Using an EXOR HMI with an SMLC

Similar documents
CODESYS V2.3 Ethernet Driver for JMobile

Please refer to application note AN00129 for further details on HCP2 configuration in ABB motion control products.

ABB Modbus RTU Driver for JMobile

Using the Panasonic GT01 HMI with Exlar s Tritex Drive

Using Modbus TCP with Brainboxes products

CODESYS V3 Ethernet Driver for JMobile

Modbus ASCII Serial Device Driver Help 2009 Kepware Technologies

Simatic S7 Ethernet driver for JMobile

Modicon Modbus Driver

Modbus Plus Driver Help Kepware Technologies

Modbus Plus Driver Help Kepware Technologies

Modbus TCP/IP Ethernet Driver Help Kepware Technologies

Modbus TCP Driver for JMobile

Operating guide. OPC server for ECL Comfort 310. Table of Contents

Micro800 Programming Basics. For Classroom Use Only!

Mitsubishi FX Driver for JMobile

Modbus Plus Driver Kepware, Inc.

Modbus RTU Serial Driver Help 2010 Kepware Technologies

PiXtend with CODESYS Create Project

CODESYS Driver PTC Inc. All Rights Reserved.

Connecting UniOP to the ABB 07KT97 Controllers

SCE Training Curriculum for the end-to-end automation solution Totally Integrated Automation (TIA)

ivu Plus Industrial Ethernet Instruction Manual

Polling ASCII devices as Modbus slaves. February

Internal PLC (CODESYS) User Manual

Using the WAGO AS-i Module with the SMLC. 9/13/2007 Using the WAGO AS-i Module with the SMLC 1

Wago Ethernet Driver Help Kepware Technologies

Addendum to Verbatim Gateway Owner's Manual How to configure a Verbatim EtherNet/IP with RSLogix 5000

Motion Control Products Application note MotiFlex e180 PROFINET configuration AN

Simulator Driver PTC Inc. All Rights Reserved.

Yokogawa Application Note 4. The CPU Device Area Setup is now displayed. In the example below, no global memory has been allocated for use

Connecting UniOP as a Modbus Slave

Getting started with Java

Switching Circuits and Logic Design Prof. Indranil Sengupta Department of Computer Science and Engineering Indian Institute of Technology, Kharagpur

EZware Quick Start Guide

Modbus RTU Serial Driver Help 2009 Kepware Technologies

APPLICATION NOTES. Advanced Graphical Interface - AGI Internal PLC (CODESYS V3) SHENDONG

Honeywell Trendview Recorder & Acromag 967EN Modbus/TCP Module as Remote I/O

Variables and Functions. ROBOTC Software

REPLACING A PEERLINK NETWORK WITH 2572-A / 2572-B ETHERNET

CODESYS Driver PTC Inc. All Rights Reserved.

Micro800 Controllers Starter Pack Quick Start

Connecting UniOP as Modbus/TCP Server

TOP Server V5 to MicroLogix Using DNP3 Ethernet Driver

Addendum to Catalyst Owner's Manual How to configure a Catalyst EtherNet/IP with RSLogix 5000

ARGEE 2 Reference Manual

cmt3090 and Remote I/O Quick Start Guide

Allen-Bradley Micro800 Ethernet Driver Help Kepware Technologies

Micro800 Programming Basics. For Classroom Use Only!

Opto 22 Ethernet Driver Help Kepware Technologies

FlexiSoft Software Release Note

OPEN MODBUS/TCP SPECIFICATION

ControlLogix PLC Example. Show Controller: V16 Pro Script File: PLC_ControlLogix.ami

Lecture 2 Tao Wang 1

CONTROLLER INFORMATION SHEET

MW100 Setting for Data Communications via Modbus Protocol. Connect to Ethernet. Enter Ethernet settings. Enter Server Settings

Technical Information Sheet

Motors I Automation I Energy I Transmission & Distribution I Coatings. SoftPLC CFW100. User Manual

QuickStart Guide. Configuring a RedLion HMI to communicate with an MPiec Controller via MODBUS/TCP using Crimson 3

Motors I Automation I Energy I Transmission & Distribution I Coatings. SoftPLC CFW500. User s Manual

Lufkin Modbus Serial Driver Help Kepware Technologies

CODESYS V3 Quick Start

INTRODUCTION...2 GENERAL INFORMATION...3 DEVICE CHARACTERISTICS...3 LINK CHARACTERISTICS...3 DRIVER CHARACTERISTICS...3 CONFORMANCE TESTING...

Section 2.3 Rational Numbers. A rational number is a number that may be written in the form a b. for any integer a and any nonzero integer b.

Will introduce various operators supported by C language Identify supported operations Present some of terms characterizing operators

MULTIPROG QUICK START GUIDE

Using ModbusTest. Introduction:

FBE - Library. Reference Guide for use with EASY242 & EASY2606

Motion Control Products Application note Connecting CP600 to motion products via Modbus RTU

Micro800 Programmable Controllers: Getting Started with CIP Client Messaging

Yokogawa YS100 Serial Driver Help Kepware Technologies

13-1. This chapter explains how to use different objects.

Ignition HMI interface to Fanuc Industrial Robots

Modbus TCP Server Driver for JMobile

Motion Control Products Application note Connecting CP600 to motion products via Modbus TCP

Understanding Design Annotation. Contents

Introduction. Contents (these are links; click to jump to a topic)

Honeywell HC-900 with Acromag 967EN Modbus/TCP Module as Remote I/O

Setting up Pinnacle Ethernet IP communication with Allen Bradley PLCs

Connecting UniOP to Modbus/TCP

Version 2.0. January For Firmware versions 4.25 and 5.2

Servo press kit YJKP - Host interface

CSCI 2010 Principles of Computer Science. Data and Expressions 08/09/2013 CSCI

Modbus Unsolicited Serial Driver PTC Inc. All Rights Reserved.

A PLC Achievement Test

Motion Control Products Application note Connecting CP600 to motion products via Modbus RTU

series Guide to MICREX-SX ~ Using simulator function of D300winV3 ~ FEH253-1

Siemens S7 MPI Driver PTC Inc. All Rights Reserved.

ICC. Modbus/TCP Client Driver Manual INDUSTRIAL CONTROL COMMUNICATIONS, INC Industrial Control Communications, Inc.

WebAccess AB LOGIX PLC Ethernet Driver Guide. Advantech WebAccess. - AB LOGIX PLC Ethernet Driver Guide Version: 1.02

Omron NJ Ethernet Driver Help Kepware Technologies

MODBUS TESTER SOFTWARE U S E R M A N U A L

L01 - Effective Design Methods for Integrating Safety Using Logix Controllers. For Classroom Use Only!

Motion Control Products Application note Ethernet POWERLINK routing using motion drives

3 Connecting to a Controller

CoDeSys Library Extension for EASY242 Applications. FBE - Library. Reference Guide for use with EASY242

CSc 10200! Introduction to Computing. Lecture 2-3 Edgardo Molina Fall 2013 City College of New York

Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE B5 Structured programming with function blocks

Introduction to Programming in C Department of Computer Science and Engineering. Lecture No. #17. Loops: Break Statement

Chapter 2: Using Data

Transcription:

Using an EXOR HMI with an SMLC This tutorial covers connecting an EXOR HMI to an SMLC via Ethernet. Communications will use the standard Modbus/TCP protocol supported by both the EXOR HMI and the SMLC. This tutorial covers an Ethernet connection between the two devices so the optional Ethernet port on the EXOR is required. This tutorial assumes basic familiarity with SMLC IEC 61131-3 programming. Ethernet (Modbus/TCP) connection 11/18/2005 SMLC/EXOR HMI Tutorial 1

SMLC to EXOR HMI Tutorial - Basic concepts This tutorial will cover the transfer of the following data types between an SMLC and an EXOR HMI. The IEC-61131-3 data type is in parentheses. Boolean, single bit data (BOOL) Integer, 16-bit data (INT) Double Integer, 32-bit data (DINT) Floating point, 32-bit data (REAL) Strings, 40 characters max (STRING) The SMLC contains a bank of 2000 virtual Modbus registers. These registers simulate holding registers in a Modicon PLC (4xxxxx). All access from the EXOR to the SMLC will be via these holding registers. These virtual Modbus registers can be mapped to IEC addresses in blocks of 40 at a time. Each block of registers can be mapped to either: 40 INTs 20 DINTs 20 REALs 1 STRING (80 characters) The IEC address corresponds to the Modbus register number. E.g. %QW1 = Register 400001 = Register 1, %QW2 = Register 400002 = Register 2, etc. The HMI cannot directly access the SMLC physical I/O. If you need this functionality your program will have to copy physical I/O points to HMI variables and vice versa. HMI variables are initialized to 0 at SMLC powerup so if you want HMI values to be retain/persistent you need to copy the retain/persistent value to the HMI variables once after powerup and then copy the HMI values back to the retain/persistent variables every scan after that. 11/18/2005 SMLC/EXOR HMI Tutorial 2

SMLC Configuration - Configuring the HMI driver In CoDeSys go to the PLC Configuration section of the Resources tab Select the HMI/Modbus Interface section of the SMLC - HMI/IO Configuration tree On the Module parameters tab select Modbus/TCP (Ethernet) Enter the IP Address of the SMLC Ethernet port that you will be connecting the HMI to. In this example we re going to connect the HMI to the EN0 port on the SMLC which is at the default IP address of 192.168.0.253. 11/18/2005 SMLC/EXOR HMI Tutorial 3

SMLC Configuration - Creating the Modbus Registers Right click on the HMI/Modbus Interface in the PLC Configuration tree and select Append Subelement 40 INT variables. This adds the first bank of 40 registers. The IEC address of the register corresponds to the Modbus register number. The Exor uses 4xxxxx nomenclature for Modbus registers so 400001 = %QW1 400002 = %QW2 400003 = %QW3 etc. 11/18/2005 SMLC/EXOR HMI Tutorial 4

SMLC Configuration - Boolean variables In our HMI we want to have some bit level, or boolean devices such as pushbuttons and pilot lights. To assign a bit level device we will use the bits of individual registers. Expand the register at %QW1 and double-click on the AT to the left of the %QX1.0. Enter the variable name to be used in the SMLC program. By convention we use a prefix hmi_ to indicate that this is an hmi variable and a b to indicate that its a boolean for a final variable name of hmi_bpb1. 11/18/2005 SMLC/EXOR HMI Tutorial 5

SMLC Configuration - Boolean variables Add some more boolean variables for later use in our tutorial. We will add a total of 3 pushbutton inputs, 3 inputs for selecting different string messages using a selector switch and 3 pilot light outputs. TIP when creating boolean variables for the HMI put the input bits and output bits into separate words in the PLC Configuration. If you mix input and output bits in the same word you could have a race condition between the HMI and PLC program as to who updates the its outputs last. TIP It may be useful to assign variable names to the words that contain the bits. This can help keep things organized. In this example we have named the words hmi_idiscreteinputs and hmi_idiscreteoutputs. When you re done things should look like this in registers 1 and 2. 11/18/2005 SMLC/EXOR HMI Tutorial 6

SMLC Configuration - Integer variables We want to have some integer level devices for numeric data entry and display. To assign a integer variable we will use entire registers. Registers in the SMLC are signed integers or INT in IEC type nomenclature. The Exor supports Signed and Unsigned word access. Double-click on the AT to the left of the %QW3. Enter the variable name to be used in the SMLC program. By convention we use a prefix hmi_ to indicate that this is an hmi variable and a i to indicate that its an integer for a variable name of hmi_ioutputvalue1. Add another integer variable at %QW4 called hmi_iinputvalue1. 11/18/2005 SMLC/EXOR HMI Tutorial 7

SMLC Configuration - Double Integer variables In our HMI we want to have some double integer (32-bit) level devices for displaying or entering very large values. Right-click on the HMI/Modbus Interface and append 20 DINT variables. Note that DINT register numbers increase by two because each 32-bit value is two 16-bit Modbus registers. Double click on the AT in front of %QW41 and enter the variable name to be used in the SMLC program. By convention we use di to indicate that its a DINT for a variable name of hmi_dioutputvalue1. Add another variable at %QW43 called hmi_diinputvalue1. 11/18/2005 SMLC/EXOR HMI Tutorial 8

SMLC Configuration - String variables In our HMI we want to have a string variable to display messages that are formulated by the SMLC program. The EXOR has the capability to store internal message lists that are called up by a value in a register. For that type of message you can simply use an integer register. In this example we will actually build custom strings within the SMLC program and display them in a string variable. Right-click on the HMI/Modbus Interface and append 1 STRING variable. Each string takes 40 registers and can contain up to 80 characters. Note that in the EXOR strings are limited to 40 characters. Double click on the AT in front of %QW41 and enter the variable name to be used in the SMLC program. By convention we use s to indicate that its a STRING for a variable name of hmi_smsg. 11/18/2005 SMLC/EXOR HMI Tutorial 9

SMLC Configuration - Floating point variables In our HMI we want to have some floating point devices for displaying or entering floating point values. Right-click on the HMI/Modbus Interface and append 20 REAL variables. Note that REAL register numbers increase by two because each 32-bit value is two 16-bit Modbus registers. Double click on the AT in front of %QW122 and enter the variable name to be used in the SMLC program. Note that in our naming convention we use r to indicate that its a REAL for a variable name of hmi_routputvalue1. Add another variable at %QW124 called hmi_rinputvalue1. 11/18/2005 SMLC/EXOR HMI Tutorial 10

EXOR Configuration for operation with the SMLC Start the EXOR Designer software Create a new project Select Project Configure Controller Select the Modbus/TCP driver Click on the Controller Setup button Click on... to configure the Modbus/TCP driver. 11/18/2005 SMLC/EXOR HMI Tutorial 11

EXOR Configuration for operation with the SMLC Enter the IP Address of the SMLC Leave the Port at 502 Leave the Unit identifier at 1 Set the desired timeout (the default of 2000 msec is fine) Leave the Disable Modicon Mode checkbox unchecked Make sure Use Modbus function 16 is selected. Select Generic ModbusTCP for the PLC Model. Click on the OK button NOTE: This tutorial assumes that you have already configured the Ethernet port of the EXOR display. If not, refer to the EXOR documentation. 11/18/2005 SMLC/EXOR HMI Tutorial 12

Single bit devices - Push button In Designer insert a Push Button onto the page. Click on the... next to the Ref to bring up the Data Field Properties page. Select Data Type Holding Register Set the Address Offset to 400001 (remember this corresponds to %QW1 in the SMLC) Set the Data Format to BIT Set the Bit index to 0. This refers to bit 0 in register 1 or %QX1.0 in the SMLC PLC Configuration. 11/18/2005 SMLC/EXOR HMI Tutorial 13

Single bit devices - Push button Download the CoDeSys project to the SMLC and run the program. Download the HMI project to the HMI. Press the Push Button on the HMI In the CoDeSys PLC Configuration you should see the input bit light up 11/18/2005 SMLC/EXOR HMI Tutorial 14

Single bit devices - Pilot Light Now lets create a Pilot light output. Recall that in the SMLC PLC Configuration we named bit 0 of Register 2 (%QX2.0) hmi_bpl1 (for Pilot Light 1) Add a run of logic to PLC_PRG that reads hmi_bpb1 and turns on hmi_bpl1 Download this change to the SMLC 11/18/2005 SMLC/EXOR HMI Tutorial 15

Single bit devices - Pilot Light In Designer insert an Indicator Light (Pilot light) On the Data Field Properties page set the Data Type to Holding Register Set the Address Offset to 400002 (which corresponds to %QW2 in the SMLC PLC Configuration) Set the Data Format to BIT Set the Bit Index to 00 (which corresponds to %QX2.0 in the SMLC PLC Configuration). Download this new page to the HMI Press the button on the screen. The Pilot light should turn Green and the PLC logic should indicate that the hmi_bpl1 output is turned on. EXCERSISE add the display elements and logic for two more pushbuttons and two pilot lights using the additional PB inputs and PL outputs that we defined earlier. 11/18/2005 SMLC/EXOR HMI Tutorial 16

Integer data display In the next example we want to display an integer value from the SMLC program on the HMI. Recall that in the CoDeSys PLC Configuration we created an integer variable at %QW3 called hmi_ioutputvalue1. This will be a value that we update in our PLC program and display on the HMI. In PLC_PRG add a rung of logic that adds 1 to hmi_ioutputvalue1 and stores the result in hmi_ioutputvalue1. This will cause hmi_ioutputvalue1 to increment until it reaches 32767 at which point it will wrap around to -32768 and start incrementing again. We want to see this value incrementing on the HMI. Download this change to the SMLC. 11/18/2005 SMLC/EXOR HMI Tutorial 17

Integer data display In Designer insert a Numeric Field onto the page. Set the Width to 6 Press the... to edit the Data Field Properties. On the Data Field Properties page set the Address Offset to 400003 (corresponding to %QW3 in the SMLC s PLC Configuration) Set the Data Format to WORD(Bin) Download the screen to the HMI and verify that the value is updating. 11/18/2005 SMLC/EXOR HMI Tutorial 18

Integer data input In the next example we want to enter an integer data value on the HMI and have it appear in the SMLC program. Recall that in the CoDeSys PLC Configuration we created an integer variable at %QW4 called hmi_iinputvalue1. The value entered on the HMI will show up here. 11/18/2005 SMLC/EXOR HMI Tutorial 19

Integer data input In Designer insert a Numeric Field onto the page and set the Width to 6 Press the... to edit the Data Field Properties. On the Data Field Properties page set the Address Offset to 400003 (corresponding to %QW3 in the SMLC s PLC Configuration). Set the Data Format to WORD(Bin). On the Range tab set the Access to Read/Write 11/18/2005 SMLC/EXOR HMI Tutorial 20

Double Integer data display In the next example we want to display an integer value from the SMLC program on the HMI. Recall that in the CoDeSys PLC Configuration we created an integer variable at %QW41 called hmi_dioutputvalue1. This will be a value that we update in our PLC program and display on the HMI. In PLC_PRG add a run that adds 10000 to hmi_dioutputvalue1 and stores the result in hmi_dioutputvalue1. This will cause hmi_dioutputvalue1 to increment until it reaches 2147483647 at which point it will wrap around to -2147483648 and start incrementing again. Download this to the SMLC 11/18/2005 SMLC/EXOR HMI Tutorial 21

Double Integer data display In Designer insert a Numeric Field onto the page Set the Width to 12 Press the... to edit the Data Field Properties On the Data Field Properties page set the Address Offset to 400041 (corresponding to %QW41 in the SMLC s PLC Configuration) Set the Data Format to DBLE WORD(Bin) Download this program to the HMI and verify that the value updates. 11/18/2005 SMLC/EXOR HMI Tutorial 22

Double Integer data input In the next example we want to enter an integer data value on the HMI and have it appear in the SMLC program. Recall that in the CoDeSys PLC Configuration we created a double integer variable at %QW43 called hmi_diinputvalue1. The value entered on the HMI will show up here. 11/18/2005 SMLC/EXOR HMI Tutorial 23

Double Integer data input In Designer insert a Numeric Field onto the page Set the Width to 12 and then press the... to edit the Data Field Properties On the Data Field Properties page set the Address Offset to 400043 (corresponding to %QW43 in the SMLC s PLC Configuration) Set the Data Format to DBLE WORD(Bin) On the Range tab enable Read/Write 11/18/2005 SMLC/EXOR HMI Tutorial 24

Floating point data display In the next example we want to display an integer value from the SMLC program on the HMI. Recall that in the PLC Configuration we created a real variable hmi_routputvalue1 at %QW122. This will be a value that we update in our PLC program and display on the HMI. In PLC_PRG add a run that adds.01 to hmi_routputvalue1 and stores the result in hmi_routputvalue1. This will cause hmi_routputvalue1 to increment until it reaches the maximum floating point value at which point it will wrap around to the minimum floating point value. 11/18/2005 SMLC/EXOR HMI Tutorial 25

Floating point data display In Designer insert a Numeric Field onto the page Set the Format to Fixed point and select the desired number of decimal places, in this example 4. Set the Width to 12 Press the... to edit the Data Field Properties On the Data Field Properties page set the Address Offset to 400122 (corresponding to %QW122 in the SMLC s PLC Configuration) Set the Data Format to FLOAT 11/18/2005 SMLC/EXOR HMI Tutorial 26

Floating point data input In the next example we want to enter an integer data value on the HMI and have it appear in the SMLC program. Recall that in the CoDeSys PLC Configuration we created a real variable at %QW124 called hmi_rinputvalue1. The value entered on the HMI will show up here. 11/18/2005 SMLC/EXOR HMI Tutorial 27

Floating point data input In Designer insert a Numeric Field onto the page Set the Width to 12, enable Fixed point, set the Placement to 4 and then press the... to edit the Data Field Properties On the Data Field Properties page set the Address Offset to 400124 (corresponding to %QW124 in the SMLC s PLC Configuration) Set the Data Format to FLOAT On the Range tab enable Read/Write 11/18/2005 SMLC/EXOR HMI Tutorial 28

String data display In the next example we want to display an string value from the SMLC program on the HMI. Recall that in the CoDeSys PLC Configuration we created a string variable at %QW81 called hmi_smsg. This will be a value that we update in our PLC program and display on the HMI. In PLC_PRG add logic that fills the hmi_smsg variable with three different strings depending on which input condition is true. We use the RPAD function from the OrmLibMisc library rather than a simple MOVE block so we can pad the end of the string with spaces out to the maximum string length supported by the EXOR of 40 characters. The 3rd string we make dynamic by concatenating an ever changing value. 11/18/2005 SMLC/EXOR HMI Tutorial 29

String data display In Designer insert a Numeric Field onto the page Select Style ASCII Set the Width to 40 and then press the... to edit the Data Field Properties On the Data Field Properties page set the Address Offset to 400081 (corresponding to %QW81 in the SMLC s PLC Configuration) Set the Data Format to ASCII 11/18/2005 SMLC/EXOR HMI Tutorial 30

String data display - adding a selector switch Now lets add a selector switch to choose between the three string messages In Designer insert a selector switch onto the page. Set the number of states to 3 For each state go to the Data Field Properties and set the Address offset to 400001 (%QW1), select BIT for the Data Format and set the Bit Offset at 3, 4 and 5 respectively for the three states. This corresponds to %QX1.3, %QX1.4 and %QX1.5 in the SMLC PLC Configuration 11/18/2005 SMLC/EXOR HMI Tutorial 31

Our final screen layout 11/18/2005 SMLC/EXOR HMI Tutorial 32

Dealing with Retain/Persistent HMI variables The SMLC initializes all of its I/O in the PLC Configuration at powerup including the HMI registers. If we want to have HMI variables be retained and/or persistent we will need to copy the HMI variable to retain/persistent variables every scan of our program and we will also need to copy the retain/persistent variables to our HMI variables once after powerup. To make this simpler we will create two user-defined function blocks: CopyHMItoRetain and CopyRetainToHMI. For this example the variables we will be concerned with are hmi_iinputvalue1, hmi_diinputvalue1 and hmi_rinputvalue1 but this example can easily be extended to include other HMI variables. In the first rung of our program we will copy the retain/persistent variables to the HMI variables on the rising edge of the Execute input (which will occur on the first scan of our program after powerup). In the last rung of our program we will copy the HMI variables to the retain/persistent variables. Note that we do this every scan after the CopyRetainToHMI as completed. 11/18/2005 SMLC/EXOR HMI Tutorial 33

Declaring the retain/persistent variables On the Global Variables section of the Resources tab declare our three variables in a section as shown. By convention we prefix the variable names with gnv_ which stands for global non-volatile. 11/18/2005 SMLC/EXOR HMI Tutorial 34

CopyRetainToHMI Function Block source Lets examine the CopyRetainToHMI function block On the rising edge of the Execute input (which will happen on the very first scan of our program) start a 100 msec timer. The timer is required because the SMLC initializes all of its inputs at powerup and this is done by another task and may not be completed by the time our first scan runs. By delaying 100msec we can be certain that this task has completed. After the timeout has completed we copy the contents of the HMI variables to the retain variables and then turn on the Done output. You should use this Done output to control when you start copying the HMI variables into the retain variables. 11/18/2005 SMLC/EXOR HMI Tutorial 35

CopyHMIToRetain Function Block source Now lets examine the CopyHMIToRetain function block source. If the Enable input is True then we copy all HMI variables to their retain equivalents. You should do this every scan after the CopyRetainToHMI has completed. 11/18/2005 SMLC/EXOR HMI Tutorial 36

Final SMLC program source for PLC_PRG 11/18/2005 SMLC/EXOR HMI Tutorial 37

Final SMLC program source for PLC_PRG 11/18/2005 SMLC/EXOR HMI Tutorial 38

Final SMLC program source for PLC_PRG 11/18/2005 SMLC/EXOR HMI Tutorial 39

Conclusion This concludes our SMLC/EXOR HMI tutorial Ethernet (Modbus/TCP) connection 11/18/2005 SMLC/EXOR HMI Tutorial 40