With the publication. Make the right connection: Bonding a shielded system. installation

Similar documents
Bonding and grounding NETCONNECT copper cabling systems

Screened vs Unscreened Cabling

Cabling Infrastructure

Frequently Asked Questions (FAQs) Siemon 10G ip Solutions

Dr. Paulo Marin, EE/BSc, MSc, PhD. Electrical Engineer, ICT Consultant

Communications. UNM IT/Telecommunications Guide Specification Communications

Ethernet and PoE Operation Over Single Pair Twisted-Pair Copper Cabling (SPE) Chris DiMinico AEM Technical Sales Test and Measurement

TX S HIELDED C OPPER C ABLING S YSTEM Innovative End-to-End Network Connectivity Solutions

3 Chapter Introduction. 3.2 Copper Cable

10G the Next Generation Structured Cabling. Technology Paper 002

Innovative Connectivity Solution for Maximum Performance and Security

Anticipating Cat 8 Agenda. Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards

Tarleton State University. Specifications

Site Preparation CHAPTER

Physical Layer V What does the physical layer provide?

f) Telecommunications Equipment Rooms

1 of 5 12/31/2008 8:41 AM

Cable Sharing: An ANSI & ISO Recognized Solution for High Density, Low-Speed Applications. Robert Y. Faber Jr., RCDD/NTS.

S I E M O N. Category 7/Class F Network Cabling: The longterm choice for advancing speeds and convergence CONNECTING THE WORLD TO A HIGHER STANDARD

Cables and Connectors

The Facts about Category 6 and 6A Cabling

Certification for 10G copper cabling

10G Ethernet Over Structured Copper Cabling

SYSTIMAX GigaSPEED Xpress Solution Design Guidelines

USER MANUAL MODEL 570/ Base-T (CAT-5) Surge Protectors SALES OFFICE (301) TECHNICAL SUPPORT (301)

Preparing to Install the Cisco AS5350XM Universal Gateway

Transmission Media. Criteria for selection of media. Criteria for selection of media 2/17/2016. Chapter 3: Transmission Media.

White Paper. Alien Crosstalk. Crosstalk effects and cable shielding

E. Numbering and Labeling Pathway components. In general, pathway components are not labeled.

ANSI/TIA/EIA-568-B Cabling Standard

with its cables, connectors, Switches, Hubs and topologies

Los Angeles Community College District Design Standards

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling

Cat.8 Shielded Field Termination Plug Description

New Standardized Cabling Options for NBASE-T Devices

Siemon Interconnect Solutions

Preparing to Install the VG248

TIA TR-42 Liaison to IEEE

Outdoor Risk and Equipment Protection

Saving Critical Space. Cable Management Solutions

Jamey Calloway, RCDD Product Management Specialist Optical Cable Corporation

Type DH7091 Transient Protection Assembly

Cat.8 Shielded Keystone Jack Description

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO

10GBASE-T and. Copper Cabling Choices

Cabling a Data Center to TIA-942 Standard

Dirty Power... A Guide to Surge Suppression & Filtering. Surge & Signal Protection for Business-Critical Continuity. EmersonNetworkPower.

The Field Guide for Industrial Ethernet FIELD GUIDE

Making Use of Innovative Cabling Technologies to Deliver the Best Preterminated. System for 10G Networks

Anixter Standards Reference Guide

Minimizing electrical noise in actuator drive systems for maximum reliability and performance

B E C A U S E Y O U R B U S I N E S S R U N S T H R O U G H U S A BERK-TEK WHITE PAPER. Cabling for. Secure Government Networks.

Chapter 4: Network Access

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

Network+ Guide to Networks 7 th Edition

USER MANUAL MODEL 536S Token Ring (STP) Surge Protector. SALES OFFICE (301) TECHNICAL SUPPORT (301)

LANmark-6A H I G H - S P E E D C O P P E R S O L U T I O N F O R 1 0 G I G A B I T A P P L I C A T I O N S

Copper Riser And Intrabuilding Cabling

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

Multiplexing (Recap)

WORLDSKILLS STANDARD SPECIFICATION

The six major components of a structured wiring system are:

2 Telecommunications Data Center Facility Requirements

Appendix D. EMC Installation Guidelines. Safety Considerations. Ferrite Absorbers and P-Clips. General Product Philosophy

NZQA unit standard version 3 Page 1 of 5. Demonstrate knowledge for telecommunications premises network cablers

Junos WebApp Secure 5.0 Hardware Guide

ANSI/TIA-568-C Cat 6A Field Test Specifications

Release Notes. Electrostatic Discharge and Grounding Guide for Cisco NCS 2000 Series. Prerequisites. Preparing Your Location

Installation Manual. Table of Contents

R&Mfreenet Advanced Cat 6 A Unshielded Connection Module

EMC Installation Guide

Application Note: Mode Conversion Testing Prevents Your Network from Hanging in the Balance

R&Mfreenet Advanced Cat 6A Shielded Connection Module

or go home GO SMALL SEPTEMBER 2015 FOR PROFESSIONALS MANAGING THE CABLE AND WIRELESS SYSTEMS THAT ENABLE CRITICAL COMMUNICATIONS STANDARDS

Lantech IPGC-0101DSFP. User Manual. 10/100/1000T (PoE at) to 100/1000M SFP Industrial Switch Converter

Copyright Black Box Corporation. All rights reserved.

CERTIFICATION PLUS SM

Emery County Senior Center Green River 06/07

Hardened PoE Ethernet Switch

Isobar 8-Outlet Surge Protector, 12 ft. Cord with Right-Angle Plug, 3840 Joules, Diagnostic LEDs, Metal Housing

IES User Manual. 8 FE + 1 MM SC Unmanaged Switch -40 to 75, DIN-rail. v

LANmark-6A. High-speed Copper Solution For 10 Gigabit Applications

Hitachi Cable America and Optical Cable Corporation STRUCTURED CABLING SOLUTIONS. MOving data

Communication

ANSI/TIA/EIA-568-B Cabling Standard

SYSTIMAX SCS Power Sum Solution

Field-terminated RJ45 connector with housing. Color housing: gray (RAL 7042). Color termination block: red.

Manual Version: V1.02. DVS_DC Cable Connection Guide

Isobar 4-Outlet Surge Protector, 6 ft. Cord with Right-Angle Plug, 3330 Joules, Diagnostic LEDs, Metal Housing

Power Input Assignment Power1 12VDC DC Jack VDC Power2 - Power Ground

Installation Job Aid for Ethernet Routing Switch 3600 Series

EMC-Compatible Installation of the Electric Cabinet

INTERNATIONAL STANDARD

ALLTEC PROTECTION PYRAMID TM FOR PHOTOVOLTAIC SOLAR FIELD

1993 SPECIFICATIONS CSJ , ETC. & SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM

OWNER S MANUAL GEQ 131/ 131LF GEQ 215/ 215LF GEQ 231. Single Channel 31 Band Graphic Equalizer. 2 Channel 15 Band Graphic Equalizer

USER MANUAL MODEL 570-R8/570-R R8/580-R Base-T (CAT-5) Surge Protectors

Quick Start Guide. Installation. User s Manual 1

USER MANUAL MODEL 571/ Base-T (CAT-5) Surge Protectors. SALES OFFICE (301) TECHNICAL SUPPORT (301)

USB 2.0 DIGI-USB2 1-Port USB m Category 5e/6/6a/7 Extender Set with Flexible Power. User Manual. Revision

Transcription:

Make the right connection: Bonding a shielded system installation With the publication of the IEEE 802.3an 10GBase-T standard in 2006, Augmented Category 6 (i.e., Category 6A) cabling systems are being deployed in data centers. Due to the high electrical frequency needed to support 10-Gbit/sec data rates over copper cabling, the mitigation of signal coupling between cables in close proximity, known as alien crosstalk (alien near-end crosstalk or NEXT, and alien equal-level far-end crosstalk or ELFEXT, which is also called alien attenuation-to-crosstalk-ratio at the far end, or AACRF), is critical to meet 10GBase-T performance standards. Shielded Category 6A links offer clear performance benefits at 10 Gbits/sec by reducing or eliminating the effect of alien crosstalk and providing superior immunity to electromagnetic interference (EMI), such as radio-frequency interference (RFI). But it is important that shielded cabling systems be properly bonded and ed to ensure the highest level of performance and to protect expensive IT equipment. If shielded cabling systems are not properly designed and/or installed, transmission errors may occur due to unwanted additional noise. Let s consider the performance benefits of shielded twisted-pair structured cabling, and answer the following top-of-mind user questions on bonding and ing best practices: Where, and how often, should the shielded cabling system be bonded? How can I tell if my existing ing system is adequate for shielded cable? How can I tell if -loop problems exist at the workstation, and what can be done about the loops? Performance benefits of 6A Copper is the preferred structured cabling medium for most connections in the data center and horizontal TOM TURNER is business development manager and ROBERT DENNELLY is product line manager at Panduit Corp. (www.panduit.com). Bonding the system to helps ensure optimum performance of your shielded system. -20-30 -40 PSANEXT -50 (db) -60-70 -80-90 PSANEXT performance comparison Category 6 Category 6 ASTP IEEE limit Category 6A UTP 100 200 300 400 500 600 Frequency (MHz) Power-sum alien near-end crosstalk performance characteristics of copper cabling systems over a 100-meter channel. links to the workstation due to its easy termination and installation in the field, and cost-effective electronics. Of the available copper cabling types, unshielded twistedpair (UTP) Category 6A copper solutions are specifically designed to reduce the effect of alien crosstalk by incorporating innovative features into both the cable (such as increased separation between cables and tighter twist rates) and the connectors (such as crosstalk suppression within the printed circuit board). Shielded Category 6A systems offer a different technique to suppress alien crosstalk, using foil and/or braided shielding within the cable to prevent signals from coupling between cables. These screens provide significant margin over IEEE 802.3an specifications for power-sum alien near-end crosstalk (PSANEXT) and power-sum alien attenuation-to-crosstalk ratio at the far end (PSAACRF), virtually eliminating the effect of alien crosstalk and providing more than 20 db of headroom over comparable UTP systems. This impact is similar whether the cable contains individual shields around each pair or a single foil around all pairs. The increased suppression of ANEXT and AACRF by shielded cables also eliminates the need for costly and Reprinted with revisions, from the November 2007 edition of CABLING INSTALLATION & MAINTENANCE Copyright 2007 by PennWell Corporation

Typical bonding and ing time-consuming field-testing of alien crosstalk. Further, the foil shields provide superior immunity to EMI/RFI and makes it difficult for unauthorized users to listen in by providing a more-secure data environment for such markets as government or such applications as gaming that require strong levels of security. TGB (telecommunications ing busbar) TBB (telecommunications bonding backbone) Importance of bonding, ing Although overall integrity of the power and ing system is crucial to ensure the reliability of all networked equipment, there is often confusion over how to properly and bond shielded cabling solutions. The primary purpose of the ing and bonding system is to create a robust path for equalization of voltages and for resultant surge currents to return to their source. Lightning, power-system fault currents, circuit switching (motors on and off), activation of surge-protection devices, and electrostatic discharge (ESD) are common causes of transient voltages and electrical surges. Ground loops are a potential disruption to data signals, and develop when a voltage difference occurs in the at each end of a cable shield, causing a current to flow through the shield. To realize the full performance benefits of any structured cabling system, shielded or unshielded, the overall integrity of 1 The system ing protection starts at the jack module with 360º shielding 2 The connector is then bonded to the patch panel Structured system The patch panel is bonded to the rack with bonding screws. 4 Finally, the entire system is bonded from the rack to MCBN located in the floor Following these four steps with the Structured Ground System provides robust connections that have low resistance, are easy to install, and are easily checked during inspections. MCBN (mesh common bonding network) This example of a telecommunications bonding and ing system exhibits the essential principles as well as the recommendations of the TIA-942, ANSI J-STD-607-A, and IEEE Std 1100-2005 specifications. the bonding and ing system must be sound. According to standards TIA-942, ANSI J-STD-607-A, and IEEE Std 1100-2005 (The Emerald Book), here are the principles of a properly designed ing and bonding system in a data center: An intentional design each connection must be engineered and installed to properly handle the anticipated currents; Bonds all metallic components to the ing system (e.g., equipment, racks, cabinets, access floors, ladder racks, cable trays, water pipes, conduit, building steel); Visually verifiable and generally arranged for 3 ease of inspection and testing; Equalization paths and ports for ESD-protection wrist straps; Support for the proper operation of surge protection device for IT equipment and power circuits; Electromagnetic compatibility within the data center environment; Adherence to all local electrical codes, and listed with a nationally recognized test lab. In addition, it is recommended that complete system bonding be observed over the entire network to minimize any electrical potential differences. Complete system bonding for any structured cabling system exhibits the following characteristics: Electrical continuity throughout the rack; Bonds equipment and patch panels to racks/ cabinets;

Shielded cable/jack Bonds each rack/cabinet to the telecommunications ing busbar (TGB); this may be done via a mesh common bonding network (MCBN); Bonds the telecommunications ing system to the alternating-current (AC) service panels serving the IT equipment in the room; such bonding promotes equivalent potential between the IT equipment ing and the equipment of the power system(s) serving the IT equipment; Foil of shielded cable Proper bonding and ing elements (clear covers, ID labels, green-coded conductors) to aid in visual verification of the system. Best practices for shielded For shielded cabling systems, the additional step of bonding the cable shield is essential to ensure proper system performance. The foil screen in Category 6A shielded cabling already provides enhanced system performance by preventing unwanted cable-to-cable signal coupling (i.e., alien crosstalk). A properly bonded and ed shielded cabling system further protects twisted pairs from external noise by carrying induced current along the continuous foil shield of the cable to the transceivers at each end of the cable. We recommend a 4-step process to properly bond the shield at the patch panel: 1. Bond all the shielding (foil and/or braid) of the data cable to the shielded jack module, which provides 360 shielding termination. 2. Snap the jack module into an all-metal patch panel to create a bond between the module and the unpainted tabs on the patch panel. 3. Attach the patch panel to the rack using thread-forming bonding screws; the thread on the screws removes paint from the thread holes on the rack, and the serrations on the head of the screws remove paint from the patch panel, creating a high-performance electrical bond between the patch panel and the rack. 4. So long as electrical continuity exists throughout the rack, the last step is to bond the rack to the main busbar or MCBN located under the data center s raised floor. To ensure longterm integrity of the system, always use compression connectors (not mechanical) so the connection does not loosen with vibration. Once cabling to the patch field has been bonded, attention can be turned to the rest of the bonding and ing system. Here are several best practices that must be considered during the design and installation of the rest of your shielded structured cabling system: 360 termination cap This shielded cable and jack combination from Panduit provides 360 shielding termination. Best Practice 1: Grounding the cable shield During installation, a frequently asked question is whether the installer should one or both ends of a shielded cable channel. Generally, the cable shield is bonded to the ed equipment chassis or rack at each access or patch location. In other words, if the IT equipment is ed, then any shielded cables used to connect equipment to patch panels, or to other equipment, must be ed. A typical shielded structured cabling channel runs from a switch to the workstation and comprises two patch cord links and the shielded horizontal link. One end of the channel starts in the data center where the switch, patch panel, and shielded patch cord linking them must be properly bonded to the rack. The rack is tied to the telecommunications ing system, which in turn is bonded to the AC power system. The other end of the channel terminates outside the data center at the workstation outlet. An issue to consider is whether a shielded cabling link at this outlet location can be properly bonded to a ing system without inducing a loop. A cable shield that is terminated at the workstation may be bonded to the AC via connections within the workstation itself, but the outlet AC must be at the same potential as the telecommunications ing system. The recommended method for ing the shielded link is to use workstation-provided. Use of a shielded patch cord s both ends of the shielded cable link and completes the shielded channel. However, when both ends of a shielded link are ed, there is the possibility for a current to be conducted across the shielding if the s are not at the same potential. In this example, a voltage difference may exist on the between the AC power source serving the workstation and the telecommunication within the data center. Therefore, to reduce the magnitude of such currents, all serving AC power systems must be bonded together to the same ing electrode system. (A building can have only one ing electrode system, as required by the National Electrical Code.) This approach will reduce any voltage differences that may exist either between differing AC power system s or between the AC power system and the telecommunications. An alternative industry practice is to use UTP patch cords between the outlet and the workstation, effectively ing only one end of the shielded cable channel in the data center and

Telecommunications bonding backbone Branch circuit An enterprise shielded cabling setup Ethernet switch Shielded patch cord Telecommunications ing busbar AC panel Patch panel Power distribution Data center Horizontal cabling (shielded) Workstation Workstation RJ-45 outlet Patch cord (UTP or shielded) AC outlet Branch circuit AC outlet leaving the cable link at the workstation area uned. The advantage of this option is that the risk of establishing a substantial loop current is greatly reduced. This option, however, lowers the level of protection against external noise, such as alien crosstalk, EMI, and RFI, across that link in the channel, thus lowering system performance. It commonly is used only when it is not possible to eliminate voltage differences between potentials. Best practice 2: Ensuring path continuity To optimize the performance of your shielded (or unshielded) network, you should perform a visual inspection upon installation and on an annual or semi-annual basis thereafter to check for proper bonding and ing, as well as the overall design of the power and system. An inspection that follows a line-by-line work order allows early detection of potential problems, such as: loosened or corroded connections; missing labels; conductors that have been damaged, cut, or removed; and new metallic elements that require connections to the common bonding network described in The Emerald Book. To facilitate inspection of the ing system, install connectors, busbars, and conductors in such a way to allow visual verification of the bond. There should be a logical flow as you follow the ing busbar(s). For example, follow the path(s) from the equipment chassis to the rack, from the rack to the data center ing infrastructure, then over 3-prong AC plug The typical shielded cabling channel deployed in an enterprise environment terminates in the data center at one end, and at the other end terminates at the workstation. to the local TGB. The TGB connects to the telecommunications backbone (TBB), or ing cable, that runs back to the telecommunications main ing busbar (TMGB), which is bonded to earth via the electrical entrance facility and links all the TBBs together. Inspect all splices for proper crimping, and inspect labels to ensure that proper labeling procedures have been followed. If the IT equipment is ed, then any shielded cables used to connect equipment to patch panels, or to other equipment, must be ed. Best practice 3: Testing at the workstation Once the visual inspection of the data center bonding and ing system is complete, attention can be turned to the cabling area closest to the end user the workstation. If a potential difference exists between these two points, a loop will form and current may flow within the loop. A method for testing whether a loop potential exists at a workstation is to use a true RMS multimeter to measure the potential difference between the power outlet and the shielded module on the workstation outlet. Position one multimeter probe on the face of the shielded module on the workstation and the other in the ing prong of the electrical outlet, and check the voltage reading on the meter. If the meter reads less than 1 volt of potential (as described in ANSI J-STD-607-A Annex D) between the mod- Use a two-point multimeter to measure the potential difference between the workstation outlet module (left) and the wire of the electrical outlet (right).

ule and the power outlet, the endpoint device is expected to operate properly during steady-state conditions. If the meter reads 1 volt or more, a loop problem exists that may cause data errors or equipment damage. To correct this condition, effectively bond the power sources together to the same ing electrode system. In summary, it is essential to implement proper structured ing throughout a shielded cabling system to maximize equipment uptime, maintain system performance, and protect expensive equipment. This is important for all shielded cabling systems, including Category 6A, due to the increased use of this cable type for 10GBase-T transmission. The main advantage of using a shielded Category 6A cabling system for 10GBase-T applications is the dramatic suppression of alien crosstalk; the containment of this noise helps ensure better signal integrity than can be achieved with a UTP cabling system. But the ing and bonding requirements of Category 6A shielded cables are more stringent. At the data center end of the structured cabling channels, these requirements include proper bonding of the shielding to the jack, proper ing of the jack panels, and proper deployment of the ing and bonding infrastructure within the computer room and building. At the workstation, it is important that the outlet is at the same potential as the telecommunications. Grounded for performance The ing and bonding system is more than an insurance policy against a lightning strike. It is an active, functioning system that provides protection for personnel and equipment by minimizing the detrimental effects of electrical surges and transient voltages. By following standard principles and best installation practices, your bonding and ing system is a critical enabler of high-performance shielded structured cabling solutions to improve network reliability and achieve maximum 10GBase-T performance.