DDC110-L1.. DDC110-L4 technolon Room Module

Similar documents
BMF400 Input/output module

RCW11x-L Room Controller Technolon. Application. Product Description. RCW11x-L Room Controller Technolon

Contents Notice about the device description...page 2. Device description

RCN132-L, RCN132-L-S1 technolon Room Controller

RCN200-L Room Controller

RCN122-L technolon Room Controller. Application. RCN122-L technolon Room Controller. Product Description

RBW301-C, RBW302-C, RBW304-C, RBW305-C Room Control Module

DDC110S Room Control Modul With LCD Display

TD11..15, TDF Room Temperature Sensors

HT12, HTF12 Room humidity/temperature sensor

RCC200-L Room Controller

Actuating drive with spring return DSFY/16 Modulated actuating drive with spring return

Technical Datasheet clima RCM-CC

RCN155-L, RCN151-L Room controller

TLD1..TLD4 Duct Temperature Sensors

Technical Datasheet clima RCM-FC 1. Product description

FBM034 and FBM034W Fieldbus Input Modules

BCU070-L technolon Switch Interface. Application. BCU070-L technolon Switch Interface. Product description

Installation Instructions

RCN420-B Room controller

FBM018 and FBM018W Fieldbus Input Modules

BMD4032 Input/output module

TM-2100 Series Room Command Module

FBU410 Input/ Output Modulel

Electronic Temperature Controller. Instruction Manual Version

Master room unit for RRV controllers

Product and Application Description

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

TM-2100 Series Room Command Module

IB IL 120 DI 1. Function. INTERBUS Inline Terminal With One Digital Input in the 120 V AC Voltage Area. Data Sheet 5764B

Operating instructions. Standstill monitor A / / 2011

Operating instructions for AX5801. TwinSAFE drive option card for the AX5000 servo drive. Version: Date:

TPC35 Display and operator panel

InnoMedia Business VoIP ATA Models

Analog display for resistance current

QUINT-BUFFER/24DC/24DC/40

TPC84 Display and Operator Panel

CPCI System Subrack 1 U

Temperature controller Ducted systems

Room unit with PPS2 interface

English. Operating manual. Universal transmitter UT125. Save for later reference. Companies / brands of GHM

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

TPC56 Display and operator panel

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

PNOZ m ES RS232. Configurable Control System PNOZmulti. Operating Manual EN-01

Important Information Regarding Product Safety...2 Item...3 Technical Data...3 Dimensions...4 Connection...4 Mounting...5 Maintenance...

3/4 U CPCI Serial Case System

UC102 basic version with display and knob UC102BL version with display, knob and backlight UC102DK version without knob and display

Installation, Start-up and Operating Instructions

TPC70Display and Operator Panel

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

GLT-M002-GLTM GLT-M002-GLTM. Product Description

CU port USB 2.0 hub. Version: 1.1 Date:

Operating Instructions VEGAMET 381

Device technology. Supply Bus voltage V DC. Current consumption via bus. Accuracy in the range 300 1,000 ppm 1,000 2,000 ppm 2,000 5,000 ppm

Field module for cold locations for installation in refrigerators for direct control of a pulsed expansion valve

OEM. Room unit QAA822 with2- wire interface. Building Technologies CLIMATIX TM. For use with Climatix controllers

Operating instructions. Speed monitor D / / 2014

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

PHOENIX CONTACT - 05/2007

Operation Manual. Capacitor Boxes adjustable 80 A / 125 A Track, 2,04 μf to 8 μf. Order Number

Documentation KM2042. Sixteen channel digital output module with D-Sub Connector. Version: Date:

CPCI System Subrack 3 U

Operating instructions. Switching amplifier DN0210 DN / / 2015

NEUROLOGIC RESEARCH CORPORATION MODEL 2500

PHOENIX CONTACT - 07/2006

Operating Instructions

HERZ Actuator 7708, 7990

CMC III Universal Sensor

Smart Equipment Controls (SEC)

Air Quality Sensor KNX AQS

Assembly and operating instructions DULCOMARIN II, N-Module (Power Supply Module without Relay) DXMaN

Documentation ZB8610. Fan cartridge for EtherCAT and Bus Terminals. Version: Date:

UCU Room Display. Operation Modes. Features. Applications DATASHEET

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

RCF-230CAD. Room controller with communication for fancoil applications with two analogue V DC outputs

Room unit with PPS2 interface

Rhino Redundancy Module PSM24-REM360S. Operating Instructions

252F 5WG FB_1 DELTA

Universal Controller

Products no longer available

KNX T-UP. Temperature Sensor. Technical specifications and installation instructions

3+1 U CPCI Serial System

Room Temperature Controller

Type 6150 AS-Interface Module. Type 3372 Electropneumatic Actuator with AS-interface module. Mounting and Operating Instructions EB 6150 EN

Operating instructions Evaluation system for flow sensors VS / / 2013

Pre-programmed room controller with display and communication

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W

B63/ NS MS. EtherNet/IP LINK

SBM52/04 Input / Output Module For M-Bus with 99 counters

FBS51/04 Gateway-Module For M-Bus with 6 counters

LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual

CU USB-Extender-Rx (USB and DVI Extender) Version: 0.3 Date:

Room controller STRA-17

Product and functional description

EY-RU 355: Room operating unit, ecounit355

RCF-230CD. Communicating room thermostat for fan-coil applications with on/off outputs

Installation Manual RB-RWS20-E. Lite-Vision plus Remote Controller. Model name: English

Documentation. KM2604 and KM2614. Four channel relay module. Version: Date:

NOTE Hinweis: Note the special features of firmware updates provided by EPROM-Tausch (see page 4).

Transcription:

technolon Room Module DDC110-L1, DDC110-L2, DDC110-L3 and DDC110-L4 Single room control or room display and service module for single-room control in the LON network. With display of the room temperature and manual adjustment of the room setpoint. The DDC110-L2 technolon Room Module has an additional user button for switching 3 ventilator speeds and temperature types The DDC110-L3 technolon Room Module additionally has another user button for switching day /night or standby operation and temperature type The DDC110-L4 technolon Room Module, like DDC110-L3, additionally also has a user button for switching 3 ventilator speeds With an I/O component (accessory), message inputs and servo devices for heating and cooling as well as 3-level fan control can be directly connected to a technolon Room Module. Contents subject to change Contents Notes on the device description Page 2 Safety Instructions Page 2 Qualified specialists Page 2 Application Page 3 Types Page 3 Technical data Page 3 Operating Page 4 Assembly Page 10 Installation Page 12 Initial operation Page 12 Issue date: 05/27/2005 Kieback & Peter GmbH & Co KG Tempelhofer Weg 50, D-12347 Berlin Telephone +49 (0) 30 / 600 95-0 Telefax +49 (0) 30 / 600 95 164 E-Mail: info@kieback-peter.de http://www.kieback-peter.de

Notes on the device description The description contains references for the deployment and assembly of the technolon Room Module. In case of questions which cannot be clarified with this device description, please refer to the supplier or manufacturer for further information. The indicated installation instructions/regulations are valid in the Federal Republic of Germany. When using the I/O components in other countries, the builder or operator of the plant is responsible for compliance with the respective national regulations. The operating staff is to be instructed in accordance with the description of the technical data sheet. Safety Instructions The currently valid worker s occupational health regulations and regulations for the prevention of industrial accidents must be observed when assembling and using the devices. Any work concerning the installation or initial operation of the control devices shall be exclusively carried out by qualified specialists, see section Qualified specialists. Every person using the devices shall have read and understood the descriptions in the technical data sheet. Meaning of the symbols in the technical data sheet: Danger Warning of dangerous electrical voltage Warning General warning, strictly observe this notice Note Danger Warning Note Further notice to observe means mortal danger, severe bodily injuries or serious material damage in case of non-observance. means danger of bodily injuries or material damage in case of non-observance. indicates information which is particularly emphasized. Qualified specialists Qualified specialists for the purposes set out in this technical data sheet are persons who are familiar with the described devices and possess a qualification for their respective occupation. These are for instance: Authorization to connect the devices according to the VDE rules and local Electricity Board regulations, as well as the authorization to switch the devices on and off taking the in-house regulations into account. Knowledge of the regulations for the prevention of industrial accidents. Knowledge of the utilization of the devices within the plant system. etc. Page 2 / 12

Application The technolon Room Modules DDC110-L1, DDC110-L2, DDC110-L3 and DDC110-L4 are employed in the singleroom control of the LON network as Single Room Control or as room displays and service modules. An I/O component UP can be connected at the Room Module as an accessory. The I/O component provides the direct connection of a presence detector and a window contact or dew-point detector, the direct connection of the heating and cooling circuit as well as the activation of 3-level ventilators. The I/O component is installed in a double flushmounted box. DDC110-L1 DDC110-L2 Types DDC110-L1 technolon Room Module with display of the room temperature and manual adjustment of the room setpoint. DDC110-L2 technolon Room Module with display of the room temperature and manual adjustment of the room setpoint as well as switching of three ventilator speeds. DDC110-L3 DDC110-L4 DDC110-L3 technolon Room Module with display of the room temperature and manual adjustment of the room setpoint as well as switchover to day /night or standby operation DDC110-L4 technolon Raummodul with display of the room temperature and manual adjustment of the room setpoint as well as switchover to day /night or standby operation Accessories I/O componenets UP1 UP2 UP3 UP4 2 Digital inputs for the connection of the window contact/dew-point detector and presence detector 2 Thyristor switching outputs 24 V AC, 1 A (1 x heating, 1 x cooling) like UP1, however additionally 3 Relay outputs 250 V AC, 6 A (3-level fan control) 2 Digital inputs for the connection of the window contact/dew-point detector and presence detector 2 analog outputs 0..10 V DC, 10 ma (1 x heating, 1 x cooling) like UP1, however additionally 3 Relay outputs 250 V AC, 6 A (3-level fan control) Page 3 / 12

Technical data Room Module DDC110-L1 to DDC110-L4 Mains 24 V AC/DC ± 10 %, 10 ma (without I/O component UP) Bus connection - LON FTT10 Application: According to LONMARK standard: LONMARK profile #8060 for single room control or LONMARK profile #8090 for room display and service module - Bus for I/O component UP on plug contact Measured variable Room temperature in residential and office space Measuring system integrated digital room sensor Measuring range 0..45 C Connection Terminal connection, max, 2.5 mm2 Display LCD display - Rough measured value 0..45.0 C, resolution 0.1 K - Room setpoint 0..45.0 C, resolution 0.1 K - Display icon for operating modes Control buttons DDC110-L1 Key, control setting of the room temperature DDC110-L2 Key, switchover to temperature type for setting the room setpoint Key, switchover to ventilator modules for manual switching of the ventilator speeds Key, setting the room setpoint or manual switching of the ventilator speeds backlighting of the keys depending on the configuration: Steady burning light, on for 5 sec after keystroke, or backlighting off DDC110-L3 Key, switchover to day operation Key, switchover to night or standby operation Key, switchover to temperature type for setting the room setpoint Housing Ambient conditions Degree of enclosure protection Dimensions Assembly Weight DDC110-L4 Backlighting of the keys depending on the configuration: Steady burning light, on for 5 sec after keystroke or backlighting off Key, switchover to day operation Key, switchover to night or standby operation Key, switchover to temperature type for setting the room setpoint Key, switchover to ventilator modules for manual switching of the ventilator speeds Key, switchover to ventilator modules for manual switching of the ventilator speeds Key, setting the room setpoint or manual switching of the ventilator speeds Backlighting of the keys depending on the configuration: Steady burning light, on for 5 sec after keystroke or backlighting off Hood, color RAL9010 (pure white) Special colors upon request Temperature 0..45 C, Humidity not condensing IP30 Width x height x depth: 82.5 x 82.5 x 30 mm Wall mounted/assembly in flush-mounted box 110 g Page 4 / 12

Operation DDC110-L1 Display depending on the configuration: Room temperature (actual value) with function symbol or Room setpoint with function symbol Other function symbols can be displayed depending on the configuration: Digital readout Day operation Night operation Standby operation Automatic switchover by Central Program or presence detector Room setpoint selection The room setpoint for day, night or standby operation is automatically determined by the program. Depending on the configuration release, the room setpoint can be raised or lowered by ± 3 K or ± 5 K by manual adjustment. The manual adjustment acts as setpoint correction for all operating modes alike: Example: If the current room setpoint day is raised by 2 K, then the room setpoint night and the room setpoint standby are raised by 2 K. Key Press once : The Room Module switches to temperature type control setting. or or are displayed, Simultaneously, the decimal place of the current control setting blinks. Now the room setpoint can be increased or lowered with the key in steps of 0.1 K. Without pressing a key, the Room Module switches back to the standard after 5 sec display. The new room setpoint is stored. Page 5 / 12

Operation DDC110-L2 Display depending on the configuration: Room temperature (actual value) with function symbol or Room setpoint with function symbol Other function symbols can be displayed depending on the configuration: Digital readout Day operation Night operation Standby operation Automatic switchover by Central Program or presence detector Room setpoint selection The room setpoint for day, night or standby operation is automatically determined by the program. Depending on the configuration release, the room setpoint can be raised or lowered by ± 3 K or ± 5 K by manual adjustment. The manual adjustment acts as setpoint correction for all operating modes alike: Example: If the current room setpoint day is raised by 2 K, then the room setpoint night and the room setpoint standby are raised by 2 K. Key Press once : The Room Module switches to temperature type control setting. or or are displayed, Simultaneously, the decimal place of the current control setting blinks. Now the room setpoint can be increased or lowered with the key in steps of 0.1 K. With the key, it is immediately possible to switch back to the standard display. Without pressing a key, the Room Module switches back to the standard after 5 sec display. The new room setpoint is stored. Switching ventilator speeds on and off The ventilator speeds are automatically switched on and off by the program. If required, the ventilator speeds can be switched by manual control. Key and the Room Module switches to ventilator mode for manual control. is displayed, Simultaneously, the current ventilator setting blinks 0, 1, 2, 3 or auto. 0 Ventilator off, No function symbol 1 Ventilator level 1 on 2 Ventilator level 2 on 3 Ventilator level 3 on Auto Automatic operation: lights up in seconds beat The new ventilator level is set with the key. With the key, it is immediately possible to switch back to the standard display. Without pressing a key, the Room Module switches back to the standard after 5 sec display. The new room setpoint is stored. Page 6 / 12

Operation DDC110-L3 Display depending on the configuration: Room temperature (actual value) with function symbol or Room setpoint with function symbol Other function symbols can be displayed depending on the configuration: Digital readout Day operation Night operation Standby operation Automatic switchover by Central Program or presence detector Room setpoint selection The room setpoint for day, night or standby operation is automatically determined by the program. Depending on the configuration release, the room setpoint can be raised or lowered by ± 3 K or ± 5 K by manual adjustment. The manual adjustment acts as setpoint correction for all operating modes alike: Example: If the current room setpoint day is raised by 2 K, then the room setpoint night and the room setpoint standby are raised by 2 K. Key Press once : The Room Module switches to temperature type control setting. or or are displayed, Simultaneously, the decimal place of the current control setting blinks. Now the room setpoint can be increased or lowered with the key in steps of 0.1 K. Without pressing a key, the Room Module switches back to the standard after 5 sec display. The new room setpoint is stored. Switch on day or standby operation The night or standby operation is automatically switched on or off by the Central Program. The day operation is switched on by the presence detector or manually with the key. Switch on day operation The day operation can only be switched on manually in the operation mode night or standby. For the manual switching of night to day operation, the day operation is switched on only for a time period determined by the program. After expiration of this time, the Room Module switches back to night operation. Switch on day operation Standby operation Press key, function symbol is displayed. When switching over from night to day operation, the time period for switched on day operation is displayed for 5 sec. The standby operation can be switched on by a presence detector or manually only in the daytime operation mode, e.g. upon vacating the room. Standby operation Press key, function symbol is displayed. The key switches off the standby operation again. Page 7 / 12

Operation DDC110-L4 Display depending on the configuration: Room temperature (actual value) with function symbol or Room setpoint with function symbol Other function symbols can be displayed depending on the configuration: Digital readout Day operation Night operation Standby operation Automatic switchover by Central Program or presence detector Room setpoint selection The room setpoint for day, night or standby operation is automatically determined by the program. Depending on the configuration release, the room setpoint can be raised or lowered by ± 3 K or ± 5 K by manual adjustment. The manual adjustment acts as setpoint correction for all operating modes alike: Example: If the current room setpoint day is raised by 2 K, then the room setpoint night and the room setpoint standby are raised by 2 K. Key Press once : The Room Module switches to temperature type control setting. or or are displayed, Simultaneously, the decimal place of the current control setting blinks. Now the room setpoint can be increased or lowered with the key in steps of 0.1 K. With the key, it is immediately possible to switch back to the standard display. Without pressing a key, the Room Module switches back to the standard after 5 sec display. The new room setpoint is stored. Switch on day or standby operation The night or standby operation is automatically switched on or off by the Central Program. The day operation is switched on by the presence detector or manually with the key. Switch on day operation The day operation can only be switched on manually in the operation mode night or standby. For the manual switching of night to day operation, the day operation is switched on only for a time period determined by the program. After expiration of this time, the Room Module switches back to night operation. Switch on day operation Standby operation Press key, function symbol is displayed. When switching over from night to day operation, the time period for switched on day operation is displayed for 5 sec. The standby operation can be switched on by a presence detector or manually only in the daytime operation mode, e.g. upon vacating the room. Standby operation Press key, function symbol is displayed. The key switches off the standby operation again. Page 8 / 12

Switching ventilator speeds on and off The ventilator speeds are automatically switched on and off by the program. If required, the ventilator speeds can be switched by manual control. Key and the Room Module switches to ventilator mode for manual control. is displayed, Simultaneously, the current ventilator setting blinks 0, 1, 2, 3 or auto. 0 Ventilator off, No function symbol 1 Ventilator level 1 on 2 Ventilator level 2 on 3 Ventilator level 3 on Auto Automatic operation: lights up in seconds beat The new ventilator level is set with the key. With the key, it is immediately possible to switch back to the standard display. Without pressing a key, the Room Module switches back to the standard after 5 sec display. The new room setpoint is stored. Page 9 / 12

Assembly Warning The assembly may only be carried out by qualified personnel on voltage-fee switched connecting leads. The Room Module can be mounted in the wall or in a flush-mounted box. For rapid and correct measurement of the room temperature, the Room Module is to be assembled in such a way that the airflow of the room is included. Airflow 1, 5 m correct false Assembly Page 10 / 12

3 Attach hood and tighten securing screw For surface-mounted or flush-mounted wiring, the hood and base have labelled housing parts that can be broken out depending on the cable leads. Note Furthermore, pluggable hood inserts are a part of the delivery which can be exchanged for the standard inserts : C1 C1/D1 Inserts without air vents for greater wall influence. D2 Inserts for cable inlet from below. D1 D2 The device protection type IP30 is only guaranteed when the air gap at the cable inlet is 2.5 millimeters. In the building phase, the carton box serves as protective cover. Please tear off the box top and depress side straps to the inside. Page 11 / 12

Installation Warning The electrical installation and the Room Module connection may only be carried out by qualified personnel. This must be done in accordance with the VDE regulations and local specifications. Connection DDC110-L.. 1 20 19 18 LON-Bus A B 24 V AC/DC 0 V AC/DC Mains The bus connection lines Clamps 1/20 are mutually exchangeable. Warning: Supply voltage 230 V for use of I/O components UP2 or UP4! Note without fail the technical device manual in the Technical Data Sheet 1.10-51.110-91! Danger The I/O component UP with inputs and outputs can be connected at the Room Module. Room Module and I/O component form a device unit. The I/O component is employed in a double flush-mounted box with a depth of at least 60 millimeters, the Room Module is mounted on the flush-mounted box. The connection between the Room Module and the I/O component UP is carried out on the 5-line bus line of the I/O component which is connected with a socket plug on the Room Module. Initial operation Warning! Warning: Supply voltage 230 V for use of I/O components UP2 or UP4! Initial startup by switching on the supply voltage may only take place after the configuration setting and connection testing of the Room Module by the startup technician/engineer. Danger Before mains network has been switched on, check the electric wiring acc. to VDE (Association of German electrotechnicians) regulations and the local regulations, te correct mounting location for recording the room temperature, the competent assembly as well as the permissible ambient conditions according to the technical data. The Room Module is configured as a single room control or as display and service module with the parameter settingson a network management tool (e.g. LonMaker) with the service PC. After the network is switched on, check the total function of the Room Module (if necessary. including I/O component UP) with the plant components of the room control loop. Page 12 / 12