How can you display error messages and warnings of a frequency converter on a panel? WinCC flexible RT and Panels FAQ

Similar documents
Why can you not transfer the HMI configuration to the panel? - PROFIBUS Connection - FAQ 03/2014

Cover. Configuration of an IM 308-C as DP Slave to a CP as DP Master PROFIBUS DP. FAQ July Service & Support. Answers for industry.

Service & Support. Which options exist for reading hardware limit switch signals into a technology CPU? Technology CPU.

FAQ about Drive Technology

FAQ Communication over PROFIBUS

Communication between HMI and Frequency Converter. Basic Panel, Comfort Panel, Runtime Advanced, SINAMICS G120. Application Example 04/2016

09/2014 SINAMICS G/S: HMI

TECHNICAL NOTE TNOI30

Service & Support. How can the Safety Functions of SINAMICS S120 be activated in an existing STEP 7 Project? Technology CPU.

Operating system update with ProSave. ProSave. FAQ July Service & Support. Answers for industry.

Applications & Tools. Brief instructions on the communication connection of the MSS 3RK3 to the S via AS-Interface.

Applications & Tools. Failsafe and standard cross communication of the MSS 3RK3 via AS-Interface. SIRIUS Safety. FAQ February 2012

SITRAIN. Introduction TIA Portal. Siemens AG All rights reserved. Unrestricted

FAQ about Drive Technology

TS8000. Profibus DP Slave Configuration Application Note TS8922U001

FAQ 03/2014. How do I go online? SIMOTION & SINAMICS.


Drive System Application

Drive System Application

Service & Support. How do I configure extended PROFIsafe on the CU240E-2?

Cover. IP Address Assignment Using Primary Setup Tool (PST) Electrical Lean Switch. FAQ June Service & Support. Answers for industry.

Table of Contents 1 ABOUT THIS DOCUMENT GENERAL COPYRIGHT INFORMATION TERMS ABOUT THE GATEWAY PRODUCT FUNCTIO

Getting Started - Startdrive. Startdrive SINAMICS. Introduction 1. Connecting the drive unit to the PC. Creating a project 3

SINAMICS V: Speed Control of a V20 with S (TIA Portal) via MODBUS RTU, with HMI

SIMATIC. Communications processor CP First Steps in Commissioning. Getting Started 09/2008 A5E

SINUMERIK Integrate Create MyHMI / WinCC V13 SP1 SINUMERIK. SINUMERIK 840D sl SINUMERIK Integrate Create MyHMI / WinCC V13 SP1. Preface.

Changeover SINAMICS CU240E to CU240E-2 (as from Firmware V4.4) SINAMICS G120. FAQ October Service & Support. Answers for industry.

PLC COURSE LIST NMU TRAINING CENTRE

Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE D3

FAQ about communication via IE

Operator Station (V8.0) SIMATIC. Process Control System PCS 7 Operator Station (V8.0) Preface 1. The PCS 7 Operator Station

Display of a Cam Disk of the Technology CPU with WinCC flexible in HMI. Technology CPU. FAQ Januar Service & Support. Answers for industry.

Information About the Getting Started PCS 7 - First Steps Documentation

Applications & Tools. Communication between WinAC MP and a SIMATIC S7. Application for the PUT and GET Function Blocks of the S7 Communication

Multi Panel options. SIMATIC WinAC MP 2/169

Storage Concept and Data Backup Mechanisms for SIMATIC S7-300

How Do You Replace a CPU 41x with the CPU 410-5H Process Automation? SIMATIC PCS 7 FAQ 01/2016

Block Library Motor Starter SIRIUS for SIMATIC PCS 7

SIMATIC. S7 and Profibus- DP Configuration Guide G1026

Danfoss FCD 300 AS-i and Siemens DP/AS-i Link 20E

Korea PROFIBUS/PROFINET Association 각사회사이름 각사 LOGO

Process Control System PCS 7 V7.0. Getting Started First Steps Documentation November 2006

Advanced Process Functions V2.0

SIMATIC. Process Control System PCS 7 First Steps (V7.1) Preface 1. Creating the PCS 7 Project 2. Configuring the hardware and networks

SIMATIC. PCS 7 process control system OpenPCS 7. Preface 1. Basics 2. Installation and licensing 3. PCS 7 Engineering 4. System configurations 5

General information. Supply voltage. Input current

While every effort was made to verify the following information, no warranty of accuracy or usability is expressed or implied.

Applications & Tools. Configuration of Frequency Converters with the APL Channel Block FbDrive in SIMATIC PCS 7 SIMATIC PCS 7 V8.0

Press Presse Press Presse


Display of SINAMICS Error Messages in Runtime Professional

Display of SINAMICS Fault Messages in WinCC V7.4


Service & Support. How do you create a weekly timer with WinCC flexible? WinCC flexible 2008 SP2. FAQ October Answers for industry.

SIMATIC. PCS 7 process control system OpenPCS 7 (V8.1) Preface 1. Basics 2. Installation and licensing 3. PCS 7 Engineering 4. System configurations 5

SIMATIC HMI. WinCC V7.0 SP1 MDM - WinCC/Options for Process Control. Overview of process control system options 1. OS Project Editor 2.

General information. Supply voltage. Input current

General information. Supply voltage. Input current

FAQ Kommunikation over PROFIBUS

Connecting UniOP to Simatic S7 Profibus

CPU 319F-3 PN/DP. Page 1682 Mar 2008 Siemens ITS

SIMATIC HMI. WinCC V7.4 WinCC/Options for Process Control. Overview of process control system options 1. OS Project Editor 2.

Micro Application Example

Service & Support. S7 Diagnostics Block for the 3RK3 Modular Safety System (MSS) SIMATIC S7 300/400 CPU. FAQ February Answers for industry.

Applications & Tools. Configuration of SINAMICS and MICROMASTER Drives with Drive ES in PCS 7 SIMATIC PCS 7. Application Example February 2012


SCE Training Curriculum for Integrated Automation Solutions Totally Integrated Automation (TIA)

Application for Process Automation

Applications & Tools. Remote Control of Operator Panel in Applications requiring Validation in the Pharmaceutical Environment


General information. Supply voltage. Input current

www. ElectricalPartManuals. com SIMATIC HMI WinCC flexible 2005 Communication Part 1 Preface Working with connections 1

SIMATIC. Process Control System PCS 7 Operator Station. Preface, Contents. The PCS 7 OS 1 Introduction to PCS 7 OS Configuration

Creating the program. TIA Portal. SIMATIC Creating the program. Loading the block library 1. Deleting program block Main [OB1]

PROFIBUS DP/CAN Gateway PCA-100. User Manual

Drive System Application


SIMATIC. PCS 7 process control system OpenPCS 7 (V8.2) Security information 1. Preface 2. Basics 3. Installation and licensing 4. PCS 7 Engineering 5

STEP 7 function block to control a MICROMASTER 4 or SINAMICS G120/G120D via PROFIBUS DP

SIMATIC. Process Control System PCS 7 PCS 7 Documentation (V8.1) Options for Accessing Documentation 1. Documentation for the Planning Phase 2

FAQ 05/2016. How do you configure the horn in SIMATIC PCS 7?

SITRAIN Training for Industry. Customer Services Information 2019

CAN 300 PRO, Communication Module

Applications & Tools. Time-of-Day Synchronization between WinCC Runtime Professional and S7 Controllers. WinCC Runtime Professional

SCE Training Curriculum for Integrated Automation Solutions Totally Integrated Automation (TIA)

Description of the Simotion D4xx Firmware update

I-Device Function in Standard PN Communication SIMATIC S7-CPU, CP, SIMOTION, SINUMERIK. Configuration Example 08/2015

Sitrain. Training which combines theory and practice. Complete training catalogue. Innovation for generations.

SIMATIC. Automation Systems S7-300 CPU 317T-2 DP: Controlling a SINAMICS S120. Introduction. Preparation 2. Learning units 3. Further Information 4

Deckblatt. APL Operator Guide SIMATIC PCS 7. Application description June Applikationen & Tools. Answers for industry.

Applications & Tools. Configuration of Direct Starters with the APL Channel Block FbSwtMMS in SIMATIC PCS 7 SIMATIC PCS 7 V8.0

Besides PU functions with S5 for Windows also S7-HMI devices can read and write variables from the PLC. The following protocols are supported:

Cut down your costs, increase your productions efficiently with the knowledge of PLC s Siemens technology. SITRAIN TM THAILAND Page 1 of 13

Sample project Filling Station SIMATIC. STEP 7 Professional / WinCC Advanced V11 for Sample project Filling Station. Overview of the Getting.

SIMATIC. Component based Automation - WinLC PN Addendum to WinAC Basis V3.0. Foreword. Introduction to CBA and WinAC PN 2. Routing with WinLC PN 3

Aotewell SIMATIC S7-PDIAG for S7-300 and S Configuring Process Diagnostic Getting St

Spring Training Atlanta, GA

Programmable Controllers

Commissioning PC Stations - Manual. and Quick Start SIMATIC NET. PC software Commissioning PC Stations - Manual and Quick Start.

SIMATIC. Process Control System PCS 7 Getting Started Part 1. Preface, Contents. Requirements for Getting Started 1.

Transcription:

Cover How can you display error messages and warnings of a frequency converter on a panel? WinCC flexible RT and Panels FAQ February 2011 Service & Support Answers for industry.

Question This entry is from the Service&Support portal of Siemens AG, Sector Industry, Industry Automation and Drive Technologies. The general terms of use (http://www.siemens.com/terms_of_use) apply. Clicking the link below directly displays the download page of this document. http://support.automation.siemens.com/ww/view/en/29522676 Question How can you display error messages and warnings of a frequency converter on a panel? Answer The instructions and notes listed in this document provide a detailed answer to this question. 2 V1.0, Item-ID: 29522676

Table of content Table of content 1 Introduction... 4 2 Direct Connection (Panel to Frequency Converter)... 5 2.1 Configuration... 5 2.2 Sample Configuration of the Micromaster 440... 6 2.3 Sample Configuration of the MP 377 12" Touch... 7 2.4 Settings in WinCC Flexible... 8 2.5 Inserting and Configuring the Library... 9 2.6 Commissioning... 13 2.7 Expansion... 14 3 Alternatives... 16 3.1 Additional Controller with PROFIBUS... 16 3.2 Additional Controller with USS Protocol... 16 V1.0, Item-ID: 29522676 3

1 Introduction 1 Introduction In this FAQ we describe how to read out all error and warning parameters from a frequency converter of the SINAMICS/Micromaster family and display them on a panel. A library has been created in WinCC flexible for the error and warning messages. This FAQ gives a detailed description of how to establish a direct connection between a converter and the panel via PROFIBUS (except SINAMICS G110). NOTE Any HMI panel that supports PROFIBUS DP can be used as operator panel. NOTE The error and warning messages can also be read out with other connections. For example, via a connection with a S7 300 CPU or via the USS protocol and an S7 200 CPU. 4 V1.0, Item-ID: 29522676

2 Direct Connection (Panel to Frequency Converter) 2.1 Configuration The components below have been used in this sample configuration: Micromaster 440 with PROFIBUS module MP 377 12" Touch WinCC flexible 2008 The components were interconnected in a PROFIBUS DP network as in Figure 2-1. Figure 2-1 s SIMATIC MULTI PANEL TOUCH O 12 N s NOTE The R parameters (display parameters) can only be read. The P parameters can be read and written. Note here that different P parameters can only be written depending on other parameters (Quick commissioning mode, for example). More information about the parameters is available in the manual of the frequency converter concerned in each case. The manuals are available at the link below: http://support.automation.siemens.com/ww/view/de/10804921/133300. V1.0, Item-ID: 29522676 5

2.2 Sample Configuration of the Micromaster 440 You must assign a PROFIBUS address to the Micromaster to establish a connection via PROFIBUS DP. You have two options for this in the case of Micromaster MM440: Via the DIP switches on the PROFIBUS module. Via a user-specified value at parameter P0918 (DIP switches must be set to 0). If the DIP switch is not set to 0, the switch position always has priority. If this is set to 0, the bus address is determined by P0918. See here the examples in Figure 2-2. Figure 2-2 Table 2-1 No. Procedure 1 Configure the parameters of the Micromaster 440 with the specifications of the motor you have connected. 2 Connect you PROFIBUS module to the Micromaster 440. 3 Use the DIP switches to set the PROFIBUS address to 4. 6 V1.0, Item-ID: 29522676

2.3 Sample Configuration of the MP 377 12" Touch You must also configure a PROFIBUS address on the MP 377 12" Touch. This is done using the "Control Panel". Here you can configure the type of connection and its settings under "S7 Transfer Settings". Table 2-2 No. Procedure 1 Start the MP 377 12" Touch by switching on the power supply. 2 Open the "Control Panel" with the "Control Panel" button. 3 Select the "S7 Transfer Settings" option by double-clicking the "Transfer" field. 4 Mark the field PROFIBUS and open the bus settings by clicking "Properties...". Set the PROFIBUS address to 3. Make sure that the transmission rate is set to 1.5 Mbits/s. Select the option "Panel is the only master on the bus". 5 Click OK to confirm the settings made. V1.0, Item-ID: 29522676 7

Note "Only master on the bus" Disable any additional safety function against bus defects when connecting the operator panel to the network. A passive station (slave) can only send data when if requested to do so by an active station (master). Since the panel is to request the information from the Micromaster (active node) and there is no controller in between, it is mandatory to enable this option. 2.4 Settings in WinCC Flexible In WinCC flexible you must configure a SIMATIC S7 300/400 connection. The frequency converter is recognized as such a station. Here you must pay attention to the correct transmission rate, the address of the operator panel, the network configuration and the address of the controller or frequency converter. Figure 2-3 Follow the instructions in the table below to configure the connection in WinCC flexible. 8 V1.0, Item-ID: 29522676

Table 2-3 No. Procedure 1 Double-click to open the connection settings. 2 Create a new connection. This should be a SIMATIC S7 300/400 connection. 3 In the parameters you now configure the bus settings for the operator panel. Set the baud rate to 1500000. The access point is "S7ONLINE". The address must be identical to that which you set for the "S7 Transfer Settings" in the MP 377 12" Touch. Set the bus address to 3. Make sure that the "Only master on the bus" field is checked. 4 Set the network profile to "DP". Only one master is allowed in this network. 5 Now configure the controller. The address must be identical to that which you assigned using the DIP switches on the PROFIBUS module of the Micromaster 440. Set the bus address to 4. You do not need to worry about the slot and rack. 2.5 Inserting and Configuring the Library The error and warning messages of the frequency converter are collected together in a library. You can use the library with the converters below: G110 G120 V1.0, Item-ID: 29522676 9

Micromaster 410 Micromaster 420 Micromaster 430 Micromaster 440 S120 The library allows you to use drag & drop to incorporate message texts in two languages (German/English) into your project. The library has four different lists. A distinction is made in S120 and G110/G120/Micromaster whereby you can choose from short message texts (25 characters) and long texts (80 or 100 characters) in each case. A message consists of: Error number tags ("ErrorNo1") Warning number tags ("WarningNo1") A text list Two variables have been created for the error and warning messages, because these are represented by two different parameters in the frequency converter. Note The errors and warnings issued by the frequency converter can be output in two steps. However, in this example we have simplified matters and used just the first step. Therefore, only the message is output and not the additional error value and description. Follow the steps described in the table to insert the library. 10 V1.0, Item-ID: 29522676

Table 2-4 No. Procedure 1 Save the archive file in a directory of your choice and unpack it. 2 Right-click to open the WLF file in the library window of the working area with "Library > Open". 3 Incorporate the messages of the library "G110_G120_80Chr" by dragging and dropping them into the analog messages. V1.0, Item-ID: 29522676 11

No. Procedure 4 Open the "Tags" window and configure them. Set the configured connection. Change the data type to WORD. The parameter for error messages is the address DB 947 DBW 0. The parameter for warning messages is the address DB 2110 DBW 0. The following holds here: Parameter number = Data block number Note When using a SINAMICS S110/S120 note that the converter is split into separate drive objects (DO), for example DO1 = Control Unit, DO2 = Motor module 1, DO3 = Motor module 2 etc.). When you read out a parameter, you must also specify the relevant drive object. The parameter r947 in DO1 => DB 947 DBW xxxx. xxxx is calculated, for example, from 1024 * drive object number (DO no.) + subindex. Example From parameter r947 the index 4 is to be read out of DO2. The calculation here is 1024 * 2 + 4 = 2052. 5 You must insert a message display in the desired picture in order to display messages on the MP 377 12" Touch. You insert a message display by dragging and dropping the message display into the picture under the option "Extended Objects". 12 V1.0, Item-ID: 29522676

No. Procedure 6 You can now adapt the message display to suit your requirements. It is important to check the Errors and Warning fields. Note You can change the message number and message texts of the inserted library yourself to suit your needs. Furthermore, you also have the option of using the text list in a symbolic I/O field. 2.6 Commissioning Check the wiring of the components to commission the configuration. Download the WinCC flexible project to the MP 377 12" Touch. Start the complete plant and the messages are transferred to the configured message display. V1.0, Item-ID: 29522676 13

Figure 2-4 2.7 Expansion You can also control parameters individually with the direct connection. It is not possible to control "R parameters" with the acyclic data traffic used. However, you can change the "P parameters" using the panel. This expansion is explained taking the example of fixed frequencies. Follow the instructions below. 14 V1.0, Item-ID: 29522676

Table 2-5 No. Procedure 1 Create 3 tags in your WinCC flexible project (Fixed_frequency_1; Fixed_frequency_2; Fixed_frequency_3). The parameter numbers are: Fixed_frequency_1: P1001 Fixed_frequency_2: P1002 Fixed_frequency_3: P1003 (These can be taken from the parameter list of the frequency converter.) 2 In the picture you create 3 I/O fields and link these to the relevant tags. 3 Transfer the project again and start Runtime on the panel. 4 Click in one of these I/O fields created. The screen keyboard is displayed. Using the screen keyboard you enter a different value and confirm it with "Enter". 5 The value is applied and is now displayed in the I/O field. In this way you have made a user-defined change to the fixed frequencies. V1.0, Item-ID: 29522676 15

3 Alternatives 3 Alternatives 3.1 Additional Controller with PROFIBUS The frequency converter is controlled and monitored by a PLC via PROFIBUS. The controller forwards the relevant parameters to the operator panel. 3.2 Additional Controller with USS Protocol The SINAMICS G110 frequency converter supports only the USS protocol and does not support PROFIBUS. For the USS protocol there are communication blocks for the S7-200. Micro Automation Set 26 provides a general solution. http://support.automation.siemens.com/ww/view/de/21690362 16 V1.0, Item-ID: 29522676