Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016

Similar documents
Original operating instructions Safety relay with relay outputs G1501S / / 2016

Original operating instructions Fail-safe inductive sensor GI711S / / 2010

Original operating instructions Fail-safe inductive sensor GF711S / / 2013

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Speed monitor D / / 2014

Operating instructions. Standstill monitor A / / 2011

Original operating instructions Fail-safe inductive sensor GI712S

Original operating instructions Fail-safe inductive sensor GG711S

System manual AS-i safety monitor AC041S /00 05/2013

Original operating instructions Photoelectric safety sensors (safety light grid) with active / passive system OY90xS

Operating instructions Evaluation system for flow sensors VS / / 2013

Installation instructions Diagnostic electronics for vibration sensors VSE / / 2007

Operating instructions Optical distance sensor. O5D15x / / 2014

Operating instructions Optical distance sensor. OID25x / / 2014

User's Manual. english

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

Operating instructions Optical distance sensor. OID25x / / 2015

Operating instructions. Monitor FD / / 2013

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V

Operating instructions Optical distance sensor. OID20x / / 2014

SAFETY RELAY YRB-4EML-31S MAIN FEATURES

Original operating instructions. Fail-safe SmartPLC with Profinet slave interface AC402S /00 06/2016

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

Operating instructions. Monitor FS-2 / FS-2N / / 2013

Operating instructions Optical distance sensor. OID20x / / 2015

Operating instructions Diagnostic electronics for vibration sensors VSE002 / VXE002 / VXE003 VYE001 / VYE002 / VYE003 / VYE /01 05/2015

Operating instructions AC010S Compact AS-i E-STOP safety module

PSR DC/ESP4/2X1/1X2

Phone: Fax: Web: -

to 12a Added Standard and Electrical requirements for UL table 1.1

CONFIGURABLE SAFETY RELAYS

Operating instructions Optical distance sensor O1D / / 2008

SECTION 16 LED DIAGNOSTIC FEATURES: EXPANSION UNITS: SCR-31P-i. SCR-73-i. SEU-31-i. SCR-31-42TD-i. SEU-31TD-i

PSR UC/ESAM4/3X1/1X2/B

Operating instructions Monitor FD-2 DR2005 DR / / 2007

Safety Technique. SAFEMASTER C Multifunction Safety Module BH 5910

Operating instructions. Monitor FR-1 / FR-1N / / 2013

AS-Interface Safety at Work

MSR178DP. Description. Features. Specifications

Installation instructions Inclination sensor EC2019 EC / / 2013

E-STOP relays, safety gate monitors

Technical data. Dimensions: see page 116. ): 4 kv Rated insulation voltage (U i Over-voltage category: Power supply. Rated operating voltage (Un):

AS-i Safety Relay Output Module with Diagnostic Slave

Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3

PSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1

Operating instructions Memory plug E /02 11/2011

Bul. 440R Guardmaster Safety Relays (DI, DIS, SI, CI, EM, and EMD) Selection Guide

Operating instructions Safety-monitoring module SE-304 C. 1. About this document. Content

ENGLISH. Terminals 13, 14, 23, 24, 43, 44, 53, Web: Phone: Toll Free:

AS-i Safety Relay Output Module with Diagnostic Slave

ETD-BL-1T-OFF-CC- 10S

Technical data. Housing Polyamide housing PA 66, self-extinguishing V0 acc. to UL 94. Supply Rated supply voltage (U n

Operating instructions Safety-monitoring module AES 1235 AES About this document. Content

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Operating instructions Safe AS-i input module ASIM-C-M About this document. Content

Operating instructions RFID evaluation unit DTE / / 2016

Operating instructions Safety-monitoring module AES 1235 AES About this document. Content

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B

Safety relays PNOZsigma

Dimensions. Model Number. Electrical connection emitter. Features. Electrical connection receiver. Product information. Pinout OBE12M-R100-S2EP-IO-V31

Operating instructions (short version) Safety monitor AS-Interface Safety at Work ASM E1-R2 ASM E2-R2/R2. 1. About this document.

Added Standard and Electrical requirements for UL table Switching-off inductive loads 1.2

Performance Level PL d. Safety Category Type 3. Automatic reset / Manual reset. Very short reaction times. Connection of several signal transmitters

Operating instructions Control monitor for temperature sensors TR /00 04/2011

Operating instructions Optical distance sensor O1D / / 2012

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

Two-hand control unit

Options for ABB drives. User s manual Emergency stop, stop category 0 (option +Q951) for ACS880-07/17/37 drives

Making Hazardous Operations Safe and Productive

Quick reference guide 3D sensor O3D3xx

SR103AM. User Information for SR103AM. Correct Use

Datasheet - SRB 301LC/B-24V

HR1S-AC Safety Relay Modules

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

ASM1, ASM1E, ASM2E. AS-i Safety Monitor. Subject to change without prior notice. Technische Ă„nderungen vorbehalten /02

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

Dimensions. Model Number. Electrical connection. Features. Pinout. Indicators/operating means. Product information OQT150-R100-2EP-IO-V31

BETRIEBSANLEITUNG TECHNICAL INSTRUCTION INTERFACE PSE2-SC-02 (24 V AC/DC) Version 1.4

Control unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~

SR101A. User Information for SR101A. Correct Use

QUINT-PS/ 1AC/24DC/ 5

G9SX-GS. Safety Guard Switching Unit. A Safety Measure for Hazardous Operations That Does Not Lower Productivity. Auto Switching Function

Non-Contact Safety System CES-AZ

E-STOP relay, safety gate monitor

Safety Switches CES-AR/CET-AR

E-STOP relays, safety gate monitors

Operating instructions Pressure sensor. PN50xx / / 2010

Operating instructions. Monitor FS-1 / FS-1N / / 2013

Datasheet SRB301ST 24V (V.2)

Operating instructions Enabling switch (handle switch) ZSD5 ZSD6. 1. About this document. Content. 7 Appendix 7.1 Wiring example...

QUINT-BUFFER/24DC/24DC/40

FACTORY AUTOMATION. MANUAL VAA-2E-G4-SE Original Instructions Version 1.1

Technical data. Safety parameters: see page 333. DC maximum residual ripple: 10% Supply voltage tolerance: DC consumption: Control circuit

Polymer Electric. Operating Instructions. Control Unit SG-RST 153. Version 0.3

Vital. Safety controller. Approvals: Control of: Features: Entire safety system based on the dynamic safety circuit.

Datasheet - SRB 402EM-24V

Safety Technique. SAFEMASTER Light Curtain Controller With Selectable Operating Modes BH 5902/01MF2

Operating Instructions

Options for ABB drives. User s manual Emergency stop, stop category 1 (option +Q964) for ACS880-07/17/37 drives

Technical Data. Dimensions

Transcription:

Original operating instructions Safety relay with relay outputs with and without delay UK G50S 803638 / 00 0 / 06

Contents Preliminary note...4. Symbols used...4 Safety instructions...5 3 Items supplied...6 4 Functions and features...6 4. Requirements for the hardware configuration...6 4.. Product-independent requirements...6 4.. Product-dependent requirements...7 5 Structure and operating principle...8 5. Indicators and connections...8 5. Block diagram...9 6 Installation...0 7 Electrical connection...0 7. Supply voltage...0 7. Feedback contacts / monitored or automatic start... 7.3 Output circuit... 8 Connection - Function - diagnosis...3 8. Safety relay for fail-safe sensors/switches with PNP outputs...4 8.. Connection...4 8.. Function...5 8..3 diagnosis...8 8. Safety relay for clocked fail-safe sensors... 8.. Connection... 8.. Function...4 8..3 diagnosis...5 8.3 Two-hand control using electronic sensors/switches...8 8.3. Connection...8 8.3. Function...9 8.3.3 diagnosis...3 8.4 Two-hand control using mechanical switches with simultaneity monitoring 34 8.4. Connection...34 8.4. Function...36 8.4.3 diagnosis...39

8.5 Safety relay for e-stop, for -channel fail-safe sensors/switches with contact output or for mechanical switches...4 8.5. Connection...4 8.5. Function...4 8.5.3 diagnosis...44 9 Programming...47 9. Programming of the switch-off delay...47 0 Scale drawing...48 Technical data...48uk Tests/approvals...50 3 Terms and abbreviations...5 3

Preliminary note The instructions are part of the unit. They are intended for authorised persons according to the EMC, Low Voltage Directive and Machinery directives and safety regulations. The instructions contain information about the correct handling of the product. Read the instructions before use to familiarise yourself with operating conditions, installation and operation. Adhere to the safety instructions.. Symbols used Instruction > Reaction, result Cross-reference LED off LED on LED flashes LED flashes quickly Important note Non-compliance can result in malfunction or interference. Information Supplementary note. 4

Safety instructions Follow the operating instructions. Improper use may result in malfunctions of the unit. This can lead to personal injury and/or damage to property during operation of the machine. For this reason note all remarks on installation and handling given in these instructions. Also adhere to the safety instructions for the operation of the whole installation. In case of non-observance of notes or standards, specially when tampering with and/or modifying the unit, any liability and warranty is excluded. The unit must be installed, connected and put into operation by a qualified electrician trained in safety technology. The applicable technical standards for the corresponding application must be complied with. For installation the requirements according to EN 6004 must be observed. In case of malfunction of the unit please contact the manufacturer. Tampering with the unit is not allowed. Disconnect the unit externally before handling it. Also disconnect any independently supplied relay load circuits. After setup the system has to be subjected to a complete function check. Use the unit only in specified environmental conditions ( Technical data). In case of special operating conditions please contact the manufacturer. Use only as described below ( 4). UK 5

3 Items supplied safety relay G50S copy of the operating instructions safety relay, reference 803638 If one of the above-mentioned components is missing or damaged, please contact one of the ifm branch offices. 4 Functions and features The safety relay is a redundant system and suited for use as: Safety relay for fail-safe sensors/switches with PNP outputs (e.g. GM70S, chapter 8.). Safety relay for clocked fail-safe sensors (e.g. GM504S, chapter 8.). Relay for two-hand control to EN 574, type IIIC, with electronic sensors/ switches ( chapter 8.3). Relay for two-hand control to EN 574, type IIIC with mechanical switches / safety relay for mechanical switches or -channel fail-safe sensors/switches (e.g. ESPE to EN 6496-) with contact output with simultaneity monitoring ( chapter 8.4). Safety relay for e-stop, for two-channel fail-safe sensors/switches (e.g. ESPE to EN 6496-) with contact output without simultaneity monitoring (indefinite simultaneity) or for mechanical switches ( chapter 8.5). ifm electronic gmbh assumes no liability for the use of units made by external manufacturers. The safe state is when the output contacts 3-4, 3-4, 33-34, 43-44, 67-68 or 77-78 are open and the output contact 5-5 is closed. 4. Requirements for the hardware configuration The following requirements must be met when using the G50S safety relay: 4.. Product-independent requirements It must be ensured that the safety requirements of the respective application correspond to the requirements stated in these instructions. The specified technical data indicated in these instructions must be complied with. The principle of normally closed operation must be applied to all external safety circuits connected to the system. 6

The safety relays type G50S in operation have to be subjected to a self-test (switching off) within a period of maximum month. The self-test can be carried out by switching the supply voltage off and on or by a safety request. 4.. Product-dependent requirements In case of faults within the safety relay which result in the defined safe state, the safety relay must be replaced. Any faulty unit should be returned to the manufacturer. UK 7

5 Structure and operating principle 5. Indicators and connections A3 S33 S34 S43 S44 C 3 4 A Y4 Y5 Y6 Y7 C 3 4 A L- Y Y Power C3 33 34 T C4 43 44 5 5 C5 67 68 C6 77 78 A Supply voltage (L-, ), function terminals (Y, Y) A A3 Y4, Y5, Y6, Y7: Operating mode selection, auxiliary output S33, S34, S43, S44: Connection for safety inputs / output K LED yellow: Triggering the relay outputs channel K LED yellow: Triggering the relay outputs channel E E Power T C LED yellow: Input signal channel or TE (for clocked sensor) LED yellow: Input signal channel or A (for clocked sensor) LED green: Voltage supply LED red: /start-up LED red: / LED yellow: Triggering the relay output with switch-off delay 3, 4: Connection of relay output without delay, x normally open (closed when enabled) 8

C C3 C4 C5 C6 3, 4: Connection of relay output without delay, x normally open (closed when enabled) 33, 34: Connection of relay output without delay, x normally open (closed when enabled) 43, 44: Connection of signal output without delay, x normally open (closed when enabled) 5, 5: Connection of signal output without delay, x normally closed (open when enabled) 67, 68: Connection of relay output with switch-off delay, x normally open (closed when enabled) 77, 78: Connection of relay output with switch-off delay, x normally open (closed when enabled) UK 5. Block diagram C C C3 C4 C4 C5 C6 L- Y4 Y S34 S43 Y5 Y Y6 S33 S44 Y7 3 3 33 43 5 67 77 INPUT CIRCUIT OUTPUT CIRCUIT MCU (CONTROLLER) K3 MCU (CONTROLLER) K4 4 4 34 44 5 68 78 9

6 Installation Mount the unit on a DIN rail in a housing protected against dust and humidity (min. IP54 - degree of soiling ). 7 Electrical connection Use 60/75 C copper conductors only. 7. Supply voltage The external supply unit must have a safe separation. In case of a fault the voltage can exceed the value of 60 V DC for a maximum of 00 ms, but must not exceed the value of 0 V DC. Connect supply voltage Manual reset RESET For safety reasons the unit can only be restarted by separation from the supply voltage in case of a fault. It is thus recommended to install a RESET switch in series with the circuit. After power on or a RESET the unit carries out self diagnostic functions. After this self diagnosis the unit is ready for operation. 0

7. Feedback contacts / monitored or automatic start Automatic start A L- Y Y Automatic activation without monitoring. Monitoring of the feedback contacts (normally closed) for automatic start The circuit is enabled when the feedback contacts are closed. Consider the current flowing through the feedback contacts ( Technical data). UK : feedback contact Monitored start Activate the relay outputs: Press and release the start button (> 50 ms). This function is not active when used as two-hand control. : start button Monitoring of the feedback contacts (normally closed) for monitored start Activate the relay outputs: Feedback contacts are closed Press and release the start button (> 50 ms). This function is not active when used as two-hand control. Consider the current flowing through the feedback contacts ( Technical data). : feedback contact : start button

7.3 Output circuit Last anschließen C 3 4 3,6 A Connect the load to be controlled to the relay outputs on C (3, 4), C (3, 4), C3 (33, 34), C5 (67, 68) or C6 (77, 78). Adhere to max. and min. contact rating ( Technical data). C 3 4 3,6 A C3 33 34 K3 3,6 A C5 67 68 K4 3,6 A C6 77 78 K5 3,6 A C4 43 44 5 5 The relay outputs C4 (43, 44 and 5, 5) provide a non safety-related signal. The signal corresponds to that triggering the relays at the outputs C (3, 4); C (3, 4) and C3 (33, 34). The total current, i.e. the max. current load of all output circuits of the safety relay (C-C6), must not exceed A.

A Y4 Y5 Y6 Y7 The signal output Y7 provides a non-safety related signal for communication to a plc. The signal corresponds to that triggering the relays at the outputs C5 (67, 68) and C6 (77,78). The output data is compatible with the input data of the current-sinking inputs of type,, 3 to EN 63-. : Input : SPS 8 Connection - Function - diagnosis The safety relay can be connected or used in different ways:. Safety relay for fail-safe sensors/switches with PNP outputs (e.g.gm70s).. Safety relay for clocked fail-safe sensors (e.g. GM504S). 3. Relay for two-hand control to EN 574 with electronic sensors. 4. Relay for two-hand control to EN 574 with mechanical switches / safety relay for mechanical switches or -channel fail-safe sensors/switches (e.g. ESPE to EN 6496-) with contact output with simultaneity monitoring. 5. Safety relay for e-stop, for two-channel fail-safe sensors/switches (e.g. ESPE to EN 6496-) with contact output without simultaneity monitoring (indefinite simultaneity) or for mechanical switches. UK 3

8. Safety relay for fail-safe sensors/switches with PNP outputs Example of fail-safe sensors/switches: Fail-safe inductive sensor GM70S Light barrier Light curtain (ESPE to EN 6496-) Laser scanner 8.. Connection Fail-safe sensor/switch with a current consumption of 50 ma: G50S : Fail-safe sensor/switch Fail-safe sensor/switch with a current consumption of > 50 ma: G50S : Fail-safe sensor/switch 4

8.. Function Input circuit Output status LED display Y7 3 4 3 4 33 34 43 44 5 5 67 68 77 78 td = 0...0 s T UK Y7 0 3 4 3 4 33 34 43 44 T 5 5 67 68 77 78 td = 0...0 s * T Stop flashing: Activate inputs in correct time sequence ( fig. above) * During the switch-off delay (td > 0 s) 5

Input circuit Output status LED display Y7 0 3 4 3 4 33 34 43 44 5 5 67 68 77 78 td = 0...0 s Y7 0 3 4 3 4 33 34 43 44 T 5 5 67 68 77 78 td = 0...0 s * T T T * During the switch-off delay (td > 0 s) 6

Input circuit Output status LED display Y7 0 3 4 3 4 33 34 43 44 5 5 67 68 77 78 td = 0...0 s * UK Y7 0 3 4 3 4 33 34 43 44 T 5 5 67 68 77 78 td = 0...0 s * T T T * During the switch-off delay (td > 0 s) 7

8..3 diagnosis In case of a fault switch the safety relay off and on again! LED display Cause of the fault Troubleshooting T No voltage supply Overvoltage Connection A/A3 or A/A reversed Check power supply T Wire break Feedback contacts open Switch the safety relay off and on again T When voltage is applied: Feedback contacts open Check output circuit Check feedback contacts Exchange external contactor T Wiring fault Short circuit Inputs S34 and S43 when voltage is applied Switch the fail-safe sensor/ switch off and on again Short circuit S33/S43 T T Short circuit S33/S43 8

LED display Cause of the fault Troubleshooting Overvoltage Undervoltage Check power supply T Overvoltage Undervoltage Check power supply T UK Undervoltage Check power supply T T T T Short circuits T Input S43 active more than 0.5 s after input S34 ( 8..) Feedback contact error Short circuit S34/S44 Switch the fail-safe sensor/ switch off and on again 9

LED display Cause of the fault Troubleshooting T The rotary switch for programming the switch-off delay was changed y programming Program it again ( 9.) 0

8. Safety relay for clocked fail-safe sensors Example of fail-safe sensors/switches: Fail-safe inductive sensor GM504S Up to 0 clocked fail-safe sensors can be connected to one safety relay. 8.. Connection Connection of one fail-safe sensor/switch: G50S UK : Fail-safe sensor/switch Connection of fail-safe sensors/switches: G50S : Fail-safe sensor/switch : Fail-safe sensor/switch

The use of the safety splitter box 569 is recommended: G50S : Fail-safe sensor/switch : Fail-safe sensor/switch 3: 569 4: e.g. EVC04 5: e.g. EVC00 wh = white bk = black bn = brown bu = blue Connection of 3 to 0 fail-safe sensors/switches: G50S : Fail-safe sensor/switch : Fail-safe sensor/switch 3: Fail-safe sensor/switch 3

The use of the safety splitter box 569 is recommended: G50S UK : Fail-safe sensor/switch : Fail-safe sensor/switch 3: Fail-safe sensor/switch 3 4: 569 5: e.g. EVC04 6: e.g. EVC00 wh = white bk = black bn = brown bu = blue 3

8.. Function Input circuit Output status LED display Y7 3 4 3 4 33 34 43 44 5 5 T 67 68 77 78 td = 0...0 s Y7 0 3 4 3 4 33 34 43 44 T 5 5 67 68 77 78 td = 0...0 s * T : First or last fail-safe sensor/switch of a row of sensors/switches : td = max. 6 ms * During the switch-off delay (td > 0 s) 4

8..3 diagnosis In case of a fault switch the safety relay off and on again! LED display Cause of the fault Troubleshooting T T No voltage supply Overvoltage Connection A/A reversed Wire break Feedback contacts open Time-dependent contacts Check power supply Switch the safety relay off and on again UK T T When voltage is applied: Feedback contacts open Short circuit Connection A/A3 or A/A3 exchanged Short circuit S43/ or S44/L- Check output circuit Check feedback contacts Exchange external contactor T Short-circuit S34/S44 or S33/ S43 T Short circuit S34/ T 5

LED display Cause of the fault Troubleshooting Short circuit S43/ or S34/S44 T T Missing clock Wiring fault Connection A/A3 reversed Short circuit S43/L- Overvoltage Undervoltage Check power supply T Overvoltage Undervoltage Check power supply T Undervoltage Check power supply T T 6

LED display Cause of the fault Troubleshooting Short circuits T T UK T The rotary switch for programming the switch-off delay was changed y programming Program it again ( 9.) 7

8.3 Relay for two-hand control using electronic sensors/switches Example of electronic sensors/switches: Capacitive sensors For product selection see www.ifm.com This wiring meets the requirements type IIIB to EN 574. Use up to type IIIC is possible using corresponding sensors/switches with two independent switching elements, internal plausibility check and protected or screened wires. 8.3. Connection Connection of two -wire DC: G50S : Electronic fail-safe sensor : Electronic fail-safe sensor 8

8.3. Function Input circuit Output status LED display Y7 3 4 3 4 33 34 43 44 5 5 67 68 77 78 td = 0...0 s T UK Y7 0 3 4 3 4 33 34 43 44 T 5 5 67 68 77 78 td = 0...0 s * T : Electronic fail-safe sensor : Electronic fail-safe sensor * During the switch-off delay (td > 0 s) 9

Input circuit Output status LED display Y7 0 3 4 3 4 33 34 43 44 T 5 5 67 68 77 78 td = 0...0 s * T Y7 0 3 4 3 4 33 34 43 44 T 5 5 67 68 77 78 td = 0...0 s * T : Electronic fail-safe sensor : Electronic fail-safe sensor * During the switch-off delay (td > 0 s) 30

Input circuit Output status LED display Y7 0 3 4 3 4 33 34 43 44 T 5 5 67 68 77 78 td = 0...0 s * UK T : Electronic fail-safe sensor : Electronic fail-safe sensor * During the switch-off delay (td > 0 s) 3

8.3.3 diagnosis In case of a fault switch the safety relay off and on again! LED display Cause of the fault Troubleshooting T No voltage supply Overvoltage Connection A/A3 or A/A reversed Check power supply T Wire break Feedback contacts open Time-dependent contacts Switch the safety relay off and on again T When voltage is applied: Feedback contacts open Check output circuit Check feedback contacts Exchange external contactor T Wiring fault Missing link Y4/Y5 Short circuit Inputs S34 and S43 activated when voltage is applied Connections A3/A reversed Deactivate inputs and RESET or voltage failure T Missing link Y4/Y5 T Overvoltage Undervoltage Check power supply T 3

LED display Cause of the fault Troubleshooting Overvoltage Undervoltage Check power supply T Undervoltage Check power supply T UK T T Short circuits T T T Inputs S34 and S43 not activated within 0.5 s ( 8.3.) Feedback contact error Short circuit S34/S44 The rotary switch for programming the switch-off delay was changed y programming Deactivate inputs and activate them again Program it again ( 9.) 33

8.4 Relay for two-hand control using mechanical switches with simultaneity monitoring Two-hand control with mechanical switches / safety relay for mechanical switches or -channel fail-safe sensors/switches with contact output with simultaneity monitoring. The contacts of the mechanical switches must allow a minimum current of 6 ma. 8.4. Connection Connection of two mechanical fail-safe switches This wiring (with only one normally open contact per sensor/switch) meets the requirements of type IIIB to EN 574. Use up to type IIIC is possible using corresponding sensors/switches approved to EN 60947-5- annex K and protected or screened wires. G50S : Mechanical fail-safe switch : Mechanical fail-safe switch 34

Connection of mechanical switches according to type IIIC to EN 574 G50S UK : Mechanical switch (no positively driven contacts) : Mechanical switch (no positively driven contacts) Connection of a -channel fail-safe sensor/switch e.g. "electro-sensitive protective equipment" (ESPE) to EN 6496- G50S : Contact of the ESPE : Contact of the ESPE 35

8.4. Function Input circuit Output status LED display Y7 3 4 3 4 33 34 43 44 5 5 T 67 68 77 78 td = 0...0 s Y7 3 4 0 3 4 33 34 43 44 T 5 5 67 68 77 78 td = 0...0 s * T : N.O. contact activated * During the switch-off delay (td > 0 s) 36

Input circuit Output status LED display Y7 3 4 0 3 4 33 34 43 44 T 5 5 67 68 77 78 td = 0...0 s * UK T Y7 3 4 0 3 4 33 34 43 44 T 5 5 67 68 77 78 td = 0...0 s * T : Electronic fail-safe sensor : Electronic fail-safe sensor * During the switch-off delay (td > 0 s) 37

Input circuit Output status LED display Y7 3 4 0 3 4 33 34 43 44 T 5 5 67 68 77 78 td = 0...0 s * T : Electronic fail-safe sensor : Electronic fail-safe sensor * During the switch-off delay (td > 0 s) : N.O. contact activated 38

8.4.3 diagnosis In case of a fault switch the safety relay off and on again! LED display Cause of the fault Troubleshooting T T No voltage supply Overvoltage Connection A/A3 or A/A reversed Wire break Feedback contacts open Time-dependent contacts Check power supply Switch the safety relay off and on again UK T T When voltage is applied: Feedback contacts open Wiring fault Missing link Y4/Y5 Short circuit Contacts closed when voltage is applied Connection A/A3 reversed Check output circuit Check feedback contacts Exchange external contactor Open contacts and RESET or voltage failure T Overvoltage Undervoltage Check power supply T Overvoltage Undervoltage Check power supply T 39

LED display Cause of the fault Troubleshooting Undervoltage Check power supply T T T Short circuits T T T Inputs S34 and S43 not activated within 0.5 s ( 8.4.) Feedback contact error Short circuit S34/S44 The rotary switch for programming the switch-off delay was changed y programming Deactivate inputs and activate them again Program it again ( 9.) 40

8.5 Safety relay for e-stop, for -channel fail-safe sensors/ switches with contact output or for mechanical switches In this operating mode the simultaneity of the contacts is not monitored. The -channel fail-safe sensors/switches are for example "electro-sensitive protective equipment" (ESPE) to EN 6496-. The contacts of the sensors/switches must allow a minimum current of 6 ma. 8.5. Connection Connection e-stop / -channel fail-safe sensors/switches: UK G50S : Fail-safe sensor/switch Connection of two mechanical switches: G50S : Mechanical switch : Mechanical switch 4

8.5. Function Input circuit Output status LED display Y7 3 4 3 4 33 34 43 44 5 5 T 3 67 68 77 78 td = 0...0 s Y7 3 4 0 3 4 33 34 43 44 T 5 5 67 68 77 78 td = 0...0 s * T : Fail-safe sensor/switch : Fail-safe sensor/switch 3: Order and time difference insignificant (indefinite simultaneity) * During the switch-off delay (td > 0 s) : N.O. contact activated 4

Input circuit Output status LED display Y7 3 4 0 3 4 33 34 43 44 T 5 5 67 68 77 78 td = 0...0 s * UK T Y7 3 4 0 3 4 33 34 43 44 T 5 5 67 68 77 78 td = 0...0 s * T : Fail-safe sensor/switch : Fail-safe sensor/switch * During the switch-off delay (td > 0 s) : N.O. contact activated 43

8.5.3 diagnosis In case of a fault switch the safety relay off and on again! LED display Cause of the fault Troubleshooting No voltage supply Overvoltage Check power supply T Short circuit Wire break T Short circuit Wire break T Short circuit Wire break T Feedback contacts open Wire break T T T When voltage is applied: Feedback contacts open Wiring fault Missing link Y4/Y5 Short circuit Check output circuit Check feedback contacts Exchange external contactor 44

LED display Cause of the fault Troubleshooting Connection A/A3 reversed T Missing link Y4/Y5 T UK Overvoltage Undervoltage Check power supply T Overvoltage Undervoltage Check power supply T Undervoltage Check power supply T T 45

LED display Cause of the fault Troubleshooting Short circuits T T T The rotary switch for programming the switch-off delay was changed y programming Program it again ( 9.) 46

9 Programming In all described operating modes (8. - 8.5) a switch-off delay for the relay outputs on terminals C5 and C6 can be set. 9. Programming of the switch-off delay Set the rotary switch to position F. Switch the unit off and on again. > > Yellow LED [] flashes quickly: The unit is in the programming mode. Set the rotary switch to the desired position without delay: Pos. F 0 3 4 5 6 7 8 9 A B C D E [s] 0.5 0.5.5.5 3 4 5 6 7 8 9 0 0 UK : Programming mode > > After.5 seconds the yellow LED [] is permanently lit > > Programming is completed, the delay is stored permanently. When the unit is switched on again, it is ready for operation with the new delay. Do not change the position of the rotary switch any more. Protection against defeating: In case of subsequent changes the unit goes into the safe state and the LEDs [T] and [] indicate an error ( fault diagnosis). Program it again. On delivery the outputs are set without delay, i.e. the rotary switch is at position E. 47

0 Scale drawing 50 05 4 35,5 LED : Rotary switch for switch-off delay : Screw terminal (supplied) Technical data G50S Safety relay with relay outputs Terminal block Phoenix Contact MSTBO Meets the requirements of: EN ISO 3849-: 008+AC009, category 4 PL e, SIL 3 (IEC 6508) Electrical design Output function Operating voltage Relay 3 safety-related NO contacts (floating) without delay; non safety-related signal outputs without delay ( x NO, x NC, floating contacts) safety-related NO contacts (floating) with switch-off delay signal output (positive switching) with delay 4 V DC (9...30) incl. 5 % residual ripple 48

Contact rating Minimum load current of the feedback contacts Short-circuit protection / overload protection Current consumption Function display Power-on delay time 6 A, 50 V AC / 4 V DC ( 6 ma) max. total current: A 0 ma The contacts are to be protected by means of fuses with a nominal current of < 3.6 A < 500 ma voltage (green), error ( x red), output status (3 x yellow), input ( x yellow) < 6 s Duration of switch-off test pulses 500 µs Response time [ms] acc. to input circuit chapter Ambient temperature 8. 8. 8.3 8.4 8.5 Release 70 60 70 0 0 Safety requirement 30 00 30 30 30-5...55 C Protection rating IP 0 Housing materials Input characteristics (S34, S43) Output characteristics Mission Time (TM) PA "": > V, 6 ma "0": < 5 V, < 500 µa S33 push-pull short-circuit proof "0": I sink ~ 30 ma "": I source 50 ma, U > 8 V S44 "0": I R 300 µa "": I source 50 ma, U > 8 V Y7 "0": I R 300 µa "": I source V @ 30 ma, 5 V @ 5 ma 75 00 h PFH D 5,86 x 0-9 / h *) B0 D 400 000 *) UK 49

Comments Additional comments concerning the culus approval (UL 508): Maximum ambient temperature 55 C (in the control cabinet) The safety functions were not assessed by UL. The approval has been made according to UL 508 for general applications. Use 60/75 C copper conductors only. For use in pollution degree environment Same polarity (phase) referred to the output contacts *) with h op = 4 h, d op = 365 days, t cycle = 3600 s Tests/approvals The G50S safety relay was tested and certified by TÜV-Nord. The safety relay was developed and tested in accordance with, for example, the following directives and standards: 006/4/EC Machinery Directive 004/08/EC EMC Directive 04/30/EU EMC Directive (effective from 0 April 06) EN 5078 (997) Electronic equipment for use in power installations EN ISO 3849-: 008+AC009 Safety of machinery, safety-related parts of control systems DIN EN 6004-:006 (where applicable) Electrical equipment of machines EN 6496- (03) Non-contact protective equipment - General requirements and tests EN 574:996+A: 008 Safety of machinery - Two-hand control devices - Functional aspects - Principles for design IEC 6508: 00 Functional safety of electrical/electronic/programmable electronic safety-related systems EN 606: 005+A: 03 Safety of machinery - Functional safety of safetyrelated electrical, electronic and programmable electronic control systems UL 508 50

3 Terms and abbreviations ESPE Electro-Sensitive Protective Equipment. Cat. Category Category Classification of the safety-related parts of a controller as regards their resistance to failures. CCF Common Cause Failure Common cause failure DC Diagnostic Coverage Diagnostic coverage. UK MTTF Mean Time to Failure Mean time to failure. MTTF d Mean Time To Dangerous Failure Mean time to dangerous failure. OSSD Output Signal Switching Device Output signal switch element, static safety-related output. PFH (PFH D ) Probability of (dangerous) Failure per Hour Probability of a (dangerous) failure per hour. PL Performance Level PL to EN ISO 3849- SIL Safety Integrity Level SIL -4 to IEC 6508 PLC Programmable Logic Controller Technical data and further information at www.ifm.com 5