OPERATING MANUAL LOW-VOLTAGE DISCONNECT PANELS LVD400 & LVD600 SERIES

Similar documents
OPERATING MANUAL INV2500-HS SERIES INVERTERS & SHELVES

ULTRA-COMPACT 48V, 24V and 12V INTEGRATED DC POWER SYSTEMS

OPERATING MANUAL PDUAC3U SERIES AC POWER DISTRIBUTION UNITS

SETUP GUIDE SNMP ALARM ADAPTOR COMPATIBLE WITH SIGMA, RADIAN, TPCMQ & BLUEstreak POWER SHELVES

TMF SERIES: 1U HOT-SWAP POWER SYSTEM Single Output 400 Watt Modules with PFC

Dual-Feed 80A Auto Low Voltage Disconnect Panel - 80LVD02

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual

Specifications, Installation, and Operating Instructions

DCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies

Installation and Operation Guide for PD5200 and PD5300 Automatic Transfer Switch

OPERATING AND SERVICE MANUAL. Universal Interface Device 47

OPERATING MANUAL RANGER SERIES FRONT-ENDS & RECTIFIERS

OPERATING MANUAL TWRI SERIES RF/WIRELESS FRONT-ENDS AND SHELVES

Innovative Circuit Technology Ltd.

CMSA-100 Manual. Cinema Media Server Automation

OPERATING AND SERVICE MANUAL. Universal Interface Device 47

Global Water Instrumentation, Inc.

OPERATING MANUAL AC POWER DISTRIBUTION UNITS VIGILANT SERIES

XBDM. 1015LV, 1020LV, 1030LV, 1020HV Models USER & INSTALLATION MANUAL BYPASS DISTRIBUTION MODULE

to 48V DC Power Supply

HUBBCOM GSC3000/GSC4000 Flush-Mount Smart Controller Quick Installation Guide

iconverter 2-Module Power Chassis

PagePac PAGEPAC PLUS ZONE EXPANSION UNIT V

FMPe30.48G 48VDC RECTIFIER 60 Amps 2900 Watts

INSTALLATION MANUAL SLI 50 INVERTER

Name No. of I/O points Model Safety inputs: 12, test outputs: 4

Automated Tuner System Power Distribution Hub

IRB-MON O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY PHOTOEYE U L M O N I T O R E D DEVICE

Push-Pull and E-Stop Switches. Datasheet

User Guide. DMXSM-H18 Splitter. DMXSM-H81 Merger. Document Release Aug Revision B

Westell. Breaker Panel Technical Practice NPDRP1114

Broadband Automatic Disconnect Switch. User Manual

Breaker Panel Technical Practice NPDRP1114

PCM-7140 Pulsed Current Source Operation Manual

FRONT-ENDS AND RECTIFIERS.

User s Guide. POWERVAR Single Phase Power Conditioners

American Power Design, Inc.

EASON TECHNOLOGY. IO8 & IO24 Break-Out Module

Carefree-Security. Installation and programming instructions 1050A. Owner s Manual

Model 4001A Modular System Bin Operating and Service Manual

Options. 24-VDC service power supply. RUN output. No Yes No 24 VDC 70 W NX-PD7001

SATA II HDD Canister KISS DA 435 Quick Reference Guide

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL

Digital Lighting Systems, Inc.

OPERATING MANUAL X200 COMPACT INTEGRATED DC POWER SYSTEM

Digital Lighting Systems, Inc.

TCP305A & TCP312A AC/DC Current Probes Instructions

PIM-Mini Pulsed Current Source Operation Manual

Power Supply (48Vdc, 2.5A)

GUARDIAN ACCESS MODELS GDN.S.48.M24 & GDN.S.48.MS32 Integrated DC Power System & Battery -48VDC 500A 26.8kW

Communication Hub. Model: HUB-1. 8 Pheasant Run Newtown, PA USA

VIP-812A DUAL NETWORKED STATION PORT

E2EY. A Proximity Sensor for Aluminum, Brass and Other Non-ferrous Metals. Iron Is Not Detected. Aluminum-detecting Proximity Sensor

S82S (3/7.5-W Models)

NJ-Series Power Supply Unit NJ-PA/PD

G3B/G3BD. Model Number Structure. Ordering Information. Solid State Relays Model Number Legend. List of Models

Zonit μats TM Users Guide μats1-lv Version 1.2

APMC4110 POWERED PMC CARRIER STANDALONE PCI INTERFACE MODULE

CS1W-B7A. CS-series B7A Interface Unit. It transmits 16 points of I/O signals per word with a pair of cables. Easy and minimized wiring effort,

Application Guide. M 2174B Moloney Replacement Adapter Panel

Agilent Technologies E5339A 38-Pin Low-Voltage Probe

Secured Series: Hub Plus Kit Single Door Controller Package Installation Manual

Name Specifications Model Standards RS-422A Converter. Converts RS-233C to RS-422A/RS-485. CJ1W-CIF11 UC1, N, L, CE

Model 4002D NIM Bin Power Supply Operating and Service Manual

Ordering Information. I/O Relay G7T. Model Number Legend Slim-styled I/O Relay Saves Space in Panel

500 Business Center Drive Pittsburgh, PA USA CAGE 1BGJ7. SwitchMaster R5000 Series Ultra-Compact Ganged A/B Switching System

E2K-F. Flat Capacitive Sensor with a Thickness of Only 10 mm. Flat Proximity Sensor. Ordering Information. Sensors [Refer to Dimensions on page 4.

Installation, Operation & Maintenance Instructions / Technical Document

87421/22A Power Supply. Operating and Service Manual

VIP-804 QUAD ENHANCED NETWORK AUDIO PORT

USER MANUAL. MODEL 56X Series 564, 566, 568, 562. Hub Surge Protectors

Manual No: Revision: F. Relay Output Modules. Installation Guide

VIP-480AL IP One-Way Horn

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L MONITORED DEVICE

G3F/G3FD. Model Number Structure. Solid State Relays Model Number Legend

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L M O N I T O R E D DEVICE

MIC-3002A Series. 3U 6-slot CompactPCI Enclosures with Rear I/O and 6" LCD. User Manual

G3FM. Model Number Structure. Ordering Information. Solid State Relays. Model Number Legend. List of Models

Power Rack 58. EXT-PS5-8R User Manual.

LCI Load Cell Junction Box with Fault Monitor

RB24 Relay Box Installation Guide For use in low voltage motorized window and skylight systems

CSM_PYF S/P2RF- -S_DS_E_2_5

VE8014A/VE8014AR QUAD NETWORKED STATION PORT

DISCONTINUED PRODUCT DISCONTINUED PRODUCT

TCD600 OPEN LOOP TENSION CONTROLLER INSTALLATION, OPERATION MANUAL ADDENDUM (NETWORK FEATURE)

INSTRUCTION MANUAL RA 19-7B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

LCI User Manual mantracourt.com

3-4 SAS/SATA II HDD Canister Entry version USER S MANUAL XC-34D1-SA10-0-R. Document number: MAN A

Sensing method Appearance Connection method Sensing distance Model. Pre-wired (2 m) Power supply Application Appearance Function Model

INSTRUCTION MANUAL RA 19-6B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

CK3W-PD048 CSM_CK3W-PD048_DS_E_DITA_1_2

SA-59. GSM Communicator. Installation Manual

RTD SAMPLER OPERATOR S MANUAL

INSTRUCTION MANUAL RA 19-5B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

Solid State Relays with Failure Detection Function

OPERATING AND SERVICE MANUAL. Universal Interface Device 45

Conductive Level Controller

G3NE. Model Number Structure. Solid State Relays. Model Number Legend. Compact, Low-cost, SSR Switching 5 to 20 A

Split2.8 RDM. 2 input DMX/RDM Splitter. User guide

Digital Lighting Systems, Inc. CD400-DMX DMX512 Four Channel Dimmer and Switch module

Transcription:

PRICE: $25.00 LOW-VOLTAGE DISCONNECT PANELS LVD400 & LVD600 SERIES www.unipowertelecom.com Manual No. LVD-201-2 8/29/01/L46Man 2001 UNIPOWER Corp. All Rights Reserved UNIPOWER Telecom, Division of UNIPOWER Corporation NORTH AMERICA 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA Tel: +1 954-346-2442 Fax: +1 954-340-7901 sales@unipower-corp.com EUROPE Parkland Business Centre, Chartwell Road, Lancing BN15 8UE, ENGLAND Tel: +44(0)1903 768200 Fax: +44(0)1903 764540 info@unipower-europe.com

CONTENTS SECTION TOPIC PAGE 1.0 Introduction 1 2.0 Features and Options 1 3.0 Product Designation 3 4.0 Safety Warnings 3 5.0 Warranty 4 6.0 Unpacking and Inspection 4 7.0 Specifications 5 8.0 Safety and Industry Standards 6 9.0 Description of Operation 6 10.0 Front Panel Description 6 11.0 Back Panel Power Connections 8 12.0 Form C Relay Contacts 8 13.0 Installation 8 14.0 Setup and Testing 10

ILLUSTRATIONS FIGURE TITLE PAGE 1 LVD400/600 Low-Voltage Disconnect Panel 2 2 Simplified Diagram of LVD400/600 2 3 Back and Side Views of LVD400/600 7 4 Connections for LVD400/600 7 5 Rear Connections to the LVD400/600 9

LOW-VOLTAGE DISCONNECT PANELS LVD400 & LVD600 SERIES 1.0 INTRODUCTION 1.1 This Operating Manual should be read through carefully before installing and operating the LVD400/600 Series Low-Voltage Disconnect Panels. 1.2 The LVD400/600 panel provides a disconnect from either the battery or load when the battery voltage drops to a critically low level. The connection for either battery or load disconnect is done by the user. Each LVD400/600 has separate A and B side disconnect panels. The two sides are completely isolated and can be separately configured for 24 or 48 volts. Positive or negative ground can be used. Each side has a set of Form C Relay contacts for alarm purposes. 1.3 Figure 1 shows the LVD400/600 Low-Voltage Disconnect Panel. The unit is only two mounting positions high, 3.5 inches, to minimize rack space. It can be specified for either a 19- or 23-inch relay rack mounting. 2.0 FEATURES AND OPTIONS 2.1 Features. The following summarizes the standard features for the LVD400/600: u Two Mounting Positions High: 3.5 u 19- or 23-inch Rack Mounting u Single or Dual (A/B) LVDs u Current Capacity: 400A or 600A per Load u Operating Voltage: 24 or 48VDC u Positive or Negative Ground u Form C Relay Contacts u LVD in Series with Battery or Load u Field Settable Disconnect & Reconnect Voltages 1

Figure 1. LVD400/600 Low-Voltage Disconnect Panel Figure 2. Simplified Diagram of LVD400/600 2

3.0 PRODUCT DESIGNATION LV DISCONNECT PANELS MODEL CONFIGURATIONS LVD400-A SINGLE 400A LVD400-A-B DUAL 400A LVD600-A SINGLE 600A LVD600-A-B DUAL 600A LVD400 Model No.: LVD400-A -B - LVD600 CODE VOLTAGE 1 48V 3 24V CODE PANEL SIZE 19 19 Mounting 23 23 Mounting Note: For a single unit the A side is specified and used. 4..0 SAFETY WARNINGS 4.1 This low-voltage disconnect operates at voltages that could potentially be hazardous. Furthermore, inadvertant short circuiting of the system battery and/or rectifier by misconnection or other error could be harmful. This product should be handled, tested and installed only by qualified technical persons who are trained in the use of power systems and are well aware of the hazards involved. 4.2 When operating this LVD400/600 the chassis ground terminal must be connected to the system frame ground or other proper safety ground for the protection of personnel. 4.3 All connections to the LVD400/600 should be carefully checked for errors before applying power to it. 4.4 This equipment is intended only for installation in a RESTRICTED ACCESS LOCATION. 3

5.0 WARRANTY All products of UNIPOWER Telecom, a division of UNIPOWER Corporation, are warranted for two (2) years from date of shipment against defects in material and workmanship. This warranty does not extend to products which have been opened, altered or repaired by persons other than persons authorized by the manufacturer or to products which become defective due to acts of God, negligence or the failure of customer to fully follow instructions with respect to installation, application or maintenance. This warranty is extended directly by the manufacturer to the buyer and is the sole warranty applicable. EXCEPT FOR THE FOREGOING EXPRESS WARRANTY, THE MANUFACTURER MAKES NO WARRANTY, EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICU- LAR PURPOSE. As the sole and exclusive remedy under this warranty, the manufacturer, at its option, may repair or replace the non-conforming product or issue credit, provided the manufacturer s inspection establishes the existence of a defect. To exercise this remedy, the buyer must contact the manufacturer s Customer Service Department to obtain a Return Material Authorization number and shipping instructions. Products returned without prior authorization will be returned to buyer. All products returned for repair must be shipped freight prepaid to UNIPOWER. If the buyer fails to fully comply with the foregoing, the buyer agrees that no other remedy (including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property or any other incidental or consequential losses) shall be available to the buyer. 6.0 UNPACKING AND INSPECTION 6.1 This low-voltage disconnect was carefully tested, inspected and packaged for shipment from our factory. Upon receipt of the unit it should be carefully unpacked and inspected for any damage in shipment. 6.2 If there is evidence of damage, do not attempt to install the unit. The freight carrier should be notified immediately and a claim for the cost of the unit should be filed with the carrier for direct reimbursement. Be sure to include the model and serial number of the damaged unit in all correspondence with the freight carrier. Also save the shipping carton and packing material as evidence of damage for the freight carrier s inspection. 6.3 UNIPOWER Telecom will cooperate fully in case of any shipping damage investigation. 6.4 Always save the packing materials for later use in shipping the unit. Never ship the LV disconnect without proper packing. 4

7.0 SPECIFICATIONS INPUT / OUTPUT LVD Capacity... 400 or 600A Per Load,... 800 or 1200A Total Configuration... Single or Dual LVD Voltage, 1 48V Version... 42-59VDC 24V Version... 21-29VDC Polarity... Positive or Negative Ground LVD Connection... In Series with Battery or Load LVD Disconnect Voltage 2 48V Version... 42.5 VDC 24V Version... 21.25 VDC LVD Reconnect Voltage 2 48V Version... 49.0 VDC 24V Version... 24.5 VDC ALARMS Alarm Connections... Form C Relay Contacts SAFETY STANDARDS...UL1950, CSA22.2 No.950, EN60-950 ENVIRONMENTAL Operating Temp. Range... -10 C to +50 C Storage Temp. Range... -40 C to + 85 C Humidity... 0% to 95%, Non-Condensing PHYSICAL SPECIFICATIONS Case Material... Steel Finish... Powder Coat Gray Rack Mounting Width... 19 or 23 Inches Dimensions, Inches (mm)... 3.5 H x 19.00 W x 10.50 D (88.9 x 483 x 267)... 3.5 H x 23.00 W x 10.50 D (88.9 x 584 x 267) Weight, Dual LVD... 18 lbs. (8.2 kg.) 3.5 H x 23.00 W x 10.50 D (88.9 x 584 x 267) CONNECTIONS Input & Output... 5/16-18 Bolts Chassis Ground Connection... No. 10-32 Stud Alarm Connections... Miniature Screw Terminals NOTE: 1. See Ordering Guide to specify voltage. 2. These voltages are field adjustable. 5

8.0 SAFETY AND INDUSTRY STANDARDS 8.1 The LVD400/600 Low-Voltage Disconnects meet the following safety certifications: STANDARD UL1950 CSA22.2-950 EN60-950 AGENCY UL CUL DEMKO 8.2 The LVD400/600 is CE marked to indicate conformance to the European Union s Low Voltage Directive. 9.0 DESCRIPTION OF OPERATION 9.1 Figure 2 shows a simplified diagram of the LVD400/600 circuit for either the A or B side. 9.2 The LVD400/600 is connected between the a rectifier and battery or load. The contactor is therefore either in series with the rectifier and load or the rectifier and battery. If the battery voltage drops to approximately 42.5V for a 48V battery or 21.25V for a 24V battery, the contactor opens, removing the load from the rectifier and battery or, alternatively, removing the battery from the rectifier and loads. The disconnect contactor is rated at 400 or 600 amperes (depending on model). See Figures 3 and 4. 9.3 If the contactor opens due to low voltage, it will close again when the battery voltage exceeds approximately 49.0 volts for a 48V battery or 24.5 volts for a 24V battery. 9.4 Other circuitry is incorporated into the LVD400/600 to turn the Form C relay on or off when low battery voltage is detected. 10.0 FRONT PANEL DESCRIPTION 10.1 The front panel comes in two widths for rack mounting: 19 inches or 23 inches. The width is determined by the ordering option. There are no controls or indicators on the front panel. 6

BACK VIEW LVD400/600 SERIES SIDE VIEW Figure 3. Back and Side Views of LVD400/600 Figure 4. Connections for LVD400/600 7

11.0 BACK PANEL POWER CONNECTIONS 11.1 Back and side views of the LVD400/600 are shown in Figure 3. The LVD400/ 600 can be connected for either load or battery disconnect. 11.2 For load disconnect operation, it is connected between the rectifier and loads. See Fig. 4(a). 11.3 For battery disconnect operation, it is connected between the battery and loads. See Fig. 4(b). 11.4 The above power connections to the LVD400/600 are made by means of ¼- inch diameter bolts and nuts to the copper bus bars on side A or B. The connections should be clean and tight to reduce contact resistance. 12.0 FORM C RELAY CONTACTS 12.1 The center of each back panel has connections to the Form C relay contacts for connection to external audible or visual alarm circuits. See Figure 5. 12.2 For each side of the LVD400/600, A or B, there is one set of Form C relay contacts. The contacts are made to miniature screw terminals which are, top to bottom: N.C., C, and N.O. 12.3 The Form C relay contacts indicate an alarm condition, i.e., that the LVD contactor is open. Normally Closed (N.C.) and Normally Open (N.O.) are defined with the LVD400/600 powered and the contactor closed; under these normal conditions the relay is energized. 12.4 Just below and to the right of the Form C relay terminals is the chassis ground terminal. This terminal is a no. 10-32 stud with nut. 13.0 INSTALLATION 13.1 Mounting. This low-voltage disconnect can be mounted in either a 19- or 23- inch rack depending on model. 13.2 Connections. Power connections should be made to the disconnect bus bars using ¼-inch diameter bolts with nuts. See Figure 4. The Form C relay contact and battery connections are made to the miniature screw terminals. The chassis ground connection is made to the no. 10-32 stud. See Section 12.4. This safety ground connection should be made before operating the 8

Figure 5. Rear Connections to the LVD400/600. 9

panel. 13.3 Checking Connections. Carefully check the correctness of all connections to the LVD400/600 before operating the unit. Reverse connections will not harm the LVD400/600. Check to make sure that the chassis safety ground connection is made. Make sure that all connections are clean and firm to minimize contact resistance. 14.0 SETUP AND TESTING 14.1 It is not necessary to have the LVD400/600 mounted in a rack for initial testing. This can be done on a bench. It is not necessary to have loads connected to the LVD400/600 for these tests. Test side A first. 14.2 Set an unconnected bench-type DC power supply with digital voltage display to 48VDC if a 48V LVD400/600 is being set up or to 24VDC if a 24V unit is being set up. Turn the power supply off. 14.3 Connect the power supply output with correct polarity to the B+ and B- terminals on the back of the LVD using AWG No. 20 copper wire. It is not necessary to make any connection to the bus bars for this test. 14.4 Turn the power supply on. You will hear the contactor close. Reduce the power supply output voltage slowly while observing the output voltage. At approximately 42.5V for the 48V version or 21.25V for the 24V version the contactor will open. With an ohmmeter, measure the resistance between the Form C relay terminals C and N.O. It should read a short. 14.5 Increase the power supply output voltage slowly while observing the voltage. At approximately 49.0V for the 48V version or 24.5V for the 24V version the contactor will close. With an ohmmeter, measure the resistance between the Form C relay terminals N.C. and C. It should read a short. Turn off the power supply. 14.6 Repeat steps 14.2 through 14.5 for the other side (B) of the LVD to test it. 14.7 Turn off the power supply and disconnect the wires to the LVD400/600. It is now ready for operation in the telecom system. 14.8 If different LVD disconnect and reconnect voltages are desired, they should be set at this time. Call factory for directions on this. 10