B2800 FLOW MONITOR. - For Liquid Meters - PROGRAMMING & INSTALLATION MANUAL Simplified Version

Similar documents
Programming and Installation Manual

Flow Meters. Model B Flow Monitor. Model B2800. Flow Monitor

Flow Monitor. B2800 Standard. User Manual. DSY-PM EN-02 (May 2015)

Flow Meters. Model B Flow Monitor. Model B2800. Flow Monitor

Flow Monitor. B2800 Standard. User Manual. DSY-PM EN-04 (March 2017)

Series FTB 1400-MD-LP FTB 1400-SD-LP FTB 1400-RD-LP Flow Monitor - Simplified Version

Series FTB 1400-MD-A-LP FTB 1400-SD-A-LP FTB 1400-RD-A-LP Flow Monitor - Advanced Version

SHPFI Smart Frequency to Current Converter & Pulse Scaler Installation and Operating Instructions

Flow Monitor. B2800XP Explosion Proof Flow Monitor Standard. User Manual. DSY-PM EN-03 (March 2017)

Global Water globalw.com. Global Water. Instrumentation, Inc.

PMDX-170 Slotted Optical Sensor

PMDX-108-Output. 8-Channel Isolated Output Board for PC parallel port pins 2-9. User s Manual

Models VSP12824V & VSP12860V

R & D SPECIALTIES SERIES 100 RO CONTROLLER USERS MANUAL. 2004, by R & D Specialties, Inc. All Rights Reserved.

MTP INSTRUCTION MANUAL

62533 Ethernet Adapter

Remote Control for Inverter RC-200. Manual. Please read this manual before operating your RC-200 Remote Control

CTI 2551-A 8-CHANNEL ISOLATED THERMOCOUPLE INPUT MODULE INSTALLATION AND OPERATION GUIDE. Version 1.3 CTI Part # * *

OPERATION MANUAL. for the BO BLASTER S OHMMETER

SERVICE MANUAL MODEL SSP-363-E (FORMERLY SSP-365-E)

PD10. Pulse Divider Instructions PROUDLY MADE IN THE USA

Xxxxx Xxxxxx DC Voltage Data Logger

500 Business Center Drive Pittsburgh, PA USA CAGE 1BGJ7. SwitchMaster R5000 Series Ultra-Compact Ganged A/B Switching System

ACLD Channel Opto-isolated Digital Input Board

User s Guide. OM-CP-PRHTEMP2000 Pressure, Humidity and Temperature Data Logger with LCD

Model CD-AW. Infrared Environmental CO2 Sensor. Operator's manual

Remote Control for Inverter RC-300. Owner's Manual. Please read this manual BEFORE operating your RC-300 Remote Control

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

Xxxxx Xxxxxx Bridge / Strain Gauge Data Logger

Bluetooth Enabled Access Control MODEL BG-FE. Operating Instructions

PMDX-105. I/O Option Riser Board User s Manual. Document Revision: 1.1 Date: 7 September 2004 PCB Revision: PCB-443A

Xxxxx Xxxxxx OM-CP-QUADVOLT. OM-CP-OCTVOLT 8-Channel Low Level DC Voltage Data Logger. 4-Channel Low Level DC Voltage Data Logger INSTRUCTION SHEET

POWER SERIES Plus Watt-VAR / Watt-Power Factor Digital Switchboard Meter User s Manual IM2492WVPF-1

Installation Manual. Flow Max 110

NOTE: The F2 button and the 4 LED annunciators do not function on the LD-ACF-I. To use these features, ask about the LD-ACF-R4/R4A.

OPERATION MANUAL BO BLASTER S OHMMETER

Resolver to Digital Expansion Board

Hybrid AC Driver [GCNC-1110]

BrewTroller Phoenix. Owners Manual. Updated - March 14, 2016 BREWTROLLER PHOENIX 1

MYRIAD LC1 LEVEL CONTROLLER INSTRUCTION MANUAL

User's Guide. MiniTec TM Series Model MN25 MultiMeter

Operations Manual EcoSense ph100

DFI 9000 PORTABLE DIGITAL INDICATOR USER S GUIDE

Bid Specifications and General Description

LCT-1 User manual_v1_2017_03_30. LCT-1 Ultimate. Load Cell Tester Issue: Revision A User s Guide

POWER SERIES Plus. 3 in 1 AC Voltage. Digital Switchboard Meter. User s Manual IM2493VVV-2

DVI KVM. Extra Long Range Extender Over One CAT5. User Manual EXT-DVIKVM-ELR. Release A8

Advanced 8-Port DisplayPort Secure KVM Switch

Advanced 4/8-Port DVI-D Matrix KVM

INSTRUCTION and OPERATIONS MANUAL. for

Ordering Information. I/O Relay G7T. Model Number Legend Slim-styled I/O Relay Saves Space in Panel

SERVICE MANUAL MODEL WPP-531-X-ADA MODEL SSP-511- X-ADA

Global Water Instrumentation, Inc.

User s Guide. OM-CP-HITEMP140-M12 High Temperature Data Logger with an M12 Probe Connector

Automatic Phone-Out Home Monitoring System

AE14-503J SERIES PRODUCTION DISPLAY SYSTEM

Operation Manual MODEL 2TX. 2-wire Isolated ph/orp Transmitter

Users Manual. TABLE OF CONTENTS 1 WORKING PRINCIPLE Operating limits Applications... 2

Advanced 2/4-Port DisplayPort Secure KVM Switch

MODEL ATV 4/6 BATTERY POWERED DIGITAL VACUUM INSTRUMENT

WS115 BREAKOUT ADAPTER USER MANUAL

PMDX-103. Parallel Port Isolator Board. User s Manual. Document Revision: 1.2 Date: 20 February 2007 PCB Revision: PCB-447B

EMS Electrical Management System

Document ID: DOC-IPG-2004 Revision: 1.10 Release Date: December 13th, Advanced 2/4-Port DVI-I Secure KVM Switch

Mini Digital Multimeter

PIECAL 510B/511B RTD Simulator Operating Instructions

COBEX RECORDERS, INC.

INSTALLATION & OPERATION MANUAL

POWER SERIES Plus Watt / VAR / Power Factor Digital Switchboard Meter User s Manual IM2493WVP-3

4-20mA Display. Installation and Operation Manual. Rev 4/3/2019 Part #

User's Guide. Phase Sequence and Motor Rotation Tester Model

OPERATING AND SERVICE MANUAL. Universal Interface Device 47

LCI Load Cell Junction Box with Fault Monitor

PMDX-105 Quad Isolator Board

Ave. Edmonton, Alberta, Canada T6E 5C5 Phone: Fax: web:

SERVICE MANUAL FOR MODEL WPP-531-X-ADA-STROBE WEATHERPROOF TELEPHONE WITH OPTIONAL STROBE FEATURE. EQUIPPED WITH SPK1.

E2EY. A Proximity Sensor for Aluminum, Brass and Other Non-ferrous Metals. Iron Is Not Detected. Aluminum-detecting Proximity Sensor

MiniSim 330 EEG Simulator

Model 3526-B Digi-Probe Multimeter

AEXX-273 SERIES WIRELESS CONTROLLED PACE CLOCKS

Instruction Manual RS-1660

USB 3.0 Spectra

SERVICE MANUAL FOR MODEL SSC-500-F (FORMERLY 501-FSZ) STAINLESS STEEL HANDS FREE CHARGE-A-CALL TELEPHONE EQUIPPED WITH LOW-POWER SPEAKER BOARD

PCM-7140 Pulsed Current Source Operation Manual

QAL50 Series Analog Line Sensor

PIECAL 322 Automated Thermocouple Calibrator Operating Instructions. Product Description. Practical Instrument Electronics

BusBlock Analog Input Module for the Smart Distributed System

CA-A480-A Elevator Controller. Reference & Installation Manual

Powered Roller Controller for DeviceNet

PSI DITHERLESS BIAS CONTROLLER USER GUIDE

700 Series 200 Amp Clamp Meters

IOX-4. Installation Instructions. AXS-100 I/O Expander 1. INTRODUCTION 2. SPECIFICATIONS 3. MOUNTING DE6314 1

LCI User Manual mantracourt.com

Model 206 Operating Instructions. Setra Systems, Inc. 159 Swanson Road, Boxborough, MA

Woolich Racing. USB ECU Interface User Guide

SERVICE MANUAL MODEL SSP-550-X (FORMERLY SSP-510-X)

SIAC-PS 3G SIGNAL ISOLATOR WITH POWER SUPPLY (PART NO. 8890) INSTALLATION INSTRUCTIONS

Motorized Filter Wheel FW-MOT-12.5 / FW-MOT-25

Name No. of I/O points Model Safety inputs: 12, test outputs: 4

Installation & Operation

Transcription:

B2800 FLOW MONITOR - For Liquid Meters - PROGRAMMING & INSTALLATION MANUAL Simplified Version 8635 Washington Avenue Racine, Wisconsin 53406 Technical Toll-Free: 877.722.4631 Sales Toll-Free: 800.235.1638 Phone: 262.639.6770 Fax: 262.417.1155 www.blancett.com

TABLE OF CONTENTS Introduction... 3 Specifications... 4 Operating the Monitor... 5 Programming Mode... 6 Programming... 6 K-factor... 7 Password... 8 Totalizer... 9 Battery Replacement... 10 Additional Input Options... 10 Wiring Diagram... 11 Troubleshooting... 12 Programming Menu... 13 Additional Scaling Parameters... 14 Installation Drawing... 17 Part Numbering Information... 18 Statement of Warranty... 19 Notice: Blancett reserves the right to make any changes or improvements to the product described in this manual at any time without notice. 2

INTRODUCTION The B2800 Flow Monitor is a state-of-the-art, digital signal processing flow monitor, designed to provide the user with exceptional flexibility at a very affordable price. Though designed for use with Blancett flow meters, this display can be used with almost any flow meter producing a low amplitude AC output or contact closure signal(s). This flow monitor is capable of accepting a low-level frequency input for calculating flow rate and total. These calculations can then be displayed in the desired units of measurement. All B2800 Flow Monitors come pre-calibrated, from the factory, if ordered with a Blancett flow meter. If required, however, it can easily be re-configured in the field. The monitor s large 8 digit by.75" numeric liquid crystal display makes extended range viewing practical. The second 8 digit by.38" alphanumeric display provides for selectable units viewing in run mode and prompts for variables in programming mode. Finally, the user can choose between displaying rate, total, or alternating between both rate and total. 3

SPECIFICATIONS Power Supply Options: Battery Powered: 1 D size 1.5 Volt alkaline battery Loop Powered: Optional 4-20 ma loop power Alphanumeric Rate and Total Display: 8 digit,.75" high numeric display 8 character,.38" high alphanumeric display Fixed or toggle modes of operation for flow rate and totalizer display Accuracy: ±0.1% Temperature Drift = 50ppm/ C (Max) Mounting Classification: Meter Mount: Type 4 Enclosure Remote Mount: Type 4 Enclosure Swivel Mount: Type 4 Enclosure Environmental: Operating Temperature: -22 ºF to +158 ºF (-30 ºC to +70 ºC) Humidity: 0-90% Non-condensing Inputs: Magnetic Pick-up input: Frequency range = 0 to 3500 Hz Trigger sensitivity = 30 mv p-p Over voltage protected = ±30 VDC Outputs: Opto-isolated open collector transistor Max. Voltage: 30 VDC Pulse width: 20mS/Max rate 20Hz Current (ON state): 0.9V drop @ 5.0 ma or 0.7V drop @ 0.1 ma Optional 4-20 ma output Certifications: CSA: Class I, Div 1 Groups C, D; Class II, Div 1 Groups E, F, G UL: Class I, II, III Div 1 Groups C, D CE: IEC 61326-1 4

OPERATING THE MONITOR The monitor has two modes of operation referred to as the RUN mode and the PROGRAM mode. Both the run mode and the program mode display screen enunciators confirming the state of the monitor. A quick glance at the lower left-hand corner of the LCD screen will confirm operating status. Normal operation will be in the RUN mode. To access the programming mode, press the MENU button until the first programming screen is displayed. After programming the display with the necessary information, a lock out feature can be turned on to prevent unauthorized access or changing the meter s setup parameters. BASIC PROGRAMMING MODE Keys: MENU Switches to Programming mode UP Arrow Scrolls forward through the parameter choices and increments numeric variables RIGHT Arrow Scrolls backward through the parameter choices and moves the active digit to the right ENTER Used to save programming information, advance to the next programming parameter, and in the reset process Modes: RUN Normal operating mode PROGRAM Used to program variables into the display If your monitor was ordered with a Blancett flow meter, the two components ship from the factory, calibrated as a set. If the monitor is a replacement, the turbine s K-factor has changed, or the monitor is being used with some other pulse generating device, programming will be necessary. 5

Programming Using Pulse Output Turbine Flow Meters Each turbine flow meter is shipped with either a K-factor value or frequency data. If frequency data is provided, the data must be converted to a K-factor before programming the monitor. K- factor information, when supplied, can usually be found on the neck of the flow meter or stamped on the body. The K-factor represents the number of pulses per unit of volume. The K-factor will be needed to program the monitor readout. ENTER PROGRAMMING MODE Change to programming mode by pressing the MENU button once. The mode indicator will change from RUN to PROGRAM. SELECT THE METER SIZE At the METER prompt, press the UP or RIGHT arrow keys to select the bore size of your meter. Press ENTER button once to save meter size choice and advance to the K-factor units selection. 6

Note: The meter connection size and the bore size are different. For example, many of the 1" NPT turbines have bore sizes that range from 3/8" up to 1". Be sure to use the correct bore size or the meter will report incorrect flows and totals. ENTER THE METER S K-FACTOR UNIT Directly after the METER size is selected, the display s K-factor unit must be chosen. Use the UP arrow key to select your K-factor unit. For meters calibrated in gallons, use PUL/GAL (pulses per gallon), for meters calibrated in cubic meters, use PUL/ M3 (pulses per cubic meter), etc. Press ENTER to save the K- factor unit and advance to the next parameter. Note: Unless otherwise specified, Blancett turbine flow meters are supplied with K-factors measured in pulses per gallon (PUL/GAL) which will automatically convert to your desired units of measure. Note: The K-factor supplied with the meter or calculated from calibration data will be needed to complete next step. ENTER THE METER S K-FACTOR To change the K- FACTOR value, use the RIGHT arrow key and select the position of the number that you wish to change. Using the UP arrow key, increment the display digit until it matches the meter s K-factor digit. Repeat this process until all K-factor digits have been entered. Press ENTER once to save the K- factor and advance to the RATE/TOTAL units selection. SELECT THE RATE/TOTAL UNITS OF MEASURE The monitor allows the choice of five common rate/total units. The monitor shows the rate/total unit that the display is currently set for. If the current selection is correct, press the ENTER key once to advance to the next parameter. To change to an alternate unit, use the arrow keys to scroll to the desired rate unit and press ENTER to save the choice. 7

SELECTION RATE TOTAL GPM/GAL Gallons per Minute Gallons LPM/LIT Liters per Minute Liters M3PH/M3 Cubic Meters per Hour Cubic Meters M3PD/M3 Cubic Meters per Day Cubic Meters BPD/BBL Oil Barrels per Day Oil Barrels 8 Note: The total unit s output multiplier cannot be modified in the Simplified program level. This option is reserved in the Advanced program level. SELECT THE DISPLAY FUNCTION The monitor can display RATE or TOTAL or alternate between BOTH rate and total. If the current selection is correct, press the ENTER key to advance to the next parameter. To change to an alternate display mode, use the arrow keys to scroll to the desired display mode and press ENTER to save the choice. A TEST function is also available in the Display Function sub -menu. With the test function selected, the display acts like a frequency counter and displays the raw input frequency being supplied to the frequency input terminals. This is very useful when troubleshooting flow problems. TOTALIZER PULSE OUTPUT The pulse output parameter can be either enabled or disabled. When enabled this output generates 20mS duration pulse for every time the least significant digit of the totalizer increments. The amplitude of the pulse is dependent on the voltage level of the supply connected to the pulse output and is limited to a maximum 30 VDC. PASSWORD Password protection prevents unauthorized users from changing programming information. Initially, the password is set to all zeros. To change the password, simply enter any 4 digit code using the arrow keys as previously

described to enter the password value. Pressing ENTER once will store the password and take you back to the RST PSWD screen. Note: This password will allow the operator to manually reset totals. RST PSWD The reset password screen allows the operator to enter any 4 digit code for the manual reset totals function. Note: This reset password code will not allow the operator to enter the programming mode. RESET TOTAL To reset the monitor total display, in run mode press the MENU and ENTER simultaneously until TOTAL RST starts to flash. The TOTAL RST will stop flashing and the display will return to the run mode at the conclusion of the reset procedure. STORE TOTAL The current total can be manually stored in the monitor s flash memory. This procedure may be desirable prior to replacing the battery. Press and hold the ENTER key for 2 seconds. The display will respond with a flashing TOTALSVD and then return to the run mode. AUTOMATIC STORE TOTAL The monitor is equipped with a store total feature that works automatically, saving the current total to flash memory. The frequency of saves depends on the power supply option chosen. Battery Powered: Once per hour and just before a low battery condition turns the unit off. Loop Powered: Once every ten minutes. 9

BATTERY REPLACEMENT Battery powered monitors use a single 1.5V, D size, alkaline battery. When replacement is necessary, use a clean fresh battery to ensure continued trouble-free operation. It is recommended that the total be saved to memory before the battery is removed. (See STORE TOTAL in the programming section of this manual). Unscrew the two captive screws on the front panel to gain access to the battery. Replace the battery being sure to observe the proper polarity, and then re-fasten the front panel. ADDITIONAL INPUT OPTIONS The B2800 Flow Monitor is capable of receiving magnetic pickup input (small signal sine wave) or a contact closure input (pulse). Since most Blancett turbine flow meters utilize a magnetic pick-up, the B2800 Flow Monitor is shipped configured for magnetic pick-up input. To change to a contact closure input, remove JP2 from the top two pins and jumper them to the bottom two pins. See Figure 2 on page 11. 10 WIRING DIAGRAM

BATTERY POWERED LOOP POWERED FIGURE 2 - CIRCUIT BOARD LAYOUT 11

TROUBLESHOOTING GUIDE Trouble No LCD Display No Rate or Total Displayed Flow Rate Display Interprets Reading Constantly Flow Rate Indicator Bounces Remedy Check battery voltage. Should be 1.5 Vdc. Replace if low or bad. Check connection from meter pick-up to display input terminals. Check turbine meter rotor for debris. Rotor should spin freely. Check programming of flow monitor. This is usually an indication of external noise. Keep all AC wires separate from DC wires. Check for large motors close to the meter pick-up. Check for radio antenna in close proximity. Try disconnecting the pick-up from the monitor pig tail. This should stop the noise. If not, then try re-orientating the meter to a new location. This usually indicates a weak signal. Replace pick-up and/or check all connections. Examine K-factor. 12

FIGURE 3 - BASIC PROGRAMMING MENU 13

ADDITIONAL SCALING PARAMETERS Note: The programming instructions below are only available when purchasing a loop powered unit. Battery powered units will not see these programming choices. B2800 Simplified 4-20 ma Programming Instructions 14 FLOW 4mA SETTING When the loop powered option is ordered, the flow rate that corresponds to 4mA must be set. Zero is default flow rate for this setting. If the current selection is correct, press the ENTER key once to advance to the next parameter. If adjustment is required, use the RIGHT arrow key to select the position of the number you wish to change. Then use the UP arrow key to increment the number. Once you have completed this step, press the ENTER key to advance to the next parameter. FLOW 20mA SETTING The flow rate that corresponds to 20mA must be set next. The turbine meter s maximum flow rate is the default value. If the current selection is correct, press the ENTER key once to advance to the next parameter. If adjustment is required, use the RIGHT arrow key to select the position of the number you wish to change. Then use the UP arrow key to increment the number. Once you have completed this step, press the ENTER key to advance to the next parameter. 4-20mA CALIBRATION When ordered with a 4-20mA option, this menu item allows the fine adjustment of the 4-20mA output. The 4mA setting is typically between 35 and 50. To set the 4mA value, connect an ammeter in series with the loop power supply. At the 4mA OUT prompt, adjust the 4mA value to obtain a 4mA reading on the ammeter. The UP arrow key increments the value and the RIGHT arrow key decrements the value. When a steady 4mA reading is obtained on the ammeter, press the ENTER key to lock in this value

and move to the 20mA adjustment. The 20mA adjustment is performed using the same procedure as the 4mA adjustment. 4-20mA TEST The monitor contains a diagnostic routine that allows the simulation of ma values between 4 and 20 to check output tracking. At the 4-20TEST prompt the arrow keys change the simulated ma output in increments of 1mA. The ammeter should track the simulated ma output. If a 4-20mA test in not necessary, pressing the ENTER key once will escape the testing at any time. Note: If your B2800 Flow Monitor was ordered with a Blancett turbine flow meter, the 4-20mA was programmed and factory calibrated. FIGURE 4 - TYPICAL AMMETER CONNECTION 15

16 FIGURE 5-4-20 ma PROGRAMMING MENU

17

PART NUMBERING INFORMATION B 2 8 X X X Program Level A = Advanced S = Simplified Power Option B = Battery L = Loop X X Units of Measure AB = Gallons Mounting Style ED = Barrels HB = Liters M = Meter Mount ID = Cubic Meters R = Remote Mount CS = Customer S = Swivel Mount Selectable* H = Hand-Held P = Panel Mount X = Explosion-Proof *Note: Advanced B2800 monitors only. The default is gallons per minute. COMPONENT PART NUMBER Keypad B260713 Battery B280601 Battery Tie Wrap B228036 Pick-up Cable B222-121 Desiccant Bag B260630 PVC Union B220016 PVC Reducer Bushing B220056 Rubber Washer B228207 Steel Lock Washer B220018 PCB Shield (battery units) B280603 Desiccant Shield B280680 Cord Grip B220103 18

STATEMENT OF WARRANTY Blancett Flow Meters, Division of Racine Federated Inc. warrants to the end purchaser, for a period of one year from the date of shipment from the factory, that all flow meters manufactured by it are free from defects in materials and workmanship. This Warranty does not cover products that have been damaged due to defects caused by misapplication, abuse, lack of maintenance, modified or improper installation. Blancett s obligation under this warranty is limited to the repair or replacement of a defective product, at no charge to the end purchase, if the product is inspected by Blancett and found to be defective. Repair or replacement is at Blancett s discretion. A return goods authorization (RGA) number must be obtained from Blancett before any product may be returned for warranty repair or replacement. The product must be thoroughly cleaned and any process chemicals removed before it will be accepted for return. The purchaser must determine the applicability of the product for its desired use and assumes all risks in connection therewith. Blancett assumes no responsibility or liability for any omissions or errors in connection with the use of its products. Blancett will under no circumstances be liable for any incidental, consequential, contingent or special damages or loss to any person or property arising out of the failure of any product, component or accessory. All expressed or implied warranties, including the implied warranty of merchantability and the implied warranty of fitness for a particular purpose or application are expressly disclaimed and shall not apply to any products sold or services rendered by Blancett. The above warranty supersedes and is in lieu of all other warranties, either expressed or implied and all other obligations or liabilities. No agent or representative has any authority to alter the terms of this warranty in any way. 19

Washington Avenue Racine, Wisconsin 53406 Technical Toll-Free: 877.722.4631 Sales Toll-Free: 800.235.1638 Phone: 262.639.6670 Fax: 262.417.1155 www.blancett.com Blancett is a registered trademark of Racine Federated Inc. UL is a registered trademark of Underwriters Laboratories. 2008 Racine Federated Inc. 20 Form: B2800 Simplified Manual Revision 07/08