FP-AO-200 AND CFP-AO-200

Similar documents
FP-AO-210 AND CFP-AO-210

FP-AIO-600 and cfp-aio-600

FP-PS-4. Features. Installation

cfp-rly-421 Features Installing the cfp-rly-421 FieldPoint Operating Instructions Eight-Channel SPST Relay Module

FieldPoint. FP-1000/1001 FieldPoint Quick Start Guide. Install the Network Module Mount the module on a DIN rail. What You Need to Get Set Up

OPERATING INSTRUCTIONS AND SPECIFICATIONS. NI 9208E 16-Channel, ±20 ma, 24-Bit Analog Input Module

FieldPoint cfp-20xx. Quick Start Guide. What You Need to Get Set Up

You need the following to set up and use your terminal block:

FP-2000/2010 FieldPoint Quick Start Guide

NI CB-37F-LP. Introduction INSTALLATION GUIDE. Connector Block for 37-Pin D-Sub Devices

NI 6521 Specifications

TBX-96 TERMINAL BLOCK

OPERATING INSTRUCTIONS AND SPECIFICATIONS NI 9870E

OPERATING INSTRUCTIONS AND SPECIFICATIONS NI 9871E

Compact FieldPoint cfp-cal

QUICK START GUIDE. What You Need to Get Set Up

NI USB Introduction USER GUIDE AND SPECIFICATIONS. 4-Channel, ±10 V, 16-Bit Analog Voltage Output Module

VME-GPIB Installation and User Guide

NI Channel, 0 20 ma, 16-Bit Analog Current Output Module

Compact FieldPoint cfp-1808

FieldPoint cfp-21xx. Quick Start Guide. What You Need to Get Set Up

INSTALLATION INSTRUCTIONS LFH160 Cable

NI SD Card Memory Module

Calibrating FieldPoint Analog Input Modules with Calibration Executive

Getting Started with the NI 8234

Getting Started with the NI PCI-1405

SCXI HIGH-VOLTAGE 8 4 MATRIX TERMINAL BLOCK

Getting Started with NI-Motion for NI 73xx Motion Controllers

Safety and Radio-Frequency Interference

FP-1600 FieldPoint Quick Start Guide

Getting Started with the NI PCI-8254R

NI 653x Cable Adapter

NI SMB-2145/2146/2147/2148

NI USB Introduction USER GUIDE AND SPECIFICATIONS. 4-Channel, 0 20 ma, 16-Bit Analog Current Output Module

Getting Started with the NI PCIe-8255R

OPERATING INSTRUCTIONS AND SPECIFICATIONS NI 9476E. 32-Channel, 24 V Sourcing Digital Output Module

NI PCIe-8255R Quick Start Guide

Getting Started with the NI PCIe-8253

TBX-1316 High-Voltage Attenuator Terminal Block

Getting Started with the NI 8234

Getting Started with the NI PXI/PCIe-8231

SCC-AO10 Isolated Analog Output Module

CB-27T, TBX-68T, AND CB-68T ISOTHERMAL TERMINAL BLOCKS INSTALLATION GUIDE

Caution Electrostatic discharge can damage your controller. To avoid such damage, handle the controller only in a proper ESD-controlled environment.

CompactRIO Reconfigurable Embedded Chassis

NI USB Introduction USER GUIDE AND SPECIFICATIONS. 8-Channel, 24 V Logic, Sinking Digital Input Device

Getting Started with the NI PCIe-1433

Electrical. SPECIFICATIONS SH Cable

Getting Started with the NI PCIe-8235

Getting Started with the NI PXI/PCI-1422

Ethernet/Serial Interfaces for Compact FieldPoint

NI crio-9101/9102/9103/9104

USER GUIDE SC-2075 SIGNAL CONDITIONING ACCESSORY

NI USB Introduction USER GUIDE AND SPECIFICATIONS. 8-Channel, 24 V Logic, Sourcing Digital Output Device

SCC-RLY01 Relay Module

GETTING STARTED GUIDE NI Channel, 50 Arms Continuous, 24-Bit, Analog Input Module

SH Cable Specifications

Getting Started with the NI PXI/PCI-1409

SCXI -1313A Terminal Block

GETTING STARTED GUIDE NI AO, 0 ma to 20 ma, 16 Bit Simultaneous

NI CAN Demo Box. NI CAN Demo Box User Guide. Power supply (+9 VDC to +12 VDC) 68-pin Multifunction Data Acquisition board

NI What You Need to Get Started. Unpacking INSTALLATION GUIDE. This document explains how to set up your NI 8262 expansion module.

CompactRIO NI crio-9012/9014

NI USB-9201/9221. Introduction USER GUIDE AND SPECIFICATIONS. 8-Channel, 12-Bit Analog Input Devices

NI Serial Hardware Specifications Guide

USER GUIDE Universal Motion Interface (UMI)-7764

8x16, 2-Wire Terminal Block for the NI PXI The following conventions are used in this guide:

LabVIEW DSP Module. Contents. Introduction RELEASE NOTES. Version 1.0

Getting Results with the NI PXI-6585R

Getting Started with R Series Multifunction RIO

Getting Started with R Series Intelligent DAQ

SCXI OFFSET-NULL AND SHUNT-CALIBRATION HIGH-VOLTAGE TERMINAL BLOCK INSTALLATION GUIDE

SAFETY, ENVIRONMENTAL, AND REGULATORY INFORMATION. NI CompactDAQ Four-Slot Controller with Quad-Core Processor

Reconfigurable Embedded Chassis with Integrated MXI-Express (x1) MXI-Express Switch

This installation guide describes how to install and connect signals to the NI TBX-2808 screw terminal accessory for use with NI SwitchBlock cards.

Warranted specifications describe the performance of a model under stated operating conditions and are covered by the model warranty.

NI REM Remote I/O Overview DATASHEET. Analog Output Module for Remote I/O

NI 9213 Calibration Procedure

AC/DC (120V) Input Module Cat. No IAD Series C

8 AI (12-Bit, 10 ks/s), 2 AO (150 Hz), 12 DIO USB Multifunction I/O Device

NI 6584R User Guide and Specifications

NI PXI-1042 Series Power Supply Shuttle

OPERATING INSTRUCTIONS AND SPECIFICATIONS NI Channel, Sinking Digital Input/Sourcing Digital Output Module. ni.

INSTALLATION INSTRUCTIONS SH160F-160M-NI SwitchBlock Cable

NI PXI-2567 Specifications

PanelView Plus/VersaView CE Terminals and Display Modules

PRODUCT DATA. Wideband Ear Simulator Type 4195-Q for Production Line Testing of Telephones

GETTING STARTED GUIDE NI V, 32-Channel (Sinking Input), 7 µs C Series Digital Module

Getting Results with the NI 5752R

Power Analyzer Firmware Update Utility Version Software Release Notes

Instructions. (For 6180 Industrial Computers) Applications. Overview & Safety

CLASS 1 DIVISION 2 PRODUCTS

GETTING STARTED GUIDE NI Channel, 60 V, High-Speed, Sourcing Digital Output Module

INSTALLATION GUIDE AND TERMINAL BLOCK SPECIFICATIONS NI PXIe-4357 and TB-4357

USB Definitions. Conditions. Analog Input SPECIFICATIONS. 8 AI (10 ks/s), 4 DIO USB Multifunction I/O Device

GETTING STARTED GUIDE NI Channel Solid-State Relay (SSR) Digital Output Module

CISCO 7304 SERIES ROUTER PORT ADAPTER CARRIER CARD

Models 2634B, 2635B, and 2636B System SourceMeter Instruments Quick Start Guide

Agilent 66000A 1200 W DC Modular Power System, GPIB

Digital ac/dc (24V) Input Module

Transcription:

FieldPoint Operating Instructions FP-AO-200 AND CFP-AO-200 Eight-Channel 20 ma Loop Output Modules These operating instructions describe how to install and use the National Instruments FP-AO-200 and cfp-ao-200 analog output modules (referred to inclusively as the [c]fp-ao-200). For information about configuring and accessing the [c]fp-ao-200 over a network, refer to the user manual for the FieldPoint network module you are using. Features The [c]fp-ao-200 is a FieldPoint analog output module with the following features: Eight 0 20 or 4 20 ma outputs 0.5 ma overranging 12-bit resolution Up to 1 kω load impedance (with 24 V loop supply) Indicators for open current loops Short-circuit protection 2,300 V rms transient overvoltage protection between the inter-module communication bus and the I/O channels 40 to 70 C operation Hot plug-and-play FieldPoint, National Instruments, NI, and ni.com are trademarks of National Instruments Corporation. Product and company names mentioned herein are trademarks or trade names of their respective companies. For patents covering National Instruments products, refer to the appropriate location: Help»Patents in your software, the patents.txt file on your CD, or ni.com/patents. 323343A-01 October 2002 2002 National Instruments Corp. All rights reserved.

Installing the FP-AO-200 The FP-AO-200 mounts on a FieldPoint terminal base (FP-TB-x). Hot plug-and-play enables you to install the FP-AO-200 onto a powered terminal base without disturbing the operation of other modules or terminal bases. The FP-AO-200 receives operating power from the terminal base. Current loop power is externally supplied. To install the FP-AO-200, refer to Figure 1 and complete the following steps: 1. Slide the terminal base key to either position X (used for any module) or position 2 (used for the FP-AO-200 module). 2. Align the FP-AO-200 alignment slots with the guide rails on the terminal base. 3. Press firmly to seat the FP-AO-200 in the terminal base. The terminal base latch locks the FP-AO-200 into place when it is firmly seated. 4. Connect a current loop supply for the outputs to the V and C terminals of the terminal base. Key Latch Alignment Slot Guide Rails I/O Module Terminal Base Figure 1. Installing the FP-AO-200 Installing the cfp-ao-200 The cfp-ao-200 mounts on a Compact FieldPoint backplane (cfp-bp-x). Hot plug-and-play enables you to install the cfp-ao-200 onto a powered backplane without disturbing the operation of other modules or connector blocks. The cfp-ao-200 receives operating power from the backplane. FP-AO-200 and cfp-ao-200 2 ni.com

To install the cfp-ao-200, refer to Figure 2 and complete the following steps: 1. Align the captive screws on the cfp-ao-200 with the holes on the backplane. The alignment keys on the cfp-ao-200 prevent backward insertion. 2. Press firmly to seat the cfp-ao-200 on the backplane. 3. Using a number 2 Phillips screwdriver with a shank of at least 64 mm (2.5 in.) length, tighten the captive screws to 1.1 N m (10 lb in.) of torque. The nylon coating on the screws prevents them from loosening. 5 2 1 4 4 5 3 1 cfp Backplane 2 cfp Controller Module 3 cfp-ao-200 4 Captive Screws 5 Screw Holes Figure 2. Installing the cfp-ao-200 National Instruments Corp. 3 FP-AO-200 and cfp-ao-200

Wiring the [c]fp-ao-200 The FP-TB-x terminal base provides connections for the eight output channels of the FP-AO-200. The cfp-cb-x connector block provides the same connections for the cfp-ao-200. Table 1 lists the terminal assignments for the signals associated with each channel. Table 1. Terminal Assignments Terminal Numbers Channel I out COM V sup 0 1 2, 18 17 1 3 4, 20 19 2 5 6, 22 21 3 7 8, 24 23 4 9 10, 26 25 5 11 12, 28 27 6 13 14, 30 29 7 15 16, 32 31 Each channel has an output terminal, I out ; a common terminal, COM; and a supply terminal, V sup. The COM terminals of all the channels are connected internally to each other and to the C terminals, and the V sup terminals are all connected to each other and to the V terminals. Refer to the sections that follow for detailed wiring instructions. Sourcing Current to a Load The [c]fp-ao-200 sources current from an external loop supply to a load. The [c]fp-ao-200 can operate with an external loop supply from 5 to 24 VDC. The voltage from the external supply determines the maximum load impedance that the [c]fp-ao-200 can drive. With a 24 VDC loop supply, each output can drive up to 1kΩ of load impedance. With a 5 VDC loop supply, each output can only drive up to 100 Ω. The [c]fp-ao-200 detects and reports error conditions due to excessive loads or insufficient loop supplies. For more information, refer to the Open-Loop Detection section. FP-AO-200 and cfp-ao-200 4 ni.com

The [c]fp-ao-200 updates the output channels as new values are sent to it by the network module. The time it takes to respond to a change on a single channel is between 3 and 6 ms. The response time to changes on all eight channels is 24 to 27 ms. Figure 3 shows the current output circuit of a single channel. V V sup 12-Bit Isolated DAC Current Sense Open Loop Indicator I out COM COM C Figure 3. [c]fp-a0-200 Current Output Circuit Figure 4 shows how to connect loads to two channels of the [c]fp-ao-200. V C + Loop Supply I out COM Load I out COM Load [c]fp-ao-200 Figure 4. Connecting to Two Channels National Instruments Corp. 5 FP-AO-200 and cfp-ao-200

Using an external COM connection may be more convenient in your application than using the COM and C terminals on the terminal base or connector block. Figure 5 shows how to connect to two channels using an external COM connection. V C + Loop I out Supply COM Load [c]fp-ao-200 I out COM Load Figure 5. Connecting to Two Channels Using an External COM Connection Output Ranges You can configure each channel independently for an output range of either 0 20 ma or 4 20 ma. The default power-up setting for each channel is 0 20 ma, with the output set to 0 ma. The [c]fp-ao-200 has overranging of 0.5 ma in each of these ranges, so that the actual full-scale ranges available are 0 20.5 ma and 3.5 20.5 ma. Overranging enables the [c]fp-ao-200 to compensate for span and offset errors in field devices. Open-Loop Detection Each channel has a monitoring circuit that compares the actual output current to the specified output current. If the [c]fp-ao-200 cannot source the specified output current for one or more channels, the monitoring circuits turn on a red STATUS LED for each affected channel and report the error condition to the network module. Generally, the error condition is caused by an open current loop either the load device or the loop supply is disconnected. However, the monitoring circuit also detects errors caused by load impedances that are too high and by loop supply voltages that are too low. If the output of a [c]fp-ao-200 channel is set to 0 ma, the monitoring circuit does not register an error condition because the FP-AO-200 and cfp-ao-200 6 ni.com

[c]fp-ao-200 can always source zero current, even to an open loop. Leave any unused and unwired channels in the default state so that they do not generate error conditions. Short-Circuit Protection Each I out terminal of the [c]fp-ao-200 is protected against short circuits to any of the other terminals. One or more channel outputs can be short-circuited indefinitely without causing damage or improper operation of other channels, as long as the maximum loop supply does not exceed 24 VDC. The outputs can withstand indefinite short circuits with loop supplies of more than 24 VDC (up to 36 VDC) without damage, but increasing internal temperatures due to such conditions may cause improper operation of other channels on the module. Status Indicators Figure 6 shows the [c]fp-ao-200 status indicators. Figure 6. Status Indicators The [c]fp-ao-200 has two green status LEDs, POWER and READY. After you insert the [c]fp-ao-200 into a terminal base or backplane and apply power to the connected network module, the green POWER indicator lights and the [c]fp-ao-200 informs the network module of its presence. When the network module recognizes the [c]fp-ao-200, it sends initial configuration information to the [c]fp-ao-200. After receiving this initial information, the green READY indicator lights and the [c]fp-ao-200 is in normal operating mode. In addition to the green POWER and READY indicators, each channel has a red, numbered error status indicator. For more information, refer to the Open-Loop Detection section. Upgrading the FieldPoint Firmware You may need to upgrade the FieldPoint firmware when you add new I/O modules to the FieldPoint system. For information on determining which firmware you need and how to upgrade, go to ni.com/info and enter fpmatrix. National Instruments Corp. 7 FP-AO-200 and cfp-ao-200

Isolation and Safety Guidelines Caution Read the following information before attempting to connect the [c]fp-ao-200 to any circuits that may contain hazardous voltages. This section describes the isolation of the [c]fp-ao-200 and its compliance with international safety standards. The field wiring connections are isolated from the backplane and the inter-module communication bus. The isolation is provided by the module, which has optical and galvanic isolation barriers designed and tested to protect against transient fault voltages of up to 2,300 V rms. Follow these guidelines to ensure a safe total system: The [c]fp-ao-200 has a safety isolation barrier between the I/O channels and the inter-module communication bus. There is no isolation between channels unless otherwise noted. If any of the channels on a module are wired at a hazardous potential, make sure that all other devices or circuits connected to that module are properly insulated from human contact. Do not share the external supply voltages (the V and C terminals) with other devices (including other FieldPoint devices), unless those devices are isolated from human contact. For Compact FieldPoint, you must connect the protective earth (PE) ground terminal on the cfp-bp-x backplane to the system safety ground. The backplane PE ground terminal has the following symbol stamped beside it:. Connect the backplane PE ground terminal to the system safety ground using 14 AWG (1.6 mm) wire with a ring lug. Use the 5/16 in. panhead screw shipped with the backplane to secure the ring lug to the backplane PE ground terminal. As with any hazardous voltage wiring, make sure that all wiring and connections meet applicable electrical codes and commonsense practices. Mount terminal bases and backplanes in an area, position, or cabinet that prevents accidental or unauthorized access to wiring that carries hazardous voltages. Operate the [c]fp-ao-200 only at or below Pollution Degree 2. Pollution Degree 2 means that only nonconductive pollution occurs in most cases. Occasionally, however, a temporary conductivity caused by condensation must be expected. FP-AO-200 and cfp-ao-200 8 ni.com

Refer to the FieldPoint product label for regulatory certification under hazardous location standards. If the FieldPoint product is not certified for operation in hazardous locations, do not operate it in an explosive atmosphere or where there may be flammable gases or fumes. Specifications These specifications are typical for the range 40 to 70 C unless otherwise noted. Output Characteristics Number of channels...8 single-ended Resolution...12 bits, 1 in 4,096 (~6 µa/bit) Current Output Output range...0 20 or 4 20 ma, programmable (0 20.5 or 3.5 20.5 ma with overranging) Type...Current source, external loop power required External loop power...5 24 VDC Internal voltage drop...3 V Resistive load...up to 1 kω with 24 V loop supply, up to 100 Ω with 5 V supply 1 Protection...Short-circuit and open-circuit Default power-up state...0 ma Accuracy Absolute accuracy...0.1% typ, 0.3% max (calculated as a percentage of full-scale reading) 1 Maximum load resistance = (Supply voltage Internal voltage drop)/0.0205 A National Instruments Corp. 9 FP-AO-200 and cfp-ao-200

Monotonicity 1...Guaranteed over operating temperature range Offset temperature coefficient...50 na/ C Gain temperature coefficient...40 ppm/ C Dynamic Characteristics Max conversion rate...200 updates/s Slew rate...0.4 ma/µs Physical Characteristics Indicators...Green POWER and READY indicators, 8 red open-loop indicators Weight FP-AO-200...140 g (4.8 oz) cfp-ao-200...110 g (3.7 oz) Power Requirements Power from network module...350 mw Isolation Voltage Channel-to-channel isolation...no isolation between channels Transient overvoltage...2,300 V rms Environmental FieldPoint modules are intended for indoor use only. For outdoor use, FieldPoint modules must be mounted inside a sealed enclosure. Operating temperature... 40 to 70 C Storage temperature... 55 to 100 C Humidity...10 to 90% RH, noncondensing Maximum altitude...2,000 m Pollution Degree...2 1 A characteristic of a DAC in which the analog output always increases as the value of the digital code input to it increases. FP-AO-200 and cfp-ao-200 10 ni.com

Shock and Vibration Operating shock (IEC 68-2-27) cfp-ao-200...50 g, 3 ms half sine, 3 shocks; 30 g, 11 ms half sine, 3 shocks Operating vibration, random (IEC 60068-2-34) FP-AO-200...10 500 Hz, 2.2 g rms cfp-ao-200...10 500 Hz, 5 g rms Operating vibration, sinusoidal (IEC 60068-2-6) [c]fp-ao-200...10 500 Hz, 5 g Safety The [c]fp-ao-200 is designed to meet the requirements of the following standards for safety and electrical equipment for measurement, control, and laboratory use. EN 61010-1, IEC 61010-1 UL 3121-1 CAN/CSA C22.2 No. 1010.1 For certifications under regulatory standards, including hazardous location standards, refer to the product label or to ni.com. Electromagnetic Compatibility CE, C-Tick, and FCC Part 15 (Class A) Compliant Electromagnetic emissions...en 55011 Class A at 10 m FCC Part 15A above 1 GHz Electromagnetic immunity...evaluated to EN 61326: 1997/A1: 1998, Table 1 Note For full EMC compliance, you must operate this device with shielded cabling. See the Declaration of Conformity (DoC) for this product for any additional regulatory compliance information. To obtain the DoC for this product, click Declaration of Conformity at ni.com/hardref.nsf/. National Instruments Corp. 11 FP-AO-200 and cfp-ao-200

Mechanical Dimensions Figure 7 shows the mechanical dimensions of the FP-AO-200 installed on a terminal base. Dimensions are given in millimeters [inches]. If you are using the cfp-ao-200, refer to the Compact FieldPoint controller user manual for the dimensions and cabling clearance requirements of the Compact FieldPoint system. 107.19 [4.22] 109.5 [4.31] 91.44 [3.60] Figure 7. FP-AO-200 Mechanical Dimensions Where to Go for Support For more information about setting up the FieldPoint system, refer to these National Instruments documents: FieldPoint network module user manual Other FieldPoint I/O module operating instructions FieldPoint terminal base operating instructions Go to ni.com/support for the most current manuals, examples, and troubleshooting information. For telephone support in the United States, create your service request at ni.com/ask and follow the calling instructions or dial 512 795 8248. For telephone support outside the United States, contact your local branch office: Australia0398795166, Austria06624579900, Belgium 02 757 00 20, Brazil 55 11 3262 3599, Canada (Calgary) 403 274 9391, Canada (Montreal) 514 288 5722, Canada (Ottawa) 613 233 5949, Canada (Québec) 514 694 8521, Canada (Toronto) 905 785 0085, China 86 21 6555 7838, Czech Republic 02 2423 5774, Denmark 45 76 26 00, Finland 09 725 725 11, France 01 48 14 24 24, Germany 089 741 31 30, Greece 01 42 96 427, Hong Kong 2645 3186, India 91 80 4190000, Israel 03 6393737, Italy 02 413091, Japan 03 5472 2970, FP-AO-200 and cfp-ao-200 12 ni.com

Korea 02 3451 3400, Malaysia 603 9596711, Mexico 001 800 010 0793, Netherlands 0348 433466, New Zealand 09 914 0488, Norway 32 27 73 00, Poland 22 3390 150, Portugal 210 311 210, Russia 095 238 7139, Singapore 65 6 226 5886, Slovenia 3 425 4200, South Africa 11 805 8197, Spain 91 640 0085, Sweden 08 587 895 00, Switzerland 056 200 51 51, Taiwan 02 2528 7227, United Kingdom 01635 523545 National Instruments Corp. 13 FP-AO-200 and cfp-ao-200