fuse 18 24 30 36 42 48 60 18 24 30 36 42 48 60 18 24 30 36 42 48 60 055 UL 5 230 3 0 x x x x x x x x x x x x x x x 056 UL 10 230 3 0 x x x x x x x x x x x x x x x 068 UL 10 230 3 6 057 UL 15 230 3 0 x x x x x x x x x x x x x x x 058 UL 15 230 3 6 059 UL 20 230 3 6 x x x x x x x x x 060 UL 5 460 3 0 x x x x x x x x x x x x 061 UL 10 460 3 0 x x x x x x x x x x x x 062 UL 15 460 3 0 x x x x x x x x x x x x 063 UL 20 460 3 0 x x x x x x x x x Table 3 Electric Heater Usage Chart Non -Export Units Continued 50JS, 601A, PH1P (PHP) 50JX, 602A, PH2P (PHP) 50JZ, 602B (PHP) Code kw V PH Fuse 18 24 30 36 42 48 60 18 24 30 36 42 48 60 18 24 30 36 42 48 60 055 UL 5 230 3 0 x x x x x x x x x x x x x x x 056 UL 10 230 3 0 x x x x x x x x x x x x 068 UL 10 230 3 6 x x x 057 UL 15 230 3 0 058 UL 15 230 3 6 x x x x x x x x x x x x x x x 059 UL 20 230 3 6 x x x x x x x x x 060 UL 5 460 3 0 x x x x x x x x x x x x 061 UL 10 460 3 0 x x x x x x x x x x x x 062 UL 15 460 3 0 x x x x x x x x x x x x 063 UL 20 460 3 0 x x x x x x x x x = base unit not offered x = Approved combination 3

Table 3 Electric Heater Usage Chart Non -Export Units Continued 50SD, 704A, PA3P (PAC) 50XP, 704B (PAC) Code kw V PH Fuse 18 24 30 36 42 48 60 18 24 30 36 42 48 60 052 UL 5 230 1 0 x x x x x x x x x x x x 064 UL 5 230 1 4 069 UL 7.2 230 1 0 x x x x x x x x x x x x 070 UL 7.2 230 1 4 065 UL 10 230 1 0 x x x x x x x x x x x 050 UL 10 230 1 4 x 051 UL 15 230 1 4 x x x x x x x x x 066 UL 15 230 1 6 x 053 UL 20 230 1 4 x x x x x 054 UL 20 230 1 6 x 055 UL 5 230 3 0 x x x x x x x x x 056 UL 10 230 3 0 x x x x x x x x x 068 UL 10 230 3 6 057 UL 15 230 3 0 x x x x x x x x x 058 UL 15 230 3 6 059 UL 20 230 3 6 x x x x x x 060 UL 5 460 3 0 x x x x 061 UL 10 460 3 0 x x x x 062 UL 15 460 3 0 x x x x 063 UL 20 460 3 0 x x x Table 3 Electric Heater Usage Non -Export Units Chart Continued 50SZ, 604A, PH3P (PHP) 50XZ, 604B (PHP) Code kw V PH Fuse 18 24 30 36 42 48 60 18 24 30 36 42 48 60 052 UL 5 230 1 0 x x x x x x x x 064 UL 5 230 1 4 x x x x 069 UL 7.2 230 1 0 x x x 070 UL 7.2 230 1 4 x x x x x x x x x 065 UL 10 230 1 0 050 UL 10 230 1 4 x x x x x x x x x x x x 051 UL 15 230 1 4 066 UL 15 230 1 6 x x x x x x x x x x 053 UL 20 230 1 4 054 UL 20 230 1 6 x x x x x x 055 UL 5 230 3 0 x x x x x x x x x 056 UL 10 230 3 0 x x x x x x x 068 UL 10 230 3 6 x x 057 UL 15 230 3 0 x 058 UL 15 230 3 6 x x x x x x x x 059 UL 20 230 3 6 x x x x x x 060 UL 5 460 3 0 x x x x 061 UL 10 460 3 0 x x x x 062 UL 15 460 3 0 x x x x 063 UL 20 460 3 0 x x x = base unit not offered x = Approved combination 4

Table 3 Electric Heater Usage Chart Non -Export Units Continued 50ES, 704D (PAC) 50VL, 707C (PAC) Code kw V PH Fuse 18 24 30 36 42 48 60 18 24 30 36 42 48 60 052 UL 5 230 1 0 x x x x x x x x x x x x x x 064 UL 5 230 1 4 069 UL 7.2 230 1 0 x x x x x x x x x x x x x x 070 UL 7.2 230 1 4 065 UL 10 230 1 0 x x x x x x x x x x x x 050 UL 10 230 1 4 x x 051 UL 15 230 1 4 x x x x x x x x 066 UL 15 230 1 6 x x 053 UL 20 230 1 4 x x x 054 UL 20 230 1 6 x x x 055 UL 5 230 3 0 x x x x x x x x x x 056 UL 10 230 3 0 x x x x x x x x x x 068 UL 10 230 3 6 057 UL 15 230 3 0 x x x x x x x x x x 058 UL 15 230 3 6 059 UL 20 230 3 6 x x x x x x 060 UL 5 460 3 0 x x x x x x x x 061 UL 10 460 3 0 x x x x x x x x 062 UL 15 460 3 0 x x x x x x x x 063 UL 20 460 3 0 x x x x x x Table 3 Electric Heater Usage Non -Export Units Chart Continued 50EZ, 604D (PHP) Series 1/B for 230 Volt 50VT, 607C (PHP) Code kw V PH Fuse 18 24 30 36 42 48 60 18 24 30 36 42 48 60 052 UL 5 230 1 0 x x x x x x 064 UL 5 230 1 4 x x x x x x 069 UL 7.2 230 1 0 x 070 UL 7.2 230 1 4 x x x x x x x x x x x 065 UL 10 230 1 0 050 UL 10 230 1 4 x x x x x x x x x x x x 051 UL 15 230 1 4 066 UL 15 230 1 6 x x x x x x x x x x 053 UL 20 230 1 4 054 UL 20 230 1 6 x x x x x x 055 UL 5 230 3 0 x x x x x x x x 056 UL 10 230 3 0 x x x x x x 068 UL 10 230 3 6 x x 057 UL 15 230 3 0 058 UL 15 230 3 6 x x x x x x x x 059 UL 20 230 3 6 x x x x x x 060 UL 5 460 3 0 x x x x x x x x 061 UL 10 460 3 0 x x x x x x x x 062 UL 15 460 3 0 x x x x x x x x 063 UL 20 460 3 0 x x x x x x = base unit not offered x = Approved combination 5

FRONT ACCESS PANEL Fig. 1 - Unit Control Box Location C99091 HEATER BLANK PLATE Fig. 2 - Heater Blank Plate Location 24V BARRIER A06282 6

Heater Fuse Block Attach Heater with 5 Screws Field Wire Connection Door Latch Heater Door (Fused Models Only) Shown Open Compressor Contactor Wire In Yellow & Black Strain Relief for Field Power Wires Low Voltage Wiring Ground Lug Location Fig. 3 - Heater Control Box A06276 THIS SIDE UP ELECTRIC SHOCK HAZARD More than one disconnect switch may be required to de-energize this equipment. Open all remote disconnects before servicing. Do not block or otherwise cover control cabinet with insulation or other materials. Heater Door Shown Closed Heater Schematic Fig. 4 - Schematic Location C01042 7

Fig. 5-050A00 Wiring Diagram A07287 Fig. 6-051A00 Wiring Diagram A07288 8

Fig. 7-052A00 Wiring Diagram A07289 Fig. 8-053A00 Wiring Diagram A07290 9

Fig. 9-054A00 Wiring Diagram A07291 Fig. 10-055A00 Wiring Diagram A07292 10

Fig. 11-056A00 Wiring Diagram A07293 Fig. 12-057A00 Wiring Diagram A07294 11

Fig. 13-058A00 Wiring Diagram A07295 Fig. 14-059A01 Wiring Diagram A07296 12

Fig. 15-060A00 Wiring Diagram A07297 Fig. 16-061A00 Wiring Diagram 13 A07298

Fig. 17-062A00 Wiring Diagram A07299 Fig. 18-063A00 Wiring Diagram A07300 14

Fig. 19-064A00 Wiring Diagram A07301 Fig. 20-065A00 Wiring Diagram A07302 15

Fig. 21-066A00 Wiring Diagram A07303 Fig. 22-068A00 Wiring Diagram A07304 16

Fig. 23-069A00 Wiring Diagram A07305 Fig. 24-070A00 Wiring Diagram A07306 17

Fig. 25-071A00 Wiring Diagram A07307 Fig. 26-072A00 Wiring Diagram A07308 18

Fig. 27-073A00 Wiring Diagram A07309 Fig. 28-074A00 Wiring Diagram A07310 19

Fig. 29-076A00 Wiring Diagram A07311 Fig. 30-077A00 Wiring Diagram A07312 20

Fig. 31-078A00 Wiring Diagram A07313 Fig. 32-079A00 Wiring Diagram A07314 21

Copyright 2008 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 03/08 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Catalog No: IIK---09 Replaces: IIK---08 22