COMMUNICATION NETWORKS FOX615/612 TEGO1 IEC 61850 GOOSE Proxy Gateway interface module.
2 FOX615/612 TEGO1 IEC 61850 GOOSE GATEWAY INTERFACE MODULE INTRODUCTION 3 FOX615/612 multiplexing platform. Enabling GOOSE messaging thanks to TEGO1 interface card. GOOSE Signal Translation. TEGO1 forms part of the IEC 61850 world. For substation automation systems, the IEC 61850 standard has been widely accepted. With the ongoing digitalization of electrical substations, GOOSE based line distance protection application becomes a greater focus. The same standard provides defined messaging for IEC 61850 signal exchange between IEDs with different protocols. For binary signals such as trip signals, GOOSE (Generic Object oriented substation events) messaging has been defined. The TEGO1 interface card of the FOX615/612 multiplexing platform now offers an integrated IEC 61850 GOOSE interface being able to connect directly to the IEC 61850 station bus of an electrical substation. This interface allows to use GOOSE messages for line distance protection or for new applications such as remote trip or interlocking. The traditional way of line distance protection application is using binary high voltage contacts, either to the teleprotection interface of the multiplexing platform itself or to the external teleprotection equipment. This remained as such even if today s IEC 61850 framework would allow the usage of GOOSE based trip signals for line distance protection applications. This traditional approach brings certain complexity to the protection system since electrical high voltage signals have to be brought from the relay to the communication equipment. EMC/ EMI aspects have to be considered as well as substantial cabling efforts since per command two cables have to be connected and usual protection schemes consist of several commands per powerline. Availability is limited since redundancy of cabling, as well as supervision of end to end solution is often not ensured. Last but not least the performance of the overall protection solution is restricted by the speed of the binary contacts with it's relatively slow switchover times leading to longer fault clearing times than necessary. The ongoing trend for digital substations with it s undoubted benefits on visibility and flexibility makes the usage of GOOSE based line distance protection applications obvious, if the same can provide the required performance parameters such as dependability and security defined in IEC 60834-1 standard as well as provide a secure access from the to the substation IEC 61850 station bus. Avoiding reconfiguration of existing IEC 61850 substation configurations. IEC 61850 has been used for substation automation for many years. It originated as a technology that was only applicable for internal substation purposes. Only with recent developments such as IEC TR 61850-90-1 GOOSE has been considered for substation to substation protection signal transmission. Three main problems arise when IEC 61850 GOOSE messages are used for inter substation communication. 01 GOOSE is a layer 2 protocol, direct connection between substations would mean connection of the two so far separated station buses with all related problems arising when different local area networks are connected on L2 basis only. 02 When IEC 61850 based substations were introduced, the concept of using GOOSE messages for communication between substations was not considered. Due to this, there has usually not been a country wide planning on IP addresses of IED s, application IDs or used VLANs. Changing this at a later stage would be a major effort related with (at least) a partial reconfiguration of the substation. 03 Since GOOSE messages are based on Ethernet packets, and the station bus is based on an Ethernet Switched network cyber security aspects such as data integrity and access restrictions need to be considered, and this in the light of critical applications with strong real time requirements TEGO1 has been developed to specifically address these issues. TEGO1 provides: A fast L2 tunnel for GOOSE messages with specific filtering in order to avoid the L2 network problems and flooding of all information to all sites. Staying on L2 ensures the highest possible performance for critical GOOSE signals. The translation functionality for GOOSE fields like VLAN and Multicast address or application ID in order to resolve potential conflicts when using GOOSE between substations hence avoiding reconfiguration of already commissioned substations when GOOSE is used for line distance protection applications. Filtering and translation happens at wire speed which results in a TEGO1 being as fast as a transparent L2 tunnel between substation with the flexibility of a proxygateway being able to change related GOOSE fields. L2 application based firewall functionality to restrict access to the station bus from the wide area network Authentication of GOOSE messages for man in the middle attack and replay protection TEGO1 is an IED acting as a proxy gateway for GOOSE signals between substations. TEGO1 represents the remote IED inside the local substation and resolves at the same time all potential conflicts by performing required translation functions at wire speed. With this, an IED cannot distinguish if the IED is just connected to the local station bus or if it is hundreds of kilometers away on the other side of the power line. By representing the remote IED all of the standard IED 61850 functionality is performed such as subscription to GOOSE messages or status supervision of the local IEC 61850 substation automation system using MMS. In order to allow this, TEGO1 is integrated into the local SCD file and configured there initially. This is done at both sides and brought together in the TEGO1 configuration tool, where the mapping between the different substations is completed. In order to finalize the configuration, updates of the different substation SCD files need to be performed.
4 FOX615/612 TEGO1 IEC 61850 GOOSE GATEWAY INTERFACE MODULE THE BENEFITS OF USING IEC 61850 5 Digital Substation with GOOSE for line distance protection. The benefits for IEC 61850 substation design. RTU RTU IEC 61870-5-104 DNP3 IEC 61870-5-104 DNP3 Substation Control System Substation Control System MMS GOOSE SNTP Station Bus Station Bus FOX 615 Multiplexer 110 VCD TRIP FOX 615 Multiplexer 110 VCD TRIP 110 VCD TRIP 01 02 01 Traditional Substation design with contact based Teleprotection 02 Digital Substation design using GOOSE for line protection Figure 1 shows a conventional setup of a line distance protection application. The distance protection relay (21) is connected with multiple cables to the teleprotection interface on the multiplexer (or to a dedicated teleprotection equipment). All those connections are replaced by a single fiber connection as indicated in Figure 2. By using IEC 61850-based protection various benefits arise: Easier setup of the protection system by using one technology resulting in overall better protection performance (faster protection system). A reduction in cabling due to less additional copper cables being required for trip signals. Less EMC/ EMI and safety problems by using fiber optic communication media. Increased flexibility since new or modified protection schemes can be implemented by software modification only. Better visibility and supervision of the solution by integrating the solution in the communication network management system as well as the substation automation system. Increased availability of protection system.
6 FOX615/612 TEGO1 IEC 61850 GOOSE GATEWAY INTERFACE MODULE THE BENEFITS OF IEC 61850 7 03 TEGO1 is capable to server various remote ends. TEGO1 forms part of the IEC 61850 world. It represents the remote IED in the local substation. TEGO1 key features. 4 x FE/ GbE interfaces (SFP based for direct connection with the station bus of IEC 61850 substations. Representation of remote IED for inter substation IEC 61850 GOOSE signal transmission. Filtering capabilities for GOOSE messages. Translation capabilities of GOOSE messages to resolve potential addressing/naming conflicts between substations. Redbox functionality for connection to PRP Redundant station bus (one card/two card solution). L2 firewall for access restriction from the to the substation station bus. Hitless redundancy for GOOSE protection communication channels. Guaranteed data integrity thanks to authentication of data streams. 6 electrical IRIG-B outputs for synchronization of end devices to GPS Grandmaster clock. Optical IRIG-B output for synchronization of end devices to GPS Grandmaster clock. SNTP master functionality for providing time of day information to IEDs. SNTP client functionality for full IEC 61850 compliance. MMS status reporting to substation automation system for full IEC 61850 compliance. Enhanced traffic supervision features providing full visibility of the communication channel performance. Full integration in FOXMAN-UN network management system and FOXCST configuration tool. Providing all optical interconnections from relay to relay through multiplexer without any converter boxes. The benefits of using IEC 61850-based line distance protection application. Innovative line protection schemes beyond todays limits. Substation A TEGO1 IED Substation B Substation C Substation D (PRP red.) Station Bus Substation E Substation F 03
REC650 REC650 8 FOX615/612 TEGO1 IEC 61850 GOOSE GATEWAY INTERFACE MODULE FURTHER BENEFITS 9 FOX 615 TEGO 1 SCL Configuration Mode - Simplified Workflow Further benefits of TEGO1 Redundancy, Security and Improved operations. INPUT TOOL ACTION Step 1: Initial substation design 1+1 hitless protection PTP ICD File IED Capability Description IEC 61850 Configuration Tool (e.g. IET600) Initial local substation configuration with TEGO1 FOX615 Step 2: Initial TEGO1 configuration IRIG-B SNTP PRP Redundant Station Bus SCD File Substation Configuration Description TEGO1 Engineering Tool Definition of which GOOSE message is sent to which remote end 04 05 Step 3: Final substation design IID File Instantiated IED Description SCD File Substation Configuration Description IEC 61850 Configuration Tool (e.g. IET600) Step 4. Final TEGO1 configuration TEGO1 Engineering Tool Update of local substation configuration on GOOSE messages received (final interconnected substation configuration) Import of TEGO1 configuration into FOX615 04 Time of day distribution to end devices. 05 FOX615 as a redbox for PRP station bus. Simple time of day distribution. Time of day information is important for many electrical grid operation applicaitons. Fault recorders, event recorders, differential protection relays and also wide area protection schemes using synchrophasors rely on it for correct operation or for statistical analysis at a later stage. FOX615 can be synchronized from a centralized grandmaster clock by using IEEE 1588v2 PTP protocol as well as Synchronous Ethernet. The accuracy of this time of day information is < 1 us. This allows distributing the time of day information through the to substations and end devices. Redundancy and security - TEGO1 increases the availability and security of your protection solution. TEGO1 provides the possibility to connect to a PRP redundant station bus architecture and acts as a redbox. In order to ensure redundancy in the communication TEGO1 provides hitless redundancy for critical GOOSE signal transmission. In case of problems in the, where one of the redundant communication channel fails, the hitless redundancy ensures that the protection application is not affected at all. In order to detect cyber security incidents, such as signal modification or replay attacks, TEGO1 allows an authentication of critical protection data. For security of the station bus infrastructure a L2 firewall working on white listing principle is implemented. With this, all unauthorized access from the to the station bus can be stopped. The solution works on a denial per default principle while the performance of the protection application is not compromised.
FURTHER BENEFITS 10 Network Management System. Network Management system. All modules of FOX615, including a variety of services and applications, are managed centrally by FOXMAN management system, the network management system for the complete communications portfolio. Easy and intuitive configuration of user dialogues and equipment views is ensured by FOXCST, the graphical configuration tool. TEGO1 offers a special configuration tool for IEC 61850 configuration where SCD files from the substations can be imported, TEGO1 IEC 61850 configuration be done and required modification of SCD file exported again to the substation automation system, as well as to the FOXCST. With FOXMAN and FOXCST utilities can enhance the overall performance of their operational networks, saving costs and accelerating the circuit provisioning process with only one element manager for all service types. Technical Data. Feature Rating or standard Synchronisation General Amount of Ports 4 SFP front ports, FE/ GbE SNTP Master/ Slave Port configuration mode Individual or PRP redundant Redundancy LAN (Station bus) Supported serial time code formats Hitless 1+1 (0 ms) PRP redbox IRIG-B002,5,6 (100pps, pulse with code, no carrier, BCD) IRIG-B output 6 electrical outputs IRIG-B002, 1 optical output Gateway IED for GOOSE between substations IEC 61850 Trip counters 4 per instance Environment Event recorder User Events and GOOSE events Temperature rating -25 C +60 C Performance <200 us transmission time back to back Fanless -25 C - +55 C EMC standards Generic: EN 61000-6-3, EN 61000-6-2; Specific: IEC 61000-4-2 / 3 / 4 / 5 / 6 / 8 / 16 / 18 / 29 Product standards IEC 61850, IEEE 1613, IEC60834-1 Electrical safety EN 60950-1 IEC 60255-5 100 years Functionality Filter criteria for GOOSE Subscription to GOOSE message Amount of GOOSE messages per card up to 32 GOOSE messages Amount of instances up to 8 Electrical isolation Translation of GOOSE fields MAC DA (Destination Address) APPID (IEC 61850 Application ID) VLAN Tag gocbref (Goose control block reference) datset (data set) goid (Goose ID) MTBF List of abbreviations FOXCST Configuration Tool for FOX615/612 SNTP Simple Network Timing Protocol TEGO1 status supervision Integrated in FOXMAN-UN MMS message for substation automation control system IED Intelligent Electronic devices PRP Parallel Redundancy Protocol Authentication L2 firewall White listing, filtering on LAN and authentication on BER Bit Error Rate Wide Area Network performance supervision Latency, availability, packet loss, BER, 15 min/ 24h, continuous supervision LAN Local Area Network MMS performance Dependability/ Security as per IEC 60834-1 Manufacturing Messaging Specification SFP Small Form Factor Pluggable "ABB's GOOSE Proxy Gateway interface module TEGO1 takes innovative line distance protection schemes beyond todays limits."
ABB Switzerland Ltd. Power Grids Grid Automation Bruggerstrasse 72 CH-5400 Baden, Switzerland +41 58 585 77 44 communication.networks@ch.abb.com abb.com/communicationnetworks We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2017 ABB All rights reserved Document ID 4CAE000374