PSBOC PSBOC 27,6V/5,5A/OC

Similar documents
BNC08128C. BNC 13,8V/8x1A/17Ah. Switch mode buffer power supply unit for CCTV. v.1.0 EN** Edition: 3 from

POE084824B. PoE 54V/8x0,3A/4x7Ah PoE buffer power supply for up to 8 IP camera. v.1.1 EN* Edition: 7 from

Features: S98-B v1.0 S98-B 9-port switch with buffer power supply for 8 IP cameras

Features: DSB98 v1.0 DIN rail mounted switch 9-port DSB98 with buffer power supply for 8 IP cameras

Features: DSFB108 v1.1 DIN rail mounted switch 10-ports DSFB108 with buffer power supply for 8 IP cameras

Features: SF108-CR v1.1 SF108-CR 10-ports switch for 8 IP cameras in enclosure with recorder space

Features: DS54 v1.0 DIN rail mounted switch 5-port DS54 for 4 IP cameras without power supply

PSBEN 3012C. PSBEN 13,8V/3A/17Ah/EN Buffer, switched mode power supply unit.

Features: Example of use

PSBEN 10A12E. PSBEN 13,8V/10A/65Ah/EN Buffer, switch mode power supply unit Grade 3.

PSBEN 5012D/LCD. PSBEN 13,8V/5A/40Ah/EN/LCD Buffer, switched mode power supply unit.

EN54-7A17 v.1.1/iv EN54 27,6V/7A/2x17Ah power supply for fire alarm systems

v.1.1/iv EN54 27,6V/7A/2x40Ah power supply for fire alarm systems

v.1.1/vi PSBEN 27,6V/5A/2x17Ah/EN buffer, switched mode power supply unit Requirements of Grade 1 Grade 2 Grade 3

PSBEN 2012B/LCD. PSBEN 13,8V/2A/7Ah/EN/LCD Buffer, switched mode power supply unit.

EN** PSBEN 10A12D v.1.1/vii PSBEN 13,8V/10A/40Ah/EN buffer, switch mode power supply unit Grade 3. Requirements of. Grade 1 Grade 2 Grade 3

PSBEN 2012B/LCD v.1.0 PSBEN 13,8V/2A/7Ah/EN/LCD buffer, switched mode PSU. Requirements of. Grade 1 Grade 2 Grade 3

Interface RS485-TTL CODE: INTR. v.1.0 EN* Edition: 3 from

PSBEN 2012B v.1.1/vii PSBEN 13,8V/2A/7Ah/EN buffer, switch mode power supply unit Grade 3. Requirements of. Grade 1 Grade 2 Grade 3

v.1.1/vi PSBEN 27,6V/5A/2x17Ah/EN/LCD buffer, switched mode power supply unit Requirements of Grade 1 Grade 2 Grade 3

Interface WI-FI CODE: INTW. v.1.0. Edition: 2 from Supersedes the: 1 from edition

RТTH DUAL ROOM SWITCH

QUALITY POWER SOLUTIONS BACKED UP BY REAL-WORLD ENGINEERING EXPERIENCE

Buffered Power Supply PS-30DR v1.0

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions

ELV12 Series. Instruction Manual

Buffer power supply units. compliant with EN are intended to alarm system devices

CA-A480-A Elevator Controller. Reference & Installation Manual

DXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

Interface RS485-WiFi

V /06/ Velleman nv

Operating instructions. Switching amplifier DN0210 DN / / 2015

EN54-2A17. EN54 27,6V/2A/2x17Ah power supply for fire alarm systems

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

RXTH DUAL ROOM SENSOR / SWITCH

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

Installation Manual for D244X Series 24-volt Power Supplies

7032 Digital-Analog Multimeter

MCX402DR-BRD I/O expander. Operating Manual

CliQ II DC-UPS Module 24V 40A / DRU-24V40ABN

Conductive Level Controller

E2Q4 Square Proximity Sensor

Solid-state Timer H3FA. Model Number Structure. DIP Model Timer for PC Board Use Provides Contact and Solid-state Output

RXTP ROOM TEMPERATURE

2-Way Wireless I/O Expander Installation Guide

DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER

E2A. Ordering Information. Cylindrical Proximity Sensor. Safe Mounting with Greater Sensing Distance. E2A Cylindrical Proximity Sensor 1

Operating instructions. Speed monitor D / / 2014

ETHOS Auto Ranging Digital Multimeter

Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3

2 in 1 LAN Tester and Multimeter Model:

Thread length (overall length)

Rhino PSM Power Supplies. Operating Instructions

RTU500 series Data Sheet Power Supply CP-E 24/2.5

The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits.

Features. Regulated Converter. RAC35-G/OF 35 Watt 4 x 2 Open Frame RAC35- SG/OF. AC/DC Converter

VSD-1MC MANUAL 0-10V / 4-20mA Variable Speed Module with Manual Override

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

Ferrous metal (The sensing distance decreases with non-ferrous metal.) Power supply voltage (operating voltage range)

Redundancy unit CP-A RU

PRODUCT SPECIFICATION. PC Board Relays. Series.

Parameter Condition Min. Typ. Max. Internal Input Filter. nom. Vin = 230VDC 115VAC 230VAC 115VAC 230VAC. No load Power Consumption

Model HM-535 Power Supply Installation and Service Instructions

User Guide. Control Box. RoscoLED TM.

PMT. Model Number: CC Code PM 24V 200W 1 A Panel Mount Product Type T Enclosed L L Frame*

Mini Digital Multimeter

Ordering Information. I/O Relay G7T. Model Number Legend Slim-styled I/O Relay Saves Space in Panel

IEC/EN/UL60950 & CE certified, EN55032 Class B

Polymer Electric. Operating Instructions. Control Unit SG-RST 153. Version 0.3

is then retained absolutely without interruption.

Industriefunkuhren. Technical Manual. Signal Converter. for DIN Rail Mounting Series 4800xx-yy ENGLISH

80W (16V/5A) Power Supply with USB Output. User Manual

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Ordering Information. I/O Relay G7T. Model Number Legend Slim-styled I/O Relay Saves Space in Panel

MC 11 EB-2 Power supply cabinet with external bus, AC version

Mini Digital Multimeter

MVS RAIL ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

Model Number Structure

TSP-BCM48, TSP-BCM48A. Operating Instruction Manual. Page 1 of 13

Mini Digital Multimeter Model MN15. User's Guide

Operating Instructions Differential Pressure Transducer PS27

LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E

Parameter Condition Min. Typ. Max. Internal Input Filter 115VAC 230VAC 115VAC 230VAC. No load Power Consumption

S-14 S-14. Compact Digital Multimeter. Compact Digital Multimeter

Mini Digital Multimeter

User's Guide. MiniTec TM Series Model MN25 MultiMeter

Phase comparator. User manual Document version: 02i00 Update:

Safety Standards. Model Number: Unit Weight:

Flat. PIFN-C072B Flat 75W LED Driver. Features. Electrical Specifications. Input Specifications 1 / 8 18V - 23V / 2.00A - 3.

Series Specifications Ta= 25 C, nom. Vin, full load and after warm-up unless otherwise stated) Parameter Condition Min. Typ. Max.

iconverter 2-Module Power Chassis

PIM-Mini Pulsed Current Source Operation Manual

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

Thread length (overall length) material

D-Pack 6 Classic ORDERCODE 50315

Operating Instructions

VM-11 SERIES MODEL VM-11B ACCELERATION INPUT VIBRATION SIGNAL CONDITIONER INSTRUCTION MANUAL. MANUAL No E1.8. Revised in Mar.

Installation Sensing distance Connection Output configuration Operation mode NO Operation mode NC

Resolver to Digital Expansion Board

Transcription:

v.1.1 PSBOC 27,6V/5,5A/OC Enclosed buffer switch mode power supply unit with technical outputs. EN** Edition: 8 from 01.06.2016 Supercedes edition: 7 from 10.04.2015

Features: 27,6VDC/5,5A uninterrupted supply* wide range of supply voltage 176 264VAC high efficiency 84% battery charge and maintenance control deep discharge battery protection (UVP) battery charging current 0,5/2A, jumper selectable battery output protection against short circuit and reverse polarity connection LED indication EPS technical output indicating AC power loss OC and relay type PSU technical output indicating PSU failure OC and relay type LoB technical output indicating battery low OC and relay type voltage protections: SCP short-circuit protection OVP over voltage protection surge protection OLP overload protection warranty 2 year from the production date CONTENTS: 1. Technical description. 1.1 General description 1.2 Block diagram 1.3 Description of PSU components and connectors 1.4 Specifications 2. Installation. 2.1 Requirements 2.2 Installation procedure 3. Operating status indication. 3.1 LED indication of operating status 3.2 Technical outputs 4. Operation and use. 4.1 Overload or short circuit of the PSU output 4.2. Battery-assisted operation 4.3. Maintenance 1. Technical description. 1.1 General description A buffer PSU is intended for an uninterrupted supply to devices requiring stabilized voltage of 24V DC (+/- 15%). The PSU provides voltage of U=27,6V DC with current capacity: 1. Output current 5A + 0,5A battery charging* 2. Output current 3,5A + 2A battery charging* Total device current + battery: 5,5A max * In the case of power failure from prime supply, the unit is instantly switched to battery assisted operation. The power supply unit features: short circuit, overload, surge and over voltage protections. * See chart 1 2

1.2 Block diagram. (fig.1). Fig.1. Block diagram of the PSU. 1.3 Description of PSU components and connectors. Table 1. Elements of the PSU (see fig. 2). Element no. Description [1] LED indicating presence of AC power [2] LED indicating presence of DC power [3] LED indicating correct battery voltage [4] EPS - AC absence technical output relay type [5] PSU - output indicating DC absence/psu failure relay type [6] LoB - output indicating battery low voltage relay type [7] EPS - AC absence technical output OC type [8] PSU - output indicating DC absence/psu failure - OC type [9] LoB - output indicating battery low voltage - OC type [10] V ADJ - potentiometer, DC voltage adjustment [11] +V,-V- DC supply output [12] L-N 230V/AC power connector, PE protection connector [13] Battery connectors: +BAT =red, - BAT = black [14] LED indication on the front panel Battery charging current selection Ibat =0,5 A [15] Ibat =2 A Legend: dip switch installed dip switch removed 3

Fig. 2. The view of the PSU. 1.4 Specifications: - electrical specifications (tab.2) - mechanical specifications (tab.3) - operation safety (tab.4) - operating specifications (tab.5) Electrical specifications (tab. 2). Mains supply 176 264V AC Current consumption 1,4A@230VAC max. PSU power 155W max. Efficiency 84% Output voltage 22V 27,6V DC buffer operation 19V 27,6V DC battery-assisted operation Output current t AMB <30 C 5A + 0,5A battery charge see chart 1 3,5A + 2A battery charge see chart 1 Output current t AMB =40 C 3,3A + 0,5A battery charge - see chart 1 1,8A + 2A battery charge - see chart 1 Voltage adjustment range Ripple voltage Current consumption by PSU systems Battery charging current Short-circuit protection SCP Overload protection OLP Battery circuit protection SCP and reverse polarity connection Surge protection Surge over voltage protection OVP Deep discharge protection UVP Technical outputs: - EPS; output indicating AC power failure 24 28V DC 150 mv p-p max. 50 ma 0,5A/2A jumper selectable electronic, automatic recovery 105-150% of power supply, automatic recovery polymer fuse varistors >32V (automatic recovery) U<19V (± 5%) disconnection of the battery terminal - relay type: 1A@ 30VDC/50VAC - OC type, 50mA max., normal status: L (0V) level, failure: hi-z level - PSU; output indicating DC absence/psu failure - LoB; output indicating battery low voltage - relay type: 1A@ 30VDC/50VAC - OC type, 50mA max., normal status: L (0V) level, failure: hi-z level - relay type: 1A@ 30VDC/50VAC - OC type, 50mA max., normal status: (U BAT >23V): L (0V) level, failure: (U BAT <23V): hi-z level\ The power supply unit does not feature a battery detection function. 4

Temperature characteristics. Chart 1. Acceptable output current from the PSU depending on ambient temperature. Mechanical specifications (tab. 3). Enclosure dimensions 199 x 110 x 50 +23 [mm] (LxWxH) (+/- 2) Net/gross weight 0,89kg / 0,94kg Connectors power supply, technical outputs: Φ0,63 2,5 I/O PCB: Φ0,41 1,63 BAT battery outputs: 6,3F-2,5/40cm, Led indication output: 3-pin 5 mm Operation safety (tab.4). Protection class PN-EN 60950-1:2007 I (first) Degree of Protection PN-EN 60529: 2002 (U) IP20 Electrical strength of insulation: - between PSU input circuit and output circuits (I/P-O/P) 3000 V/AC min. - between input circuit and PE protection circuit (I/P-FG) 1500 V/AC min. - between output circuit and PE protection circuit (O/P-FG) 500 V/AC min. Insulation resistance: - between input circuit and output or protection circuit 100 MΩ, 500V/DC Operating specifications (tab.5). Operating temperature Storage temperature Relative humidity Vibrations during operation Impulse waves during operation Direct insolation Vibrations and impulse waves during transport -10ºC...+40ºC -20ºC...+60ºC 20%...90%, without condensation unacceptable unacceptable unacceptable PN-83/T-42106 2. Installation. 2.1 Requirements The buffer PSU is to be mounted by a qualified installer, holding relevant permits and licenses (applicable and required for a given country) for 230V/AC interference and low-voltage installations. The unit should be mounted in confined spaces, in accordance with the 2nd environmental class, with normal relative humidity (RH=90% maximum, without condensation) and temperature from -10 C to +40 C. The device shall be mounted in a metallic enclosure (a cabinet, an intended case). In order to fulfil LVD and EMC requirements, the rules for: power-supply, encasing and screening shall be followed, according to application. The PSU provides voltage of U=27,6V DC with current capacity: 1. Output current 5A + 0,5A battery charging* 2. Output current 3,5A + 2A battery charging* Total device current + battery: 5,5A max *. * See chart 1 5

2.2. Installation procedure. 1. Before installation of the power supply unit, make sure that 230VAC power if cut off. 2. Mount the unit in the intended location. 3. Connect the 230VAC power cables. Connect the PE cable (yellow-green) to an appropriate PSU terminal (marked with - earth symbol). The shock protection circuit shall be performed with a particular care, i.e. the yellow and green wire coat of the power cable shall stick to one side of the PE terminal. Using the PSU without a properly made and fully operational shock protection circuit is UNACCEPTABLE! It can cause a device failure or an electric shock. 4. Connect load/loads to proper output connectors of the power supply (positive pole is marked as +V, negative pole as -V) 5. Connect the technical outputs to the central or other device. 6. Connect the battery in accordance with the signs (colours). 7. Once the tests and operation control have been completed, the enclosure/cabinet can be locked. 3. Operating status indication. Fig 3. Mechanical view of the PSU. 3.1 LED indication The PSU is equipped with 3 LEDs on the PCB board: - red LED (Fig.2, element 1) normal status (AC power): permanently illuminated. AC power absence is indicated by the AC diode going out. - green LED (Fig.2, element 2) indicates DC power at the PSU output. Under normal status the diode is permanently illuminated. In case of a short circuit or an overload, the diode is off. - green LED (Fig.2, element 3) indicates battery voltage level. Under normal status (U BAT > 23V) the diode is permanently illuminated. In case of decrease of battery voltage (U BAT < 23V) the diode is off. 6

3.2 Technical outputs The PSU has indication outputs: EPS - absence of AC supply output: - OC type output that indicates AC power loss. Under normal status, with 230V AC supply, the output is connected to ground (L level 0V). In case of power loss, the PSU will switch the output into high impedance. - relay output indicating the absence of AC supply. In case of power loss, the PSU module will switch the relay contacts. CAUTION! In Fig.2. the contact set in the potential-free status corresponds to a state with no AC power (AC power failure). PSU technical output indicating absence of DC voltage at the PSU: - OC type output indicating the PSU failure. In normal state (during correct operation) the output is connected to ground (L level 0V). In case of absence of DC voltage at the output (e.g. short circuit), the output is switched into high impedance state hi-z. - relay output. In case of a failure, the contacts of the relay change over. CAUTION! In the Fig.2. the set of contacts shows a potential-free status of the relay which corresponds to a state with no DC power (PSU failure). LoB technical output indicating battery voltage: - OC type output. Under normal status (U BAT > 23V) the output is connected to ground (L level 0V). In case of decrease of battery voltage (U BAT < 23V) the output is switched into high impedance state hi-z. - relay output. In case of a battery voltage drop U BAT < 23V, the contacts of the relay change over. The power supply unit does not feature a battery detection function. In the case of no battery or non battery connected, the output is in the normal mode. CAUTION! In the Fig.2. the set of contacts shows a potential-free status of the relay which corresponds to a state with low battery level (U BAT <23V). 4. Operation and use. Fig. 4. Electrical diagram of OC outputs. 4.1 Overload or short circuit of the PSU module output In case of an overload or a short circuit at the PSU output, the output voltage is automatically cut off. The voltage is restored automatically after removing the failure (overload). 4.2 Battery-assisted operation. In case of a main power outage, the device is immediately switched into a battery-assisted operation. The PSU is equipped with the discharged battery disconnection system. During the battery-assisted operation, reducing voltage below 19V at the battery terminals will cause battery disconnection. 4.3 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network. The PSU does not require performing any specific maintenance measures. However, in case of significant dust ingress, it is recommended to clean the PSU with compressed air. 7

WEEE MARK According to the EU WEE Directive It is required not to dispose of electric or electronic waste as unsorted municipal waste and to collect such WEEE separately. The power supply unit is adapted for a sealed lead-acid battery (SLA). After the operation period it must not be disposed of but recycled according to the applicable law. GENERAL WARRANTY CONDITIONS 1. Pulsar (the manufacturer) grants a two-year warranty for the equipment, counted from the device s production date. 2. The warranty includes free-of-charge repair or replacement with an appropriate equivalent (the selection is at the manufacturer s discretion) if the malfunction is due to the manufacturer, includes manufacturing or material defects, unless such defects have been reported within the warranty period (item 1). 3. The equipment subject to warranty is to be brought to the place where it was purchased, or directly to the main office of the manufacturer. 4. The warranty applies to complete equipment, accompanied by a properly filled warranty claim with a description of the defect. 5. Should the claim be accepted, the manufacturer is obliged to provide warranty repairs, at the earliest convenienve, however not later that within 14 days from the delivery to the service centre of the manufacturer. 6. The repair period mentioned in item 5 may be prolonged, if there are no technical possibilities to carry out the repairs, or if the equipment has been conditionally accepted, due to the breaking warranty terms by the claimant. 7. All the services rendered by force of the warranty are carried out at the service centre of the manufacturer, exclusively. 8. The warranty does not cover the defects of the equipment, resulting from: - reasons beyond the manufacturer's control, - mechanical damage, - improper storage and transport, - use that violates the operation manual or equipment s intended use - fortuitous events, including lightning discharges, power failures, fire, flood, high temperatures and chemical agents, - improper installation and configuration (in defiance with the manual), 9. The warranty is void in any of the following circumstances: - construction changes - repairs carried out by any unauthorized service center - damage or removal of warranty labels - modifications of the serial number 10. The liability of the manufacturer towards the buyer is limited to the value of the equipment, determined according to the wholesale prices suggested by the manufacturer on the day of purchase. 11. The manufacturer takes no reponsibility for the defects that result from: - the damaging, malfunctioning or inability to operate the equipment - defects that result from using the equipment outside its stated specifications and operating parameters failing to abide by the recommendations and requirements contained in the manual, or the use of the equipment. Pulsar Siedlec 150, 32-744 Łapczyca, Poland Tel. (+48) 14-610-19-40, Fax. (+48) 14-610-19-50 e-mail: biuro@pulsar.pl, sales@pulsar.pl http:// www.pulsar.pl, www.zasilacze.pl 8