The HART Module on the WAGO ETHERNET Controller Application Note

Similar documents
Redundant ethernet communication with WAGO Ethernet-Controller Application note

WAGO Remote IO with Fanuc Robot using EtherNet/IP Protocol Application note

Using WAGO Series 750 DeviceNet IO with an A-B SLC SDN Scanner Application note

Using WAGO Series 750 DeviceNet IO with an A-B ControlLogix 1756-DNB Scanner Application note

Using the WAGO as Remote I/O with an Omron SYSMAC CJ2 Series PLC. Application note. A116700, English Version 1.1.0

Application note. WAGO-I/O-SYSTEM 750 DALI Multi-Master Module Configuration of a DALI Lighting System via WAGO- I/O-PRO V2.

Using the WAGO as Remote I/O with a ControlLogix Ethernet/IP Bridge Module Application note

Application Note. Building. Automation WAGO-I/O-PRO V2.3. openvpn with Linux based Devices A500880_en. Version 1.1.1

Fieldbus Independent I/O Modules Bluetooth RF Transceiver Quick Start

Application Note. a HART Tool-routing with Emerson AMS HART over TH LINK PROFIBUS for Asset Management 1.0.0

Using WAGO Series 750 EtherCAT coupler with CoDeSys SP Win V3 Application note

Application Note. WAGO-I/O-SYSTEM 750 Connecting energy meters with M-Bus interface to the WAGO-I/O-SYSTEM

Fieldbus Independent I/O Modules 8 DI DC 24 V 3.0 ms, Manual

Library for Building Automation. Module Descriptions for KNX IP Master

Application Note. Connection of an WAGO ETHERNET Coupler/Controller to a S controller

Libraries for Building Automation. Module Descriptions for the WINSTA Sunblind Box /

Fieldbus Independent I/O Modules 4 AI Pt100/ RTD , (/xxx-xxx) Manual

Using the WagoAppEtherNetIP_Adapter library with a CompactLogix Controller A500930

Application Note. Enable port forwarding for PFC. A500840, English Version 1.0.0

Fieldbus Independent I/O Modules SSI Transmitter Interface Manual

Fieldbus Independent I/O Modules End Module (/xxx-xxx) Manual

WAGO-I/O-SYSTEM 750 CODESYS-2-Library WagoLibWakeOnLan.lib Wake on lan Remote wake up of network devices

Fieldbus Independent I/O Modules 4 AI DC 0-10 V, Single-Ended Manual

Fieldbus Independent I/O Modules Field Side Connection Manual

Fieldbus Independent I/O Modules 1 AI DMS Manual

Library Description. DALI_647_SpecialSensor_02.lib Specific Sensor Solutions. Version 1.0.1

Configuring National Instruments Lab View with WAGO I/O Application note

Fieldbus Independent I/O Modules 2 AI 4-20 ma, Single-Ended Manual

Fieldbus Independent I/O Modules 2 DI DC 24 V 3.0 ms, High-Side Switching (/xxx-xxx) Manual

Fieldbus Independent I/O Modules 24 V DC Power Supply/Fuse/Diagn Manual

Fieldbus Independent I/O Modules 4 DO DC 24 V 0.5 A, High-Side Switching (/xxx-xxx)

PROFIsafe modules V2 ipar 75x-66x/ WAGO Safety-Editor-75x Quickstart

WagoLib_CAN_Gateway_02.lib

Using PROFIsafe modules in combination with PROFIBUS-DP and PROFINET Application note

Libraries for Building Automation. Function Blocks and Data Types for the BACnet Controller

Libraries for Building Automation. Function Block Description for DALI Multi-Master Module

Fieldbus Independent I/O Modules 2 AO 4-20 ma Manual

Library for Building Automation. Library Description for for the WAGO BACnet Library BACnet_02.lib

Library Description. MBUS_649_01.lib WAGO M-Bus Library. Version 1.0.1

Library Description. KNX_02.lib. CODESYS V2.3 Function Block for the KNX/EIB/TP1 Module

Library for Building Automation

Library for Building Automation. Function block descriptions for time- switching functions

Using power measurement module with TIA A500671

Manual Version WAGO TO-PASS 761. Telecontrol Modules. 761-xxx. System Description

Libraries for Building Automation

Fieldbus Independent I/O Modules Serial Interface RS 232 C (/xxx-xxx) Manual

Library Description. Enocean_06.lib WAGO EnOcean Profile Library. Version 1.0.1

Library Description. ColourConverter_01.lib Library for Converting Color Formats. Version 1.0.2

Quickstart reference for the software e!cockpit

The Next Level of Energy Data Management Fast Data Acquisition via Parameterization No Programming

Modbus/TCP OPC Server

Library Description. Building WAGO-I/O- PRO V2.3. Automation. MpBus_03.lib CODESYS V2.3 Module for MP-Bus. Version 1.0.1

Manual. PLC Lib: Tc2_SMI. TwinCAT 3. Version: Date:

Ethernet Modbus X80 Gateway Device Type Manager

Manual. PLC Lib: Tc2_Coupler. TwinCAT 3. Version: Date:

Manual. Software Protection. TwinCAT 3. Version: Date:

Manual. PLC Lib: Tc2_DMX. TwinCAT 3. Version: Date:

WAGO-I/O-SYSTEM 750 IO-Link Master

Brief instructions WAGO TOPLON for TOPLON IF und TOPLON PRIO

APPLICATION NOTES. Advanced Graphical Interface - AGI Internal PLC (CODESYS V3) SHENDONG

FBP FieldBusPlug. Technical Manual. USB to FBP UTF21-FBP UTF21-FBP DTM V

Servo press kit YJKP - Host interface

WAGO-I/O-SYSTEM 750 IO-Link Master

Manual. PLC Lib: Tc2_DataExchange. TwinCAT 3. Version: Date:

Manual. PLC Lib: Tc2_DataExchange. TwinCAT 3. Version: Date:

WAGO Energy Data Management Efficiency Is That Easy!

Manual. TC3 Power Monitoring. TwinCAT 3. Version: Date: Order No.: TF3650

Documentation for. TwinSAFE User. Tool to modify the User Administration of a TwinSAFE Logic. Version: Date:

Instruction Manual. VISAM TouchPanel VTP-AX 328. A product of the. VBASE - HMI/SCADA family. Document: HB_VTPAX_328_v1.0e_FINAL.

DF FA SE. SIPLUS RIC IEConS7. Advanced Buffer Version V1.6. Siemens Parts

Manual DNP3 Solution for programmable Controls of Telecontrol Technology. Version 1.4.0

IP67 IP20. Controllers Open Flexible Compact SPEEDWAY. Programmable. Fieldbus Couplers. Programmable. Fieldbus Controllers

Application Note. Modbus on CMMP-AS- -M3/M0. Connection and configuration of the motor controller CMMP-AS- -M3/M0 within a Modbus/TCP network.

DeviceNet ILxxxx-B520. IO Data Mapping DeviceNet Objects Indicators and Switches

Manual / Electronic Circuit Breaker DC 24 V, A. Version 1.0.0

APPLICATION SUPPORT. The fast way to the first automation project with. VBASE-Editor version 11 or higher

Type Operating Instructions - Software. Bedienungsanleitung - Software Manuel d utilisation - Logiciel

SoMachine Scan for Buttons Linked to ZBRN Modules Harmony ZBRN Library Guide

YJKP with Mitsubishi Q series PLC control via Modbus TCP

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. MOVIFIT SNI Fieldbus Gateway UFF41B for MOVIGEAR SNI

Operation Manual BK5000. Bus Coupler for CAN-CAL Version: 1.12

Replacement of MS6-SV-1/2-E-ASIS-

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. MOVIFIT SNI UFF41B/UFR41B Fieldbus Gateway for MOVIGEAR SNI

Manual. TwinCAT MC Flying Saw. TwinCAT 3. Version: Date: Order No.: TF5055

Using the WAGO AS-i Module with the SMLC. 9/13/2007 Using the WAGO AS-i Module with the SMLC 1

Your Global Automation Partner. Startup. Getting Started Guide

Quick Start Guideline MICRO PANEL

Anybus CompactCom 40 Diagnostic Events for Modbus-TCP APPLICATION NOTE

S900 I/O DTM 6.x. System Version 6.0. Power and productivity for a better world TM

Aotewell SIMATIC S7-PDIAG for S7-300 and S Configuring Process Diagnostic Getting St

Application Note I-Port event/error list

DTM for Hilscher EtherCAT Master Device

Connection Procedure of WAGO CANopen Bus Coupler and Pro-face AGP-3****-CA1M/LT. Instruction Manual. Version1.1 (

Manual. PLC Lib: Tc2_Standard. TwinCAT 3. Version: Date:

Manual. TC3 Virtual Serial COM. TwinCAT 3. Version: Date: Order No.: TF 6360

Ethernet MBX Driver Help Ethernet MBX Driver for Modbus TCP Networks

Generic Slave DTM for AS-Interface Slave Devices

Manual. PLC Lib: Tc2_Drive. TwinCAT 3. Version: Date:

CODESYS v. 2.3, Ethernet driver for AGI 3xx Use the CODESYS Ethernet driver in the AGI Creator Set up the CODESYS for use with the AGI Creator

Embedded Linux Automation for the Future

Transcription:

The HART Module 750-482 on the WAGO ETHERNET Controller Application Note, English Version 1.0.0

2 General Copyright 2015 by WAGO Kontakttechnik GmbH & Co. KG All rights reserved. WAGO Kontakttechnik GmbH & Co. KG Hansastraße 27 D-32423 Minden Phone: +49 (0) 571/8 87 0 Fax: +49 (0) 571/8 87 1 69 Email: Web: info@wago.com http://www.wago.com Technical Support Phone: +49 (0) 571/8 87 5 55 Fax: +49 (0) 571/8 87 85 55 Email: support@wago.com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation. However, as errors can never be fully excluded, we always appreciate any information or suggestions for improving the documentation. We wish to point out that the software and hardware terms, as well as the trademarks of companies used and/or mentioned in the present manual, are generally protected by trademark or patent.

Contents 3 TABLE OF CONTENTS 1 Important Notes 4 1.1 Legal Principles 4 1.1.1 Copyright 4 1.1.2 Personnel Qualification 4 1.1.3 Intended Use 4 1.2 Scope of Validity 5 1.3 Symbols (erase symbols that are no longer required) 5 2 Description 6 2.1 Components 6 3 Execution of Local HART Commands 7 4 Device-specific HART Commands 11 5 Parameter Setting using FDT/DTM 14 5.1 HART Module on the WAGO ETHERNET Controller 14

4 Important Notes 1 Important Notes 1.1 Legal Principles 1.1.1 Copyright To ensure fast installation and start-up of the units, we strongly recommend that the following information and explanations are carefully read and adhered to. This document, including all figures and illustrations contained therein, is subject to copyright. Any use of this document that infringes upon the copyright provisions stipulated herein is prohibited. Reproduction, translation, electronic and phototechnical filing/archiving (e.g., photocopying), as well as any amendments require the written consent of WAGO Kontakttechnik GmbH & Co. KG, Minden, Germany. Non-observance will entail the right of claims for damages. WAGO Kontakttechnik GmbH & Co. KG reserves the right to make any alterations or modifications that serve to increase the efficiency of technical progress. WAGO Kontakttechnik GmbH & Co. KG owns all rights arising from granting patents or from the legal protection of utility patents. Third-party products are always mentioned without any reference to patent rights. Thus, the existence of such rights cannot be excluded. 1.1.2 Personnel Qualification 1.1.3 Intended Use The use of the product described in this document is exclusively geared to specialists having qualifications in PLC programming, electrical specialists or persons instructed by electrical specialists who are also familiar with the appropriate current standards. WAGO Kontakttechnik GmbH & Co. KG assumes no liability resulting from improper action and damage to WAGO products and third-party products due to non-observance of the information contained in this document. For each individual application, the components are supplied from the factory with a dedicated hardware and software configuration. Modifications are only admitted within the framework of the possibilities documented in this document. All other changes to the hardware and/or software and the nonconforming use of the components entail the exclusion of liability on part of WAGO Kontakttechnik GmbH & Co. KG. Please send your requests for modified and new hardware or software configurations directly to WAGO Kontakttechnik GmbH & Co. KG.

Important Notes 5 1.2 Scope of Validity This application note is based on the stated hardware and software from the specific manufacturer, as well as the associated documentation. This application note is therefore only valid for the described installation. New hardware and software versions may need to be handled differently. Please note the detailed description in the specific manuals. 1.3 Symbols (erase symbols that are no longer required) DANGER Always observe this information to protect persons from injury. NOTICE Always observe this information to prevent damage to the device. NOTE Guidelines that must always be observed to ensure smooth operation. ESD (Electrostatic Discharge) Warning of damage to the components through electrostatic discharge. Observe precautionary measures for handling components at risk of electrostatic discharge. Note Routines or advice for efficient use of a device and software optimization. Additional Information References to additional literature, manuals, data sheets and INTERNET pages.

6 Description 2 Description This application note describes the connection of any HART sensor to the WAGO ETHERNET Controller 750-841 using the TH102 from ABB, for example. The connection is made via the HART Module 750-482 and Wago- LibHART_03.lib CODESYS library. In addition to function blocks for local execution of HART commands, the WagoLibHART_03.lib library contains a program that works together with the WAGO Modbus TCP DTM and that allows parameterization of the HART sensor from any FDT/DTM frame applications. Section 3 describes the creation of a PLC program that reads and processes data from the HART sensor cyclically. Section 4 describes the execution of device-specific HART commands, e.g., Promag23 from Endress&Hauser. Section 5 describes the parameterization of the HART sensor from the FDT/DTM frame application WAGOframe. 2.1 Components The application note is created and tested based on the use of the listed components. Designation Item No. Version Manufacturer CODESYS: WAGO-I/O-PRO CAA 759-2.3.9.3 WAGO Library: WagoLibHART_03-3.1 WAGO ETHERNET Controller 750-841 FW: 02.12.02(14) WAGO HART module: 2AI 4-20mA HART 750-482 FW:(19) WAGO HART sensor: TH102 TH102 SW:1.10 ABB HART sensor: Promag 23 Promag 23 Endress&Hauser FDT frame: WAGOframe 759-1.0.1 WAGO Communication DTM: WAGO Modbus TCP DTM 759-1.0.0 WAGO Gateway DTM: WAGO 075x-08xx Modbus TCP/HART Gateway 759-1.0.0 WAGO Device DTM: ICS Generic HART DTM - 3.1.10 ICS

Execution of Local HART Commands 7 3 Execution of Local HART Commands This section describes the creation of a PLC program step by step that executes Universal HART Command 3 (Reed all variables) cyclically and displays the data read in a visualization. Open the example project WagoLibHART03_Example01.pro. Alternatively, proceed as follows: 1.) Open CODESYS V2.3. 2.) In the File menu, select the New menu item to create a new project. 3.) Select WAGO_750-841_(FW12-..) as the target system. 4.) Select FUP as the programming language for PLC_PRG. 5.) Open the library manager via the menu Window -> Library Management. 6.) From the background menu of the window (top left), select the Other Library menu item and navigate to the Application folder in the file dialog. Select WagoLibHART_03.lib and close the dialog by clicking the Open button. 7.) Double-click PLC_PRG in the Modules window to open the FUP Editor to input the PLC program. 8.) Open the background menu of the instruction window and select the Mod-

8 Execution of Local HART Commands ule entry. As a result, an AND module is added in Network 1. Overwrite the module name with HART_INFO to add the program call for identification and access management of up to eight HART modules to your PLC program. 9.) Add the following variables to the project in the declaration window: (* Identification of HART modules and access synchronization*) xinforeset : BOOL; dwinfoerror: DWORD; sinfostatus: STRING; 10.) Apply the inputs and outputs of the HART_INFO module to the variables just declared. Set the xstart input to TRUE directly. To apply dwerror to the output, first select the Assignment entry from the background menu. 11.) Now add other networks and modules according to the example. 12.) Initialization of the bmodule and bchannel depends on your node structure. The bmodule parameter corresponds to the position of the 2- channel analog input modules (750-482) after the fieldbus coupler. 13.) In the Project menu, select the Clear all entry to clear all temporary data. In the same menu, then select the Compile all entry. As a result, 0 errors, 0 warnings should be output in the output window Any errors in the project are displayed in red and described in the output window. Double-click the respective error message to display the relevant line of code in the instruction window. Correct the lines of code as required and compile the project again. 14.) To transfer the PLC program to the controller 750-841, select Communication parameters in the Online menu. Click the New... button in the dialog that opens. Enter a name for the new connection and select Tcp/Ip(3S Tcp/Ip driver) as the device. Apply the entries by clicking OK. In the Value column, doubleclick in the Address row and overwrite localhost with the IP address of your controller 750-841. Make sure that you exit the input field before applying the changes by clicking OK. 15.) To load the PLC program in the controller (750-841) select the Login entry in the Online menu. You are prompted to confirm that you really want to load the program in the controller. Click Yes to confirm. After the program has been loaded in the controller, the editor also switches to online mode and displays current process values. 16.) Select the Start entry in the Online menu to execute the PLC program. 17.) Select the Boot Project entry in the Online menu to write the program permanently to the controller. 18.) To launch the PLC program at PowerOn, move the slide switch of the service interface to the top position. If successful, the example project should appear as follows:

Execution of Local HART Commands 9 A central components of each PLC program that operates with the HART Module 750-482 is the HART_INFO program. The HART_INFO program identifies the connected HART sensors and synchronizes execution of the individual HART commands. The dwerror and sstatus outputs show the current status. In the start-up phase or after a reset, the program searches the node structure for HART modules. The Device ID of the connected sensors is determined for each channel of all modules found with HART Command 0 (Read unique identifier and stored in the g_athartmodules global variables of the library. The Device ID is required to execute all other HART commands. After completing the start-up phase, the program switches to the OPERATIONAL status and enables execution of HART_CMD3.

10 Execution of Local HART Commands In the example, the data read via HART_CMD3 is displayed in a visualization. The visualization also displays the status of the HART_INFO program and statistics of the executed HART-CMD3s. The TH102(ABB) used provides only three HART variables; it declares the specific values of the fourth HART variable. A rising edge at the xstart input is required to execute a HART command. The function block resets xstart after execution. It is recommended to check the dwerror output for the falling edge of xstart. The data in stdata are only valid when dwerror = 0. Access to the individual data in the stdatacmd3 structure occurs with the dot operator (e.g., rmytemp := stcmd3data.rvarsecondary;). The next section will help if you add other HART commands to the program and if a command is not in the library..

Device-specific HART Commands 11 4 Device-specific HART Commands To provide additional functions that go beyond the Universal and Common- Practice Commands, device manufacturers add their own HART commands. Using HART sensor Promag23 from Endress&Hauser as an example, this section shows how to reproduce and execute any HART commands using the HART_CMDCustom function block from the WagoLibHART_03. The starting point is the sensor manual, command number and reference parameters. Specifically: CMD Function Request Data Response Data 174 Read BYTE 0-2 Address (B) 0-2 3 4 174 Read REAL 0-2 Address (B) 0-2 3 4-7 175 Write BYTE 0-2 3 4 175 Write REAL 0-2 3 4-7 Address 0xFB (constant) Value Address 0xFB (constant) Value (B) 0-2 3 4 5 (B) 0-2 3 4-7 8 Address 0xFB (constant) Value Address 0xFB (constant) Value Address 0xFB (constant) Value Checksum Address 0xFB (constant) Value Checksum The listed commands are general access functions to memory locations. Additionally, the memory map is needed to trigger targeted actions in the HART sensor. For Promag23: (B) (B) (F) (B) (B) (F) Memory Map Address Value Access Upper-range value volume flow (value for 20 ma) 16#606701 REAL Read/ Write Unit identification: Volume flow 16#1C6601 BYTE Read/ Write Counter 1 (forward) Address Value Access Unit identification: Mass 16#2C6501 BYTE Read/ Write Unit identification: Volume 16#2C6601 BYTE Read/ Write Counter value 16#2C6E01 REAL Read No. of overruns 16#2C6F01 REAL Read Clear counter value and overruns 16#2C6B01 BYTE Write Counter 2 (backward) Address Value Access Unit identification: Mass 16#2D6501 BYTE Read/ Write Unit identification: Volume 16#2D6601 BYTE Read/ Write Counter value 16#2D6E01 REAL Read No. of overruns 16#2D6F01 REAL Read Clear counter value and overruns 16#2D6B01 BYTE Write

12 Device-specific HART Commands Now, only the encoding map for unit identification is missing: Volume flow: Unit Seconds [s] Minutes [min] Hours [h] Days [day] [cm 3 ] [dm 3 ] [m 3 ] Milliliter [ml] Liter [l] Hectoliter [hl] Megaliter [Ml] 16#00 16#04 16#08 16#0C 16#10 16#14 16#18 16#01 16#05 16#09 16#0D 16#11 16#15 16#19 16#02 16#06 16#0A 16#0E 16#12 16#16 16#1A 16#03 16#07 16#0B 16#0F 16#13 16#17 16#1B Mass: Unit Code Gram [g] Kilo [kg] Tonne [t] 16#00 16#01 16#08 Volume: Unit Code [cm 3 ] [dm 3 ] [m 3 ] Milliliter [ml] Liter [l] Hectoliter [hl] Megaliter [Ml] 16#00 16#01 16#02 16#03 16#04 16#05 16#06 If the unit identification of the volume flow is set to Liters per minute [l/min], for example, HART command 175 (WriteByte) is used to write the value 16#11 for [l/min] to memory location 16#1C6601. CMD Function Request Data Response Data 175 Write BYTE 0-2 3 4 0x1C6601(Address) 0xFB (constant) 0x11Value [l/min] (B) 0-2 3 4 5 Address 0xFB (constant) Value Checksum (B) The example WagoLibHART03_Example03.pro shows how you trigger this task using the HART_CMDCustom function block. The project uses the program HART_INFO to identify all connected HART modules and to synchronize access to the process image of the mailbox. The HART_CMDCustom function block can be used to execute any HART command. The sequence: 1.) Create HART command number and Request Data at the module. 2.) Execute command with xstart := TRUE. 3.) Wait until xstart := FALSE and check dwerror. 4.) Evaluate Response Data.

Device-specific HART Commands 13 The abdata and bdatacount inputs declared as VAR_IN_OUT must be parameterized before execution with the Request Data and its byte count. After execution, abdata contains the Response Data and bdatacount contains the number of bytes received. To execute the HART command, go online and set the xdoit variable to TRUE using Write values [Ctrl]+[F7]. In cases like these, where the same HART command can be used for a variety of tasks, it is expedient to create your own function blocks for the basic function. The WagoLibHART03_Example04.pro example provides its own function blocks for Endress&Hauser-specific HART commands 174 and 175. The next step would be the creation of an EH_Promag.lib. For this purpose, only save the project as an Internal Library.

14 Parameter Setting using FDT/DTM 5 Parameter Setting using FDT/DTM Most HART device manufacturers use the FDT/DTM standard for parameterization of their devices. The aim of FDT/DTM is to provide a single application for diagnostics and parameterization of devices from any manufacturer. Such applications are also called FDT containers or FDT frames. WAGO has its own FDT frame with WAGOframe. The FDT frame operates with Device Type Managers (DTMs). 3 groups of DTMs are specified: - Device DTMs - Gateway DTMs - Communication DTMs The device manufacturers provide Device DTMs for their devices, which include the graphical user interface for configuration and diagnostics. Gateway DTMs function as mediators, e.g., between two bus systems such as HART and Modbus TCP. A communication DTM provides a protocol-specific driver, e.g., for Modbus TCP. 5.1 HART Module on the WAGO ETHERNET Controller This section describes how you expand your PLC application with FDT/DTM support using the WagoLibHART_03.lib library. If the HART module 750-482 is on a WAGO ETHERNET controller, communication between the FDT frame and controller occurs via the Modbus TCP protocol. A PLC program is required on the ETHERNET controller that receives the MODBUS requests, extracts the HART commands and forwards to the HART sensor. The WagoLibHART_03.lib library contains the HART_FDT program for this task. In the FDT frame, a Modbus TCP communication DTM and HART/Modbus TCP gateway DTM are required. You can get both DTMs on the WAGO homepage under item number 759-359. Specifically, that is the WAGO_Modbus_TCP_DTM and WAGO_075x- 08xx_DTM. Any HART device DTM can be connected below the HART/Modbus TCP gateway DTM.

Parameter Setting using FDT/DTM 15 The WagoLibHART03_Example05.pro example shows the HART_FDT program in use. The PLC program only functions as a Modbus TCP/HART gateway. The only input parameter is ttimeout that you use to specify when the FDT request is discarded. The bmsgid output displays the ID of the FDT request being processed. If additional local HART commands are executed, then add the required HART_CMD function blocks to the program. Note the polling interval of the local HART commands as they compete with the FDT requests, which can lead to timeouts in the DTM. In other words, make sure that there is enough time for requests from the FDT/DTM. WagoLibHART03_Example06.pro is an example of this application. How to access HART sensors behind a WAGO ETHERNET controller with the FDT/DTM frame application is described separately in Application Note A116101.

WAGO Kontakttechnik GmbH PO Box 2880 D-32385 Minden Hansastraße 27 D-32423 Minden Phone: +49 (0) 571/8 87 0 Fax: +49 (0) 571/8 87 1 69 Email: info@wago.com Online: http://www.wago.com