Modbus. Serial communication and control of Rotork actuators. Established Leaders in Valve Actuation. Electric Actuators and Control Systems

Similar documents
Modbus Actuator Control

DeviceNet. Controller Area Network control of Rotork actuators. Established Leaders in Valve Actuation. Electric Actuators and Control Systems

Foundation Fieldbus. Serial communication and control of Rotork actuators. Established Leaders in Valve Actuation

Profibus. Serial communication and control of Rotork actuators. Established Leaders in Actuation Technology

DeviceNet. Controller Area Network control of Rotork actuators. Redefining Flow Control

Foundation Fieldbus. actuator control. Established Leaders in Actuation Technology. Foundation Fieldbus. Freedom to Choose, Power to Integrate

HART. Actuator Control. Redefining Flow Control

Profibus Actuator Control

Note 1: Throughout this manual the Modbus Module Mk2 may simply be referred to as the module.

Modbus RTU Actuator Control Mk2 Option Card Technical Manual (IQ Pro, IQT Pro, SI Pro, EH Pro, ROMpak and Q)

IQM & IQML RANGE CONTROL AND MONITORING FACILITIES. Publication E420E issue 7/02

Established Leaders in Actuation Technology. Pakscan IIE high integrity master station. Publication S110E issue 09/04

IQ Pro SIL option TÜV Certified for use in SIL 2 & 3 applications

Electric Actuators and Control Systems. Established Leaders in Valve Actuation. Pakscan P3 Systems. Network Control. Publication S000E Issue 05/07

IQ Range Intelligent Electric Actuator

CVA Range. Control and Monitoring Facilities. Established Leaders in Valve Actuation. Electric Actuators and Control Systems

Established Leaders in Actuation Technology. In-Vision PC based supervisory control. Publication S210E issue 04/03

DTM Solutions. Setup, parameterisation, monitoring, and asset management information. Redefining Flow Control

profibus Actuator control by Profibus Profibus DP module - serial communication unit publication S113E issue 11/99

E.CK Centronik Control and Indication Specification CENTRONIK FUNCTION AND PROTECTION DETAILS. Local Control. Local Indication.

CVA Range. Control and Monitoring Facilities. Keeping the World Flowing

Skilmatic SI3-3 Electric Fail-Safe Actuators

IQ SIL Option. IQ actuators for use in applications up to SIL 3. sira CERTIFICATION

IQT 3 rd Generation Intelligent Part-turn Electric Actuator

Foundation Fieldbus FF01 Mk 2 Option Card Installation Manual

Modbus RTU Actuator Control Mk 3 Option Card Technical Manual. (IQ3, SI3, CVA, CMA, K-Range) Publication PUB _0918

Tank terminal demonstrates the electrically operated solution for Emergency Shutdown Valves

Skilmatic SI-1Q. Keeping the World Flowing. Spring-Return Electric Quarter-Turn Actuator (65 to 480 Nm)

PRODUCT INFORMATION. DeviceNet Triple Play Digital Communications Board. SA Actuator with AUMA Matic Motor Controls

Profibus Actuator Control Profibus DP Option Card Installation Manual

Pakscan Field Unit Technical Manual. (IQ / IQT 3 rd generation, CVA, CMA, ROMpak, CK, SI3) Publication PUB _1116

Electric Actuators and Control Systems. Established Leaders in Valve Actuation AD Instruction Manual. Publication P972E Issue 08/09

Pakscan P3 Wireless Quick Start Guide

PRODUCT INFORMATION. AUMA Actuators, Inc. Pittsburgh PA USA. Triple Play Digital Communications Board DeviceNet / Modbus CDN455

Pakscan P3 System. Network Control. Established Leaders in Actuation Technology

S-series Serial Interface

Foundation Fieldbus FF-01 Option Card Installation Manual

ROSoV Actuation Solutions

/8 DIN Motorized Valve Controller

The final column has Navigation controls to the individual FCU screens.

TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND

User Guide IM/C250 MOD_3. Modbus (RTU) Communications Option C250 and V250

IQ Range. IQ and IQT Multi-turn and Part-turn Electric Valve Actuators Control and Monitoring Facilities. Redefining Flow Control

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

User Guide Supplement Modbus TM Serial Data Communications Option IM/C100 MOD_6. /8 DIN Process Indicators and Controllers C100, C150, C160 and V100

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III

M-series Serial Interface Series 2

SmartMod DC Digital Input Module HE359DIM610 12/24VDC Negative Logic

M-series Serial Interface Series 2

Operating Guide MODBUS (RTU) Communications Option IM/L150 MOD_2. Level Indicator L150 and L160

Chapter 1. Introduction. Additional Documentation

S-series Serial Interface

Pakscan General Purpose Field Control Unit Technical Manual

MOD-IO9 Modbus Input / Output Modules, Wall Mounted

F02 SERIES ELECTRIC ACTUATORS

INTEGRATED AUTOMATION ACTUATORS AND OPERATORS

QUCM Limitorque Controller

Electric Actuators and Control Systems. Established Leaders in Valve Actuation AD-8140 & AD Instruction Manual. Publication P971E Issue 08/09

EUROTHERM FLEXIBLE SOLUTIONS SERIES CONTROLLERS......in tune with your needs

Skilmatic SI 3 Range. Spring-Return and Double-Acting Self-Contained Electro-Hydraulic Actuators. Keeping the World Flowing

What is SCADA? What is Telemetry? What is Data Acquisition? Differences between SCADA and DCS? Components of SCADA. Field Instrumentation

Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual.

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

3rd Generation Skilmatic SI Range

The Infinity TCX 865 programmable Infinet terminal controller is a unique, low-cost VAV box

MODBUS Trouble Shooting

/8 DIN Universal Process Indicator

MODERNIZE YOUR DC CRANES. Convert Your DC Controls to State-of-the-Art Energy Efficient OmniPulse DDC Series 2 Drives

Documentation. M-Bus 130-mbx

HART Actuator Field Unit Technical Manual. (IQ / IQT 3 rd generation, CVA, CMA DEV_REV2) Publication PUB _0615

FEATURES DESCRIPTION SPECIFICATIONS

ATS Automatic transfer switches Advanced version

Mega_Link Telemetry Communication System

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

MULTIPLE PROTOCOLS FOR VALVE ACTUATOR CONNECTIVITY

UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

Designing a Reliable Industrial Ethernet Network

Wall-/Pipe Mounted Universal Process Indicator

Intrinsically Safe Temperature Concentrator System

General Specifications. P2-SCM Serial Communications

PLC Fundamentals. Module 2: Hardware and Terminology. Academic Services Unit PREPARED BY. August 2011

Micro Motion Model 7950 and Model 7951 Signal Converters

DI-917MB/DI-918MB. Heavy-duty 1A solid-state relays provide dependable on/off control of industrial devices. Analog Output Module. Four Analog Outputs

The IQ240 panel mount load cell indicator is a precision digital indicator for load cell and strain gauge applications.

Getting Started with your D3000M Series Module

FCU-MULTI Modbus Fan Coil Unit Controller

NF770 Temperature Compensation Liquid Flow Computer

All data in this brochure are given for information only and are subject to change without notice. INTELLI+ Intelligent control

Temperature/Process Controllers Manual

Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual.

EY-CM 721: Communication module with EIA-232 and EIA-485 interfaces, modu721

P3-SCM. General Specifications

Industrial Electric Actuators AC and DC Voltages Nm/ inch lbs

DI-904MB/DI-905MB/DI-906MB

CERBERUS. Cerberus multi I/O. Datasheet. Shaping the future of sound reinforcement. Cerberus. Applies to Part Number:

Eurotherm advanced controllers providing solutions for simple to demanding applications...

USER MANUAL. Modbus IHP24-A IHP24-AF IHP24-B IHP24-BF IHP24-F IHP24-I 1/26

Optidrive Applications Support Library

KTA-250 Anemometer Alarm Card

Transcription:

Electric Actuators and Control Systems Established Leaders in Valve Actuation Modbus Serial communication and control of Rotork actuators Publication S117E Issue 04/09

Rotork actuators have been in use all around the world for over 50 years. In this time Rotork has grown to become the leader in the valve automation industry. With manufacturing, service centres, offices and representatives throughout the world, Rotork is able to offer global service solutions to your company. In the 50 years since the company was founded, Rotork has become a byword for excellence in the field of valve, sluice gate and damper actuation products for the oil, gas, power, water and waste treatment industries - worldwide. We owe our success to an uncompromising focus on quality at every stage - and at every level - of Rotork s operations. From initial site survey, specification and design, through to materials, manufacturing and testing, installation, commissioning and after-sales service we accept nothing but the best. At the heart of the company is an exceptional workforce - the highly trained, forward-thinking engineers, technicians and support staff who each have a crucial role to play in maintaining Rotork s unrivalled reputation for innovation, reliability and first class customer support. The Rotork family of products also includes pneumatic, hydraulic and electro-hydraulic actuators as well as a comprehensive range of gearboxes and valve accessories. Rotork s bespoke Pakscan digital control system offers market leading features whilst all our actuators offer the ability to interface with other digital control systems. Rotork. Established leaders in valve actuation technology. 2

Contents Contents Actuator Control 4 Rotork Modbus Module 5 RS485 Communication Highway 5 Rotork Modbus Overview 6 Single Channel Module 6 Dual Channel Module 7 Single Channel plus Repeater Module 7 Control Features 8 Data Logging 9 Function Code Support 9 Configuration 9 Lightning Protection 10 Technical Data 11 Direct Modbus control of Rotork actuators by 2-wire RS485 serial communications provides a simple and reliable control strategy for valve automation. Rotork electric actuators may be controlled over the low cost RS485 network using the Modbus RTU protocol when they are fitted with the Rotork Modbus option module. The inherent flexibility of the Modbus RTU protocol allows the systems engineer to control the data flow on the highway as well as the registers read and written to. There are no complications with device description files or special tools needed to set up a Modbus system. The PLC and DCS drivers are all simple and easy to use. Established Leaders in Valve Actuation Technology 3

Modbus Actuator Control Modbus: Modbus is the most popular communication protocol in use today. It has the widest acceptance and highest number of applied systems of any automation protocol. International Open Standard. Highly reliable standardised communications. Simple connectivity, easy configuration. Rotork Modbus module: Compatible with all Rotork electric actuators. RS485, RTU communication. Low installation and maintenance costs. High control system flexibility. Data transfer between 300 and 115 kbaud. Simple plant expansion. Cabling requires 2 wires only per channel provided the ground potentials are equal. Three versions available: Single Channel, with and without repeater and Dual Channel. IQ For more information on Modbus consult the web site at http://www.modbus.org. Modbus was developed by Modicon in the 1980s and remains one of the leading protocols used in the field of process control and automation. 4

Rotork Modbus Module The Modbus module is fitted inside the actuator electrical housing and interfaces directly with the actuator electronics. Once fitted, all the normal commands associated with moving the actuator together with feedback and some historical data become available on the Modbus RS485 highway. There are a number of user settings to be made for the system variables and actuator performance, such as the baud rate and the slave address of the actuator. These are set by either using the infrared communication link to the actuator or by writing over the network to the appropriate registers in the module. All the settings are held in non-volatile EEPROM memory on the card. Dual Channel Modbus Module RS485 Communication Highway The Modbus module is a slave device and it uses 2-wire, half duplex, RTU communications on the balanced RS485 highway. An additional connection is provided at each actuator for a common wire linking all the actuators together. The RS485 standard requires the common mode differential voltage between all the points on the highway to be less than 7 Volts. If the site wide common mode is above this level, the additional connection to a third wire should be made to ensure successful field communication. PLC Address 1 Address 2 Address 3 1500 metres at 9600 baud Data Rate (baud) 300 600 1k2 2k4 4k8 9k6 19k2 38k4 57k6 115k2 Maximum Cable Length 24km 12km 12km 6km 3km 1.5km 1.2km 1.0km 750m 500m Total Spur Length 2km 1km 1km 500m 500m 500m 500m 300m 200m 100m Note: Each actuator includes up to 0.6 m of cable spur. Calculations based on Belden 8770 cable parameters, 18 AWG, 1 mm 2 cross section, 3 cores. Established Leaders in Valve Actuation Technology 5

Modbus Overview The Rotork Modbus Module is available in three forms for different applications. The Single Channel card is the simplest of the three with only one highway connection. The Dual Channel card has two independent communication channels and is usually connected to two highways with redundant communication paths. This increases the plant availability by reducing the probability of communication failure preventing the actuator from being controlled. The third option has an internal repeater so that it can be used on a single highway and allows the highway to be extended in distance or number of units without an external repeater. With this option the actuator should remain powered at all times to ensure system communications are maintained. Outputs - Commands Inputs - Feedback Modbus RTU The protocol used for the communication is RTU (Remote Terminal Unit). This is the most common Modbus application, where each network will have one master, usually a PLC or DCS, and several slave devices. In all cases the Rotork module is a slave device and will only send a message in response to a request from the master on the system. Because all messages are under the control of the master there should never be any data collisions or interruptions. The master also controls the message retry mechanism and monitors each slave for its responses to requests for data. Only one slave device at a time sends messages on the highway. The Rotork module only supports half duplex communication. On a 2-wire RS485 Comms Highway cable the pair is used for passing messages in one direction at a time, either from the master to the slave, or vice versa. This means the master is transmitting only half of the time, hence using half duplex communication. Full duplex requires 4 wires and is more complex, while a half duplex communication system is easier to trouble shoot and keep running. Modbus Single Channel Module The single channel option is the simplest implementation of the Modbus module to apply. There is only one RS485 highway connection to the actuator and only one channel inside the actuator for communication. There is also an additional input that may be connected to an instrument analogue transmitter signal for relaying the value over the network. The module operates as an RTU slave on the network and uses only one address. 2-wire RS485 Single Comms Highway. 1 analogue input channel. Full actuator control and data reporting. Externally selectable termination components. Full isolation on both the RS485 connection and the Analogue channel. Includes full lightning protection on RS485 highway connection. Multiple data base for back compatibility. Fully network configurable. 6

Modbus Dual Channel Module The dual channel version caters for those applications where redundant highways are being used for high integrity field connection. The two channels are isolated from one another and provide independent communications. Both channels share the same processor, address and baud rate for the communications. The ability to utilise dual highways makes this version ideal for critical installations where redundant communication paths are required. Two 2-wire RS485 communication highways. Full actuator control and data reporting. Externally selectable termination components. Full isolation on both channels and between channels. Includes full lightning protection on each RS485 highway connection. Channel 1 takes priority over Channel 2 when simultaneous messages are received. Fully network configurable. Common address between the two channels. Common communication speed for both channels. Modbus Single Channel plus Repeater Module The single channel with repeater Modbus module includes an internal repeater to allow the highway to be extended over greater distances, or for those applications where a ring is to be constructed. The repeater works in both directions and has minimal turn round time between transmit and receive modes. The number of connected modules can be extended over 32 using the repeater version, however the recommendation for repeaters is that no more than 9 are used in a system. With 9 repeaters it is easy to build a system over 15 km in length that will run at 9600 baud. The operation is similar to the single channel unit with the addition of the repeater function. Two connections for single RS485 highway use. Full isolation between the two segments. Minimal turn round time within the repeater to ensure maximum speed communication. Allows for spur and ring topology networks. Includes full lightning protection on each RS485 highway connection. Established Leaders in Valve Actuation Technology 7

Modbus Control Features Feedback and Control The Modbus module allows data to be collected from the actuator about the status of the valve and actuator combination. This data includes logging features when the module is in an IQ or IQT actuator. In addition full digital and analogue control of the actuator is available without the need to add more components to the actuator. Feedback Data IQ IQT Q Digital Inputs: Actuator moving Close limit switch Open limit switch Actuator running closed Actuator running open Digital Outputs: Analogue Outputs: Control Data IQ IQT Q Stop Close Open ESD Relay 1* 7 Relay 2* 7 Relay 3* 7 Relay 4* 7 Desired actuator position Note: The Aux input 1-4 and Relay 1-4 outputs may be used for direct actuator remote control and indication. * Remote input and relay board must be fitted Remote control selected Local stop selected Local control selected Thermostat tripped Monitor relay Valve obstructed Valve jammed Manual movement Motion inhibit timer active Positioner control enabled Watchdog tripped Slow mode 7 7 Open interlock input 7 Close interlock input 7 Battery low 7 Aux input 1 7 Aux input 2 7 Aux input 3 7 Aux input 4 7 Analogue Inputs: Measured actuator position User analogue input channel Current actuator torque value 7 8

C Data Logging Data Highway Out Terminator 2 2A 2B Common 2 r C With IQ and IQT actuators the Modbus module also makes available some of the standard data logger feedback information. A torque profile is provided in each direction together with the total number of times the motor starter has been energised in each direction. There is a short delay after the actuator stops (around 2 seconds) before this data is compiled and presented to the network. Starts - Open 7346 Starts - Close 7782 Starts - Open 7346 Starts - Close 7782 Closed 0 10 20 30 40 50 60 70 80 90 100 Open Opening Direction Torque The registers containing this information can be accessed periodically to update the control system with the latest data. Closed 0 10 20 30 40 50 60 70 80 90 100 Open Closed 0 10 20 30 40 50 60 70 80 90 100 Open Closing Direction Torque Closing Direction Torque Function Code Support The Modbus module supports all the major function codes and uses a technique whereby data and commands can be read and written using more than one code. For example, all actuator control and indication can be obtained using register read/write functions 03 and 16, or discrete inputs can be read with function 02 and so on. Full position control of the actuator can be achieved by writing a value to the position control register. Code Function 01 Read Output Coil status 02 Read Input status 03 Read Holding register 04 Read Input register 05 Force single coil 06 Preset single register 07 Read Exception status 08 Loopback Diagnostic test 15 Force multiple coils 16 Preset multiple registers 17 Report Slave ID Configuration The Modbus module requires a number of configurable parameters to be set, including the address and baud rate for communication. All the parameters may be set using the communication link itself. In most cases, the default setting will match the valve operation. To cater for those more exacting applications, the ability to match the communication and actuator performance to the valve characteristics is invaluable. In the case of the IQ and IQT actuator the primary parameters can be set using the actuator infra-red communication link. Description Modbus Address Baud Rate (baud) & Parity/Stop bits Data Base Format Actuator Tag Name Action on Loss of Comms Limited Range Position Min & Max Deadband and Hysteresis Motion Inhibit Time Aux Input Mask & ESD DI-4/Net Disable Valve Jammed Time Manual Movement Travel Watchdog Timeout & Comms Fault Timer Analogue Input scaling Established Leaders in Valve Actuation Technology 9

Lightning Protection All the communications ports on each variant of the Modbus module are fitted with components designed to reduce the effect of high voltage induced signals, such as those generated by a lightning strike. A combination of gas discharge tubes and Transorb semiconductors, together with varistors ensures that in most cases the induced voltage levels cause no damage to the communication network. To make full use of the internal protection, the screen should be earthed and a separate common wire should be used. 10

Modbus Technical Data Dual Channel Modbus Module Interface: Number of channels: Address range: Data rate: Parity: Communication Protocol: Function Codes: EIA-485 (RS485) suitable for 2-wire connection. 1 on Single channel, fully isolated from the actuator circuits. 2 on Dual channel, fully mutually isolated. 2 on Single channel with repeater, fully mutually isolated. 1 to 247, address 0 reserved for broadcast messages. 300 to 115k2 baud, selected over the Modbus network. Configurable, odd, even or none. Modbus RTU (slave device). All popular function codes including 01, 02, 03, 04, 05, 06, 15, 16. Analogue Input: 1 on Single channel, 4-20 ma or 0-5 VDC, externally powered, 0.1% resolution and 1% linearity at 20 ºC, fully isolated. User defined Digital Inputs: 4 off (IQ and IQT only), potential-free input contacts. User defined Digital Outputs: 4 off contacts 5 A, 120 VAC or 1 A, 30 VDC (IQ and IQT, requires additional relay board option). Enclosure: Environment: Power consumption: Suitable for fitting within Rotork IQ, IQT and Q range actuators. -40 to +70 ºC, environmentally protected by Rotork actuator double sealing to IP68. All Modbus module power is taken from the actuator, no external supply is required. Established Leaders in Valve Actuation Technology 11

Rotork Controls Inc, Rochester, USA Rotork Controls Ltd, Bath, UK As part of a process of on-going product development, Rotork reserves the right to amend and change specifications without prior notice. Published data may be subject to change. For the very latest version release, visit our website at www.rotork.com The name Rotork is a registered trademark. Rotork recognises all registered trademarks. Published and produced in the UK by Rotork Controls Limited. POWTG0409 UK head office Rotork Controls Limited tel Bath 01225 733200 fax 01225 333467 email mail@rotork.co.uk USA head office Rotork Controls Inc tel Rochester (585) 247 2304 fax (585) 247 2308 email info@rotork.com Electric Actuators and Control Systems Fluid Power Actuators and Control Systems A full listing of our worldwide sales and service network is available on our website at: Gearboxes and Gear Operators Projects, Services and Retrofit www.rotork.com