ABB i-bus KNX Fan Coil Actuator, PWM, MDRC FCA/S , 2CDG110195R0011

Similar documents
ABB i-bus KNX Fan Coil Actuators FCA/S Product Manual

ABB i-bus KNX Fan Coil Actuators FCA/S Product Manual

ABB i-bus KNX Switch Actuator, x-fold, 10 A, MDRC SA/S x , 2CDG11015xR0011

ABB i-bus KNX Switch Actuator, Current Detection, x-fold, 16/20 A, C-Load, MDRC SA/S x , 2CDG1101xxR0011

ABB i-bus KNX Analogue Input, 4-fold, MDRC AE/S , 2CDG110190R0011

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x , 2TAZ710xx1R2161

Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011

ABB i-bus KNX Weather Unit, 1-fold, MDRC WZ/S , 2CDG110184R0011

ABB i-bus KNX HCC/S Heating/cooling circuit controller

ABB i-bus KNX Analogue Actuator, 4-fold, MDRC, 0-10 V, 0-20 ma AA/S 4.1.2, 2CDG110202R0011

ABB i-bus KNX BCI/S Boiler/Chiller Interface

ABB i-bus KNX Switch Actuator, x-fold, 6 A, MDRC SA/S x.6.1.1, 2CDG x R0011

ABB i-bus KNX Logic Controller ABA/S 1.2.1, 2CDG110192R0011

ABB i-bus KNX DALI Light Controller, 8-fold, MDRC DLR/S M, 2CDG110101R0011

Operating voltage Maximum

ABB i-bus KNX IP Router, MDRC IPR/S 3.1.1, 2CDG110175R0011

ABB i-bus KNX AC/S Application Controller

ABB i-bus KNX Blower Actuator FCL/S x Product Manual

ABB i-bus EIB / KNX Blower/Fan Coil-Aktuator LFA/S 1.1, LFA/S 2.1. Product Manual. Intelligent Installation Systems ABB

ABB i-bus KNX Blower/Fan Coil-Actuator LFA/S 1.1, LFA/S 2.1. Product Manual. Intelligent Installation Systems ABB

ABB i-bus KNX Room Master Basic RM/S 1.1 Product Manual

ABB i-bus KNX Room Master Basic RM/S 1.1 Product Manual

ABB i-bus KNX Fan Coil Actuator FCA/S 1.1M Product Manual

ABB i-bus KNX Room Master Premium RM/S 2.1 Product Manual

ABB i-bus KNX Room Master RM/S 3.1 Product Manual

ABB i-bus. KNX JRA/S Blind/Roller Shutter Actuator with Binary Inputs Product Manual

PRODUCT MANUAL. ABB i-bus KNX SV/S KNX-Power Supplies

ABB i-bus KNX Binary Inputs BE/S Product Manual

Datasheet RCUXXYY EAE KNX Room Control Unit RCUXXYY DT R1.0. General Description. EAE Technology Page 1/10

ABB i-bus KNX Blind/Roller Shutter Actuators JRA/S Product Manual

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

ABB i-bus KNX Thermoelectric Valve Drive, 230 V TSA/K 230.2, 2CDG R0011

ABB i-bus KNX Blind/Roller Shutter Actuator JRA/S Product Manual

DC562, digital input/output module,

DX561 Digital Input/Output Module

Switching Actuators N530, 6AX Switching Actuators N532, 10AX Switching Actuators N534, 16/20AX

DC561, digital input/output module,

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING

Device technology. Supply Bus voltage V DC. Current consumption via bus. Accuracy in the range 300 1,000 ppm 1,000 2,000 ppm 2,000 5,000 ppm

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

Switching relay CT-IRS with 1, 2 or 3 c/o contacts Data sheet

Switching relay CT-IRE with 1 c/o (SPDT) contact

Product and functional description

AI561 Analog Input Module

Electronic timer CT-SDD.22 Star-delta change-over with 2 n/o contacts

Electronic timer CT-ARE OFF-delayed without auxiliary voltage, 1 c/o (SPDT) contact

Electronic timer CT-ERD ON-delayed with 1 c/o contact Data sheet

Power supply CP-E 48/1.25 Primary switch mode power supply

Product and functional description

DI572 Digital Input Module

Electronic timer CT-VWD Impulse-ON with 1 c/o contact Data sheet

Electronic timer CT-SDS.23 Star-delta change-over with 2 n/o contacts

PHOENIX CONTACT Features

Power supply CP-E 24/0.75 Primary switch mode power supply

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs

Product and functional description

Product and functional description

Boxed interface relays and optocouplers R600 Boxed slim relays, optocouplers and accessories

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

1 Safety instructions. 2 Device components. 3 Function. Control unit 1-10 V, 3-gang. Art.-No.: 2193 REG. Operationsmanual

ABB i-bus KNX DALI Gateway Emergency Lighting DGN/S Product Manual

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

DI561 Digital Input Module

Power supply CP-D 12/2.1 Primary switch mode power supply

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet

1 Safety instructions. 2 Device components. 3 Function. Control unit, 1-10 V 3-gang. Order-No. : Operating instructions

Product and functional description

ABB i-bus KNX SUG/U 1.1 Split Unit Gateway Product Manual

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

AO561 Analog Output Module

Intrusion Detection Technology SafeKey Switching Module SSM/A, SSM/U Product Manual

Power supply CP-C 24/5.0

Power supply CP-E 24/10.0 Primary switch mode power supply

Three-phase monitoring relay

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet

Linienkoppler S KNX. Line coupler S KNX. Line coupler S KNX Status: March 16 (Subject to change) Page 1 of 29

Electronic timer CT-AWS Impulse-OFF with 2 c/o contacts Data sheet

Switch Actuator, 4-fold, 20 A, MDRC AT/S , GH Q R0111

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

TU531, TU532 Terminal Unit

Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages

RTU500 series Data Sheet Power Supply CP-E 24/2.5

Electronic timer CT-ERD.12

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

Thermistor motor protection relay CM-MSS.11

Electronic timer CT-ARS.11

Relay actuators & Status indicating modules

RM35TF. Main. Product or component type. Product specific application. Relay monitored parameters 250 V AC 5 A AC

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA 250 V AC

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Electronic timer CT-AHD.22

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

Electronic timer CT-ERS.12 ON-delayed with 1 c/o (SPDT) contact

Product and Applications Description. Application Programs. Example of Operation. Installation Instructions. load circuit AC 230/400V L1 L2 L3 N

ABB i-bus KNX KNX/EnOcean Gateway EG/A , 2CDG R0011

High-performance switching actuators

Transcription:

Technical data 2CDC508136D0202 ABB i-bus KNX Product description The device is a modular installation device (MDRC) in Pro M design. It is intended for installation in distribution boards on 35 mm mounting rails. The assignment of the physical addresses as well as the parameterization is carried out with ETS. The device is powered via the ABB i-bus KNX and requires no additional auxiliary voltage supply. The device is ready for operation after connecting the bus voltage.

Technical data Supply Bus voltage 21 32 V DC Current consumption, bus Leakage loss, bus < 12 ma Maximum 250 mw Leakage loss, device Maximum 3.05 W* *The maximum power consumption of the device KNX connection 0.25 W results from the following specifications: Relay 16 A 1.0 W Relay 6 A Electronic outputs Connections KNX Via bus connection terminal Inputs/Outputs 0.6 W 1.2 W Via screw terminals Connection terminals Screw terminal Screw terminal with universal head (PZ 1) 0.2 4 mm² stranded, 2 x (0.2 2.5 mm²) 0.2 6 mm² single core, 2 x (0.2 4 mm²) Ferrules without/with plastic sleeves Without: 0.25 2.5 mm² With: 0.25 4 mm² TWIN ferrules 0.5 2.5 mm² Contact pin length min. 10 mm Tightening torque Maximum 0.6 Nm Grid 6.35 Operating and display elements Button/LED For assignment of the physical address Button /, LED For toggling between manual operation/ operation via ABB i-bus KNX and displays Protection IP 20 To DIN EN 60 529 Protection class II To DIN EN 61 140 Isolation category Overvoltage category III to DIN EN 60 664-1 Pollution degree II to DIN EN 60 664-1 KNX safety extra low voltage SELV 24 V DC Temperature range Operation -5 C +45 C Transport -25 C +70 C Storage -25 C +55 C Temperatures exceeding +45 C reduce the service life! Ambient conditions Maximum air humidity 93 %, no condensation allowed Design Modular installation device (MDRC) Modular installation device, ProM Dimensions 108 x 90 x 64.5 mm (H x W x D) Mounting width in space units 6 x 18 mm modules Mounting depth 64.5 mm Mounting On 35 mm mounting rail To DIN EN 60 715 Installation position Any Weight 0.3 kg Housing/color Plastic housing, gray Approvals KNX to EN 50 090-1, -2 Certification CE mark In accordance with the EMC guideline and low voltage guideline 2 2CDC508136D0202 FCA/S 1.1.1.2

Device type Application Max. number of Max. number of Max. number of communication objects group addresses assignments FCA/S 1.1.1.2 Fan Coil Actuator PWM/...* 70 254 255 * = Current version number of the application. Please refer to the software information on our website for this purpose. Note For a detailed description of the application see Fan Coil Actuators FCA/S product manual. It is available free-of-charge at www.abb.com/knx. ETS and the current version of the device application are required for programming. The current version of the application is available on the Internet for download at www.abb.com/knx. After import into ETS, it appears in the Catalogs window under Manufacturers/ABB/Heating, Ventilation, Air Conditioning/Fan Coil Actuator PWM. The device does not support the locking function of a KNX device in ETS. If you use a BCU code to inhibit access to all the project devices, it has no effect on this device. Data can still be read and programmed. FCA/S 1.1.1.2 2CDC508136D0202 3

Outputs, valve (thermoelectric, PWM) Rated values Quantity 4, non-isolated, short-circuit proofed U n rated voltage 24 230 V AC (50/60 Hz) I n rated current (per output pair) 0.5 A Continuous current 0.5 A resistive load at T u up to 20 C 0.3 A resistive load at T u up to 60 C Starting current Maximum 1.6 A, 10 s at T u up to 60 C T u = ambient temperature Minimum load 0.5 VA per PWM output Outputs, valve (motor-driven, 3-point) Rated values Quantity 2, non-isolated, short-circuit proofed U n rated voltage 24 230 V AC (50/60 Hz) I n rated current (per output pair) 0.5 A Continuous current 0.5 A resistive load at T u up to 20 C 0.3 A resistive load at T u up to 60 C Starting current Maximum 1.6 A, 10 s at T u up to 60 C T u = ambient temperature Minimum load 0.5 VA per PWM output Inputs Rated values Quantity 3 Contact scanning Floating Scanning current 1 ma Scanning voltage 10 V Resistance PT100 2-conductor technology, PT1000 2-conductor technology, A selection of KT/KTY 1,000/2,000, user-defined Resolution, accuracy and tolerances See next page Cable length Between sensor and device input Maximum 30 m, simple 4 2CDC508136D0202 FCA/S 1.1.1.2

Resolution and accurancy and tolerances Please note that the tolerances of the sensors which are used will need to be added to the listed values. With sensors based on resistance measurement, it is also necessary to consider the cable error. In the supplied state of the device, the stated accuracies will not be initially achieved. After initial commissioning, the device performs an autonomous calibration of the analogue measurement circuit. This calibration takes about an hour and is performed in the background. It is undertaken regardless of whether or not the device is parameterized and is independent of the connected sensors. The normal function of the device is not affected. After calibration has been completed, the calibration values which have been determined will be stored in the non-volatile memory. Thereafter, the device will achieve this level of accuracy every time it is switched on. If the calibration is interrupted by programming or bus voltage failure, it will recommence every time it is restarted. The ongoing calibration is displayed in the status byte by a 1 in bit 4. Resistance signals Sensor signal Resolution Accuracy Accuracy Accuracy Remark at 25 C T u * 3 at 0 50 C T u * 3 at -20 70 C T u * 3 PT100* 4 0.01 ohms ±0.15 ohm ±0.2 ohms ±0.25 ohm 0.1 ohm = 0.25 C PT1000* 4 0.1 ohms ±1.5 ohms ±2.0 ohms ±2.5 ohms 1 ohm = 0.25 C KT/KTY 1,000* 4 1 ohm ±2.5 ohms ±3.0 ohms ±3.5 ohms 1 ohm = 0.125 C/at 25 C KT/KTY 2,000* 4 1 ohm ±5 ohms ±6.0 ohms ±7.0 ohms 1 ohm = 0.064 C/at 25 C * 3 in addition to current measured value at ambient temperature (T u ) * 4 incl. cable and sensor errors PT100 The PT100 is precise and exchangeable but subject to faults in the cables (cable resistance and heating of the cables). A terminal resistance of just 200 milliohms causes a temperature error of 0.5 C. PT1000 The PT1000 responds just like the PT100, but the influences of cable errors are lower by a factor of 10. Use of this sensor is preferred. KT/KTY The KT/KTY has a low level of accuracy, can only be exchanged under certain circumstances and can only be used for very simple applications. Please note that there are different tolerance classes for the sensors in the versions PT100 and PT1000. The table indicates the individual classes according to IEC 60 751 (date: 2008): Description Tolerance Class AA 0.10 C + (0.0017 x t) Class A 0.15 C + (0.002 x t) Class B 0.30 C + (0.005 x t) Class C 0.60 C + (0.01 x t) t = Current temperature Example for class B: At 100 C, the deviations of the measurement value are reliable up to ± 0.8 C FCA/S 1.1.1.2 2CDC508136D0202 5

Fan rated current 6 A Rated values Number 3 contacts U n1 rated voltage 250/440 V AC (50/60 Hz) I n1 rated current (per output) 6 A Switching currents AC3* operation (cos ϕ = 0.45) 6 A/230 V to DIN EN 60 947-4-1 AC1*operation (cos ϕ = 0.8) 6 A/230 V to DIN EN 60 947 4-1 Fluorescent lighting load to DIN EN 60 669-1 6 A/250 V (35 µf) 1) Minimum switching capacity 20 ma/5 V 10 ma/12 V 7 ma/24 V DC current switching capacity (resistive load) 6 A/24 V= Service life Mechanical service life > 10 7 Electronic endurance of switching contacts to DIN IEC 60 947-4-1 AC1* (240 V/cos ϕ = 0.8) > 10 5 AC3* (240 V/cos ϕ = 0.45) > 1.5 x 10 4 AC5a* (240 V/cos ϕ = 0.45) > 1.5 x 10 4 Switching times 2) Maximum relay position change per output and minute if only one relay is switched. 2,683 1) The maximum inrush current peak may not be exceeded. 2) The specifications apply only after the bus voltage has been applied to the device for at least 10 seconds. Typical delay of the relay is approx. 20 ms. *What do the terms AC1, AC3 and AC5a mean? In intelligent installation systems, different switching capacities and performance specifications that are dependent on the special applications, have become established in domestic and industrial installations. These performance specifications are rooted in the respective national and international standards. The tests are defined to simulate typical applications, e.g. motor loads (industrial) or fluorescent lamps (residential). Specifications AC1 and AC3 are switching performance specifications which have become established in the industrial field. Typical application: AC1 Non-inductive or slightly inductive load, resistive furnaces (relates to switching of ohmic/resistive loads) AC3 Squirrel-cage motors: starting, switching off motors during running (relates to (inductive) motor load) AC5a Switching of electric discharge lamps These switching performances are defined in the standard EN 60947-4-1 Contactors and motor-starters - Electromechanical contactors and motor-starters. The standard describes starters and/or contactors that were originally used primarily in industrial applications. 6 2CDC508136D0202 FCA/S 1.1.1.2

Fan lamp load 6 A Lamps Incandescent lamp load 1,200 W Fluorescent lamps T5/T8 Uncompensated 800 W Parallel compensated 300 W DUO circuit 350 W Low-voltage halogen lamps Inductive transformer 800 W Electronic transformer 1,000 W Halogen lamps 230 V 1,000 W Dulux lamp Uncompensated 800 W Parallel compensated 800 W Mercury-vapor lamp Uncompensated 1,000 W Parallel compensated 800 W Switching capacity (switching contact) Maximum peak inrush-current I p (150 µs) 200 A Maximum peak inrush-current I p (250 µs) 160 A Maximum peak inrush-current I p (600 µs) 100 A Number of electronic ballasts (T5/T8, single element) 1) 18 W (ABB EVG 1 x 18 SF) 10 24 W (ABB EVG-T5 1 x 24 CY) 10 36 W (ABB EVG 1 x 36 CF) 7 58 W (ABB EVG 1 x 58 CF) 5 80 W (Helvar EL 1 x 80 SC) 3 1) For multiple element lamps or other types, the number of electronic ballasts must be determined using the peak inrush current of the ballasts. FCA/S 1.1.1.2 2CDC508136D0202 7

Output, rated current 16 A Rated values Quantity 1 U n2 rated voltage I n2 rated current Switching currents AC3* operation (cos ϕ = 0.45) to DIN EN 60 947-4-1 AC1* operation (cos ϕ = 0.8) to DIN EN 60 947 4-1 Fluorescent lighting load AX as per EN 60 669-1 250/440 V AC (50/60 Hz) 16 A 8 A/230 V 16 A/230 V 16 A/250 V (70 µf)1) Minimum switching capacity 100 ma/12 V 100 ma/24 V DC current switching capacity (resistive load) 16 A/24 V Service life Mechanical service life > 3 x 10 6 Electronic endurance of switching contacts to DIN IEC 60 947-4-1 AC1* (240 V/cos ϕ = 0.8) > 10 5 Switching times 2) Maximum relay position change per output and minute if only one relay is switched. 313 1) The maximum inrush current peak may not be exceeded. 2) The specifications apply only after the bus voltage has been applied to the device for at least 10 seconds. Typical delay of the relay is approx. 20 ms. *What do the terms AC1, AC3 and AC5a mean? In intelligent installation systems, different switching capacities and performance specifications that are dependent on the special applications, have become established in domestic and industrial installations. These performance specifications are rooted in the respective national and international standards. The tests are defined to simulate typical applications, e.g. motor loads (industrial) or fluorescent lamps (residential). Specifications AC1 and AC3 are switching performance specifications which have become established in the industrial field. Typical application: AC1 Non-inductive or slightly inductive load, resistive furnaces (relates to switching of ohmic/resistive loads) AC3 Squirrel-cage motors: starting, switching off motors during running (relates to (inductive) motor load) AC5a Switching of electric discharge lamps These switching performances are defined in the standard EN 60947-4-1 Contactors and motor-starters - Electromechanical contactors and motor-starters. The standard describes starters and/or contactors that were originally used primarily in industrial applications. 8 2CDC508136D0202 FCA/S 1.1.1.2

Output, lamp load 16 A Lamps Incandescent lamp load 2,500 W Fluorescent lamps T5/T8 Uncompensated 2,500 W Parallel compensated 1,500 W DUO circuit 1,500 W Low-voltage halogen lamps Inductive transformer 1,200 W Electronic transformer 1,500 W Halogen lamps 230 V 2,500 W Dulux lamp Uncompensated 1,100 W Parallel compensated 1,100 W Mercury-vapor lamp Uncompensated 2,000 W Parallel compensated 2,000 W Switching capacity (switching contact) Maximum peak inrush-current I p (150 µs) 400 A Maximum peak inrush-current I p (250 µs) 320 A Maximum peak inrush-current I p (600 µs) 200 A Number of electronic ballasts (T5/T8, single element) 1) 18 W (ABB EVG 1 x 18 SF) 23 24 W (ABB EVG-T5 1 x 24 CY) 23 36 W (ABB EVG 1 x 36 CF) 14 58 W (ABB EVG 1 x 58 CF) 11 80 W (Helvar EL 1 x 80 SC) 10 1) For multiple element lamps or other types the number of electronic ballasts must be determined using the peak inrush current of the ballasts. FCA/S 1.1.1.2 2CDC508136D0202 9

Connection schematic (thermoelectric, PWM) 2CDC072014F0015 1 Label carrier 2 Programming button 3 Programming LED (red) 4 Bus connection terminal 5 Inputs a, b, c 6 Valve V1 (e.g. heating) 7 Valve V2 (e.g. cooling) 8 Fan 9 Output H 10 2CDC508136D0202 FCA/S 1.1.1.2

Connection schematic (motor-driven, 3-point) 2CDC072017F0013 1 Label carrier 2 Programming button 3 Programming LED (red) 4 Bus connection terminal 5 Inputs a, b, c 6 Valve V1 (e.g. heating) 7 Valve V2 (e.g. cooling) 8 Fan 9 Output H FCA/S 1.1.1.2 2CDC508136D0202 11

All outputs can be controlled independently of one another. The following table provides an overview of the functions possible with the outputs of the Fan Coil Actuator and the application: Functions of the output A B C D General - Overload - Parallel operation free free Valve drives allocated to the Fan Coil unit - Thermoelectric (PWM) - 1 control value/1 valve free free free - 2 control values/1 valve free free free - 2 control values/2 valves free free Setting facilities for valve drives - Thermoelectric (PWM) - Separate heating/cooling - Direction OPEN/CLOSE OPEN/CLOSE OPEN/CLOSE OPEN/CLOSE - Motor-driven (3-point) - Separate heating/cooling - Direction OPEN CLOSE OPEN CLOSE = Function is supported - = Function is not supported free = Is available and can be used separately Functions of the output E F G H Switch function Normally closed/normally open contact Time Staircase lighting Fan Level 1 2 3 - = Function is supported - = Function is not supported 12 2CDC508136D0202 FCA/S 1.1.1.2

Dimension drawing 2CDC072016F0013 FCA/S 1.1.1.2 2CDC508136D0202 13

Contact ABB STOTZ-KONTAKT GmbH Eppelheimer Straße 82 69123 Heidelberg, Germany Telefon: +49 (0)6221 701 607 Telefax: +49 (0)6221 701 724 E-Mail: knx.marketing@de.abb.com Further information and local contacts: www.abb.com/knx Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. The agreed properties are definitive for any orders placed. ABB AG shall not be liable for any consequences arising from errors or incomplete information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Reproduction, transfer to third parties or processing of the content including sections thereof is not permitted without prior expressed written permission from ABB AG. Publication number 2CDC508136D0202 (06/2015) Copyright 2015 ABB All rights reserved