THE SOLUTION. MFW product family OPERATING INSTRUCTIONS. I/O expansion modules. Modules from the

Similar documents
THE SOLUTION. MFW product family OPERATING INSTRUCTIONS. Modular optical fibre telecontrol system. Application-ready systems from the

THE SOLUTION. MFW product family DATASHEET. MFW - Modular radio telecontrol system. A system from the. INFOwww.ees-online.de

Modular Two-Wire Telecontrol System

Analog display for resistance current

Article no. BWU2045: AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input 1.23 NC

CMC III Universal Sensor

MINI MCR-SL-UI-REL(-SP)

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

Modular telecontrol system for GPRS and network structures

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Operating instructions. Speed monitor D / / 2014

TRIO-DIODE/12-24DC/2X10/1X20

Operating instructions. Switching amplifier DN0210 DN / / 2015

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

I/O module, universal, digital, S0 inputs, modu533

Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011

MINI MCR-SL-UI-2I(-SP)(-NC)

Assembly and operating instructions DULCOMARIN II, N-Module (Power Supply Module without Relay) DXMaN

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

Products no longer available

PHOENIX CONTACT - 12/2007

ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors

Documentation KM2042. Sixteen channel digital output module with D-Sub Connector. Version: Date:

PHOENIX CONTACT - 07/2006

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

MID approval no. DE-08-MI004-PTB004 Date of release

MINI MCR-SL-PT100-UI-200

ETD-BL-1T-230(-PT) Multifunctional time relay with various functions and adjustable times. Data sheet. 1 Description

Binary output and supervision 520CSD01 Data sheet

EY-EM : Remote I/O module, ecolink

SIMOCODE 3UF Motor Management and Control Devices

EMD-SL-LL-230. Electronic monitoring relay for level monitoring of conductive liquids. INTERFACE Data sheet _en_04. 1 Description.

AS-Interface I/O Module

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

Assembly and operating instructions DULCOMARIN II, P-Module (Power Supply Module with Relay) DXMaP

CONFIGURABLE SAFETY RELAYS

Documentation EM2042. Sixteen Channel Digital Output Module with D-Sub Connector. Version: Date:

PI-EX-ME-2NAM/COC-24VDC

QUINT-BUFFER/24DC/24DC/40

RIC PROGRAMMABLE INTELLIGENT CONTROLLER

English. Operating manual. Universal transmitter UT125. Save for later reference. Companies / brands of GHM

Data sheet ACT20P ACT20P-CMT-10-AO-RC-S. Phone: Fax: Web: - [!

PSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1

QUINT-PS/ 1AC/24DC/ 5

ABB i-bus KNX Analogue Input, 4-fold, MDRC AE/S , 2CDG110190R0011

Assembly. Front view. LED yellow: Relay output I. LED yellow: Relay output II

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

CMC III Temperature/Humidity Sensor

Power Supply HARTING pcon

LM24A-MOD. Cable 1 m, 6 x 0.75 mm 2 RJ12 socket

ABB i-bus KNX Analogue Actuator, 4-fold, MDRC, 0-10 V, 0-20 ma AA/S 4.1.2, 2CDG110202R0011

PI-EX-ME-2NAM/COC-120VAC

Data Sheet T 6493 EN. TROVIS 6400 Automation System TROVIS 6493 Compact Controller. For panel mounting (front frame 48 x 96 mm/1.89 x 3.

Digital Output Module 4-Channel Version for Zone 1 Series 9475/

BMF400 Input/output module

AV24-MFT AV24-MFT2 AV24-MFT2-C105. Power consumption In operation For wire sizing N 1700 N Control Control signal Y Operating range

Functional data Factory settings Variable Setting Torque Inhibiting torque

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B

I/O module, digital and universal inputs, modu530

VersaPoint I/O Module

ABB i-bus KNX Switch Actuator, x-fold, 6 A, MDRC SA/S x.6.1.1, 2CDG x R0011

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

Power Supply HARTING pcon

MINI MCR-SL-PT100-UI(-SP)(-NC)

Installation / control / monitoring technique. CANopen PLC IL 5504, IN 5504 minimaster

s Climatix AHU ext. module 14 I/O POL955.XX/XXX Climatix

Zelio Control-modular measurement and control relays 1

24 V DC typ. 0,65 W. Liquid level with conductive probes (type SK1, SK5) Resistance measurement E1-E0, E2-E0, E3-E0, E4-E0

Installation / Control / Monitoring Technique

SRQ24A. Technical data. Safety notes. Rotary actuator for ball valves Torque 16Nm Nominal voltage AC/DC 24V Control: Open-close Running time 9s

Operating instructions Safe AS-i input module ASIM-C-M About this document. Content

MINI-PS AC/10-15DC/8

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Installation / control / monitoring technique. CANopen PLC IL 5504, IN 5504 minimaster

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA

RE11RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

9.5 nominal torque 4.5 W 16 VA. Min. 30 nominal voltage Min. 30 Nm. Reversible with switch By mounting. MIN (minimum position)

SITOP 3-phase 24 V DC, 20 to 40 A

MINI MCR-SL-PT100-UI. Active resistance thermometer measuring transducer. Data sheet. 1 Description

Digital Output Module 4-Channel Version for Zone 1 Series 9475/

Safety Switching Devices SNO 4003K. Basic device for Emergency-Stop and Safety Gate Applications PI E

ISOMETER isoev425 with coupling device AGH420

PHOENIX CONTACT Features

PSR UC/ESAM4/3X1/1X2/B

PSR DC/ESP4/2X1/1X2

Operating Manual -ENGLISH- Page 1 KWG-ISO

TM5C12D6T6L compact I/O expansion block TM5-24 I/0-12 DI - 6 DO transistor - 4 AI - 2 AO

Signal Doublers. VariTrans A 20300

Assembly. Front view. LED yellow: Relay output. LED red: LB/SC Power Rail

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA 250 V AC

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

IST ULTRASTAB Power Supply for high precision transducers

Operating instructions. Standstill monitor A / / 2011

QUINT-PS AC/24DC/10

PHOENIX CONTACT - 05/2007

XU1-E Earth fault voltage relay. (August 1996) Manual XU1-E (Revision New)

Transcription:

Modules from the MFW product family 14.06.2004 I/O expansion modules Increasing the number of inputs and outputs of the MFW basic modules INFOwww.ees-online.de

Table of contents 1 Applicability 3 2 General notes 3 2.1 Symbols used 3 2.2 Terminology 4 2.3 Safety instructions 4 2.4 Correct and proper usage 5 2.5 Functional description 5 3 Assembly and installation 6 4 Configuring the expansion modules 7 4.1 General principles 7 4.2 Digital modules 7 4.2.1 Digital inputs 8 4.2.2 Digital outputs 9 4.2.3 Digital output modules in systems with IEC interface 10 4.3 Analogue modules 11 4.3.1 Analogue inputs 11 4.3.2 Analogue outputs 12 5 Control lamps 13 6 Technical data 13 7 Accessories 15 Page 2 of 15

1 Applicability The description applies to the following MFW modules: Item number 97AXXGAX0BA0 97AXXGAX0BB0 97AXXGAX0BE0 97AXXGAX0BF0 97AXXGAX0BJ0 97AXXGBX0BB0 97AXXGCX0BX0 97AXXGEX0BX0 97AXXGIX0BX0 2 General notes 2.1 Symbols used Type EM-G8DEX-0-BA-0 EM-G8DEX-0-BB-0 EM-G8DEX-0-BE-0 EM-G8DEX-0-BF-0 EM-G8DEX-0-BJ-0 EM-G8DAL-0-BB-0 EM-G8DAR-0-BX-0 EM-G4AE0-0-BX-0 EM-G4AA0-0-BX-0 The following symbols are used in this document: Safety instruction This symbol marks warnings, prohibitions and directions relating to hazards. It is essential that they are observed and obeyed. Additional note This symbol indicates additional information. Important section This symbol indicates particularly important information. Cross-reference This symbol refers to diagrams and to other locations within the document. Page 3 of 15

2.2 Terminology MFW The MFW modular telecontrol network consists of a central station and up to 31 outstations. Each station requires at least one basic module. Up to 15 expansion modules can be connected to this. Basic module The basic modules represent the minimum core of a telecontrol station. They contain at least the following function groups: internal modem optionally 8 binary inputs or outputs with status LED, or an additional serial interface for protocol coupling two CAN bus interfaces for connecting the expansion modules watchdog LED and fault signalling contact The basic modules are obtainable in two versions master module and outstation module. Master module Only one master module, whose type name contains MF-, needs to be present in the system, and is usually used in the central station. It co-ordinates the flow of data. Outstation module The outstation module, whose type name contains UF-, is used in the outstations. Expansion module Each basic module can be fitted with up to a maximum of 15 expansion modules in order to increase the I/O scope. These are connected via the CAN bus interface. I/O module The majority of basic modules contain 8 inputs or outputs. These are referred to as I/O modules. In the same way, the expansion modules contain an I/O module consisting of 8 binary inputs, 8 binary outputs, 4 analog inputs or 4 analog outputs. Station address To identify the stations in the MFW system, each outstation module is given a station address (1-31). The address 0 is reserved for the master module. Station addresses must be unique. Each I/O module is given a module number. The data is exchanged between modules with the same module number. The physical arrangement of the modules within the system (the station address) is of no significance at all here. The input module with number 5, for instance, transmits its data to all the output modules whose number is 5. 2.3 Safety instructions These operating instructions must be carefully read, understood and followed! Risk of interference with electronic devices! When operating the telecontrol system close to devices that are subject to interference, the special regulations for these areas must be observed! Page 4 of 15

Risk of ignition from electromagnetic fields! The MFW modules must not be operated in the neighbourhood of inflammable gases or liquids (fuel depots, petrol stations, chemical works, gas containers etc.)! Risk of damage! The MFW modules must not be opened or subjected to improper modification! 2.4 Correct and proper usage The telecontrol system is intended exclusively for the applications described in these operating instructions. Any other usage can be hazardous and is forbidden. The manufacturer cannot be held liable for the consequences of improper use of the MFW modules or for any application that does not accord with the contents of these operating instructions. 2.5 Functional description The expansion modules are for enlargement of the number of analogue or digital inputs and outputs of the basic modules of the MFW telecontrol network. They are connected over a bus cable to one of the two CAN bus sockets. The bus cable is part of the scope of delivery of the extension modules. The second socket is for connection of another module or an additional power supply unit or it is used for test purposes. The power supply of the expansion modules is by the basic modules over the CAN bus. In parallel it is possible to feed the modules by an additional supply unit, for instance type WSN ( à data sheet in our catalogue, column: power supply units). The configuration of the modules is done simply by DIP switches. The extension modules registrate themselves independently at the basic module and are thus immediately available. If an extension module fails, this is recognized by the basic module and treated as error (à operating instruction of the used basic modules). If the expansion module is removed consciously, the basic modul must be interrupted from the power supply. Hereby it is ensured that the removed extension module is cancelled from the table of the connected modules. If this would not be done, the module would be recognized as out of order and would be registrated as distored. At restarting all connected extension modules registrate themselves again. Page 5 of 15

3 Assembly and installation 1. Unpack all the telecontrol system s modules, and check them for transport damage. Report any transport damage immediately to the responsible carrier. Please check that the delivery is complete. The delivery can include master and outstation modules, expansion modules and other accessories. 2. Select mounting locations for the individual stations. 3. Module configuration (--> section covering Configuring the expansion modules ) 4. Click the expansion modules [7] next to the basic modules onto the rail [6] and connect them with the sockets of the basic modules by using the bus cable supplied. 5. Connect the input and output leads. The length of the input and output leads should not exceed a maximum of 3 m. OK-LED (green) [9] lights up and the CAN-Bus LED (yellow) [11] flashes. The expansion module is ready for operation. 9 Page 6 of 15 11

4 Configuring the expansion modules 4.1 General principles Data within the telecontrol system is exchanged on the basis of module numbers. A module number is assigned to every basic or expansion module that contains an I/O module. The data is exchanged between modules with the same module number. The physical arrangement of the modules within the system (the station address) is of no significance at all here. The input module with number 5, for instance, transmits its data to all the output modules for which the module number has also been set to 5. More than one output module can have the same module number. An input module number, however, can only be used once within one system. All the important settings can be made with the aid of DIP switches. These include, for instance, the station address (1 31), the module number (0 254), selection between static and counter values in the case of digital I/O or between current and voltage in the case of analog signals and so forth. DIP switches A and B [4, 5] are located on the sidewall of the expansion modules. s 251...254 are reserved for the output of station errors. 4.2 Digital modules The digital modules can be obtained in three versions: 8 digital inputs 8 relay outputs 8 transistor outputs There are 2 groups each of 4 inputs and outputs with a common root that are electrically isolated from one another. The exceptions are the transistor outputs; all those 8 outputs have the same GND. The first 4 inputs or outputs of each module can be optionally switched as binary or counter value. By output modules it is possible to switch between two count rates and the given impulse lengths. Page 7 of 15

4.2.1 Digital inputs Meaning Signal voltage Signal voltage Values of the I/O module 0 250 1-4 Binary or counter Page 8 of 15 : (Binary or counter) Channel 1 & 2 as counter input Adressing: (example for module numbers) Channel 2 & 4 as counter input

4.2.2 Digital outputs MFW-8DAR C - Connection point of common potential (selective + or -) Meaning Other count rates on request. Page 9 of 15 C - Internal ground (GND) Values of the I/O module 0 254 Kind of output 1-4 count rate Counter frequency Binary or counter 1 Hz / 12 Hz Kind of output: (Binary or counter) Count rate: Channel 1 & 2 as counter count rate = 1 Hz Adressing: (example for module numbers) Attention: positive switched PNP transistors! Channel 2 & 4 as counter count rate = 12 Hz

4.2.3 Digital output modules in systems with IEC interface In MFW systems, whose master is equipped with IEC 60870-5-101 interface, pulse and continuous commands can be read out over the output modules. If switch B5 is set to position On, the use of continuous commands as well as pulse commands is possible on all outputs. In this case the count pulse output on this module is not possible any more. A pulse width valid for all outputs in the range 40 ms to 120 s can be adjusted with switch B1 B4. B1 B2 B3 B4 pulse time Off Off Off Off 40 ms Off Off Off On 120 ms Off Off On Off 280 ms Off Off On On 600 ms Off On Off Off 1 s Off On Off On 1,5 s Off On On Off 2 s Off On On On 3 s On Off Off Off 5 s On Off Off On 8 s On Off On Off 10 s On Off On On 15 s On On Off Off 20 s On On Off On 30 s On On On Off 60 s On On On On 120 s Page 10 of 15

4.3 Analogue modules The analogue modules are available as input or output components. 4.3.1 Analogue inputs The input modules contain 4 analogue inputs, that have a common GND. The inputs are electrically isolated from the power supply. Each input can be switched between current and voltage by DIP switch (0 (4)... 20 ma or 0...10 V). Meaning Attention: common GND of the inputs! Page 11 of 15 Values of the I/O module 0 250 Current or voltage input may be set for each channel : (Current / voltage Current / voltage Channel 1 & 2 = I Channel 3 & 4 = U Adressing: (example for module numbers) Channel 2 & 4 = I Channel 1 & 3 = U

4.3.2 Analogue outputs The output modules include 4 short-circuit proof analogue current and voltage outputs (0 (4)... 20mA or 0...10V), for which no auxiliary voltage is required. Meaning The common GND is equipotential with the power supply. Attention: common GND of the inputs! analogue input module Values of the I/O module 0 250 Adressing: (example for module numbers) Page 12 of 15

5 Control lamps 6 Technical data 9 11 10 9 OK control lamp 10 Control lamps Digital inputs or outputs light up if a signal is present. 11 Control lamp CAN-Bus flashes if the module exchanges data with the basic module. General Data Operating and ambient temperature -20 C... +60 C Air humidity maximum 95 %, non-condensing Connection terminals nominal cross section 2.5 mm 2 Housing / protection class Plastic / IP 40 Digital input module Power consumption Signal voltage Input resistance Electrical isolation between signal and supply voltage Digital output module Power consumption With relay outputs With transistor outputs Contact loading of the relay outputs* minimum maximum Page 13 of 15 max. 1 W see table see table 4 kv eff max. 3 W max. 2 W logic + load current 1.2 V / 1 ma (suitable for control of LED) 250 V AC / 400 ma 250 V AC / 2 A (purely ohmic load) 30 V DC / 2 A 110 V DC / 0.2 A 220 V DC / 0.1 A Total 230 V AC current (purely ohmic load) 8 A Load capacity at transistor outputs max. 50 ma per output count rate switchable between 1 Hz or 12 Hz ** pulse width / pause 500 ms or 40 ms ** electrical isolation between relay contacts and power supply 4 kv eff (not for transistor outputs!)

Analogue input modules Power consumption max. 2 W resolution 12 bit Accuracy error < 0.25% of final value / 1 year *** Input current load 100 Ω Input resistance at voltage input 100 kω Analogue output modules Power consumption max. 3.5 W resolution 12 bit Accuracy error < 0.5% of final value / 1 year *** Maximum output current load 500 Ω Minimum load resistance (voltage) 1 kω to infinite Digital input modules are available with various signal voltages. The corresponding voltage is defined by the 13th digit of the type identification. Type Rate voltage Voltage range Input resistance limit EM-G8DEX-0-BA-0 12V AC/DC 9V 24V AC/DC approx. 5kΩ EM-G8DEX-0-BB-0 24V AC/DC 16V 48V AC/DC 10 kω EM-G8DEX-0-BE-0 60V AC/DC 35V 75V AC/DC 22 kω EM-G8DEX-0-BF-0 110V AC/DC 75V 130V AC/DC 68 kω EM-G8DEX-0-BJ-0 220V AC/DC 180V 255V AC/DC 180 kω * We would be happy to supply you with more precise specifications on request. ** Other values on request *** For greatest accuracy an annual calibration service is available. Page 14 of 15

I/O expansion modules Dimensional drawing I/O expansion modules Order identification EM-G8DEX-0-BB-0 EM-G8DAR-0-BX-0 EM-G8DAL-0-BB-0 EM-G4AE0-0-BX-0 EM-G4AA0-0-BX-0 7 Accessories HOTLINE +49(0)7191-182-235/214 INTERNET www.ees-online.de Elektra Elektronik GmbH & Co Störcontroller KG Hummelbühl 7-9 D-71522 Backnang/Germany P.O.Box 12 40 D-71502 Backnang Phone: +49(0)7191/182-0 Fax: +49(0)7191/182-200 e-mail: info@ees-online.de expansion module 8 digital inputs expansion module 8 relay outputs expansion module 8 transistor outputs expansion module 4 analogue inputs 0 (4)... 20 ma or 0...10 V expansion module 4 analogue outputs 0 (4)... 20 ma or 0...10 V Dimensions in mm The right to make technical changes is reserved Only accessories approved by the manufacturer may be connected to the MFW module. Further accessories and more detailed information may be found in the appropriate product sections in the catalogue.