Line distance protection IED REL 670

Similar documents
Application. The control is performed from remote (SCADA/Station) through the communication bus

Customized 1MRK BEN Product version: 1.1 Revision: Issued: March 2007 Data subject to change without notice

Line distance protection IED REL 670

Substation Automation Products. Line differential protection RED670 Relion 670 series

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Relion 670 series. Busbar protection REB670 Pre-configured Product Guide

Relion 670 series. Bay control REC670 Customized Product Guide

Busbar protection REB 670

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

CSC-161 Line Protection IED Product Guide

Protection relays.

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

Content REF615 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

TWO-WINDING TRANSFORMER DIFFERENTIAL

MiCOM P122C Time-Overcurrent Protection

Relion 670 series. Line distance protection REL670 ANSI Pre-configured Product Guide

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters.

CSC-211 Multifunction Protection IED Product Guide

Relion 670 series. Line differential protection RED LE Customized Product Guide

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

PROTECTION, AUTOMATION & CONTROL

Protection and Control IEDs Selection Guide

DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830

DRTS 33. The new generation of advanced three phase relay test set

GE Multilin 350 Feeder Protection Relay Specifications

DRTS 66 can test all the following relays

Recloser Controller for feeder protection and automation siemens.com/distribution-automation

MiCOM P521. Fast feeder differential protection

DRTS 66. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

MiCOM P521. Fast Feeder Differential Protection

Siprotec 7ST61 / 7ST63

Numerical motor protection in medium voltage networks Motor Protection and Control REM620

Use of frame agreement to standardize Protection in Digital Substation Automation Systems, Cooperation between Statnett and ABB

Relion 670 series. Busbar protection REB670 ANSI Pre-configured Product Guide

NPW800R RETROFITTING. Power and Volatge Protection Relay

NEO 3000 Substation System THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES. Energy Sector

THE NEW GENERATION OF ADVANCED TEST EQUIPMENTS FOR RELAYS, ENERGY METERS, TRANSDUCERS AND POWER QUALITY METERS.

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

ELG4125: System Protection

Relion. Distributed busbar protection REB500 Product Guide

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Relion 670 series. Busbar protection REB670 Installation and commissioning manual

DS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

Connectivity Packages. User's Guide - ANSI Version

Feeder protection relay SPAA 121 C. Product Guide

Relion 670 series. Busbar protection REB670 Pre-configured Product Guide

CSC-121 Breaker Protection IED Product Guide

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs

Landsnet-Icegrid. Requirements for protection and control systems. Principles for the Icelandic power transmission network.

Earth-fault Relay SPAJ 110 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

Residual overvoltage relay

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.

Feeder protection relay SPAA 341 C. Product Guide

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS

2 nd Edition INTRODUCTION

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

A low-cost, economical solution for distribution feeder protection

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

Relion 670 series. Phasor measurement unit RES670 ANSI Customized Product Guide

MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits

SIPROTEC 5 Application Note. Breaker-and-a-half solutions. SIP5-APN-002, Edition 2.

RELAYABLE POWER. AQ-200 series protection, control, measurement and monitoring IEDs

Feeder protection relay

MiCOM Agile P746. Grid Solutions. Key Benefits. Numerical Busbar Protection. A Combination of Speed, Security and Selectivity. About MiCOM P40 Agile

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

RMS Product Presentation

Relion 670 series. Busbar protection REB670 Customized Product Guide

Protection, Automation, and Bay Control System. Advanced feeder protection and complete substation bay control in one economical system

SIPROTEC 4 7SA522 Distance Protection Relay for Transmission Lines

Power Systems Communications Implementation of IEC61850 in a Substation Environment

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers

Relion 670 series. Busbar protection REB670 ANSI Installation and commissioning manual

System Protection and Control Subcommittee

Protection, Monitoring and Control Terminals for Sub-transmission and Transmission Networks

1) IED Protection and Control Manager PCM 600 Tool (SEP-601) The following subjects will be studied:

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs

MiCOM Agile P541 & 542. Grid Solutions. High-speed current differential unit protection. Key Benefits. Key Features. Current Differential Protection

THE MODELING APPROACH OF IEC

THE INTEGRATED TESTING SOLUTION

Grid Automation Controller COM600 How it fits into the Smart Grid?

Perfect protection smallest space

SIPROTEC 4 7SD52/53 Multi-End Differential and Distance Protection in One Relay

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection

Feeder/ Motor Protection Relay VAMP 40

Bus Bar Protection Relay B-PRO 4000

Transcription:

Line distance protection IED REL 670 Revision: G Issued: February 2007 Data subject to change without notice Page 1 Features Four configuration alternatives for single- or multi-breaker arrangements available ready to connect For overhead lines and cables For single and/or three phase tripping High impedance differential protection for tee-feeders Full scheme phase-to-phase and phase-to-earth distance protection with up to five zones: - All types of scheme communication - Load encroachment feature Four step directional and/or non-directional overcurrent earth fault protection: - Each step can be inverse or definite time delayed - Each step can be blocked on second harmonic component Synchrocheck and dead-line check function for single- or multi-breaker arrangements: - Selectable energizing direction - Two functions with built-in voltage selection - For automatic or manual synchrocheck and with different settings Auto-reclosing function for single- two-, and/or three-phase reclosing: - Two functions with priority circuits for multi-breaker arrangements - Co-operation with synchrocheck function - Can be switched On-Off from remote through communication or with local switches through binary inputs Built-in data communication modules for station bus IEC 61850-8-1 Data communication modules for station bus IEC 60870-5-103, LON and SPA Remote end communication function with capability for 192 binary signals Integrated disturbance and event recorder for up to 40 analog and 96 binary signals Time synchronization over IEC 61850-8-1, LON, SPA, binary input or with optional GPS module Analog measurements accuracy up to below 0.5% for power and 0.25% for current and voltage and with site calibration to optimize total accuracy Versatile local human-machine interface Extensive self-supervision with internal event recorder Six independent groups of complete setting parameters with password protection Powerful software PC tool for setting, disturbance evaluation and configuration Remote end data communication modules for C37.94 and G.703 Application The REL 670 IED is used for the protection, control and monitoring of overhead lines and cables in solidly earthed networks. The IED can be used up to the highest voltage levels. It is suitable for the protection of heavily loaded lines and multi-terminal lines where the requirement for tripping is one, two-, and/or three pole. The IED is also suitable as back-up protection on power transformers, reactors etc. The full scheme distance protection provides protection of power lines with high sensitivity and low requirement on remote end communication. The five zones have fully independent measuring and setting which gives high flexibility for all types of lines. The auto-reclose for single-, two-, and/or three phase reclose includes priority circuits for multi-breaker arrangements. It co-operates with

Revision: G, Page 2 the synchrocheck function with high-speed or delayed reclosing. High set instantaneous phase and earth overcurrent, four step directional or un-directional delayed phase and earth overcurrent, thermal overload and two step under and overvoltage functions are examples of the available functions allowing the user to fulfill any application requirement. The distance and earth fault protection can communicate with remote end in any communication scheme. With the included remote communication, following the IEEE C37.94 standard, 6 x 32 channels for intertrip and binary signals is available in the communication between the IEDs. The IED can also be provided with a full control and interlocking functionality including co-operation with the synchrocheck function to allow integration of the main or back-up control. The advanced logic capability, where the user logic is prepared with a graphical tool, allows special applications such as automatic opening of disconnectors in multi-breaker arrangements, closing of breaker rings, load transfer logics etc. The graphical configuration tool ensures simple and fast testing and commissioning. Serial data communication is via optical connections to ensure immunity against disturbances. The wide application flexibility makes this product an excellent choice for both new installations and the refurbishment of existing installations. Four packages has been defined for following applications: Single-breaker (double or single bus) with three phase tripping (A31) Single-breaker (double or single bus) with single phase tripping (A32) Multi-breaker (one-and a half or ring) with three phase tripping (B31) Multi-breaker (one-and a half or ring) with single phase tripping (B32) The packages are configured and set with basic functions active to allow direct use. Optional functions are not configured but a maximum configuration with all optional functions are available as template in the graphical configuration tool. Interface to analogue and binary IO are configurable from the Signal matrix tool without need of configuration changes. Analogue and tripping IO has been pre-defined for basic use on the, as standard supplied one binary input module and one binary output module. Add IO as required for your application at ordering. Other signals need to be applied as required for each application. For details on included basic functions refer to section "Available functions". The applications are shown in figures 1 and 2 for single resp. multi-breaker arrangement.

Revision: G, Page 3 BUS B BUS A TRIP BUSBAR 79 25 O->I SC/VC 94/86 I->O CLOSE TRIP 50BF 3I> 21 Z < 5 5 51/67 3I> 4 4 51N/67N IN> 4 4 59 3U> 2 2 27 2 2 3U< en05000276.vsd Figure 1: The single breaker packages for single- and three phase tripping typical arrangement for one protection sub-system is shown here.

Revision: G, Page 4 BUS A TRIP BUSBAR & CB2 79 25 O->I SC/VC CLOSE 94/86 I->O TRIP CB1 79 25 O->I SC/VC 59 2 2 3U> 21 Z < 5 5 51/67 3I> 4 4 Σ 50BF 3I> 50BF TRIP 3I> CB1/X 94/86 I->O TRIP CLOSE 27 51N/67N CB2 2 2 3U< IN> 4 4 en05000317.vsd Figure 2: The multi breaker packages for single- and three phase tripping typical arrangement for one protection sub-system is shown here. Auto-reclose, Synchrocheck and Breaker failure functions are included for each of the two breakers.

Revision: G, Page 5 Available functions ANSI Function description Single breaker, 3-phase tripping (A31) Basic Option (Qty/ Option design) Multi breaker, 3-phase tripping (B31) Basic Option (Qty/ Option design) Single breaker, 1-phase tripping (A32) Basic Option (Qty/ Option design) Multi breaker, 1-phase tripping (B32) Basic Option (Qty/ Option design) Differential protection 87 High impedance differential protection (PDIF) - 3/A02-3/A02-3/A02-3/A02 Distance protection 21 Distance protection zones (PDIS) 5-5 - 5-5 - 21 Phase selection with load enchroachment (PDIS) 1-1 - 1-1 - Directional impedance (RDIR) 1-1 - 1-1 - 78 Power swing detection (RPSB) 1-1 - 1-1 - Automatic switch onto fault logic (PSOF) 1-1 - 1-1 - Current protection 50 Instantaneous phase overcurrent protection (PIOC) 1-1 - 1-1 - 51/67 Four step phase overcurrent protection (POCM) 1-1 - 1-1 - 50N Instantaneous residual overcurrent protection (PIOC) 1-1 - 1-1 - 51N/67N Four step residual overcurrent protection (PEFM) 1-1 - 1-1 - 26 Thermal overload protection, one time constant (PTTR) 1-1 - 1-1 - 50BF Breaker failure protection (RBRF) 1-2 - 1-2 - 50STB Stub protection (PTOC) - 1 - - 1-52PD Pole-discordance protection (RPLD) - - - - 1-2 - Voltage protection 27 Two step undervoltage protection (PUVM) 1-1 - 1-1 - 59 Two step time delayed overvoltage protection (POVM) 1-1 - 1-1 - 59N Two step residual overvoltage protection (POVM) 1-1 - 1-1 - Frequency protection 81 Underfrequency protection (PTUF) - 2/E02-2/E02-2/E02-2/E02 81 Overfrequency protection (PTOF) - 2/E02-2/E02-2/E02-2/E02 81 Rate-of-change frequency protection (PFRC) - 2/E02-2/E02-2/E02-2/E02 Multipurpose protection General current and voltage protection (GAPC) - 4/F01-4/F01-4/F01-4/F01 Secondary system supervision Current circuit supervision (RDIF) 1-2 - 1-2 - Fuse failure supervision (RFUF) 3-3 - 3-3 - Control 25 Synchrocheck and energizing check (RSYN) 1-2 - 1-2 - 79 Autorecloser (RREC) 1-2 - 1-2 - Apparatus control for single bay, max 8 apparatuses incl. interlocking (APC8) - 1/H07 - - - 1/H07 - - Apparatus control for single bay, max 15 apparatuses (2CBs) incl. interlocking (APC15) - - - 1/H08 - - - 1/H08 Scheme communication 85 Scheme communication logic for distance protection (PSCH) 1-1 - 1-1 - 85 Current reversal and weak-end infeed logic for distance protection (PSCH) 1-1 - 1-1 - Local acceleration logic (PLAL) 1-1 - 1-1 - 85 Scheme communication logic for 1-1 - 1-1 - residual overcurrent protection (PSCH) 85 Current reversal and weak-end infeed logic for residual overcurrent protection (PSCH) 1-1 - 1-1 -

Revision: G, Page 6 ANSI Function description Single breaker, 3-phase tripping (A31) Basic Option (Qty/ Option design) Multi breaker, 3-phase tripping (B31) Basic Option (Qty/ Option design) Single breaker, 1-phase tripping (A32) Basic Option (Qty/ Option design) Multi breaker, 1-phase tripping (B32) Basic Option (Qty/ Option design) Logic 94 Tripping logic (PTRC) 1-2 - 1-2 - Trip matrix logic (GGIO) 12-12 - 12-12 - Monitoring Measurements (MMXU) 3/10/3-3/10/3-3/10/3-3/10/3 - Event counter (GGIO) 5-5 - 5-5 - Disturbance report (RDRE) 1-1 - 1-1 - Fault locator (RFLO) 1-1 - 1-1 - Metering Pulse counter logic (GGIO) 16-16 - 16-16 - Station communication IEC61850-8-1 Communication 1-1 - 1-1 - LON communication protocol 1-1 - 1-1 - SPA communication protocol 1-1 - 1-1 - IEC60870-5-103 communication protocol 1-1 - 1-1 - Single command, 16 signals 3-3 - 3-3 - Multiple command and transmit 60/10-60/10-60/10-60/10 - Remote communication Binary signal transfer 4-4 - 4-4 - Functionality Differential protection High impedance differential protection (PDIF, 87) The high impedance differential protection can be used when the involved CT cores have same turn ratio and similar magnetizing characteristic. It utilizes an external summation of the phases and neutral current and a series resistor and a voltage dependent resistor externally to the relay. Distance protection Distance protection zones (PDIS, 21) The line distance protection is a five zone full scheme protection with three fault loops for phase to phase faults and three fault loops for phase to earth fault for each of the independent zones. Individual settings for each zone resistive and reactive reach gives flexibility for use on overhead lines and cables of different types and lengths. The function has a functionality for load encroachment which increases the possibility to detect high resistive faults on heavily loaded lines (see figure 3). end at phase-to-earth faults on heavily loaded Figure 3: Typical distance protection zone with load encroachment function activated The independent measurement of impedance for each fault loop together with a sensitive and reliable built in phase selection makes the function suitable in applications with single phase auto-reclosing. Built-in adaptive load compensation algorithm prevents overreaching of zone1 at load exporting power lines. X Reverse operation Forward operation R en05000034.vsd

Revision: G, Page 7 The distance protection zones can operate, independent of each other, in directional (forward or reverse) or non-directional mode. This makes them suitable, together with different communication schemes, for the protection of power lines and cables in complex network configurations, such as parallel lines, multi-terminal lines etc. Power swing detection (RPSB, 78) Power swings may occur after disconnection of heavy loads or trip of big generation plants. Power swing detection function is used to detect power swings and initiate block of selected distance protection zones. Occurrence of earth fault currents during a power swing can block the power swing detection function to allow fault clearance. Automatic switch onto fault logic (PSOF) Automatic switch onto fault logic is a function that gives an instantaneous trip at closing of breaker onto a fault. A dead line detection check is provided to activate the function when the line is dead. Current protection Instantaneous phase overcurrent protection (PIOC, 50) The instantaneous three phase overcurrent function has a low transient overreach and short tripping time to allow use as a high set short-circuit protection function, with the reach limited to less than typical eighty percent of the power line at minimum source impedance. Four step phase overcurrent protection (POCM, 51_67) The four step phase overcurrent function has an inverse or definite time delay independent for each step separately. All IEC and ANSI time delayed characteristics are available together with an optional user defined time characteristic. The function can be set to be directional or non-directional independently for each of the steps. Instantaneous residual overcurrent protection (PIOC, 50N) The single input overcurrent function has a low transient overreach and short tripping times to allow use as a high set short circuit protection function, with the reach limited to less than typical eighty percent of the power line at minimum source impedance. The function can be configured to measure the residual current from the three phase current inputs or the current from a separate current input. Four step residual overcurrent protection (PEFM, 51N/67N) The four step single input overcurrent function has an inverse or definite time delay independent for each step separately. All IEC and ANSI time delayed characteristics are available together with an optional user defined characteristic. The function can be set to be directional, forward, reverse or non-directional independently for each of the steps. A second harmonic blocking can be set individually for each step. The function can be used as main protection for phase to earth faults. The function can be used to provide a system back-up e.g. in the case of the primary protection being out of service due to communication or voltage transformer circuit failure. Directional operation can be combined together with corresponding communication blocks into permissive or blocking teleprotection scheme. Current reversal and weak-end infeed functionality are available as well. The function can be configured to measure the residual current from the three phase current inputs or the current from a separate current input. Thermal overload protection, one time constant (PTTR, 26) The increasing utilizing of the power system closer to the thermal limits have generated a need of a thermal overload function also for power lines. A thermal overload will often not be detected by other protection functions and the introduction of the thermal overload function can allow the protected circuit to operate closer to the thermal limits. The three phase current measuring function has an I 2 t characteristic with settable time constant and a thermal memory. An alarm level gives early warning to allow operators to take action well before the line will be tripped. Breaker failure protection (RBRF, 50BF) The circuit breaker failure function ensures fast back-up tripping of surrounding breakers. The breaker failure protection operation can be current based, contact based or adaptive combination between these two principles. A current check with extremely short reset time is used as a check criteria to achieve a high security against unnecessary operation. The breaker failure protection can be single- or three-phase started to allow use with single phase

Revision: G, Page 8 tripping applications. For the three-phase version of the breaker failure protection the current criteria can be set to operate only if two out of four e.g. two phases or one phase plus the residual current starts. This gives a higher security to the back-up trip command. The function can be programmed to give a singleor three phase re-trip of the own breaker to avoid unnecessary tripping of surrounding breakers at an incorrect starting due to mistakes during testing. Stub protection (PTOC, 50STB) When a power line is taken out of service for maintenance and the line disconnector is opened in multi-breaker arrangements the voltage transformers will mostly be outside on the disconnected part. The primary line distance protection will thus not be able to operate and must be blocked. The stub protection covers the zone between the current transformers and the open disconnector. The three phase instantaneous overcurrent function is released from a NO (b) auxiliary contact on the line disconnector. Pole discordance protection (RPLD, 52PD) Single pole operated circuit breakers can due to electrical or mechanical failures end up with the different poles in different positions (close-open). This can cause negative and zero sequence currents which gives thermal stress on rotating machines and can cause unwanted operation of zero sequence current functions. Normally the own breaker is tripped to correct the positions. If the situation consists the remote end can be intertripped to clear the unsymmetrical load situation. The pole discordance function operates based on information from auxiliary contacts of the circuit breaker for the three phases with additional criteria from unsymmetrical phase current when required. Voltage protection Two step undervoltage protection (PUVM, 27) Undervoltages can occur in the power system during faults or abnormal conditions. The function can be used to open circuit breakers to prepare for system restoration at power outages or as long-time delayed back-up to primary protection. The function has two voltage steps, each with inverse or definite time delay. Two step overvoltage protection (POVM, 59) Overvoltages will occur in the power system during abnormal conditions such as sudden power loss, tap changer regulating failures, open line ends on long lines. The function can be used as open line end detector, normally then combined with directional reactive over-power function or as system voltage supervision, normally then giving alarm only or switching in reactors or switch out capacitor banks to control the voltage. The function has two voltage steps, each of them with inverse or definite time delayed. The overvoltage function has an extremely high reset ratio to allow setting close to system service voltage. Two step residual overvoltage protection (POVM, 59N) Residual voltages will occur in the power system during earth faults. The function can be configured to calculate the residual voltage from the three phase voltage input transformers or from a single phase voltage input transformer fed from an open delta or neutral point voltage transformer. The function has two voltage steps, each with inverse or definite time delayed. Frequency protection Underfrequency protection (PTUF, 81) Underfrequency occurs as a result of lack of generation in the network. The function can be used for load shedding systems, remedial action schemes, gas turbine start-up etc. The function is provided with an undervoltage blocking. The operation may be based on single phase, phase-to-phase or positive sequence voltage measurement. Up to two independent under frequency function instances are available. Overfrequency protection (PTOF, 81) Overfrequency will occur at sudden load drops or shunt faults in the power network. In some cases close to generating part governor problems can also cause overfrequency. The function can be used for generation shedding, remedial action schemes etc. It can also be used as a sub-nominal frequency stage initiating load restoring. The function is provided with an undervoltage blocking. The operation may be based on single phase, phase-to-phase or positive sequence voltage measurement. Up to two independent over frequency function instances are available.

Revision: G, Page 9 Rate-of-change frequency protection (PFRC, 81) Rate of change of frequency function gives an early indication of a main disturbance in the system. The function can be used for generation shedding, load shedding, remedial action schemes etc. The function is provided with an undervoltage blocking. The operation may be based on single phase, phase-to-phase or positive sequence voltage measurement. Each step can discriminate between positive or negative change of frequency. Up to two independent rate-of-change frequency function instances are available. Multipurpose protection General current and voltage protection (GAPC) The function can be utilized as a negative sequence current protection detecting unsymmetrical conditions such as open phase or unsymmetrical faults. The function can also be used to improve phase selection for high resistive earth faults, outside the distance protection reach, for the transmission line. Three functions are used which measures the neutral current and each of the three phase voltages. This will give an independence from load currents and this phase selection will be used in conjunction with the detection of the earth fault from the directional earth fault protection function. Secondary system supervision Current circuit supervision (RDIF) Open or short circuited current transformer cores can cause unwanted operation of many protection functions such as differential, earth fault current and negative sequence current functions. It must be remembered that a blocking of protection functions at an occurring open CT circuit will mean that the situation will remain and extremely high voltages will stress the secondary circuit. The current circuit supervision function compares the residual current from a three phase set of current transformer cores with the neutral point current on a separate input taken from another set of cores on the current transformer. A detection of a difference indicates a fault in the circuit and is used as alarm or to block protection functions expected to give unwanted tripping. Fuse failure supervision (RFUF) Failures in the secondary circuits of the voltage transformer can cause unwanted operation of distance protection, undervoltage protection, neutral point voltage protection, energizing function (synchrocheck) etc. The fuse failure supervision function prevents such unwanted operations. There are three methods to detect fuse failures. The method based on detection of zero sequence voltage without any zero sequence current. This is a useful principle in a directly earthed system and can detect one or two phase fuse failures. The method based on detection of negative sequence voltage without any negative sequence current. This is a useful principle in a non-directly earthed system and can detect one or two phase fuse failures. The method based on detection of du/dt-di/dt where a change of the voltage is compared to a change in the current. Only voltage changes means a voltage transformer fault. This principle can detect one, two or three phase fuse failures. Control Synchrocheck and energizing check (RSYN, 25) The synchrocheck function checks that the voltages on both sides of the circuit breaker are in synchronism, or with at least one side dead to ensure that closing can be done safely. The function includes a built-in voltage selection scheme for double bus and one- and a half or ring busbar arrangements. Manual closing as well as automatic reclosing can be checked by the function and can have different settings, e.g. the allowed frequency difference can be set to allow wider limits for the auto-reclose attempt than for the manual closing. Autorecloser (RREC, 79) The autoreclosing function provides high-speed and/or delayed auto-reclosing for single or multi-breaker applications. Up to five reclosing attempts can be programmed. The first attempt can be single-, two and/or three phase for single phase or multi-phase faults respectively. Multiple autoreclosing functions are provided for multi-breaker arrangements. A priority circuit allows one circuit breaker to close first and the second will only close if the fault proved to be transient. Each autoreclosing function can be configured to co-operate with a synchrocheck function. Apparatus control (APC) The apparatus control is a function for control and supervision of circuit breakers, disconnectors and earthing switches within a bay. Permission to oper-

Revision: G, Page 10 ate is given after evaluation of conditions from other functions such as interlocking, synchrocheck, operator place selection and external or internal blockings. Interlocking The interlocking function blocks the possibility to operate primary switching devices, for instance when a disconnector is under load, in order to prevent material damage and/or accidental human injury. Each apparatus control function has interlocking modules included for different switchyard arrangements, where each function handles interlocking of one bay. The interlocking function is distributed to each IED and is not dependent on any central function. For the station-wide interlocking, the IEDs communicate via the system-wide interbay bus (IEC 61850-8-1) or by using hard wired binary inputs/outputs. The interlocking conditions depend on the circuit configuration and apparatus position status at any given time. For easy and safe implementation of the interlocking function, the IED is delivered with standardized and tested software interlocking modules containing logic for the interlocking conditions. The interlocking conditions can be altered, to meet the customer s specific requirements, by adding configurable logic by means of the graphical configuration tool. Scheme communication Scheme communication logic for distance protection and directional residual overcurrent protection (PSCH, 85) To achieve instantaneous fault clearance for all line faults, a scheme communication logic is provided. All types of communication schemes e.g. permissive underreach, permissive overreach, blocking, intertrip etc. are available. The built-in communication module (LDCM) can be used for scheme communication signalling when included. Logic for loss of load and/or local acceleration in co-operation with autoreclose function is also provided for application where no communication channel is available. Current reversal and weak-end infeed logic for distance protection and directional residual overcurrent protection (PSCH, 85) The current reversal function is used to prevent unwanted operations due to current reversal when using permissive overreach protection schemes in application with parallel lines when the overreach from the two ends overlaps on the parallel line. The weak-end infeed logic is used in cases where the apparent power behind the protection can be too low to activate the distance protection function. When activated, received carrier signal together with local under voltage criteria and no reverse zone operation gives an instantaneous trip. The received signal is also echoed back to accelerate the sending end. Local acceleration logic (PLAL) To achieve fast clearing of faults on the whole line, when no communication channel is available, local acceleration logic (ZCLC) can be used. This logic enables fast fault clearing during certain conditions, but naturally, it can not fully replace a communication channel. The logic can be controlled either by the auto re-closer (zone extension) or by the loss of load current (loss-of-load acceleration). Logic Tripping logic (PTRC, 94) A function block for protection tripping is provided for each circuit breaker involved in the tripping of the fault. It provides the pulse prolongation to ensure a trip pulse of sufficient length, as well as all functionality necessary for correct co-operation with autoreclosing functions. The trip function block includes functionality for evolving faults and breaker lock-out. Trip matrix logic (GGIO, 94X) Twelve trip matrix logic blocks are included in the IED. The function blocks are used in the configuration of the IED to route trip signals and/or other logical output signals to the different output relays. The matrix and the physical outputs will be seen in the PCM 600 engineering tool and this allows the user to adapt the signals to the physical tripping outputs according to the specific application needs. Configurable logic blocks A high number of logic blocks and timers are available for user to adapt the configuration to the specific application needs. Fixed signal function block The fixed signals function block generates a number of pre-set (fixed) signals that can be used in the configuration of an IED, either for forcing the unused inputs in the other function blocks to a certain level/value, or for creating a certain logic. Monitoring Measurements (MMXU) The service value function is used to get on-line information from the IED. These service values makes it possible to display on-line information on the local HMI and on the Substation automation system about:

Revision: G, Page 11 measured voltages, currents, frequency, active, reactive and apparent power and power factor, the primary and secondary phasors, differential currents, bias currents, positive, negative and zero sequence currents and voltages, ma, pulse counters, measured values and other information of the different parameters for included functions, logical values of all binary in- and outputs and general IED information. Supervision of ma input signals (MVGGIO) The main purpose of the function is to measure and process signals from different measuring transducers. Many devices used in process control represent various parameters such as frequency, temperature and DC battery voltage as low current values, usually in the range 4-20 ma or 0-20 ma. Alarm limits can be set and used as triggers, e.g. to generate trip or alarm signals. The function requires that the IED is equipped with the ma input module. Event counter (GGIO) The function consists of six counters which are used for storing the number of times each counter has been activated. It is also provided with a common blocking function for all six counters, to be used for example at testing. Every counter can separately be set on or off by a parameter setting. Disturbance report (RDRE) Complete and reliable information about disturbances in the primary and/or in the secondary system together with continuous event-logging is accomplished by the disturbance report functionality. The disturbance report, always included in the IED, acquires sampled data of all selected analogue input and binary signals connected to the function block i.e. maximum 40 analogue and 96 binary signals. The disturbance report functionality is a common name for several functions: Event List (EL) Indications (IND) Event recorder (ER) Trip Value recorder (TVR) Disturbance recorder (DR) Fault Locator (FL) The function is characterized by great flexibility regarding configuration, starting conditions, recording times and large storage capacity. A disturbance is defined as an activation of an input in the DRAx or DRBy function blocks which is set to trigger the disturbance recorder. All signals from start of pre-fault time to the end of post-fault time, will be included in the recording. Every disturbance report recording is saved in the IED in the standard Comtrade format. The same applies to all events, which are continuously saved in a ring-buffer. The Local Human Machine Interface (LHMI) is used to get information about the recordings, but the disturbance report files may be uploaded to the PCM 600 (Protection and Control IED Manager) and further analysis using the disturbance handling tool. Event list (RDRE) Continuous event-logging is useful for monitoring of the system from an overview perspective and is a complement to specific disturbance recorder functions. The event list logs all binary input signals connected to the Disturbance report function. The list may contain of up to 1000 time-tagged events stored in a ring-buffer. Indications (RDRE) To get fast, condensed and reliable information about disturbances in the primary and/or in the secondary system it is important to know e.g. binary signals that have changed status during a disturbance. This information is used in the short perspective to get information via the LHMI in a straightforward way. There are three LEDs on the LHMI (green, yellow and red), which will display status information about the IED and the Disturbance Report function (trigged). The Indication list function shows all selected binary input signals connected to the Disturbance Report function that have changed status during a disturbance. Event recorder (RDRE) Quick, complete and reliable information about disturbances in the primary and/or in the secondary system is vital e.g. time tagged events logged during disturbances. This information is used for different purposes in the short term (e.g. corrective actions) and in the long term (e.g. Functional Analysis). The event recorder logs all selected binary input signals connected to the Disturbance Report function. Each recording can contain up to 150 time-tagged events. The event recorder information is available for the disturbances locally in the IED.

Revision: G, Page 12 The event recording information is an integrated part of the disturbance record (Comtrade file). Trip value recorder (RDRE) Information about the pre-fault and fault values for currents and voltages are vital for the disturbance evaluation. The Trip value recorder calculates the values of all selected analogue input signals connected to the Disturbance report function. The result is magnitude and phase angle before and during the fault for each analogue input signal. The trip value recorder information is available for the disturbances locally in the IED. The trip value recorder information is an integrated part of the disturbance record (Comtrade file). Disturbance recorder (RDRE) The Disturbance Recorder function supplies fast, complete and reliable information about disturbances in the power system. It facilitates understanding system behavior and related primary and secondary equipment during and after a disturbance. Recorded information is used for different purposes in the short perspective (e.g. corrective actions) and long perspective (e.g. Functional Analysis). The Disturbance Recorder acquires sampled data from all selected analogue input and binary signals connected to the Disturbance Report function (maximum 40 analog and 96 binary signals). The binary signals are the same signals as available under the event recorder function. The function is characterized by great flexibility and is not dependent on the operation of protection functions. It can record disturbances not detected by protection functions. The disturbance recorder information for the last 100 disturbances are saved in the IED and the Local Human Machine Interface (LHMI) is used to view the list of recordings. Event function (EV) When using a Substation Automation system with LON or SPA communication, time-tagged events can be sent at change or cyclically from the IED to the station level. These events are created from any available signal in the IED that is connected to the Event function block. The event function block is used for LON and SPA communication. Analog and double indication values are also transferred through the event block. Fault locator (RFLO) The accurate fault locator is an essential component to minimize the outages after a persistent fault and/or to pin-point a weak spot on the line. The built-in fault locator is an impedance measuring function giving the distance to the fault in percent, km or miles. The main advantage is the high accuracy achieved by compensating for load current and for the mutual zero sequence effect on double circuit lines. The compensation includes setting of the remote and local sources and calculation of the distribution of fault currents from each side. This distribution of fault current, together with recorded load (pre-fault) currents, is used to exactly calculate the fault position. The fault can be recalculated with new source data at the actual fault to further increase the accuracy. Specially on heavily loaded long lines (where the fault locator is most important) where the source voltage angles can be up to 35-40 degrees apart the accuracy can be still maintained with the advanced compensation included in fault locator. Metering Pulse counter logic (GGIO) The pulse counter logic function counts externally generated binary pulses, for instance pulses coming from an external energy meter, for calculation of energy consumption values. The pulses are captured by the binary input module and then read by the pulse counter function. A scaled service value is available over the station bus. The special Binary input module with enhanced pulse counting capabilities must be ordered to achieve this functionality. Basic IED functions Time synchronization Use the time synchronization source selector to select a common source of absolute time for the IED when it is a part of a protection system. This makes comparison of events and disturbance data between all IEDs in a SA system possible. Human machine interface The local human machine interface is available in a small, and a medium sized model. The principle difference between the two is the size of the LCD. The small size LCD can display seven line of text and the medium size LCD can display the single line diagram with up to 15 objects on each page. Six SLD pages can be defined. The local human machine interface is equipped with an LCD that can display the single line diagram with up to 15 objects. The local human-machine interface is simple and easy to understand the whole front plate is divided into zones, each of them with a well-defined functionality:

Revision: G, Page 13 Status indication LEDs Alarm indication LEDs which consists of 15 LEDs (6 red and 9 yellow) with user printable label. All LEDs are configurable from the PCM 600 tool Liquid crystal display (LCD) Keypad with push buttons for control and navigation purposes, switch for selection between local and remote control and reset An isolated RJ45 communication port Figure 5: Medium graphic HMI, 15 controllable objects Figure 4: Small graphic HMI Station communication Overview Each IED is provided with a communication interface, enabling it to connect to one or many substation level systems or equipment, either on the Substation Automation (SA) bus or Substation Monitoring (SM) bus. Following communication protocols are available: IEC 61850-8-1 communication protocol LON communication protocol SPA or IEC 60870-5-103 communication protocol Theoretically, several protocols can be combined in the same IED. IEC 61850-8-1 communication protocol Single or double optical Ethernet ports for the new substation communication standard IEC61850-8-1 for the station bus are provided. IEC61850-8-1 allows intelligent devices (IEDs) from different vendors to exchange information and simplifies SA engineering. Peer- to peer communication according to GOOSE is part of the standard. Disturbance files uploading is provided. Serial communication, LON Existing stations with ABB station bus LON can be extended with use of the optical LON interface. This allows full SA functionality including peer-to-peer messaging and cooperation between existing ABB IED's and the new IED 670.

Revision: G, Page 14 SPA communication protocol A single glass or plastic port is provided for the ABB SPA protocol. This allows extensions of simple substation automation systems but the main use is for Substation Monitoring Systems SMS. IEC 60870-5-103 communication protocol A single glass or plastic port is provided for the IEC60870-5-103 standard. This allows design of simple substation automation systems including equipment from different vendors. Disturbance files uploading is provided. Single command, 16 signals The IEDs can receive commands either from a substation automation system or from the local human-machine interface, LHMI. The command function block has outputs that can be used, for example, to control high voltage apparatuses or for other user defined functionality. Multiple command and transmit When 670 IED's are used in Substation Automation systems with LON, SPA or IEC60870-5-103 communication protocols the Event and Multiple Command function blocks are used as the communication interface for vertical communication to station HMI and gateway and as interface for horizontal peer-to-peer communication (over LON only). Remote communication Binary signal transfer to remote end, 6x32signals Each of the six binary signal transfer function blocks can be used for sending and receiving of 32 signals, transfer trip and/or other binary signals between local and/or remote IEDs. An IED can communicate with up to IEDs by means of the data communication module (LDCM). Line data communication module, short, medium and long range (LDCM) The line data communication module (LDCM) is used for communication between the IEDs situated at distances <150 km or from the IED to optical to electrical converter with G.703 or G.703E1 interface located on a distances <3 km away. The LDCM module sends and receives data, to and from another LDCM module. The IEEE/ANSI C37.94 standard format is used. The line data communication module is used for binary signal transfer. The module has one optical port with ST connectors. Galvanic interface G.703 The external galvanic data communication converter G.703 makes an optical-to-galvanic conversion for connection to a multiplexer. These units are designed for 64 kbit/s operation. The converter is delivered with 19 rack mounting accessories. Hardware description Hardware modules Power supply module (PSM) The power supply module is used to provide the correct internal voltages and full isolation between the terminal and the battery system. An internal fail alarm output is available. Binary input module (BIM) The binary input module has 16 optically isolated inputs and is available in two versions, one standard and one with enhanced pulse counting capabilities on the inputs to be used with the pulse counter function. The binary inputs are freely programmable and can be used for the input of logical signals to any of the functions. They can also be included in the disturbance recording and event-recording functions. This enables extensive monitoring and evaluation of operation of the IED and for all associated electrical circuits. Binary output modules (BOM) The binary output module has 24 independent output relays and is used for trip output or any signalling purpose. Binary input/output module (IOM) The binary input/output module is used when only a few input and output channels are needed. The ten standard output channels are used for trip output or any signalling purpose. The two high speed signal output channels are used for applications where short operating time is essential. Eight optically isolated binary inputs cater for required binary input information. ma input module (MIM) The milli-ampere input module is used to interface transducer signals in the 20 to +20 ma range from for example OLTC position, temperature or pressure transducers.the module has six independent, galvanically separated channels. Optical ethernet module (OEM) The optical fast-ethernet module is used to connect an IED to the communication buses (like the station bus) that use the IEC 61850-8-1 protocol. The module has one or two optical ports with ST connectors. Serial SPA/IEC 60870-5-103 and LON communication module (SLM) The optical serial channel and LON channel module is used to connect an IED to the communication that use SPA, LON, or IEC60870 5 103. The module has two optical ports for plastic/plastic, plastic/glass, or glass/glass. Line data communication module (LDCM) The line data communication module is used for binary signal transfer. Each module has one optical

Revision: G, Page 15 port, one for each remote end to which the IED communicates. Alternative cards for Short range (900 nm multi mode) are available. Transformer input module (TRM) The transformer input module is used to galvanically separate and transform the secondary currents and voltages generated by the measuring transformers. The module has twelve inputs in different combinations. High impedance resistor unit The high impedance resistor unit, with resistors for pick-up value setting and a voltage dependent resistor, is available in a single phase unit and a three phase unit. Both are mounted on a 1/1 19 inch apparatus plate with compression type termnals. Layout and dimensions Dimensions F E A B C D xx05000003.vsd Figure 6: 1/2 x 19 case with rear cover Figure 7: Side-by-side mounting xx05000004.vsd Case size A B C D E F 6U, 1/2 x 19 265.9 223.7 201.1 242.1 252.9 205.7 6U, 3/4 x 19 265.9 336.0 201.1 242.1 252.9 318.0 6U, 1/1 x 19 265.9 448.1 201.1 242.1 252.9 430.3 (mm) Mounting alternatives Following mounting alternatives (IP40 protection from the front) are available: 19 rack mounting kit Flush mounting kit with cut-out dimensions: - 1/2 case size (h) 254.3 mm (w) 210.1 mm - 3/4 case size (h) 254.3 mm (w) 322.4mm - 1/1 case size (h) 254.3 mm (w) 434.7mm Wall mounting kit See ordering for details about available mounting alternatives.

Revision: G, Page 16 Connection diagrams Table 1: Designations for 1/2 x 19 casing with 1 TRM slot Module Rear Positions PSM X11 BIM, BOM or IOM X31 and X32 etc. to X51 and X52 GSM X51 SLM X301:A, B, C, D OEM X311:A, B, C, D LDCM X312:A, B LDCM X313:A, B TRM X401 Table 2: Designations for 3/4 x 19 casing with 2TRM slot Module Rear Positions PSM X11 BIM, BOM, IOM or MIM X31 and X32 etc. to X71 and X72 GSM X71 SLM X301:A, B, C, D LDCM X302:A, B LDCM X303:A, B OEM X311:A, B, C, D LDCM X312:A, B LDCM X313:A, B TRM X401, 411 Table 3: Designations for 1/1 x 19 casing with 2 TRM slots Module PSM BIM, BOM or IOM MIM GSM SLM OEM LDCM LDCM TRM 1 TRM 2 Rear Positions X11 X31 and X32 etc. to X131 and X132 X31, X41, etc. or X131 X131 X301:A, B, C, D X311:A, B, C, D X312:A, B X313:A, B X401 X411

Revision: G, Page 17 Current/voltage configuration (50/60 Hz) CT/VT-input designation according to figure 8 AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12 9I and 3U, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 0-220V 0-220V 0-220V 9I and 3U, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 0-220V 0-220V 0-220V 5I, 1A and 4I, 5A and 3U 1A 1A 1A 1A 1A 5A 5A 5A 5A 0-220V 0-220V 0-220V 6I and 6U, 1A 1A 1A 1A 1A 1A 1A 0-220V 0-220V 0-220V 0-220V 0-220V 0-220V 6I and 6U, 5A 5A 5A 5A 5A 5A 5A 0-220V 0-220V 0-220V 0-220V 0-220V 0-220V Figure 8: Transformer input module (TRM) Figure 9: Binary input module (BIM). Input contacts named XA corresponds to rear position X31, X41, etc. and input contacts named XB to rear position X32, X42, etc. Figure 10: ma input module (MIM)

Revision: G, Page 18 Figure 11: Binary in/out module (IOM). Input contacts named XA corresponds to rear position X31, X41, etc. and output contacts named XB to rear position X32, X42, etc. Figure 12: Communication interfaces (OEM, LDCM, SLM and HMI) Note to figure 12 1) Rear communication port IEC 61850, ST-connector 2) Rear communication port C37.94, ST-connector 3) Rear communication port SPA/ IEC 60870-5-103, ST connector for glass alt. HFBR Snap-in connector for plastic as ordered 4) Rear communication port LON, ST connector for glass alt. HFBR Snap-in connector for plastic as ordered 5) Front communication port, Ethernet, RJ45 connector Figure 14: GPS time synchronization module (GSM) Figure 13: Power supply module (PSM)

Revision: G, Page 19 Figure 15: Binary output module (BOM). Output contacts named XA corresponds to rear position X31, X41, etc. and output contacts named XB to rear position X32, X42, etc.

Revision: G, Page 20 BBP-TRIP ST BFP L1 ST BFP L2 ST BFP L3 ST BFP 3PH *) *) *) QB1-OPEN QB1-CL QB2-OPEN QB2-CL BUS A BUS B -QB1 -QB2 START AR INHIBIT AR 3PH TRIP *) TRM1:10 MCB-OK IN TEST MAN CLOSE TRM1:11 MCB-OK FAULT SIGNALLING QA1-OPEN QA1-CL QA1-PD QA1-SPR UNCH TRM1:1-3 *) *) CLOSE QA1 CLOSE Reinf TRIP QA1 L1,L2,L3 TRIP Reinf REL/RED 3 Phase MAIN 2 TRIP -QA1 C C T C T C -BI1 P1 TRM1:5 Reserved for parallal line IN at mutual comp of FL TO MAIN 2 RELAY BUSBAR TRIP PERMIT 1PH TRIP MAIN 2 1PH AR IN PROG *) *) TO BUS PROT CR Z< TO/FROM PLC/MUX CS Z< CR DEF CS DEF CR DIT CS DIT QB9-OPEN QB9-CL TRM1:7-9 MCB OR FUSE -QB9 -BU1 MCB-OK X11 O 3 IRF X11 2 5 4 - + REMOTE END COMMUNICATION *) is only valid for single phase tripping arrangements NOTE! CB CLosed is CB Closed L1&L2&L3 CB Open is CB Open L1 OR L2 OR L3 en05000261.vsd Figure 16: Typical connection diagram for a single breaker arrangement with control integrated.

Revision: G, Page 21 BBP-TRIP ST BFP L1 ST BFP L2 ST BFP L3 ST BFP 3PH *) *) *) QB1-OPEN QB1-CL QB6-OPEN QB6-CL BUS A -BU1 -QB1 START AR INHIBIT AR 3PH TRIP MAN CLOSE =1 FAULT SIGNALLING *) TRM1:11 MCB-OK QA1-OPEN QA1-CL QA1-PD QA1-SPR UNCH *) *) CLOSE QA1 CLOSE Reinf TRIP QA1 L1,L2,L3 TRIP Reinf MCB OR FUSE REL/RED 3 Phase MAIN 2 TRIP =1-QA1 C C T C T C ST BFP L1 ST BFP L2 ST BFP L3 ST BFP 3PH START AR INHIBIT AR 3PH TRIP TRM1:1-3 =2-QB9-OPEN =2-QB9-CL =2-QA1-OPEN =2-QA1-CL TRM1:7-9 MCB-OK For Voltage selection MCB OR FUSE -BI1 TO MAIN 2 RELAY TO BUS PROT -BU1 -QB6 P1 -QB9 BUSBAR TRIP TRIP =2-QA1 PERMIT 1PH TRIP MAIN 2, =1 PERMIT 1PH TRIP MAIN 2, =3 1PH AR IN PROG CR Z< CS Z< TO/FROM PLC/MUX IN TEST MAN CLOSE =3 CR DEF CS DEF CR DIT CS DIT DIT2 Line 2 *) *) *) X11 3 IRFX11 2 5 4 - + QA1-OPEN QA1-CL QA1-PD QA1-SPR UNCH O QB9-OPEN QB9-CL TRM2:1-3 MCB-OK TRM2:11 TRM1:12 REMOTE END COMMUNICATION TRM1:5 MCB-OK TO MAIN 2 RELAY Reserved for parallal line IN at mutual comp of FL CLOSE QA1 CLOSE Reinf TRIP QA1 L1,L2,L3 TRIP Reinf MAIN 2 TRIP MCB OR FUSE MCB OR FUSE -BU1 -BU1 -QB61 -BI1 =3-QA1 C C T C T C -QB62 -QB6 =2-QA1 -QB2 P1 -QB9 NOTE! CB CLosed is CB Closed L1&L2&L3 CB Open is CB Open L1 OR L2 OR L3 BUS B *) is only valid for single phase tripping arrangements en05000267.vsd Figure 17: Typical connection diagram for a multi breaker arrangement (1 1/2 CB) with control integrated.