Increasing Data Center Efficiency by Using Improved High Density Power Distribution

Similar documents
Rack Powering Options for High Density

A Scalable, Reconfigurable, and Efficient High Density Data Center Power Distribution Architecture

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

Watts and Volt-Amps: Powerful Confusion

Rack Powering Options for High Density

The Different Types of UPS Systems

Improving Rack Cooling Performance Using Blanking Panels

Reliability Models for Electric Power Systems

> Executive summary. Implementing Energy Efficient Data Centers. White Paper 114 Revision 1. Contents. by Neil Rasmussen

Server Technology Inc.

The Different Types of AC Power Connectors in North America

Effect of UPS on System Availability

Rack Power Distribution. Rack power distribution offerings for entry-level networking equipment and high-density server and blade environments

Energy efficiency within data centers Is your IT organization capitalizing on the latest technology options and best practices?

APC APPLICATION NOTE #74

HP Power Calculator Utility: a tool for estimating power requirements for HP ProLiant rack-mounted systems

Cooling Strategies for Ultra-High Density Racks and Blade Servers

Calculating Total Power Requirements for Data Centers

QuickSpecs. HPE Standard Series G2 Basic Power Distribution Units (PDU) Overview. Basic, reliable power distribution for your HPE IT solutions

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Pros and Cons of Various DC Distribution Architectures

Two-Stage Power Distribution: An Essential Strategy to Future Proof the Data Center

QuickSpecs. HP Basic Power Distribution Units (bpdu) Overview

Deploying High Power to IT Equipment Racks

QuickSpecs. HPE Standard Series G2 Basic Power Distribution Units (PDU) Overview. Basic, reliable power distribution for your HPE IT solutions

Power and Cooling for Ultra-High Density Racks and Blade Servers

E f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; V D C p o w e r f e e d s o l u t i o n

Avoiding Costs From Oversizing Datacenter Infrastructure

Deploying High Power to IT Equipment Racks

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

HP Uninterruptible Power Supplies Overview

84 kw, Tier 3, Direct Expansion, 937 ft 2

Powering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM

QuickSpecs. HPE Basic Power Distribution Units (PDU) Overview

Liebert MPX Rack Power Distribution Unit (PDU) Guide Specifications 1.0 GENERAL 1.1 SUMMARY

CAN YOUR PDU PIVOT? TRUE INNOVATION. ONLY FROM SERVER TECH. Available in Basic, Metered, and Smart PDU models.

CS-10H0A413H3 (Master) Key Features. CL-10H0A413H3 (Link)

CPS VS UPS FOR POWERING DATA CENTERS

Best Practices Guide. EMC VMAX3 Family. Best Practices Guide for AC Power Connections REVISION 2.0. August, 2015

Highly Efficient Power Protection for High Density Computing Applications

Systems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development

CS-12HDE444C8 (Master) Key Features. CL-12HDE444C8 (Link)

Mission Critical Power Review

Metered Rack PDU Rack PDU, Metered, Zero U, 5.7kW,208V,(36)C13& (6)C19; 10' Cord

Server Technology, Inc.

Tel: AC Power for Business-Critical Continuity TM

The Different Types of UPS Systems

E-Series Site Preparation Guide

Metered Rack PDU Rack PDU, Metered, Zero U,12.5kW,208V,(30)C13, (6)C19; 10' Cord

APC by Schneider Electric Solutions for Cisco Unified Computing System (UCS) Blade Applications

PRODUCT & SYSTEM OFFERINGS

Power distribution solutions for the ProLiant DL580 G2 server

Retired. Full Rack Vertical PDU Model (Ideal for 36U to 47U racks)

Powering HP BladeSystem c7000 Enclosures

Configurable power distribution

3331 Quantifying the value proposition of blade systems

Table 1 shows all the different variations of output modules available.

Metered Rack PDU Rack PDU, Metered, Zero U, 20A, 120V, (24) NEMA 5-20R

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

Applications Electronic Design/Development Battery Charging Launch Control Rackmount ATE Systems. DLM 600 Near Linear 600W DC Power Supply

Technical Specifications

PDI Modular Compact Remote Power Panel

IBM eserver System x and BladeCenter IBM DPI PDU+ Power Distribution Units. 10/9/ IBM Corporation

Symmetra PX. Symmetra PX 48kW Scalable from 16kW to 48kW. Modular, Scalable, High-Efficiency Power Protection for Data Centers

1008 kw, Tier 2, Chilled Water, ft 2

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

Modular Systems: The Evolution of Reliability

The Basics of Selecting Rack-Mount Power Distribution Units (PDUs) and Power Strips

CS-24VD-L30MA (Master) Key Features. CL-24VD-L30MA (Link)

Liebert Precision Power Center

HPC Solutions in High Density Data Centers

Modular and Scalable Power Converters in the UPS Industry

SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications

Applying branch circuit breakers and supplementary protectors in North America

StorNext M440 Site Planning Guide

Symmetra PX 48kW. Scalable from 16 to 48kW. Make the most of your energy TM. Modular, Scalable, High-Efficiency Power Protection for Data Centers

Liebert GXT3 5kVA-10kVA UPS Compact UPS Systems For High Power Network Rack Applications. AC Power For Business-Critical Continuity

QuickSpecs. HP Remote Monitoring Power Distribution Units. Overview

Cisco CRS 16-Slot Chassis Power Systems

Industrial Facility Wide Protection

High Voltage Direct Current Power Solutions for Data Centers

HP Rackmountable 3 Phase Uninterruptible Power Systems Overview

Models. Specifications

QuickSpecs. HPE Rackmountable 3 Phase Uninterruptible Power Systems. Overview. (UPS R8000/3 and R12000/3)

QuickSpecs. HP Intelligent Power Distribution Unit (ipdu) Overview


MFJ-1164B AC Line RFI Filter

Zenith Series DPB. Distributed Power Busway

Data Center Design: Power, Cooling & Management

2016 IEEE / MCPG meetings cycle,

ZONIT POWER DISTRIBUTION SYSTEM DEPLOYMENT GUIDE

PRODUCT BROCHURE. Deploying effective power protection in data centers

Rack-Level I/O Consolidation with Cisco Nexus 5000 Series Switches

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

DC Energy, Efficiency Challenges

Data Sheet FUJITSU Server PRIMERGY CX400 M1 Scale out Server

XTREME POWER CONVERSION THE VALUE LEADER IN POWER PROTECTION

Liebert STS2/PDU, Static Transfer Switch 2/Power Distribution Unit. A Streamlined Package For Power Distribution And Source Switching

QuickSpecs. HP Intelligent Power Distribution Unit (ipdu) Overview

Make the most of your Energy from Power Plant to Plug. Chris Simard, Regional Director Field Sales Group

Transcription:

Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Revision 1

Executive Summary A new approach to power distribution for high density server installations saves floor space, simplifies power cabling, saves capital cost, reduces weight, and increases electrical efficiency. This paper describes this distribution architecture and quantifies the benefits. Note: The methods in this paper only apply in North America and are for problems that are unique to North America 2

Introduction The standard power distribution system for large data centers in North America is a 277/480V three-phase power system supplying distributed Power Distribution Units (PDUs) which convert the voltage to the 208V and 120V single-phase branch circuits utilized by IT equipment. This arrangement is represented by the one-line diagram of Figure 1. Figure 1 One-line diagram showing standard power distribution system for North American data centers PDU(s) 120 / 208 V 120 / 208 V 277 / 480 V UPS 277 / 480 V 120 / 208 V High density server installations where racks can draw from 10 kw to 40 kw per rack place significant strains on this standard power distribution system. This increased rack power density is causing: Multiple branch circuits per rack, with corresponding breakers and cabling PDUs to become up to 30% of the floor space PDUs to become up to 30% of the floor weight loading More PDUs installed per IT rack, driving up capital costs However, these problems are unique to North America. In Europe and the rest of the world the power distribution system is simpler and more efficient. This paper shows that it is practical to take the power distribution system used in the rest of the world and apply it to North American data centers to reduce cost, reduce weight, save floor space, and increase electrical efficiency. 3

In the past it was not practical to consider alternative higher voltage power distribution systems because a significant fraction of IT equipment operated from 120V. However in the modern high density data center virtually all rack-based equipment operates on 208V (or 240V outside North America). Even devices that can run on 120V are also capable of operating on higher voltage. Virtually all IT equipment manufactured today is designed for worldwide compatibility. This means it can operate on the North American 120/208 volt system, the Japanese 100/200 volt system, and the 240 V system used in the rest of the world. Alternative Power Distribution for North America The alternate power distribution system proposed and described in this paper is an adaptation of the power distribution system used in the rest of the world. The majority of countries around the world use 230 VAC line to neutral. This paper proposes increasing the voltage to 240 VAC line to neutral since this is the highest voltage supported by most IT equipment. This arrangement is represented by the one-line diagram of Figure 2. Figure 2 One-line diagram showing alternative power distribution system for North American data centers 240 / 415 240 / 415 277 / 480 277/ 480 240/ 415 UPS 240 / 415 Autotransformer 240 / 415 240 / 415 The differences between this diagram and the diagram of Figure 1 are subtle, and include: Three-phase branch circuit power distribution that is 240 V (line to neutral) instead of 208 V (line to line) Elimination of the PDU transformers A transformer that is used to change 277/480 V to 240/ 415 V at the output of the UPS. 4

These items are explained in more detail in the following sections. Three-phase branch power distribution 240V (line to neutral) instead of 208V (line to line) While the proposed power distribution method sounds like a minor change, it actually creates a very large impact on the power distribution system. First, the typical North American three-phase branch power dis tribution is at 120/208 Volts, while the proposed distribution uses 240/415 V. This is shown in Figure 3. Figure 3 Diagram showing the difference between three-phase 208 V distribution and 240 V distribution 120 V Neutral Neutral 208 V Typical Load 240 V Typical Load Servers draw their power from the 208 V high voltage (line to line) connection in North America, while they draw their power from the 230 V low voltage (line to neutral) connection in almost every other country in the world. It is important to recognize that when comparing the line to neutral voltages of both distribution methods, the comparison should be between 120 V and 240 V and NOT between 208 V and 240 V. This line to line and line to neutral difference becomes readily apparent when the power capacity for a for a three-phase branch circuit is calculated. For example, assume 20 amp circuits are provided to the load in either case. The power capacity for the 120 V line to neutral distribution method is calculated as (20 amps x 120 V x 3 = 7.2 kw), while the capacity for the 240 V line to neutral distribution method is calculated as (20 amps x 240 V x 3 = 14.4 kw). Given the same circuit current rating, the 240 V distribution provides 100% more power than the 120 V distribution. This increases the power density capability per rack without adding extra circuit breakers as would be the case with the 120/208 V distribution. These additional breakers present additional points of failure resulting in decreased data center reliability. Consider now the same comparison except this time assuming a fixed branch circuit power capacity. For example, assume 10 kw is available to the load in either case. The power capacity for the 120 V line to neutral distribution is calculated as (27.7 amps x 120 V x 3 = 10 kw), while the capacity for the 240 V line to neutral distribution is calculated as (13.9 amps x 240 V x 3 = 10 kw). Given the same power, the 240 V / 415V distribution method provides the same power capacity with nearly half the current required by the 120 5

V / 208V distribution method. This significant difference in current requires the branch circuit wires in the traditional North American system to be 300% larger in terms of their size and weight. Elimination of the PDU transformer Even more important than the cost, size, and weight savings in wiring is the savings in transformers. The PDU transformers can be eliminated. The PDU transformers are required in North American to change the voltage from the UPS output of 277/480 down to the 120/208 utilization voltage. In the rest of the world, the UPS output of 230V/400 V can be directly utilized by the IT loads without the need for an additional transformer. Similarly, the proposed North American distribution eliminates distribution transformers and supplies the IT loads with 240V. In a North American data center with 30 kw racks, approximately 20% of space that would be available for racks is consumed by PDUs. In addition, the PDUs would make up more that 25% of the weight on the raised floor. Note that these impacts were much lower in data centers of the past which operated at approximately 2 kw per rack. Therefore, the benefit of using this new power distribution approach increases dramatically as the rack power density increases. Transformer changes UPS output from 277/480 to 240/415 An additional transformer is used to change the UPS output voltage from 277/480V to 240/415V in the proposed new method. While it appears that this transformer replaces the PDU transformers, in fact it is 90% smaller and less expensive than the PDU transformers for the following reasons: It is wired as an autotransformer 1, and is therefore less than 20% of the size and weight of a standard transformer of the rated UPS capacity. It is sized to the UPS capacity, in contrast to the PDU transformers which as a group are typically sized at 1.5 to 3 times the UPS capacity. In addition, this transformer can be located outside of the data center server space, such as in a back room, which further conserves valuable data center space. The autotransformer described in this new power distribution approach for North America can be eliminated in some cases, resulting in further savings. For new installations the facility could be directly wired for 415V input from the utility company, and a 415V UPS can be used. If this is done, then the auto transformer is not needed. The disadvantage of this approach is that various related AC powered devices, such as pumps, generators, and switchgear are not readily available in North America at a 415V rating. Therefore at this time the preferred approach is to use the auto transformer as described in this paper. 1 An autotransformer has only one winding (primary) as opposed to two in an isolation transformer (primary and secondary). 6

Performance Comparison The alternate power distribution system proposed and described in this paper can save a significant amount of capital cost, space, and operating cost. A comparison of conventional power distribution design with the alternative design was performed based on an actual customer s data center. Their data center is 2,175 ft 2 and consists of 2 redundant modular UPSs at 600 kw each. A total of 104 racks range in density from 1.6 to 6.5 kw each. The results of this comparison are provided in Table 1. Table 1 Performance comparison for alternative power distribution in a 600 kw high density data center in North America Characteristic Standard 120/208 V System Alternative 240/415 V System Comment UPS operating voltage 480 V 480 V Same UPS system UPS output transformer None Equivalent 164 kva A 82 kva autotransformer is required for each side of the architecture. PDU transformer Equivalent 1.8 MW None 8 x 225 kva PDU transformers (4 on each side). Typically oversized by at least 1.6 and sometimes as high at 3.5 times the UPS capacity. PDU / RDP / Transformer costs $145,091 $71,773 The PDU in the standard system is replaced with autotransformers and rack based remote distribution panels (RDP) in the alternative system for a 51% cost savings. PDU / RDP / Transformer weight 20,800lb 2,090 lb Two auto transformers are used and a total of 16 RDPs are used for a weight savings of 90%. PDU / RDP / Transformer area 135 sq ft 92 sq ft Area savings of 32% which includes access areas. Copper wire weight 5,658 lb 2,700 lb Copper only. Estimated based on 104 racks with varying power densities of 1.6 to 6.5 kw each, fed by 8 x 225 kva PDUs or 16 RDPs. Average whip length 42 ft each. Average of 29 whips per PDU and 15 per RDP. (52% weight savings) Total distribution power loss 8,894 W 801 W Includes power needed to cool the transformers and distribution copper losses. (Based on 500 watts of power required by the air conditioning system to remove 1 kw of heat.) (91% savings) 120 V support Y N The alternative system requires a transformer for the few 120V devices that cannot operate on 240 V Power distribution 10 year TCO $262,381 $102,631 Note: Blue shading indicates best performance for the characteristic Based on 30% load (15% on each redundant UPS) (61% savings) 7

Note the large savings in TCO and the large savings in space of the alternative approach of 61% and 32% respectively. The 10 year TCO savings by distributing at 240 volts is $159,751 or 61% savings. Of the TCO savings approximately 47% is due to material cost savings and 53% is due to energy cost savings. Special Cases There are some special cases where the alternative power distribution system is perceived to have limitations. These cases and how the alternative distribution system addresses them are described here. Occasional 120V loads Data centers in North America encounter occasional 120 V loads, even in high density areas. These are dealt with as follows: Many 120 V loads are actually 120/240 V rated. These ratings are always on the devices. The vast majority of these devices have a detachable power cord. The solution is simply to change the power cord to a universal IEC C-13 or C-19 power cord. In some cases it may be necessary to change a switch setting on the device. In cases where it is not possible to avoid using 120 V for isolated device(s), a local rackmount transformer can be used to step down 240 V to 120 V. These are available from APC and other suppliers. Isolation and grounding The conventional North American power distribution system provides isolation of the neutral wire at each power distribution unit. This characteristic has historically been considered desirable and is given various names including: galvanic isolation, separately derived source, and regenerated neutral. Many of the claims regarding the benefit of this arrangement are not based on science. In fact there is no data to suggest that data centers in North America are more reliable than data centers outside of North America, most of which operate according to principles outlined in this paper. This subject is discussed in more detail in APC White Paper #8, Inter-System Ground Noise: Causes and Effects and APC White Paper #87, Use of the Signal Reference Grid in Data Centers. Existing installations The alternative system can be used alongside existing standard power distribution and is particularly well suited for data center expansions focused on high density server applications. Connectors The appropriate connectors for use with 240V circuits are IEC C13 and C19 types. This is the power cord connector provided by most OEM server manufacturers with rack-mount servers and storage devices. Therefore, most high density servers are already provided with the appropriate connector for use with a 8

240V system. Occasionally, a device may be provided with a power cord that uses a North American NEMA style twist lock connector. These are dealt with as follows: If the power cord is the detachable type with a IEC C13 or C19 connector on the chassis, then the cord should be replaced with a cord with IEC connectors at both ends. These are available from virtually all IT OEMs, and they are available from suppliers such as APC. Note that when substituting power cords it may be advisable to purchase a cord of shorter than standard length in order to simplify power cabling in the rack. In the case where the cord is permanently attached to the IT device, if the plug is 20A or less an adapter cable can be used. In the case where the connector is a three-phase connector, see the following section Circuit breakers The branch circuit breakers used in the system described in this paper operate at higher voltage than normal branch circuits in North American data centers. Most circuit breakers that are currently used in North American data centers are not rated for this voltage and cannot be used. Conversely, most European circuit breakers panels are not certified by UL for use in North America. Recently, manufacturers have introduced compact worldwide circuit breakers and circuit breaker panel boards that are rated and certified for high voltage use in North America. Companies like APC offer complete data-center PDUs, remote power panels, and rack power panels that are appropriately rated and certified for high voltage distribution in North America. Three-phase IT loads A very few IT loads are equipped with three-phase connectors. These include some Compaq blade servers, large EMC storage units, and mainframe-style servers. The key thing to understand here is that none of these devices actually require three-phase power. In fact all such devices actually use multiple power supplies drawing single phase power. Furthermore, all of these devices have versions that are sold outside North American and therefore are compatible with the alternative power distribution system. These devices are dealt with as follows: For large deployments of devices with three-phase connectors, specify to the supplier that the power input is to be wired for European voltage. This is often a simple internal jumper setting. Determine if the device is field re-wirable for European voltage operation. Many large devices are. If it is impractical to change the device or convert it, then consider using standard distribution to this device, or install a dedicated PDU to convert the voltage for this device. The above information is provided to assist with implementation of the alternative power distribution system in special cases. Note that in the vast majority of cases, no modifications of any kind are needed to the IT 9

equipment, the power cords, or the rack power distribution devices. Devices which are known to work seamlessly in the alternative power system include: IBM blade servers, 1U servers, virtually all enterprise rack mount servers, and virtually all rack mount SAN and NAS storage devices. Comparison With DC Distribution Alternatives From time to time DC power distribution, either at low voltage or high voltage, has been proposed as an alternative to AC power distribution. The hypothetical benefits of a DC system are claimed to include substantial increases in electrical efficiency. The system proposed in this paper achieves many of the same benefits with much lower cost and complexity. Therefore, the high voltage AC distribution system is a preferred strategy to improve data center efficiency. This subject is discussed in more detail in APC White P aper #127, A Quantitative Comparison of High Efficiency AC vs. DC Power Distribution for Data Centers. Conclusion There are significant advantages to using a higher voltage power distribution system in high density data centers in North America. Use of the proposed 240/415 V distribution system instead of the standard 120/208 system can save 61% in the lifetime cost of the distribution system, and save floor space and weight loading. The benefits are most apparent for high density installations. Furthermore, the alternative design can operate alongside conventional power distribution designs in existing data centers. About the Author: Neil Rasmussen is a founder and the Chief Technical Officer of American Power Conversion. At APC, Neil directs the world s largest R&D budget devoted to power, cooling, and rack infrastructure for critical networks, with principal product development centers in Massachusetts, Missouri, Denmark, Rhode Island, Taiwan, and Ireland. Neil is currently leading the effort at APC to develop modular scalable data center solutions. Prior to founding APC in 1981, Neil received his Bachelors and Masters degrees from MIT in electrical engineering where he did his thesis on the analysis of a 200MW power supply for a Tokamak Fusion reactor. From 1979 to 1981 he worked at MIT Lincoln Laboratories on flywheel energy storage systems and solar electric power systems. 10