Installation Note for the Cisco ME 3800X and ME 3600X Switch Power Supply and Fan Modules

Similar documents
Installation Notes for the Catalyst 3750-X and 3560-X Switch Power Supply Modules

Power Supply and Fan Module Installation

Power Supply Installation

Power Supply and Fan Module Installation

Installation Notes for Catalyst 3750-E and Catalyst 3560-E Switch Fan Modules

Replacing the Power Supply

Installing a Power Supply

Installation Notes for the Catalyst 3750-X and 3560-X Network Modules

Catalyst 6500 Series Wireless LAN Services Module Installation and Verification Note

Installation Notes for the Cisco TwinGig and OneX Converter Modules

Installing a Network Module

Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2. Cisco CRS 3-Phase AC Power Distribution Unit 2

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

Installing a Network Module

Dell Networking S4810 Open Networking (ON) Getting Started Guide

M5 and M10 Routers Power Supply and Power Cord Component Replacement Instructions

Installing the Cisco 2524 and Cisco 2525 Routers

Installing the Cisco AS5400XM Universal Gateway

Installing the IPS 4345 and IPS 4360

Installing a Network Module

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual

Installing the Cisco ADE 2130 and 2140 Series Appliance Hardware Options

Perle MCR200 Installation Guide

Quick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport

Installation and Maintenance

Catalyst 2360 Switch Getting Started Guide

TRC-190 User s Manual

Replacing the RAID Battery Backup Unit Assembly on Series 3 FireSIGHT 3500 Defense Centers, Version 5.x

Junos WebApp Secure 5.0 Hardware Guide

PIX 515/515E. PIX 515/515E Product Overview CHAPTER

Connecting Power and Ground

Installing or Replacing Modules, Fan Trays, and Power Supplies

TRC-190 User s Manual

Installation Job Aid for Ethernet Routing Switch 3600 Series

Installing and Upgrading Internal Modules and FRUs in Cisco 1900 Series ISRs

Installing the Cisco MDS 9020 Fabric Switch

Installation Job Aid for Ethernet Routing Switch 5900 Series

Installing the DS1-28/DS3-EC1-3 and DS1-84/DS3-EC1-3 Cards in the Cisco ONS MA

Upgrading Memory in Cisco 800 Series Routers

QFX10008 Switch Quick Start Guide

RAID Battery Replacement for Supported Cisco Security Appliances

Cisco ME 3800X and ME 3600X Switch Hardware Installation Guide

RMB Peripheral Units Installation Guide

Media Conversion Rack-Mount Chassis AT-MCR12. Installation Guide Rev. A

Quick Start Guide S X. 1. Unpacking the Switch. 2. Identifying Your System. Front View

Installing ONS SDH FMEC-E3/DS3 Cards

AI130 AIswitch Series 130 Chassis Installation Guide

Installation Job Aid for VSP 4450GTX-HT- PWR+

Maintaining the Cisco Internet Router

Maintaining the Cisco Catalyst 5500 Multiswitch Router

S4112-ON Series. Setup Guide

PIX 520. PIX 520 Product Overview CHAPTER

Cisco MDS SAN-OS Release Compatibility Matrix for Storage Service Interface Images

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions

Install the Cisco ONS CL

Installing the Cisco ASR 901 Mobile Wireless Router as a Satellite Shelf

Installing and Removing SDRAM and DRAM

Cisco MDS 9132T 32-Gbps 32-Port Fibre Channel Switch Hardware Installation Guide

NI PXI-1042 POWER SUPPLY SHUTTLE USER GUIDE

Dell SC460 Expansion Enclosure Getting Started Guide

Dell EMC Storage MD1280 Enclosure Owner's Manual

User s Guide. Mobile Rack Device Mounting Kit for Echo Express III-R and xmac Pro Server. Quick Start Guide Video Available Online!

HP UPS R/T3000 ERM. Overview. Precautions. Installation Instructions

Installation of the POTS splitter card requires the following steps: Determining the cables you need. Installing the POTS splitter chassis

Installation Job Aid for VSP 4850GTS

Dell Storage MD1400 Enclosures Hardware Owner's Manual

Perle IDS-108F(XT) Unmanaged 10/100 Ethernet Switches. Installation Guide. P/N (Rev G)

Product Overview. Cisco ME 6524 Ethernet Switch (ME-C6524GS-8S) CHAPTER

Dell SCv300 and SCv320 Expansion Enclosure Owner's Manual

Cisco ASR 1004 Router Overview and Installation

Dual-Feed 80A Auto Low Voltage Disconnect Panel - 80LVD02

XCM8800 PSU Cover. Installation Guide. 350 East Plumeria Drive San Jose, CA USA. May v1.0

4 10/100/1000T Mini-GBIC with 4 IEEE 802.3at High Power PoE Industrial Wide Temperature Switch. User Manual SISTP LRT

Removing and Replacing FRUs from the Cisco ASR 1001-X Router

NI PXI-1042 Series Power Supply Shuttle

SCv360 Expansion Enclosure

Installation Job Aid for Avaya Virtual Services Platform 8400

SRX 5600 Services Gateway DC Power Supply Installation Instructions

9. NTP-C11 Remove and Replace an Ethernet Card, page 1-13 As needed, complete this procedure to remove and replace an ONS CL Ethernet card.

Dell SC7020 Storage Controller Getting Started Guide

Switch Installation. Preparing for Installation. Safety Warnings

SGI InfiniteStorage 120

NI PXIe-1062Q Power Supply Shuttle

Installing the Cisco UCS 6200 Series Fabric Interconnect

Managing Individual Components

Cisco MDS NX-OS Release Compatibility Matrix for Storage Service Interface Images

InnoMedia Business VoIP ATA Models

Installing the Router

AT-8900, AT-9900, AT-9900s Switches Removable Power Supply and Fan Installation Guide

N3150 Installation and Setup Instructions

LVN5200A-R2, rev. 1, Hardware Installation Guide

Dell PowerVault MD3060e Storage Enclosure Owner's Manual

Dell Networking S4100-ON Series. Set-Up Guide

How to Set Up Your SRX4100 Services Gateway

PIX 535. PIX 535 Product Overview CHAPTER

Installation RA5112-C-16A-C20. Basic Rack Power Distribution Unit

Preparing to Install the VG248

Dell SCv3000 and SCv3020 Storage System Getting Started Guide

Dell SC5020 and SC5020F Storage Systems Getting Started Guide

Installing the Cisco NCS RU

Transcription:

Installation Note for the Cisco ME 3800X and ME 3600X Switch Power Supply and Fan Modules This document provides the installation and removal instructions for the AC and DC input power supply and fan modules for the Cisco Metro Ethernet (ME) 3800X and ME 3600X switches. Your switch ships with at least one power supply module installed, either AC or DC, depending on your order. The power supply and fan modules are field-replaceable units (FRUs). Note The power supplies and fan modules are hot-swappable devices. For translations of the safety warnings in this chapter, see the Regulatory Compliance and Safety Information for the Cisco ME 3800X and ME 3600X Switch on Cisco.com. Power Supply Module Description, page 2 Fan Module Description, page 4 Connector-Side Description, page 5 Power Supply and Fan Module Installation, page 5 Finding the Power Supply and Fan Module Serial Number, page 14 Technical Specifications, page 15 Related Publications, page 16 Obtaining Documentation and Submitting a Service Request, page 16 Americas Headquarters: Cisco Systems, Inc., 170 West Tasman Drive, San Jose, CA 95134-1706 USA

Power Supply Module Description Power Supply Module Description Table 1 Power Supply Module Model Numbers and Descriptions Model number PWR-ME3KX-AC PWR-ME3KX-DC Description AC input power supply DC input power supply The AC input power supply module is an autoranging unit that supports input voltages between 100 and 240 VAC. The AC power supply modules ship with a power cord to connect to an AC power outlet. The DC input power supply module has a single input feed and supports input voltages from 18 to 32 VDC or 36 to 72 VDC. The DC power supply module ships with a terminal block to be wired for DC power outlet connections. The terminal block is covered by a clear plastic block cover that snaps onto the terminal block. You must remove the block cover before you work with the wires. The block cover is slotted so that the wires can exit only one end. If you want the wires to exit in a different direction, remove the block cover, rotate it, and snap it back on. Each power supply is cooled by three internal fans. A fan failure triggers an alarm. When a fan fails, replace the power supply immediately. Both slots must be occupied either by two power supplies or a power supply and a fan module. Do not run the switch with an empty slot unless you are replacing a faulty power supply or fan module. Running the switch with an empty slot triggers an alarm. Figure 1 2 1 AC Input Power Supply Module Handle Side PSU OK AC 207446 3 4 5 6 1 AC input power supply module 4 Extraction handle 2 Power supply module status LED 5 Power switch 3 Power input LED 6 AC power connector 2

Power Supply Module Description Figure 2 2 1 DC Input Power Supply Module Handle Side PSU OK AC 3 4 5 6 207447 1 DC input power supply module 4 Extraction handle 2 Power supply module status LED 5 DC input power terminal block 3 Power input LED 6 Power switch Table 2 Color Green Red Off Power Supply Module Status LED System Status The power supply module is installed, output is OK, all internal fans OK, and power switch is ON. The power supply module is installed, output has failed or one of the internal fans has failed, power switch is ON. The power supply module is installed, power switch is OFF, no input power, or invalid input power. Table 3 Color Green Amber Off Power Supply Input LED System Status The power supply module is installed, AC or DC input power is OK, power switch is ON or OFF. The power supply module is installed, AC or DC input power is insufficient or not present and a redundant power supply is functioning properly. The power supply module is installed, no input power present at both power supplies. 3

Fan Module Description Fan Module Description Table 4 Model number ME-FANTRAY Fan Module Model Number and Description Description Fan module The fan module provides cooling and proper airflow when only one power supply is installed. Both slots must be occupied either by two power supplies or a power supply and a fan module. Do not run the switch with an empty slot unless you are replacing a faulty power supply or fan module. Running the switch with an empty slot triggers an alarm. Each fan module contains three fans. The switch can operate safely if one fan fails. A fan failure triggers an alarm. When a fan fails, replace the fan module immediately. Figure 3 2 1 Fan Module Handle Side FAN 207448 3 1 Fan module 3 Extraction handle 2 Fan module status LED Table 5 Color Green Red Off FAN LED System Status All internal fans are OK. One or more internal fans have failed. The fan module is not installed, or power is not present. 4

Connector-Side Description Connector-Side Description Figure 4 shows the connector side of the power supply and fan module that connects to the switch rear panel through its power supply module slot. Figure 4 Power Supply Module Connector Side 1 1 1 207449 2 1 Fans 2 Connector pins Power Supply and Fan Module Installation Equipment That You Supply, page 5 Installation Guidelines, page 6 Installing an AC Power Supply Module, page 6 Installing a DC Power Supply Module, page 8 Installing a Fan Module, page 13 Equipment That You Supply You need a ratcheting screwdriver with a Phillips head that exerts up to 15 inch-pounds (in-lb) of torque. 5

Power Supply and Fan Module Installation Installation Guidelines When you install a fan or power supply module: Do not force the fan or power supply module into the slot. This can damage the pins on the switch if they are not aligned with the unit. A fan or power supply module that is only partially connected to the switch can disrupt the system operation. Verify that you are using the correct power cord. Note You can run both AC and DC power supplies on the same chassis. Do not reach into a vacant slot or chassis while you install or remove a module or a fan. Exposed circuitry could constitute an energy hazard. Statement 206 Only trained and qualified personnel should be allowed to install, replace, or service this equipment. Statement 1030 Do not work on the system or connect or disconnect cables during periods of lightning activity. Statement 1001 To prevent overheating and to maintain proper air flow, either a power supply module or a fan module must be installed in each power supply module slot at all times. Never operate the switch for extended periods of time without either a power supply module or a fan module installed in each power supply module slot. Installing an AC Power Supply Module This procedure is for installing an AC power supply module in the PSU 1 power supply module slot. Repeat these steps to install a power supply module in the PSU 2 power supply slot. To install an AC input power supply module, follow these steps: Step 1 Step 2 Verify that the power from the power source is off. Insert the new power supply module in the power supply module slot, and gently push it into the slot (see Figure 5). When correctly inserted, the power supply module is flush with the switch rear panel. 6

PSU OK Power Supply and Fan Module Installation Figure 5 Inserting an AC power supply Module in a Switch AC Step 3 Step 4 Step 5 Align the two captive screws with the screw holes in the panel. Use a ratcheting torque screwdriver to torque each screw to 10 in-lb. Connect the AC power cord to the power supply and to an AC power outlet. (Optional) Attach the power-cord retainer clip to the power supply and thread the plastic bushing until it is snug against the plug (Figure 6). Figure 6 AC Power Supply Module and Power-Cord Retainer in a Switch 278366 207478 Step 6 Step 7 Turn on the power at the power source and set the power supply switch ON. From the front of the switch, confirm that both the PS IN and the PS/FAN LEDs are green. If you can access the switch rear panel, verify that the PSU and INPUT LEDs are green. See Table 2 and Table 2 on page 3 for a description of the power supply module LEDs. Removing AC Power Supply Modules Step 1 Step 2 Step 3 Step 4 Turn off the power at its source and set the power supply switch to OFF. Detach the power-cord retainer and the plastic bushing from the power cord. Remove the power cord from the power connector. Use a Phillips screwdriver to loosen the two captive screws that secure the power supply module to the chassis. 7

Power Supply and Fan Module Installation Do not leave the power supply slot open for more than: - 5 minutes provided the ambient temperature is 25 C and at 5000 feet or lower elevation - 90 seconds in all other conditions. Step 5 Wait 5 minutes prior to reopening a power supply slot. Remove the power supply module from the power slot by pulling on the extraction handle. Installing a DC Power Supply Module This procedure is for installing an DC power supply module into the PSU 1 power supply slot. Repeat these steps to install a power supply module in the PSU 2 power supply slot. To connect the switch to a DC input power source, follow these steps: 1. Preparing for Installation, page 9 2. Grounding the Switch, page 9 3. Installing the DC Power Supply Module in the Switch, page 10 4. Wiring the DC Input Power Source, page 11 An exposed wire lead from a DC-input power source can conduct harmful levels of electricity. Be sure that no exposed portion of the DC-input power source wire extends from the terminal block plug. Statement 122 Before connecting or disconnecting ground or power wires to the chassis, ensure that power is removed from the DC circuit. To ensure that all power is OFF, locate the circuit breaker on the panel board that services the DC circuit, switch the circuit breaker to the OFF position, and tape the switch handle of the circuit breaker in the OFF position. Use a voltmeter to test for 0 (zero) voltage at the power terminals on the chassis. Statement 196 Installation of the equipment must comply with local and national electrical codes. Note We recommend that you use 14 or 16 AWG copper wiring for Network Equipment Building Systems (NEBS) installation, following the guidelines for DC power wiring in the central office. Note You can use the grounding lug to attach a wrist strap for ESD protection during servicing. 8

Power Supply and Fan Module Installation Preparing for Installation Grounding the Switch You need these tools and equipment: Ratcheting torque Phillips-head screwdriver that exerts up to 36 inch-pounds (in-lb). Crimping tool. Wire-stripping tools. Copper ground wire (6 AWG, insulated or noninsulated) for the ground connection. Two leads of 14 or 16 AWG copper wire. Follow the grounding procedure instructions and observe these warnings: This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain that suitable grounding is available. Statement 1024 When installing or replacing the unit, the ground connection must always be made first and disconnected last. Statement 1046 To make sure that the equipment is reliably connected to earth ground, follow the grounding procedure instructions, and use a UL-listed lug suitable for number-6 AWG wire and two number-10-32 ground-lug screws. Follow these steps to install a dual-ground lug on the switch. Make sure to follow any grounding requirements at your site. Step 1 Step 2 Step 3 Locate the dual-hole lug that ships with the switch. If your ground wire is insulated, use a wire stripping tool to strip the 6 AWG ground wire to 0.875 inch (12.7 mm) ± 0.02 inch (0.5 mm). Slide the open end of the ground lug over the exposed area of the wire. Step 4 Crimp the ground lug to the wire (see Figure 7). 9

Power Supply and Fan Module Installation Figure 7 Crimping the Ground Lug Step 5 Attach the dual-hole lug and the wire assembly to the chassis ground connection with the supplied screws (Figure 8). Figure 8 Attaching the Ground Lug and Wire Assembly 207475 280938 1 1 Dual-hole ground lug Step 6 Step 7 Use a ratcheting torque Phillips-head screwdriver to torque the ground-lug screws to 32 in-lb. Connect the other end of the grounding wire to an appropriate grounding point at your site or to the rack. Installing the DC Power Supply Module in the Switch Step 1 To ensure that power is removed from the DC circuits, locate the circuit breakers for the DC circuits, switch the circuit breakers to the OFF position, and tape the circuit-breaker switches in the OFF position. Step 2 Insert the new power supply module into the power supply slot, and gently push it into the slot (Figure 9). When correctly inserted, the power supply is flush with the switch rear panel. 10

PSU OK PSU OK Power Supply and Fan Module Installation Figure 9 Inserting a DC Power Supply Module AC AC 207479 Step 3 Step 4 Align the two captive screws with the screw holes. Use a ratcheting torque Phillips-head screwdriver to torque each screw to 10 in-lb. Connect the input power as described in the Wiring the DC Input Power Source section. Wiring the DC Input Power Source Before you wire the DC input power source, review these warnings and information: This product relies on the building s installation for short-circuit (overcurrent) protection. Ensure that the protective device is rated not greater than: 24VDC 30A 48VDC 15A Statement 1005 A readily accessible two-poled disconnect device must be incorporated in the fixed wiring. Statement 1022 Only trained and qualified personnel should be allowed to install, replace, or service this equipment. Statement 1030 The DC power supply voltage should be within 18 to 32 VDC or 36 to 72 VDC. If the supply voltage is not in this range, the switch might not operate properly or might be damaged. Step 1 Step 2 To ensure that all power is OFF, locate the circuit breaker that services the DC circuit, switch the circuit breaker to the OFF position, and tape the switch handle of the circuit breaker in the OFF position. Remove the terminal block cover. Note The terminal block is covered by a clear plastic block cover that snaps onto the terminal block. You must remove the block cover before you work with the wires. The block cover is slotted so that the wires can exit only one end. If you want the wires to exit in a different direction, remove the block cover, rotate it, and snap it back on. 11

Power Supply and Fan Module Installation Step 3 Step 4 Step 5 Using a wire-stripping tool, strip each of the wires coming from the DC input power source to 0.350 inch (8.9 mm) ± 0.02 inch (0.5 mm). Crimp the fork-type terminals to the 14 or 16 AWG DC power input wires. Connect the wires to the DC input power terminals as shown in Figure 10. Make sure to match the polarity (negative to negative, positive to positive) when connecting the wires to the terminal. Figure 10 Connecting the DC Input Power Terminals to the Terminal Blocks 1 2 207935 1 Negative 2 Positive Step 6 Use a ratcheting torque Phillips-head screwdriver to torque the terminal-block screw to 14 in-lb. Do not overtorque the terminal-block screws. The recommended maximum torque is 14 in-lb. Step 7 Step 8 Step 9 Step 10 Secure the wires coming from the terminal block so that they cannot be disturbed. For example, use tie wraps to secure the wires to the rack. After ensuring that all wire connections are secure, reinstall the terminal block cover. Remove the tape from the circuit-breaker switch handle, and move the circuit-breaker handle to ON. Move the DC power supply switch to ON. From the front of the switch, confirm that the PS IN and the PS/FAN LEDs are green. If you can access the switch rear panel, verify that the power supply module PSU and INPUT LEDs are green. See Table 2 and Table 3 on page 3 for a description of the power supply module LEDs. 12

Power Supply and Fan Module Installation Removing the DC Power Supply Module Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Move the DC power supply switch to OFF. Turn off power at the DC circuits. To ensure that power is removed from the DC circuits, locate the circuit breakers for the DC circuits, switch the circuit breakers to OFF, and tape the circuit-breaker switches. Remove the terminal block cover from the power supply terminal blocks. Use a Phillips screwdriver to remove the DC input power wires from the power terminals. Use a Phillips screwdriver to loosen the two captive screws that secure the power supply module to the switch chassis. Remove the power supply module from the power slot by pulling on the extraction handle. To prevent overheating and to maintain proper air flow, either a power supply module or a fan module must be installed in each power supply module slot at all times. Installing a Fan Module Step 1 Insert the new fan module in the power supply slot, and gently push it into the slot (Figure 11). When correctly inserted, the fan module is flush with the switch rear panel. Figure 11 Inserting a Fan Module in a Switch 207480 Step 2 Step 3 Align the two captive screws with the screw holes in the panel. Use a ratcheting torque screwdriver to torque each screw to 10 in-lb. From the front of the switch, confirm that the PS/FAN LED is green. If you can access the switch rear panel, verify that the FAN LED is green. See the Table 5 on page 4 for a description of the fan module LED. 13

Finding the Power Supply and Fan Module Serial Number Finding the Power Supply and Fan Module Serial Number If you contact Cisco Technical Assistance regarding a power supply or fan module, you need to know the serial number. See Figure 12 to find the serial number. Figure 12 Power Supply and Fan Module Serial Number Location 208327 SN: XXXNNNNXXXX 14

Technical Specifications Technical Specifications Table 6 Environmental and Physical Specifications for the AC and DC Input Power Supply and Fan Modules Environmental Ranges Operating temperature 40 to 122 F ( 40 to 50 C) Storage temperature 49 to 185 F ( 45 to 85 C) Relative humidity 5 to 95% (noncondensing) Altitude Up to 10,000 ft (3049 m) Physical Specifications Weight AC: 2.9 lb (1.32 kg) DC: 3.1 lb (1.41 kg) Fan: 1.65 lb (0.75 kg) Dimensions (H x W x D) 1.64 x 8.55 x 5.94 in. (4.16 x 21.72 x 15.09 cm) Table 7 Technical Specifications for the AC Power Supply Module Power Specifications Maximum output power Input voltage range and frequency Input current Maximum output ratings Total input BTU 390 W 100 to 240 VAC ± 10% (auto ranging), 50 to 60 Hz 5 to 2.5 A 12 V @ 32.5 A 1705 BTUs per hour Table 8 Technical Specifications for the DC Power Supply Module Power Specifications Maximum output power Input voltage range Input current Maximum output ratings Total input BTU 390 W 18 to 32 VDC and 36 to 72 VDC 30 A maximum at minimum input 18 VDC 15 A maximum at maximum input voltage 72 VDC 12 V @ 32.5 A 1840 BTUs per hour 15

Related Publications Related Publications These documents provide information about the switches and are available on Cisco.com: http://www.cisco.com/go/me3800x_docs Release Notes for the Cisco ME 3800X and ME 3600X Switch Note Before installing, configuring, or upgrading the switch, see the release notes on Cisco.com for the latest information. Cisco ME 3800X and ME 3600X Switch Hardware Installation Guide Cisco ME 3800X and ME 3600X Switch Getting Started Guide Regulatory Compliance and Safety Information for the Cisco ME 3800X and ME 3600X Switches Cisco ME 3800X and ME 3600X Switch Software Configuration Guide Cisco ME 3800X and ME 3600X Switch Command Reference Cisco ME 3800X and ME 3600X System Message Guide Cisco Small Form-Factor Pluggable Modules Installation Notes Cisco CWDM GBIC and CWDM SFP Installation Notes These compatibility matrix documents are available on Cisco.com: http://www.cisco.com/en/us/products/hw/modules/ps5455/products_device_support_tables_list.html Cisco Gigabit Ethernet Transceiver Modules Compatibility Matrix Cisco 100-Megabit Ethernet SFP Modules Compatibility Matrix Cisco CWDM SFP Transceiver Compatibility Matrix Cisco Small Form-Factor Pluggable Modules Compatibility Matrix Compatibility Matrix for 1000BASE-T Small Form-Factor Pluggable Modules Obtaining Documentation and Submitting a Service Request For information on obtaining documentation, submitting a service request, and gathering additional information, see the monthly What s New in Cisco Product Documentation, which also lists all new and revised Cisco technical documentation, at: http://www.cisco.com/en/us/docs/general/whatsnew/whatsnew.html Subscribe to the What s New in Cisco Product Documentation as a Really Simple Syndication (RSS) feed and set content to be delivered directly to your desktop using a reader application. The RSS feeds are a free service and Cisco currently supports RSS version 2.0. This document is to be used in conjunction with the documents listed in the Related Publications section. Cisco and the Cisco logo are trademarks or registered trademarks of Cisco and/or its affiliates in the U.S. and other countries. To view a list of Cisco trademarks, go to this URL: www.cisco.com/go/trademarks. Third-party trademarks mentioned are the property of their respective owners. The use of the word partner does not imply a partnership relationship between Cisco and any other company. (1110R) 2010 Cisco Systems, Inc. All rights reserved. 16