HI ma Simulator

Similar documents
HI ma Simulator

HI 8751 HI 8752 HI 8753 Portable Thermistor Thermometers

HI HI HI HI Portable Microprocessor Thermistor Thermometers

HI HI HI HI HI HI HI

HI HI N HI HI

HI HI N HI HI

Instruction Manual HI 9033 HI Waterproof Multi-Range EC and TDS Meters for Field Applications.

HI HI HI HI Portable Microprocessor Printing and Logging PT-100 Thermometers

HI8564 HI Portable Thermo-Hygrometers. Instruction Manual. These Instruments are in Compliance with the CE Directives

Instruction Manual HI Portable Logging Haze Meter

User's Guide. MiniTec TM Series Model MN25 MultiMeter

User s Guide. 600A AC Clamp Meter. Model 38387

User's Guide. Video Borescope. Model BR100

User s Guide. 600A True RMS AC/DC Clamp Meter. Model 38389

User's Guide. Extech AM A AC Analog Clamp Meter

HI 2300 Auto-ranging Microprocessor EC/TDS/NaCl/ºC Bench Meter

Manual No Revision MODEL GLI-9835 HAND-HELD/PORTABLE CONDUCTIVITY/TDS METER

Light Meter (Foot Candles)

4-20/10-50 ma/v Loop Calibrator

7032 Digital-Analog Multimeter

Instruction Manual HI Autoranging & Logging Portable Waterproof Microprocessor EC/TDS/NaCl/ C Meter

Instruction Manual HI HI Portable Microprocessor Printing and Logging Multi-Range Conductivity Meters

User's Manual. Model Heavy Duty Datalogging Module with Windows Software

NTP-5521/5531/5561 SWITCHING MODE POWER SUPPLY

Net-Ritef Continuity and Wiremap Tester Trace-Ritef Tone Generator and Amplified Tone Tracer User's Guide.

Operation Manual MODEL 2TX. 2-wire Isolated ph/orp Transmitter

INSTRUCTION MANUAL. Model True RMS AC/DC 30A Mini Clamp-on Meter. Introduction. True RMS AC Current and Voltage

Operation Manual CX10 1/8 DIN Microcomputer Based Conductivity/Resistivity Controller

Torque Meter. Instruction Manual

Light Meter with Bar Graph

Sound Level Pen Instruction Manual

DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER

MiniSim 330 EEG Simulator

Operation Manual TX10 1/8 DIN Microcomputer Based ph/orp Controller

Instruction Manual C 102. Multiparameter Turbidity & Ion Specific Meter. This Instrument is in Compliance with the CE Directives.

Mini Digital Multimeter

Operation Manual CX20 1/8 DIN Microcomputer Based Conductivity/Resistivity Controller

AC/DC Current Probe Model SL201

4-Channel Thermometer

TH2683 Insulation Resistance Meter. User s Mannual

User's Guide. Datalogging Light Meter with PC Interface. Model

User's Guide. Model Laser Photo Tachometer

User's Guide. Model Noise Dosimeter with PC Interface. Introduction

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL:

Torque Meter. Instruction Manual

Kramer Electronics, Ltd. USER MANUAL

Type K/J Thermometers

True RMS AC Voltage/Current Datalogger

MTP INSTRUCTION MANUAL

TC100 Precision Thermocouple Calibrator

Platinum RTD Thermometer MODEL NO

INSTRUCTION MANUAL. Model Dual Input RTD Thermometer. Measures two temperatures simultaneously. Dual RTD probe inputs

USER MANUAL. Kramer Electronics, Ltd. Models:

DIGITAL SOUND LEVEL METER. Instruction Manual

Variable Temperature Digital Solder and Testing Station

USER MANUAL. VM-2DP 1:2 DisplayPort Distributor MODEL: P/N: Rev 2

Kramer Electronics, Ltd. USER MANUAL. Model: VM-80HP. 1:8 Stereo Headphone Distributor

Kramer Electronics, Ltd.

Micro-Ohmmeter Model 6292

Kramer Electronics, Ltd.

AC/DC Current Probe Model SL206 USER MANUAL

Kramer Electronics, Ltd. USER MANUAL. Model: VP-200XLN. XGA Line Amplifier / DA

DFI 9000 PORTABLE DIGITAL INDICATOR USER S GUIDE

MC1000 Multi-Function Calibrator

User's Guide Video Borescope Model BR200

OPERATION MANUAL MODEL TT-LP

User Guide. ExStik TM Model RE300 Waterproof ORP Meter. Patent Pending RE300 ORP

Platinum RTD Thermometer MODEL NO

Kramer Electronics, Ltd.

CL600 SIMPLE LOGGER RMS CLAMP-ON MODULE E N G L I S H. User Manual

Vacuum Meter Instruction Manual

User's Guide. Phase Sequence and Motor Rotation Tester Model

SOUND LEVEL PEN INSTRUCTION MANUAL SPER SCIENTIFIC

PIECAL 510B/511B RTD Simulator Operating Instructions

Operation Manual. Hand-held ph/mv/temperature Meter. ph6810

PS-5030 (5A) OPERATION MANUAL

Kramer Electronics, Ltd.

Electrostatic Fieldmeter Model 775

PIECAL 322 Automated Thermocouple Calibrator Operating Instructions. Product Description. Practical Instrument Electronics

Heavy Duty Datalogger Module

Kramer Electronics, Ltd.

MCR 808LX RELAY MANAGEMENT MODULE

Operation Manual. MODEL ph6175. Microcomputer Based ph/orp/temperature Benchtop Meter

Kramer Electronics, Ltd. USER MANUAL. Model: VS-4x4FW. 4x4 FireWire Switcher

ENGLISH. User manual.

PS-1030 (30V) OPERATION MANUAL

Earth Resistance and Resistivity Tester

Kramer Electronics, Ltd. USER MANUAL. Model: RC-BT1 / BT-1. Bluetooth controller

Global Water Instrumentation, Inc.

Mini Digital Multimeter

Heavy Duty Datalogger Module

MODBUS MANUAL For the AccUView UV Transmission Monitor

MODEL PS-11 DIGITAL PORTION SCALE

Kramer Electronics, Ltd. USER MANUAL. Model: VM-2HDCP. 1:2 DVI Distributor

User Guide. Moisture Meter. Model MO250

Datalogging Conductivity/ TDS Meter. Instruction Manual

HI HI 9034 HI HI 9130 HI HI 9635 Portable Waterproof Multi-Range Conductivity/TDS/ Fertilizer Meters

Cole-Parmer Instrument Company

USER MANUAL AD331 AD332 Waterproof Portable Meters for EC and TDS Measurements

ph 300 ph 301 ph 302 Microprocessor GLP Bench-top ph/mv/ise/ C Meters Instruction Manual

Transcription:

Instruction Manual HI 931002 4-20 ma Simulator http://www.hannainst.com These Instruments are in Compliance with the CE Directives

Dear Customer, Thank you for choosing a Hanna Instruments Product. Please read this instruction manual carefully before using the instrument. This manual will provide you with all the necessary information for the correct use of the instrument, as well as a precise idea of its versatility in a wide range of applications. These instruments are in compliance with directives EN 50081-1 and EN 50082-1. TABLE OF CONTENTS PRELIMINARY EXAMINATION... 3 GENERAL DESCRIPTION... 3 FUNCTIONAL DESCRIPTION AND SPECIFICATIONS HI931002... 4 OPERATIONAL GUIDE... 5 ma - ph RELATION... 9 BATTERY REPLACEMENT... 9 FUSE REPLACEMENT... 9 ACCESSORIES... 10 WARRANTY... 10 CE DECLARATION OF CONFORMITY... 11 2 ISO 9000 Certified Company since 1992 PRELIMINARY EXAMINATION Remove the instrument from the packing material and examine it carefully to make sure that no damage has occurred during shipment. If noticeable damage is found, immediately notify your Dealer. In addition to this manual you should find the following items: HI 931002 meter; 12 VDC power adapter (HI710005 or HI710006); 1 m (3.3') connection cables; 9 V battery. Note: Save all packing material until the instrument has been observed to function correctly. All defective items must be returned to the Dealer in their original packing. GENERAL DESCRIPTION HI 931002 is a portable 4-20 ma simulator, ammeter and calibrator designed specifically for monitoring and regulating a 4-20 ma current loop from practically any process meter with or without voltage source. Four operational modes are provided: 1) Passive Drive/Calibrator Mode. HI 931002 can be set to simulate 4-20 ma current values and the user can then adjust the process meter accordingly. 2) Active Drive/Simulator Mode. HI 931002 simulates the correct values as above in addition to providing power to the current loop. Power is provided through an external adapter (included) which is connected to the simulator. This mode is ideal for calibrating chart recorders, pressure transducers or current indicators. 3) Passive Measurement/Tester Mode. HI 931002 practically becomes an Ammeter. It measures and displays the ma (or ph) values transmitted by the process meter. 4) Active Measurement/Tester Mode. Same as point 3 in addition to providing voltage to the 4-20 ma bus. HI 931002 can practically measure incoming current, provide power and simulate 4-20 ma output to calibrate almost any process meter. A large LCD shows current values. You can select between drive and measurement modes through a switch on the front panel and two dials that allow for quick adjustment of the current. 3

FUNCTIONAL DESCRIPTION AND SPECIFICATIONS HI 931002 OPERATIONAL GUIDE INITIAL PREPARATION Each meter is supplied complete with a 9V battery. Slide off the battery compartment cover on the back of the meter (see page 9), install the battery while paying attention to its polarity. PASSIVE DRIVE (CALIBRATOR) MODE This mode is intended to calibrate an active receiver unit. The HI 931002 simulates 4 to 20 ma current, powered by the active receiver from the 4-20 ma bus. The current value displayed on the LCD, can be adjusted through two single turn potentiometers in increments of 0.01 ma. Disconnect the external power adapter from HI 931002 if present. Select the measurement unit by pressing the UNIT key. 1) LCD display 2) Mode selection switch 3) coarse setting knob 4) Unit selection key 5) ON/OFF key Range Active Drive 2.00 to 19.99 ma -1.50 to 14.00 ph Passive Drive 2.00 to 19.99 ma -1.50 to 14.00 ph Active Measure 0.00 to 19.99 ma -3.50 to 14.00 ph Passive Measure 0.00 to 19.99 ma -3.50 to 14.00 ph Resolution 0.01mA 0.01 ph Accuracy (@20 C/68 F) ±0.01mA ±0.01 ph EMC Typical Deviation ±1% f.s. Input resistance 20 Ω Fuse 5x20 mm, 200mA, 250V Battery Type/Life 9V alkaline/1600 hours of continuous use Ext. Power Supply 12 to 32 VDC Environment 0 to 50 C (32 to 122 F); 95% RH Dimensions 180 x 83 x 40 mm (7.1 x 3.3 x 1.6") Weight 320 g (11.3 oz.) 4 6) fine setting knob 7) Ext. power adapter socket 8) "A" connector 9) "P" connector 10) "Com." connector. Switch the selection switch to the "Drive" mode. Wire the calibrator "Com." and "P" connectors to the Device Under Test (D.U.T.) input contacts (see page 4, #10 and #9 respectively) ("Com." to - and "P" to + terminals). Turn the Fine and Coarse knobs to any desired value and make sure that the D.U.T. reflects the current value displayed on the HI 931002 LCD. Calibrate the D.U.T. according to manufacturer instructions if necessary. 5

ACTIVE DRIVE (SIMULATOR) MODE This mode is intended to drive a chart recorder, calibrate a pressure/ current transducer or a current indicator. The HI 931002 supplies a voltage to the 4-20 ma bus via an external connected 12-32 VDC power supply. The calibrator regulates the current, displayed on the LCD, as in the previous mode (Passive Drive). PASSIVE MEASURING (TESTER) MODE This mode is intended to test an active transmitter. The HI 931002 reads the current produced by the transmitter via the 4-20 ma bus and displays the reading in ma or ph units. Disconnect the external power adapter from HI 931002 if present. Select the measurement unit by pressing the UNIT key. Switch the selection switch to the "Drive" mode. Connect the external power adapter to the power socket on the right side of the HI 931002. Wire the calibrator "Com." and "A" connectors to the Device Under Test (D.U.T.) input contacts (see page 4, #10 and #8 respectively) ("Com." to - and "A" to + terminals). Turn the Fine and Coarse knobs to any desired value and make sure that the D.U.T. reflects the current value displayed on the HI 931002 LCD. Calibrate the D.U.T. according to manufacturer instructions if necessary. Note: the battery powers on the display only. Calibrator operational mode is functional even without a battery or if battery is discharged. Select the measurement unit by pressing the UNIT key. Switch the selection switch to the "Measure" mode. Wire the calibrator "Com." and "P" connectors to the Device Under Test (D.U.T.) input contacts (see page 4, #10 and #9 respectively) ("Com." to - and "P" to + terminals). Verify that the D.U.T. displays the same reading of the HI 931002 and calibrate the D.U.T. according to manufacturer instructions if necessary. IMPORTANT NOTE: Set the selection switch to MEASURE mode only if the D.U.T. is a transmitter and can limit current below 100mA. WRONG OPERATION WILL BREAK THE INTERNAL FUSE. 6 7

ACTIVE MEASURING (TESTER) MODE This mode is intended to test a passive transmitter. The HI 931002 supplies only the power to the 4-20 ma bus via an external connected 12-32 VDC power supply and displays the value of the current produced by the transmitter. Select the measurement unit by pressing the UNIT key. ma - ph RELATION The HI 931002 LCD will show the current from the transmitter in ma or in ph units according to the relation: 4 ma = 0 ph 12 ma = 7 ph ma = 1.14 x (ph reading) + 4 20 ma = 14 ph. Press UNIT key to select the desired range. The reading will toggle between the ma and ph reading. Switch the selection switch to the "Measure" mode. Connect the external power adapter to the power socket on the right side of the HI931002. Wire the calibrator "Com." and "A" connectors to the Device Under Test (D.U.T.) input contacts (see page 4, #10 and #8 respectively) ("Com." to - and "A" to + terminals). Verify that the D.U.T. displays the same reading of the HI 931002 and calibrate the D.U.T. according to manufacturer instructions if necessary. IMPORTANT NOTE: Set the selection switch to MEASURE mode only if the D.U.T. is a transmitter and can limit current below 100mA. WRONG OPERATION WILL BREAK THE INTERNAL FUSE. BATTERY REPLACEMENT The instruments uses a 9 volt battery that lasts for approximately 1600 hours of continuous use. When the battery is rundown, "V" and two decimal points blink on the LCD to warn the user. Battery replacement must only take place in a non hazardous area using the battery types specified in this instruction manual (see page 4). To change battery, slide the bottom back cover, replace the old battery and replace the cover. FUSE REPLACEMENT The HI 931002 is equipped with a protection fuse inside the instrument. In the event the fuse would break contact your nearest Hanna Service. 8 9

ACCESSORIES CE DECLARATION OF CONFORMITY HI 710001 Soft carrying case, dimensions 230 x 100 x 50 mm HI 7826/1 Simulator 1 m (3.3') connection cables HI 710031 Hard carrying case, dimensions 340 x 230 x 90 mm HI 710005 115VAC-12VDC voltage adapter HI 710006 230VAC-12VDC voltage adapter HI 721310 9V battery (10 pcs) MN931002R1Instruction manual WARRANTY All Hanna Instruments meters are warranted for two years against defects in workmanship and materials when used for their intended purpose and maintained according to instructions. The electrodes and the probes are warranted for a period of six months. This warranty is limited to repair or replacement free of charge. Damages due to accident, misuse, tampering or lack of prescribed maintenance are not covered. If service is required, contact the dealer from whom you purchased the instrument. If under warranty, report the model number, date of purchase, serial number and the nature of the failure. If the repair is not covered by the warranty, you will be notified of the charges incurred. If the instrument is to be returned to Hanna Instruments, first obtain a Returned Goods Authorization number from the Customer Service department and then send it with shipping costs prepaid. When shipping any instrument, make sure it is properly packaged for complete protection. To validate your warranty, fill out and return the enclosed warranty card within 14 days from the date of purchase. All rights are reserved. Reproduction in whole or in part is prohibited without the written consent of the copyright owner, Hanna Instruments Inc. Hanna Instruments reserves the right to modify the design, construction and appearance of its products without advance notice. 10 Recommendations for Users Before using these products, make sure that they are entirely suitable for the environment in which they are used. Operation of these instruments in residential area could cause unacceptable interferences to radio and TV equipments, requiring the operator to take all necessary steps to correct interferences. Any variation introduced by the user to the supplied equipment may degrade the instruments' EMC performance. To avoid damages or burns, do not perform any measurement in microwave ovens. 11

PRINTED IN PORTUGAL MN931002R1 04/98