Parameters MICROMASTER 420

Similar documents
COMBIMASTER 411 & MICROMASTER 411

MICROMASTER 430. Parameter List Issue 03/02. User Documentation 6SE6400-5AF00-0BP0

List Manual Issue 11/2004. simatic. Frequency Converter ET 200S FC Control Unit ICU24 Power Module IPM25

Parameter Manual Issue 07/2005. simatic. Frequency Converter ET 200S FC Power Module IPM25 Control Unit ICU24 / ICU24F

Parameter Manual Edition 06/2007

Parameter Manual Edition 05/2007

Optidrive Applications Support Library

5 MICROMASTER 420 specifications

Firmware Manual - EC Series Drives

Metasys N2 Instruction Manual VLT Adjustable Frequency Drive. 12/ Revision B

Optidrive Applications Support Library

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Revision 1.10

Using USS Protocol with SED2

5 MICROMASTER 440 specifications

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Revision 2.00

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Issue 06

3GV M Modbus RTU Register Map

Optidrive VTC Modbus RTU Register Map

ADVANCED OPERATOR PANEL (AOP)

MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION

MODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION

QUICK REFERENCE GUIDE

Operating Instructions Edition 10/2007

Quick Start Guide For GVX9000 AF Drives

PowerFlex 40 Sample Specification

GV3000/SE AC Drive Quick Reference Version 6.06

vacon nx ac drives brake chopper unit (bcu) application user s manual

Micro Application Example

VFA7/VFP7 Parameter List (Ver315)

E2 Modbus RTU Register Map Revision History Version Comments Author Date 1.02 Previous version PAE 11/06/ Revised to new format PAE 09/03/09

MC Series Drives. Flexible, simple, rugged, robust!

lnvertek Drives.com ct,ve ELECTRICAL SUPPLIERS LTD

VLT 2800 DRIVE SPECIFICATIONS

E2 Modbus RTU Register Map

ATV12P037F1 variable speed drive ATV kW hp V - 1ph - on base plate

MICROMASTER 4 th. Generation. A&D SD Thailand MM4 Next.Generation /50

Optidrive Plus 3 GV. Advanced User Guide. Vertical Market Solution : Industrial Washing Machines. Revision 1.00

FLÄKTGROUP OFFERS A WIDE RANGE OF PER- MANENT MAGNET MOTORS (PM) AND FREQUENCY CONVERTERS FOR PLUG FANS. POWER RANGE IS FROM 0,8 KW TO 15 KW.

Parameter Reference Guide. KBG2 Series. RFC-A Mode

SENSORLESS VECTOR CONTROL

ATV12H018M2 variable speed drive ATV kW hp V - 1ph

Quick Start Guide Cutler-Hammer SVX9000 Drives from Eaton Corporation CONTENT STEP 1 Keypad Operation Overview STEP 2 Standard Wiring Diagrams and

CATALOG SELECTION / PRODUCT SELECTION

ATV12HU22M3 variable speed drive ATV12-2.2kW - 3hp V - 3ph - with heat sink

4. Setting parameters

ACOPOSinverter P74. User's Manual. Version: 2.20 (August 2016) Model no.: Original instruction

AF-60 LP TM Micro Drive. Programming Guide

ATV12H075M3 variable speed drive ATV kW - 1hp V - 3ph - with heat sink

ATV310HU30N4E variable speed drive ATV310-3 kw - 4 hp V - 3 phase

MOTOR STARTERS & VARIABLE SPEED DRIVES Variable speed drives

Frequency Inverters WJ200 Series Compact Inverter

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III

Flexible, simple, economical, robust.

HVAC Products. Introducing the SED2 Variable Frequency Drives

ATV12P075M3 variable speed drive ATV kW - 1hp V - 3ph - on base plate

Parameter Reference Guide. Unidrive M200. RFC-A Mode. Issue:

DriveWare. User s Guide DriveConfig

SV9000 AF DRIVES SVReady User Manual. Pump and Fan Control Application

VARIABLE SPEED DRIVES VLA1 SERIES

Technical Instructions Document No February 25, Modbus RTU Interface Module for SED2. Description. Product Part Number

SED2 EasyComm Startup and Operating Instructions

TR200 DRIVE STANDARD FEATURES

ATV320U04N4C variable speed drive ATV kW V - 3 phase - compact

ATV310H075N4E variable speed drive ATV kw - 1 hp V - 3 phase

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

MAKING MODERN LIVING POSSIBLE. Instruction VLT HVAC Basic Drive Cascade Controller

KOLLMORGEN. SERVOSTAR CD. SERCOS IDN Manual M-SS rev. F. Solutions by D A N A H E R M O T I O N

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety

ATV320U07M2C variable speed drive ATV kW V - 1 phase - compact

Tracking the MOP setpoint to another setpoint source to bumplessly changeover the setpoint

TL5 Programming Terminal USER MANUAL

3 CU240E-2 6SL3244-0BB12-1BA1 3 CU240E-2 DP 6SL3244-0BB12-1PA1. RS485/USS 6 3 (opt. per 2 DI) 3 CU240E-2 F 6SL3244-0BB13-1BA1

RT4F-48V/50A-WAC RECTIFIER

Unidrive M400 (Frame 1 to 4) Quick Start Guide

OPTIDRIVE PLUS 3 GV 3 rd Generation Vector Control AC Variable Speed Drive kW

Frequency Inverters. WJ200 Series. Compact Inverter. WJ200 Series

SINAMICS IOP. Intelligent Operator Panel. Operating Instructions February 2009 SINAMICS

SED2 Variable Frequency Drives

ATV32HU11M2437 variable speed drive ATV32-1.1kW 200V - 1P - Bluetooth built-in - w heat sink

E510. Compact Drive IP 20/ NEMA HP (230V) 1-75 HP (460V)

COMBIMASTER 411 & MICROMASTER 411

Powered to Perform. Everyday Reliability. Exceptional Value. Expertise and Support

PART 1: GENERAL PART 2: PRODUCT. Effective: 12/29/10 Page 1 of 6 FECA-TE-104D

MODBUS TCP MODULE INSTRUCTIONS. for use with WSIQ2/WSE

CU250S-2 Control Units SINAMICS. SINAMICS G120 CU250S-2 Control Units. Fundamental safety instructions 1. Scope of delivery.

ABB Industrial Systems Inc. Standard Drives. ACH500-06E Effective 6/1/95

Vacon HVAC100 Commissioning Guide

EQ5 SERIES Quick Start Guide for Constant Torque Applications

The easy to use three-phase digital DC drive for regenerative and non-regenerative applications from HP

1.1.1 Software Version Introduction About this Manual References 2

Instructions. Modbus RTU Card (WSIQ-COM-MB)

160 AA02SF1 AF DS-D17

Specification Number: Product Name: FRENIC-Mega AC Drives for General Purpose Applications (½ - 150Hp at 230V and ½ Hp at 460V)

Q9 ASD LOW VOLTAGE DRIVE

1336 PLUS II Quick Start Guide

YASKAWA AC Drive - Z1000

GE Consumer & Industrial Electrical Distribution. AF-600 FP TM Metasys. Operating Instructions

RT4F-110V/25A RECTIFIER

CU240S CU240S DP CU240S DP-F CU240S PN CU240S PN-F

1. GENERAL 2 2. DESCRIPTION 2 3. CONNECTION 3 4. PARAMETER ACCESS CODE 3

Transcription:

Parameters MICROMASTER 40 This Parameter List must only be used together with the Operating Instructions or the Reference Manual of the MICROMASTER 40. Especially pay attention to all the warnings and Notices and Notes contaned in that manual. Table of Contents 1 Introduction to MICROMASTER System Parameters... Parameter overview in functional groups... 4 Parameter Description... 11 6SE6400-5BA00-0BP0

Introduction to MICROMASTER System Parameters 1 Introduction to MICROMASTER System Parameters The layout of the parameter description is as follows. 1 Par number Parameter name 9 Min: CStat: 5 Datatype 7 Unit: 10 Def: 4 P-Group: 6 active: 8 Quick Comm: 11 Max: 1 1 Description: 1. Parameter number Indicates the relevant parameter number. The numbers used are 4-digit numbers in the range 0000 to 9999. Numbers prefixed with an r indicate that the parameter is a read-only parameter, which displays a particular value but cannot be changed directly by specifying a different value via this parameter number (in such cases, dashes - are entered at the points Unit, Min, Def and Max in the header of the parameter description. All other parameters are prefixed with a P. The values of these parameters can be changed directly in the range indicated by the Min and Max settings in the header and Possible settings section (see item 10 below).. Parameter name Indicates the name of the relevant parameter Certain parameter names include the following abbreviated prefixes: BI, BO, CI, and CO followed by a colon. These abbreviations have the following meanings: BI = Binector input, i.e. parameter selects the source of a binary signal BO = Binector output, i.e. parameter connects as a binary signal CI = Connector input, i.e. parameter selects the source of an analog signal CO = Connector output, i.e. parameter connects as an analog signal CO/BO = Connector/Binector output, i.e. parameter connects as an analog signal and/or as a binary signal Note A separate description on how to interpret and use the BICO technology is given in the MICROMASTER MM40 Reference Manual.. CStat Commissioning status of the parameter. Three states are possible Commissioning C Ready to run U Run T This indicates when the parameter can be changed. One, two or all three states may be specified. If all three states are specified, this means that it is possible to change this parameter setting in all three inverter states 4. P-Group Indicates the functional group of the particular parameter (see Section entitled Functional grouping of parameters in this Introduction to MICROMASTER System Parameters ). Section A.7 below provides a table showing the parameters arranged according to their functional grouping. Note Parameter P0004 (parameter filter) acts as a filter and focuses access to parameters according to the functional group selected. 5. Datatype The data types available are shown in the table below. The notation used in the Parameters MICROMASTER 40 6SE6400-5BA00-0BP0

Introduction to MICROMASTER System Parameters MICROMASTER MM4 Inverter Series is listed in Column 1, while the corresponding notation applicable to the MASTERDRIVES Series is listed in Column. Column provides the meaning, which is identical in each case. Notation Meaning U16 16-bit unsigned U -bit unsigned I16 16-bit integer I -bit integer Float Floating point 6. Active Indicates whether Immediately changes to the parameter values take effective immediately after they have been entered, or Cornfirm the P button on the operator panel (BOP or AOP) must be pressed before the changes take effect. 7. Unit Indicates the unit of measure applicable to the settable values 8. QuickComm Indicates whether or not (Yes or No) a parameter can only be changed during quick commissioning, i.e. when P0010 (parameter groups for commissioning) is set to 1 (quick commissioning). 9. Min Indicates the minimum value to which the parameter can be set. 10. Def Indicates the default value, i.e. the value which applies if the user does not specify a particular value for the parameter. 11. Max Indicates the maximum value to which the parameter can be set. 1. Level Indicates the level of user access. There are four access levels: Standard, Extended, Expert and Service. The number of parameters that appear in each functional group depends on the access level set in P000 (user access level). 1. Description The parameter description ma yconsist of the following sections and contents: Description: Brief explanation of the parameter function. Diagram: Where applicable, diagram to illustrate the effects of parameters on a characteristic curve, for example Possible settings Listing of possible settings Common settings: Example: Listing of most common settings, if the complete listing would contain toomuch items Optional example of the effects of a particular parameter setting. Any conditions that must be satisfied in connection with this parameter. Also any particular effects, which this parameter has on other parameter(s) or. Warning / Caution / Notice / Note Important information which must be heeded to prevent personal injury or damage to equipment/specific information which should be heed in order to avoid problems or may helpful to the user More details: Any sources of more detailed information concerning the particular parameter. Parameters MICROMASTER 40 6SE6400-5BA00-0BP0

Parameter overview in functional groups Parameter overview in functional groups The tables below provide an overview of the parameters available for the MICROMASTER 40 arranged according to functional groups. Quick commissioning (P0010=1) No Name Access level Cstat P0100 Europe / North America 1 C P000 Select motor type C P004 Motor voltage rating 1 C P005 Motor current rating 1 C P007 Motor power rating 1 C P008 Motor cosphi rating C P009 Motor efficiency rating C P010 Motor frequency rating 1 C P011 Motor speed rating 1 C P00 Motor magnetizing current CT P05 Motor cooling CT P0640 Motor overload factor [%] CUT P0700 Selection of command source 1 CT P1000 Selection of frequency setpoint 1 CT P1080 Min. speed 1 CUT P108 Max. speed 1 CT P110 Ramp-up time 1 CUT P111 Ramp-down time 1 CUT P115 OFF ramp-down time CUT P100 Control mode CT P1910 Select motor data identification CT P900 End of quick commissioning 1 C When P0010=1 is chosen, P000 (user access level) can be used to select the parameters to be accessed. This parameter also allows selection of a user-defined parameter list for quick commissioning. At the end of the quick commissioning sequence, set P900 = 1 to carry out the necessary motor calculations and clear all other parameters (not included in P0010=1) to their default settings. Note This applies only in Quick Commissioning mode. Reset to Factory default To reset all parameters to the factory default settings; the following parameters should be set as follows: Set P0010=0. Set P0970=1. Note The reset process takes approximately 10 seconds to complete. Reset to Factory default Parameters MICROMASTER 40 4 6SE6400-5BA00-0BP0

Parameter overview in functional groups Functional groups No Name Access level ADC and DAC r0750 Number of ADCs - r075 Act. input of ADC [V] or - P075 Smooth time ADC CUT r0754 Act. ADC value after scaling [%] - r0755 CO: Act. ADC after scal. [4000h] - P0756 Type of ADC CT C-Stat P0757 Value x1 of ADC-scaling CUT P0758 Value y1 of ADC-scaling CUT P0759 Value x of ADC-scaling CUT P0760 Value y of ADC-scaling CUT P0761 Width of ADC deadband CUT P076 Delay for loss of signal action CUT P0770 Number of DACs - P0771 CI: DAC CUT P077 Smooth time DAC CUT r0774 Act. DAC value [V] or - P0776 Type of DAC CT P0777 Value x1 of DAC-scaling CUT P0778 Value y1 of DAC-scaling CUT P0779 Value x of DAC-scaling CUT P0780 Value y of DAC-scaling CUT P0781 Width of DAC deadband CUT Alarms / warnings / monitoring r0947 Last fault code - r0948 Fault time - P095 Total number of faults CT P100 Alarm number stop reaction CT P101 Stop reaction value CT r110 Warning number - P111 Total number of warnings CT r114 Run time counter - P115 AOP real time clock CT P150 Hysteresis speed n_hys CUT P155 Threshold speed n_1 CUT P156 Delay time f1 CUT P164 Hysteresis speed.-deviation CUT P167 Switch-off speed n_off CUT P168 Delay Toff (inverter switch-off) CUT P170 Threshold current I,thresh CUT P171 Delay time current CUT P17 Threshold voltage Vdc,thresh CUT P17 Delay time Vdc CUT P179 Current limit for no load ident. CUT P180 Delay time for no load ident. CUT r197 CO/BO: Status word 1 of monitor - Communication P0918 CB address CT P097 Parameter changeable via CUT r0964 Firmware version data - r0967 Control word 1 - r0968 Status word 1 - P0971 Transfer data from RAM to EEPROM CUT P000 Reference frequency CT P001 Reference voltage CT Parameters MICROMASTER 40 6SE6400-5BA00-0BP0 5

Parameter overview in functional groups No Name Access level P00 Reference current CT P00 Reference torque CT C-Stat P009 USS normalization CT P010 USS baudrate CUT P011 USS address CUT P01 USS PZD length CUT P01 USS PKW length CUT P014 USS telegram off time CT r015 CO: PZD from BOP-Link (USS) - P016 CI: PZD to BOP-Link (USS) CT P018 CO: PZD from COM-Link (USS) - P019 CI: PZD to COM-Link (USS) CT r04 USS error-free telegrams - r05 USS rejected telegrams - r06 USS character frame error - r07 USS overrun error - r08 USS parity error - r09 USS start not identified - r00 USS BCC error - r01 USS length error - r0 BO: CtrlWrd1 from BOP-Link (USS) - r0 BO: CtrlWrd from BOP-Link (USS) - r06 BO: CtrlWrd1 from COM-Link (USS) - r07 BO: CtrlWrd from COM-Link (USS) - P040 CB telegram off time CT P041 CB parameter CT r050 CO: PZD from CB - r051 CI: PZD to CB CT r05 CB identification - r054 CB diagnosis - r090 BO: Control word 1 from CB - r091 BO: Control word from CB - Commands / binary I/O r0000 Drive display 1 r000 Drive state r0019 CO/BO: BOP control word - r005 CO/BO: Status word 1 - r005 CO/BO: Status word - r0054 CO/BO: Control word 1 - r0055 CO/BO: Control word - P0700 Selection of command source 1 CT P0701 Function of digital input1 CT P070 Function of digital input CT P070 Function of digital input CT P0704 Function of digital input4 CT P0719 Selection of cmd. & freq. setp. CT r070 Number of digital inputs - r07 CO/BO: Binary input values - P074 Debounce time for digital inputs CT P075 PNP / NPN digital inputs CT r070 Number of digital outputs - P071 BI: Function of digital output CUT r0747 CO/BO: State of digital outputs - P0748 Invert digital outputs CUT P0800 BI: Download parameter set 0 CT P0801 BI: Download parameter set 1 CT P0840 BI: ON/OFF1 CT P084 BI: ON/OFF1 reverse CT Parameters MICROMASTER 40 6 6SE6400-5BA00-0BP0

Parameter overview in functional groups No Name Access level P0844 BI: 1. OFF CT P0845 BI:. OFF CT P0848 BI: 1. OFF CT P0849 BI:. OFF CT P085 BI: Pulse enable CT P100 BI: Fixed freq. selection Bit 0 CT P101 BI: Fixed freq. selection Bit 1 CT P10 BI: Fixed freq. selection Bit CT P105 BI: Enable MOP (UP-command) CT P106 BI: Enable MOP (DOWN-command) CT P1055 BI: Enable JOG right CT P1056 BI: Enable JOG left CT P1074 BI: Disable additional setpoint CUT P1110 BI: Inhibit neg. freq. setpoint CT P111 BI: Reverse CT P114 BI: Enable JOG ramp times CT P10 BI: Enable DC braking CUT P10 BI: 1. Faults acknowledgement CT P104 BI:. Faults acknowledgement CT P106 BI: External fault CT P0 BI: Fixed PID setp. select Bit 0 CT P1 BI: Fixed PID setp. select Bit 1 CT P BI: Fixed PID setp. select Bit CT P5 BI: Enable PID-MOP (UP-cmd) CT P6 BI: Enable PID-MOP (DOWN-cmd) CT Motor control r000 CO: Act. speed setpoint - r001 CO: Act. speed - r00 Act. rotor speed - r004 CO: Act. output frequency - r005 CO: Act. output voltage - r007 CO: Act. output current - r0056 CO/BO: Status of motor control - r0067 CO: Act. drive current limit - r0071 CO: Max. output voltage - r0086 CO: Act. active current - C-Stat P100 Control mode CT P110 Continuous boost CUT P111 Acceleration boost CUT P11 Starting boost CUT P116 Boost end frequency CUT P10 Programmable V/F freq. coord. 1 CT P11 Programmable V/F volt. coord. 1 CUT P1 Programmable V/F freq. coord. CT P1 Programmable V/F volt. coord. CUT P14 Programmable V/F freq. coord. CT P15 Programmable V/F volt. coord. CUT P1 Start frequency for FCC CUT P15 Slip compensation CUT P16 Slip limit CUT r17 CO: Slip frequency - P18 Resonance damping gain V/F CUT P140 Imax controller prop. gain CUT P141 Imax controller integral time CUT r14 CO: Imax controller freq. output - r144 CO: Imax controller volt. output - P150 Voltage soft start CUT Drive features Parameters MICROMASTER 40 6SE6400-5BA00-0BP0 7

Parameter overview in functional groups No Name Access level C-Stat P0005 Display selection CUT P0006 Display mode CUT P0007 Backlight delay time CUT P0011 Lock for user defined parameter CUT P001 Key for user defined parameter CUT P001 User defined parameter CUT P100 Flying restart CUT P10 Motor-current: Flying start CUT P10 Search rate: Flying start CUT P110 Automatic restart CUT P111 Number of restart attempts CUT P115 Holding brake enable T P116 Holding brake release delay T P117 Holding time after ramp down T P1 DC braking current CUT P1 Duration of DC braking CUT P16 Compound braking current CUT P17 Dynamic braking duty cycle CUT P140 Configuration of Vdc controller CT r14 CO: Switch-on level of Vdc-max - P14 Dynamic factor of Vdc-max CUT P15 Vdc-controller output limitation CUT P154 Auto detect Vdc switch-on levels CT Inverter r0018 Firmware version 1 - r006 CO: Act. DC-link voltage - r004 Motor thermal protection (It) - r007 CO: Drive temperature - r009 CO: Energy consumpt. meter [kwh] - P0040 Reset energy consumption meter CT r000 Act. power stack code number - P001 Power stack code number C r00 Act. power stack type - r004 Power stack features - r006 Rated drive power or - r007 Rated drive current - r008 Rated drive voltage - P010 Supply voltage CT r01 Max. cable length - P090 Drive overload reaction CT P091 Config. of inverter protection CT P09 Drive overload warning CUT P1800 Pulse frequency CUT r1801 CO: Act. switching frequency - P180 Modulator mode CUT P180 Reverse output phase sequence CT Motor P000 Select motor type C P004 Motor voltage rating 1 C P005 Motor current rating 1 C P007 Motor power rating 1 C P008 Motor cosphi rating C P009 Motor efficiency rating C P010 Motor frequency rating 1 C P011 Motor speed rating 1 C r01 Motor pole pairs - P00 Motor magnetizing current CT r00 Rated motor slip - Parameters MICROMASTER 40 8 6SE6400-5BA00-0BP0

Parameter overview in functional groups No Name Access level r01 Rated magnetisation current - r0 Rated power factor - P05 Motor cooling CT P040 Calculation of motor parameters CT C-Stat P044 Motor weight CUT P046 Magnetization time CUT P047 Demagnetization time CUT P050 Stator resistance (line-to-line) CUT r084 Rotor time constant - r095 Total stator resistance [%] - P0610 Motor It temperature reaction CT P0611 Motor It time constant CT P0614 Motor It overload warning time CT P0640 Motor overload factor [%] CUT P1910 Select motor data identification CT r191 Identified stator resistance CUT Setpoint channel / RFG P1000 Selection of frequency setpoint 1 CT P1001 Fixed frequency 1 CUT P100 Fixed frequency CUT P100 Fixed frequency CUT P1004 Fixed frequency 4 CUT P1005 Fixed frequency 5 CUT P1006 Fixed frequency 6 CUT P1007 Fixed frequency 7 CUT P1016 Fixed frequency mode - Bit 0 CT P1017 Fixed frequency mode - Bit 1 CT P1018 Fixed frequency mode - Bit CT r104 CO: Act. fixed frequency - P101 Setpoint memory of the MOP CUT P10 Inhibit reverse direction of MOP CT P1040 Setpoint of the MOP CUT r1050 CO: Act. Output freq. of the MOP - P1058 JOG frequency right CUT P1059 JOG frequency left CUT P1060 JOG ramp-up time CUT P1061 JOG ramp-down time CUT P1070 CI: Main setpoint CT P1071 CI: Main setpoint scaling CT P1075 CI: Additional setpoint CT P1076 CI: Additional setpoint scaling CT r1078 CO: Total frequency setpoint - r1079 CO: Selected frequency setpoint - P1080 Min. speed 1 CUT P108 Max. speed 1 CT P1091 Skip frequency 1 CUT P109 Skip frequency CUT P109 Skip frequency CUT P1094 Skip frequency 4 CUT P1101 Skip frequency bandwidth CUT r1114 CO: Freq. setp. after dir. ctrl. - r1119 CO: Freq. setp. before RFG input - P110 Ramp-up time 1 CUT P111 Ramp-down time 1 CUT P110 Ramp-up initial rounding time CUT P111 Ramp-up final rounding time CUT P11 Ramp-down initial rounding time CUT P11 Ramp-down final rounding time CUT Parameters MICROMASTER 40 6SE6400-5BA00-0BP0 9

Parameter overview in functional groups No Name Access level C-Stat P114 Rounding type CUT P115 OFF ramp-down time CUT r1170 CO: Speed setpoint - Technology controller P00 BI: Enable PID controller CT P01 Fixed PID setpoint 1 CUT P0 Fixed PID setpoint CUT P0 Fixed PID setpoint CUT P04 Fixed PID setpoint 4 CUT P05 Fixed PID setpoint 5 CUT P06 Fixed PID setpoint 6 CUT P07 Fixed PID setpoint 7 CUT P16 Fixed PID setpoint mode - Bit 0 CT P17 Fixed PID setpoint mode - Bit 1 CT P18 Fixed PID setpoint mode - Bit CT r4 CO: Act. fixed PID setpoint - P1 Setpoint memory of PID-MOP CUT P Inhibit rev. direct. of PID-MOP CT P40 Setpoint of PID-MOP CUT P50 CO: Output setpoint of PID-MOP - P5 CI: PID setpoint CUT P54 CI: PID trim source CUT P55 PID setpoint gain factor CUT P56 PID trim gain factor CUT P57 Ramp-up time for PID setpoint CUT P58 Ramp-down time for PID setpoint CUT r60 CO: Act. PID setpoint - P61 PID setpoint filter timeconstant CUT P6 CO: Act. PID filtered setpoint - P64 CI: PID feedback CUT P65 PID feedback filter timeconstant CUT r66 CO: PID filtered feedback - P67 Max. value for PID feedback CUT P68 Min. value for PID feedback CUT P69 Gain applied to PID feedback CUT P70 PID feedback function selector CUT P71 PID tranducer type CUT r7 CO: PID scaled feedback - r7 CO: PID error - P80 PID proportional gain CUT P85 PID integral time CUT P91 PID output upper limit CUT P9 PID output lower limit CUT P9 Ramp-up /-down time of PID limit CUT r94 CO: Act. PID output - Parameters MICROMASTER 40 10 6SE6400-5BA00-0BP0

Parameter Description r0000 Drive display Min: - P-Group: - active: - QuickComm. - Max: - Displays the user selected output as defined in P0005. Pressing the "Fn" button for seconds allows the user to view the values of DC link voltage, output current, output frequency, and chosen r0000 setting (defined in P0005). r000 Drive state Min: - P-Group: COMMANDS active: - QuickComm. - Max: - Displays actual drive state. State visible only while precharging DC link, and when externally powered communications board is fitted. 0 Commissioning mode (P0010!= 0) 1 Ready to run Fault Starting (DC-link precharging) 4 Running 5 Stopping (ramping down) P000 User access level Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 1 P-Group: ALWAYS active: Immediately QuickComm. - Max: 4 Defines user access level to parameter sets. The default setting (standard) is sufficient for most simple applications. 0 User defined parameter list - see P001 for details on use 1 Standard: Allows access into most frequently used parameters. Extended: Allows extended access e.g. to inverter I/O functions. Expert: For expert use only. 4 Service: Only for use by authorized service personal - password protected. P0004 Parameter filter Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: ALWAYS active: Immediately QuickComm. - Max: Filters available parameters according to functionality to enable a more focussed approach to commissioning. Example: P0004 = specifies that only PID parameters will be visible. Parameters marked "Quick Comm: Yes" in the parameter header can only be set when P0010 = 1 (Quick Commissioning). 0 All parameters Inverter Motor 7 Commands, binary I/O 8 ADC and DAC 10 Setpoint channel / RFG 1 Drive features 1 Motor control 0 Communication 1 Alarms / warnings / monitoring Technology controller (e.g. PID) The inverter will start with any setting of P0004. P0005 Display selection Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 1 P-Group: FUNC active: Immediately QuickComm. - Max: 4000 Selects display for parameter r0000 (drive display). 1 Actual frequency 5 Output voltage 6 DC link voltage 7 Output current 1 1 1 Parameters MICROMASTER 40 6SE6400-5BA00-0BP0 11

These settings refer to read only parameter numbers ("rxxxx"). P0006 Display mode Min: 0 CStat: CUT Datatype: U16 Unit: - Def: P-Group: FUNC active: Immediately QuickComm. - Max: 4 Defines mode of display for r0000 (drive display). 0 In Ready state alternate between setpoint and output freq. In run display output freq. 1 In Ready state display setpoint. In run display output freq. In Ready state alternate between P0004 value and output freq. In run display P0004 value In Ready state alternate between r000 value and output freq. In run display P000 value 4 In all states just display P0004 When inverter is not running, the display alternates between the values for "Not Running" and "Running". Per default, the setpoint and actual frequency values are displayed alternately. P0007 Backlight delay time Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: FUNC active: Immediately QuickComm. - Max: 000 Defines time period after which the backlight display turns off if no operator keys have been pressed. Value: P0007 = 0 : Backlight always on (default state) P0007 = 1-000 : Number of seconds after which the backlight will turn off P0010 Commissioning parameter filter Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: ALWAYS active: Immediately QuickComm. - Max: 0 Filters parameters so that only those related to a particular functional group are selected. Reset to 0 for inverter to run. P000 (user access level) also determines access to parameters. 0 Ready 1 Quick commissioning Inverter 9 Download 0 Factory setting If P900 is not 0 (0 is the default value), this parameter is automatically reset to 0. P0011 Lock for user defined parameter Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: FUNC active: Immediately QuickComm. - Max: 6555 See parameter P001 (user defined parameter) P001 Key for user defined parameter Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: FUNC active: Immediately QuickComm. - Max: 6555 See parameter P001 (user defined parameter). P001[0] User defined parameter Min: 0 CStat: CUT Datatype: U16 Unit: - Def: 0 P-Group: FUNC active: Immediately QuickComm. - Max: 6555 Defines a limited set of parameters to which the end user will have access. Instructions for use: Step 1: Set P000 = (expert user) Step : Go to P001 indices 0 to 16 (user list) Step : Enter into P001 index 0 to 16 the parameters required to be visible in the user-defined list. The following values are fixed and cannot be changed: - P001 index 19 = 1 (key for user defined parameter) - P001 index 18 = 10 (commissioning parameter filter) - P001 index 17 = (user access level) Step 4: Set P000 = 0 to activate the user defined parameter. First, set P0011 ("lock") to a different value than P001 ("key") to prevent changes to user-defined parameter. Then, set P000 to 0 to activate the user-defined list. When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter (and view other parameters) is to set P001 ("key") to the value in P0011 ("lock"). Alternatively, set P0010 = 0 (commissioning parameter filter = factory setting) and P0970 = 1 (factory reset) to perform a complete factory reset. The default values of P0011 ("lock") and P001 ("key") are the same. r0018 Firmware version Min: - CStat: - Datatype: Float Unit: - Def: - P-Group: INVERTER active: - QuickComm. - Max: - Displays version number of installed firmware. 1 1 Parameters MICROMASTER 40 1 6SE6400-5BA00-0BP0

r0019 CO/BO: BOP control word Min: - P-Group: COMMANDS active: - QuickComm. - Max: - Displays status of operator panel commands. The settings below are used as the "source" codes for keypad control when connecting to BICO input parameters. Bitfields: Bit00 ON/OFF1 0 NO Bit01 OFF: Electrical stop 0 YES 1 NO Bit0 OFF: Fast stop 0 YES 1 NO Bit08 JOG right 0 NO Bit09 JOG left 0 NO Bit11 Reverse (setpoint inversion) 0 NO Bit1 Motorpoti (MOP) up 0 NO Bit14 Motorpoti (MOP) down 0 NO When BICO technology is used to allocate functions to panel buttons, this parameter displays the actual status of the relevant command. The following functions can be "connected" to individual buttons: ON/OFF1, OFF, JOG, REVERSE, INCREASE, DECREASE r000 CO: Act. frequency setpoint Min: - CStat: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL active: - QuickComm. - Max: - Displays actual frequency setpoint (input from ramp function generator). r001 CO: Act. frequency Min: - CStat: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL active: - QuickComm. - Max: - Displays actual inverter output frequency (r004) excluding slip compensation, resonance damping and frequency limitation. r00 Act. rotor speed Min: - CStat: - Datatype: Float Unit: 1/min Def: - P-Group: CONTROL active: - QuickComm. - Max: - Displays calculated rotor speed based on inverter output frequency [Hz] x 10 / number of poles. This calculation makes no allowance for load-dependent slip. r004 CO: Act. output frequency Min: - CStat: - Datatype: Float Unit: Hz Def: - P-Group: CONTROL active: - QuickComm. - Max: - Displays actual output frequency. Slip compensation, resonance damping and frequency limitation are included. r005 CO: Act. output voltage Min: - CStat: - Datatype: Float Unit: V Def: - P-Group: CONTROL active: - QuickComm. - Max: - Displays [rms] voltage applied to motor. r006 CO: Act. DC-link voltage Min: - CStat: - Datatype: Float Unit: V Def: - P-Group: INVERTER active: - QuickComm. - Max: - Displays DC-link voltage. r007 CO: Act. output current Min: - CStat: - Datatype: Float Unit: A Def: - P-Group: CONTROL active: - QuickComm. - Max: - Displays [rms] value of motor current [A]. r004 CO: Motor temperature (it) Min: - CStat: - Datatype: Float Unit: % Def: - P-Group: MOTOR active: - QuickComm. - Max: - Displays calculated motor temperature (it model) as [%] of the maximum permissible value. A value of 100 % means that the motor has reached its maximum permissible operating temperature. In this case, the motor will attempt to reduce the motor loading as defined in P0610 (motor It temperature reaction). r007 CO: Drive temperature [ C] Min: - CStat: - Datatype: Float Unit: C Def: - P-Group: INVERTER active: - QuickComm. - Max: - Parameters MICROMASTER 40 6SE6400-5BA00-0BP0 1

Displays internal inverter heatsink temperature. r009 CO: Energy consumpt. meter [kwh] Min: - CStat: - Datatype: Float Unit: kwh Def: - P-Group: INVERTER active: - QuickComm. - Max: - Displays electrical energy used by drive since display was last reset (see P0040 - reset energy consumption meter). Value is reset when P900 = 1 (end quick commissioning), P0970 = 1 (factory reset) or P0040 = 1 (reset energy consumption meter). P0040 Reset energy consumption meter Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: INVERTER active: Immediately QuickComm. - Max: 1 Resets value of parameter r009 (energy consumption meter) to zero. Value: 0 = No reset 1 = Reset r009 to 0 No reset until "P" is pressed. Parameters MICROMASTER 40 14 6SE6400-5BA00-0BP0

r005 CO/BO: Status word 1 Min: - P-Group: COMMANDS active: - QuickComm. - Max: - Displays first active status word of inverter (bit format) and can be used to diagnose inverter status. The display segments for the status word are shown in the diagram below. Bit 15 Bit 14 Bit 1 Bit 1 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit Bit Bit 1 Bit 0 Bitfields: Bit00 Drive ready 0 NO Bit01 Drive ready to run 0 NO Bit0 Drive running 0 NO Bit0 Drive fault active 0 NO Bit04 OFF active 0 YES 1 NO Bit05 OFF active 0 YES 1 NO Bit06 Switch on inhibit active 0 NO Bit07 Drive warning active 0 NO Bit08 Deviation setp. / act. value 0 YES 1 NO Bit09 PZD control 0 NO Bit10 Maximum frequency reached 0 NO Bit11 Warning: Motor current limit 0 YES 1 NO Bit1 Motor holding brake active 0 NO Bit1 Motor overload 0 YES 1 NO Bit14 Motor runs direction right 0 NO Bit15 Inverter overload 0 YES 1 NO Output of Bit (Fault) will be inverted on digital output (Low = Fault, High = No Fault). Parameters MICROMASTER 40 6SE6400-5BA00-0BP0 15

r005 CO/BO: Status word Min: - P-Group: COMMANDS active: - QuickComm. - Max: - Displays second status word of inverter (in bit format). See seven-segment display in r005 (status word 1) Bitfields: Bit00 DC brake active 0 NO Bit01 Act. freq. > P167 0 NO Bit0 Act. freq. > P1080 0 NO Bit0 Act. current >= P170 0 NO Bit04 Act. freq. > P155 0 NO Bit05 Act. freq. <= P155 0 NO Bit06 Act. freq. >= setpoint 0 NO Bit07 Act. voltage < P17 0 NO Bit08 Act. voltage > P17 0 NO Bit10 PID output < P91 0 NO Bit11 PID output >= P91 0 NO Bit14 Download data set 0 from AOP 0 NO Bit15 Download data set 1 from AOP 0 NO r0054 CO/BO: Control word 1 Min: - P-Group: COMMANDS active: - QuickComm. - Max: - Displays first control word of inverter and can be used to diagnose which commands are active. See seven-segment display in r005 (status word 1) Bitfields: Bit00 ON/OFF1 0 NO Bit01 OFF: Electrical stop 0 YES 1 NO Bit0 OFF: Fast stop 0 YES 1 NO Bit0 Pulse enable 0 NO Bit04 RFG enable 0 NO Bit05 RFG start 0 NO Bit06 Setpoint enable 0 NO Bit07 Fault acknowledge 0 NO Bit08 JOG right 0 NO Bit09 JOG left 0 NO Bit10 Control from PLC 0 NO Bit11 Reverse (setpoint inversion) 0 NO Bit1 Motorpoti (MOP) up 0 NO Bit14 Motorpoti (MOP) down 0 NO Bit15 Local / Remote 0 NO Parameters MICROMASTER 40 16 6SE6400-5BA00-0BP0

r0055 CO/BO: Control word Min: - P-Group: COMMANDS active: - QuickComm. - Max: - Displays second control word of inverter and can be used to diagnose which commands are active. See seven-segment display in r005 (status word 1) Bitfields: Bit00 Fixed frequency Bit 0 0 NO Bit01 Fixed frequency Bit 1 0 NO Bit0 Fixed frequency Bit 0 NO Bit08 PID release 0 NO Bit09 DC brake enable 0 NO Bit1 External fault 1 0 YES 1 NO r0056 CO/BO: Status of motor control Min: - P-Group: CONTROL active: - QuickComm. - Max: - Displays status of motor control (MM40: V/F status), which can be used to diagnose inverter status. See seven-segment display in r005 (status word 1) Bitfields: Bit00 Init. control finished 0 NO Bit01 Motor demagnetizing finished 0 NO Bit0 Pulses enabled 0 NO Bit0 Voltage soft start select 0 NO Bit04 Motor excitation finished 0 NO Bit05 Starting boost active 0 NO Bit06 Acceleration boost active 0 NO Bit07 Frequency is negative 0 NO Bit08 Field weakening active 0 NO Bit09 Volts setpoint limited 0 NO Bit10 Slip frequency limited 0 NO Bit11 F_out > F_max Freq. limited 0 NO Bit1 Phase reversal selected 0 NO Bit1 I-max controller active 0 NO Bit14 Vdc-max controller active 0 NO Bit15 Vdc-min controller active 0 NO r0067 CO: Act. drive current limit Min: - CStat: - Datatype: Float Unit: A Def: - P-Group: CONTROL active: - QuickComm. - Max: - Displays valid maximum output current of drive. This value is influenced by P0660 (max. output current), the derating characteristics and the thermal motor and drive protection. P0610 (motor It temperature reaction) defines reaction when limit is reached. The value is always % higher than the calculated limit in order to account for current ripple. Normally, current limit = rated motor current (P005) x motor current limit (P0640). It is less than or equal to 150 % of rated drive current (r007). The current limit may be reduced if the motor thermal model calculation indicates that overheating will occur. Parameters MICROMASTER 40 6SE6400-5BA00-0BP0 17

r0071 CO: Max. output voltage Min: - CStat: - Datatype: Float Unit: V Def: - P-Group: CONTROL active: - QuickComm. - Max: - Displays maximum output voltage. Actual maximum output voltage depends on the actual input supply voltage. r0086 CO: Act. active current Min: - CStat: - Datatype: Float Unit: A Def: - P-Group: CONTROL active: - QuickComm. - Max: - Displays active (real part) of motor current. P0100 Europe / North America Min: 0 CStat: C Datatype: U16 Unit: - Def: 0 P-Group: QUICK active: Immediately QuickComm. Y Max: 1 Determines whether power settings (e.g. nominal rating plate power - P007) are expressed in [kw] or [hp]. The default settings for the nominal rating plate frequency (P010) and maximum motor frequency (P108) are also set automatically here, in addition to reference frequency (P000). Stop drive first (i.e. disable all pulses) before you change this parameter. P0010 = 1 (commissioning mode) enables changes to be made. Changing P0100 (operation for Europe / North America) resets all rated motor parameters as well as other parameters that depend on the rated motor parameters (see P040 - calculation of motor parameters). 0 Europe [kw], frequency default 50 [Hz] 1 North America [hp], frequency default 60 [Hz] North America [kw], frequency default 60 [Hz] Setting the [kw]/[hp] DIP switch under the operator panel will overwrite P0100 settings 0 or 1 at power-up. Setting will not be overwritten. r000 Act. power stack code number Min: - CStat: - Datatype: U Unit: - Def: - P-Group: INVERTER active: - QuickComm. - Max: - Identifies hardware variant as shown in table below. Code Order Number Code Order Number 1 6SE640-UC11-AA0 1 6SE640-AC-0CA0 6SE640-UC1-5AA0 6SE640-AC4-0CA0 6SE640-UC1-7AA0 6SE640-AC5-5CA0 4 6SE640-UC15-5AA0 4 6SE640-UD1-7AA0 5 6SE640-UC17-5AA0 5 6SE640-UD15-5AA0 6 6SE640-UC1-1BA0 6 6SE640-UD17-5AA0 7 6SE640-UC1-5BA0 7 6SE640-UD1-1AA0 8 6SE640-UC-BA0 8 6SE640-UD1-5AA0 9 6SE640-UC-0CA0 9 6SE640-UD-BA0 10 6SE640-UC4-0CA0 0 6SE640-UD-0BA0 11 6SE640-UC5-5CA0 1 6SE640-UD4-0BA0 1 6SE640-AB11-AA0 6SE640-UD5-5CA0 1 6SE640-AB1-5AA0 6SE640-UD7-5CA0 14 6SE640-AB1-7AA0 4 6SE640-UD1-1CA0 15 6SE640-AB15-5AA0 5 6SE640-AD-BA0 16 6SE640-AB17-5AA0 6 6SE640-AD-0BA0 17 6SE640-AB1-1BA0 7 6SE640-AD4-0BA0 18 6SE640-AB1-5BA0 8 6SE640-AD5-5CA0 19 6SE640-AB-BA0 9 6SE640-AD7-5CA0 0 6SE640-AB-0CA0 40 6SE640-AD1-1CA0 0 indicates that no power stack has been identified. P001 Power stack code number Min: 0 CStat: C Datatype: U16 Unit: - Def: 0 P-Group: INVERTER active: Immediately QuickComm. - Max: 6555 Confirms actual power stack identified. r00 Act. power stack type Min: - P-Group: INVERTER active: - QuickComm. - Max: - Type number of actual power stack identified. 1 MICROMASTER 40 MICROMASTER 440 MICRO- / COMBIMASTER 411 4 MICROMASTER 410 5 SED 6 MICROMASTER 40 Parameters MICROMASTER 40 18 6SE6400-5BA00-0BP0

r004 Power stack features Min: - CStat: - Datatype: U Unit: - Def: - P-Group: INVERTER active: - QuickComm. - Max: - Displays hardware features of power stack. Bitfields: Bit00 DC input voltage 0 NO Bit01 RFI filter 0 NO 0 indicates that no power stack has been identified. r006 Rated drive power [kw] or [hp] Min: - CStat: - Datatype: Float Unit: - Def: - P-Group: INVERTER active: - QuickComm. - Max: - Displays nominal rated motor power from inverter. Value is displayed in [kw] or [hp] depending on setting for P0100 (operation for Europe / North America). r007 Rated drive current Min: - CStat: - Datatype: Float Unit: A Def: - P-Group: INVERTER active: - QuickComm. - Max: - Displays maximum continuous output current of inverter. r008 Rated drive voltage Min: - CStat: - Datatype: U Unit: V Def: - P-Group: INVERTER active: - QuickComm. - Max: - Displays nominal AC supply voltage of inverter. Value: 0 = 00-40 V +/- 10 % 400 = 400-480 V +/- 10 % P010 Supply voltage Min: 0 CStat: CT Datatype: U16 Unit: V Def: 0 P-Group: INVERTER active: Cornfirm QuickComm. - Max: 1000 Optimizes Vdc controller, which extends the ramp-down time if regenerative energy from motor would otherwise cause DC link overvoltage trips. Reducing the value enables controller to cut in earlier and reduce the risk of overvoltage. Value: Converter (AC/AC): [rms] value of the line AC voltage Inverter (DC/AC): input direct voltage Set P154 ("Auto detect Vdc switch-on levels") = 0. Cut-in levels for Vdc-controller and compound braking are then derived directly from P010 (supply voltage). Vdc_max_on = Compound braking switch-on level = 1.15* 1.1* *Vmains +Vmains If mains voltage is higher than value entered, automatic deactivation of the Vdc controller may occur to avoid acceleration of the motor. An alarm will be issued in this case. r01[] Max. cable length Min: - CStat: - Datatype: U16 Unit: m Def: - P-Group: INVERTER active: - QuickComm. - Max: - Indexed parameter to display maximum allowable cable length between drive and motor. Index: r01[0] : Max. allowed unscreened cable length r01[1] : Max. allowed screened cable length For full EMC compliance, the screened cable must not exceed 5 m in length when an EMC filter is fitted. P090 Drive overload reaction Min: 0 CStat: CT Datatype: U16 Unit: - Def: P-Group: INVERTER active: Immediately QuickComm. - Max: Selects reaction of inverter to an internal over-temperature. 0 Reduce output frequency (usually only effective on variable torque appl.) 1 Trip (F0004) Reduce pulse frequency and output frequency Reduce pulse frequency then trip (F0004) A trip will always result eventually, if the action taken does not sufficiently reduce internal temperature. The pulse frequency is normally only reduced if it is higher than khz (see P091 - configuration of inverter protection) Parameters MICROMASTER 40 6SE6400-5BA00-0BP0 19

P091 Config. of inverter protection Min: 0 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: INVERTER active: Cornfirm QuickComm. - Max: 1 Control bit for enabling/disabling automatic pulse frequency reduction at output frequencies below Hz. Bitfields: Bit00 Pulse freq reduced below Hz 0 NO P09 Drive overload warning Min: 0 CStat: CUT Datatype: U16 Unit: C Def: 15 P-Group: INVERTER active: Immediately QuickComm. - Max: 5 Defines temperature difference (in [ C]) between inverter over-temperature trip and warning thresholds. P000 Select motor type Min: 1 CStat: C Datatype: U16 Unit: - Def: 1 P-Group: MOTOR active: Immediately QuickComm. Y Max: Selects motor type. This parameter is required during commissioning to select motor type and optimize inverter performance. Most motors are asynchronous; if in doubt, use the formula below. (P010 * 60) / P011 If the result is a whole number, the motor is synchronous. Changeable only when P0010 = 1 (quick commissioning). If synchronous motor is selected, the following functions are not available: Power factor (P008) Motor efficiency (P009) Magnetization time (P046 (Level ) Demagnetization time (P047 (Level ) Flying start (P100, P10 (Level ), P10 (Level )) DC braking (P10 (Level ), P1, P1) Slip compensation (P15) Slip limit (P16) Motor magnetizing current (P00 (Level ), P00, P01, P0, P084) 1 Asynchronous motor Synchronous motor P004 Rated motor voltage Min: 10 CStat: C Datatype: U16 Unit: V Def: 0 P-Group: MOTOR active: Immediately QuickComm. Y Max: 000 Nominal motor voltage [V] from rating plate. Following diagram shows a typical rating plate with the locations of the relevant motor data. 1 P010 P005 P004 ~Mot 1LA710-4AA10 EN 6004 No UD 001509-0090-001 TICI F 15 IP 55 IM B 50 Hz 0-400 V 60 Hz 460 V P007 5.5kW 19.7/11.A 6.5kW 10.9 A Cos ϕ=0.81 1455/min Cos ϕ=0.8 1755/min == /Υ /Υ=0-40/80-40 V 19.7-0.6/11.4-11.9 A Υ=440-480 11.1-11. A 45kg 95.75% P008 Changeable only when P0010 = 1 (quick commissioning). P005 Rated motor current Min: 0.01 CStat: C Datatype: Float Unit: A Def:.5 P-Group: MOTOR active: Immediately QuickComm. Y Max: 10000.00 Nominal motor current [A] from rating plate - see diagram P004. Changeable only when P0010 = 1. Maximum value is defined as times inverter rated current (r007). Minimum value is defined as 1/ times inverter rated current (r007). P011 P009 1 Parameters MICROMASTER 40 0 6SE6400-5BA00-0BP0

P007 Rated motor power Min: 0.01 CStat: C Datatype: Float Unit: - Def: 0.75 1 P-Group: MOTOR active: Immediately QuickComm. Y Max: 000.00 Nominal motor power [kw] from rating plate. If P0100 = 1, values will be in [hp] - see diagram P004 (rating plate). Changeable only when P0010 = 1. P008 Rated motor cosphi Min: 0.000 CStat: C Datatype: Float Unit: - Def: 0.000 P-Group: MOTOR active: Immediately QuickComm. Y Max: 1.000 Nominal motor power factor (cosphi) from rating plate - see diagram P004. Changeable only when P0010 = 1. Visible only when P0100 = 0 or, (motor power entered in [kw]). Setting 0 causes internal calculation of value (see r0). P009 Rated motor efficiency Min: 0.0 CStat: C Datatype: Float Unit: % Def: 0.0 P-Group: MOTOR active: Immediately QuickComm. Y Max: 99.9 Nominal motor efficiency [%] from rating plate. Changeable only when P0010 = 1. Visible only when P0100 = 1, (i.e. motor power entered in [hp]). Setting 0 causes internal calculation of value (see r0). See diagram in P004 (rating plate) P010 Rated motor frequency Min: 1.00 CStat: C Datatype: Float Unit: Hz Def: 50.00 1 P-Group: MOTOR active: Immediately QuickComm. Y Max: 650.00 Nominal motor frequency [Hz] from rating plate. Changeable only when P0010 = 1. Pole pair number recalculated automatically if parameter is changed. See diagram in P004 (rating plate) P011 Rated motor speed Min: 0 CStat: C Datatype: U16 Unit: 1/min Def: 0 1 P-Group: MOTOR active: Immediately QuickComm. Y Max: 40000 Nominal motor speed [rpm] from rating plate. Changeable only when P0010 = 1. Setting 0 causes internal calculation of value. Required for vector control and V/F control with speed controller. Slip compensation in V/F control requires rated motor speed for correct operation. Pole pair number recalculated automatically if parameter is changed. \DEPENDENCY> See diagram in P004 (rating plate) r01 Motor pole pairs Min: - P-Group: MOTOR active: - QuickComm. - Max: - Displays number of motor pole pairs that the inverter is currently using for internal calculations. Recalculated automatically when P010 (rated motor frequency) or P011 (rated motor speed) is changed. Value: 1 = -pole motor = 4-pole motor etc. P00 Motor magnetizing current Min: 0.0 CStat: CT Datatype: Float Unit: % Def: 0.0 P-Group: MOTOR active: Cornfirm QuickComm. Y Max: 99.0 Defines motor magnetization current as [%] of full load current. Setting 0 causes calculation by P040 = 1 (data entered from rating plate) or by P900 = 1 or (end of quick commissioning). r00 Rated motor slip Min: - CStat: - Datatype: Float Unit: % Def: - P-Group: MOTOR active: - QuickComm. - Max: - Displays nominal motor slip (in [%]) based on nominal motor frequency (P010) and nominal motor speed (P011). Parameters MICROMASTER 40 6SE6400-5BA00-0BP0 1

r01 Rated magnetization current Min: - CStat: - Datatype: Float Unit: A Def: - P-Group: MOTOR active: - QuickComm. - Max: - Displays calculated magnetizing current of motor in [A]. r0 Rated power factor Min: - CStat: - Datatype: Float Unit: - Def: - P-Group: MOTOR active: - QuickComm. - Max: - Displays power factor for motor Value is calculated internally if P008 (rated motor cosphi) set to 0; otherwise, value entered in P098 is displayed. P05 Motor cooling Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: MOTOR active: Immediately QuickComm. Y Max: 1 Selects motor cooling system used. 0 Self-cooled: Using shaft mounted fan attached to motor 1 Force-cooled: Using separately powered cooling fan Motors of series 1LA1 and 1LA8 have an internal fan. This internal fan must not be confused with the fan at the end of the motor shaft. P040 Calculation of motor parameters Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: MOTOR active: Immediately QuickComm. - Max: 1 Calculates various motor parameters, including 1. Motor weight P044 (Level ). Stator resistance P050 (Level ). Magnetization time P046 (Level ) 4. Demagnetization time P047 (Level ) 5. Reference frequency P000 (Level ) 6. Reference current P00 (Level ). 0 No calculation 1 Complete parameterization This parameter is required during commissioning to optimize inverter performance. P044 Motor weight Min: 1.0 CStat: CUT Datatype: Float Unit: kg Def: 9.4 P-Group: MOTOR active: Cornfirm QuickComm. - Max: 6500.0 Specifies motor weight [kg]. This value is used in the motor thermal model. It is normally calculated automatically from P040 (motor parameters) but can also be entered manually. P046 Magnetization time Min: 0.000 CStat: CUT Datatype: Float Unit: s Def: 1.000 P-Group: MOTOR active: Cornfirm QuickComm. - Max: 0.000 Sets magnetization time [s], i.e. waiting time between pulse enable and start of ramp-up. Motor magnetization builds up during this time. Magnetization time is normally calculated automatically from the motor data and corresponds to the rotor time constant (r084). If boost settings are higher than 100 %, magnetization may be reduced. An excessive reduction of this time can result in insufficient motor magnetization. P047 Demagnetization time Min: 0.000 CStat: CUT Datatype: Float Unit: s Def: 1.000 P-Group: MOTOR active: Cornfirm QuickComm. - Max: 0.000 Changes time allowed after OFF / fault condition, before pulses can be re-enabled. The demagnetization time is approximately.5 x rotor time constant (r084) in seconds. Not active following a normally completed ramp-down, e.g. after OFF1 or JOG. Overcurrent trips will occur if the time is decreased excessively. Parameters MICROMASTER 40 6SE6400-5BA00-0BP0

P050 Stator resistance (line-to-line) Min: 0.00001 CStat: CUT Datatype: Float Unit: Ohm Def: 4.0 P-Group: MOTOR active: Cornfirm QuickComm. - Max: 000.0 Stator resistance value in [Ohms] for connected motor (from line-to-line). There are three ways to determine the value for this parameter: 1. Calculate using P040 = 1 (data entered from rating plate), P900 = 1, or (end of quick commissioning). Measure using P1910 = 1 (motor data identification - value for stator resistance is overwritten). Measurement manually using an Ohmmeter. The value entered in P050 (stator resistance) is the one obtained by the method last used. r084 Rotor time constant Min: - CStat: - Datatype: Float Unit: ms Def: - P-Group: MOTOR active: - QuickComm. - Max: - Displays calculated rotor time constant [ms]. r095 Total stator resistance [%] Min: - CStat: - Datatype: Float Unit: % Def: - P-Group: MOTOR active: - QuickComm. - Max: - Stator resistance of motor as [%] of combined stator/cable resistance. Values greater than 5 % tend to produce excessive motor slip. Check rated motor speed [rpm] value (P011) or check that motor cable is not too long. P0610 Motor It temperature reaction Min: 0 CStat: CT Datatype: U16 Unit: - Def: P-Group: MOTOR active: Immediately QuickComm. - Max: Defines reaction when motor It reaches warning threshold. Trip level = P0614 (motor It overload warning level) * 110% 0 No reaction, warning only 1 Warning and Imax reduction (results in reduced output freq.) Warning and trip (F0011) P0611 Motor It time constant Min: 0 CStat: CT Datatype: U16 Unit: s Def: 100 P-Group: MOTOR active: Cornfirm QuickComm. - Max: 16000 Defines motor thermal time constant and is calculated automatically from the motor data (see P040). A larger number increases the time taken for the calculated motor temperature to change. P0614 Motor It overload warning level Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 100.0 P-Group: MOTOR active: Immediately QuickComm. - Max: 400.0 Defines the [%] value at which warning A0511 (inverter overtemperature) is generated. Inverter It calculation is used to estimate a maximum tolerable period (i.e. without overheating) for inverter overload. The It calculation value is deemed = 100% when this maximum tolerable period is reached (see r004). A motor over-temperature trip (F0011) is produced at 110% of this level. P0640 Motor overload factor [%] Min: 0.0 CStat: CUT Datatype: Float Unit: % Def: 150.0 P-Group: MOTOR active: Cornfirm QuickComm. Y Max: 400.0 Defines instantaneous motor current limit as [%] of nominal motor current. Limited to 150 % of the nominal inverter current (r007) or to 400 % of motor current (whichever is the lower). P0700 Selection of command source Min: 0 CStat: CT Datatype: U16 Unit: - Def: P-Group: COMMANDS active: Immediately QuickComm. Y Max: 6 Selects digital command source. 0 Factory default setting 1 BOP / AOP (keypad) Terminal 4 USS on BOP link 5 USS on COM link 6 CB on COM link 1 Changing this parameter resets (to default) all settings on item selected. For example: Changing form 1 to resets all digital inputs to default settings. Parameters MICROMASTER 40 6SE6400-5BA00-0BP0

P0701 Function of digital input1 Min: 0 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: COMMANDS active: Immediately QuickComm. - Max: 99 Selects function of digital input 1. Requires P0700 (command source) or P900 (end of quick commissioning) = 1, or P0970 (factory reset) = 1 to reset. 0 Digital input disabled 1 ON/OFF1 ON reverse /OFF1 OFF - coast to standstill 4 OFF - quick ramp-down 9 Fault acknowledge 10 JOG right 11 JOG left 1 Reverse 1 MOP up (increase freq.) 14 MOP down (decrease freq.) 15 Fixed setpoint (binary coded) 16 Fixed setpoint + ON (binary coded) 17 Fixed setpoint (binary coded decimal (BCD)) 1 Local/remote 5 DC brake enable 9 External trip Disable additional freq setpoint 99 Enable BICO parameterization Setting 99 (BICO) for expert use only. P070 Function of digital input Min: 0 CStat: CT Datatype: U16 Unit: - Def: 1 P-Group: COMMANDS active: Immediately QuickComm. - Max: 99 Selects function of digital input. See P0701. 0 Digital input disabled 1 ON/OFF1 ON reverse /OFF1 OFF - coast to standstill 4 OFF - quick ramp-down 9 Fault acknowledge 10 JOG right 11 JOG left 1 Reverse 1 MOP up (increase freq.) 14 MOP down (decrease freq.) 15 Fixed setpoint (binary coded) 16 Fixed setpoint + ON (binary coded) 17 Fixed setpoint (binary coded decimal (BCD)) 1 Local/remote 5 DC brake enable 9 External trip Disable additional freq setpoint 99 Enable BICO parameterization Parameters MICROMASTER 40 4 6SE6400-5BA00-0BP0

P070 Function of digital input Min: 0 CStat: CT Datatype: U16 Unit: - Def: 9 P-Group: COMMANDS active: Immediately QuickComm. - Max: 99 Selects function of digital input. See P0701. 0 Digital input disabled 1 ON/OFF1 ON reverse /OFF1 OFF - coast to standstill 4 OFF - quick ramp-down 9 Fault acknowledge 10 JOG right 11 JOG left 1 Reverse 1 MOP up (increase freq.) 14 MOP down (decrease freq.) 15 Fixed setpoint (binary coded) 16 Fixed setpoint + ON (binary coded) 17 Fixed setpoint (binary coded decimal (BCD)) 1 Local/remote 5 DC brake enable 9 External trip Disable additional freq setpoint 99 Enable BICO parameterization P0704 Function of digital input4 Min: 0 CStat: CT Datatype: U16 Unit: - Def: 0 P-Group: COMMANDS active: Immediately QuickComm. - Max: 99 Selects function of digital input 4 (via analog input). See P0701. 0 Digital input disabled 1 ON/OFF1 ON reverse /OFF1 OFF - coast to standstill 4 OFF - quick ramp-down 9 Fault acknowledge 10 JOG right 11 JOG left 1 Reverse 1 MOP up (increase freq.) 14 MOP down (decrease freq.) 15 Fixed setpoint (binary coded) 16 Fixed setpoint + ON (binary coded) 17 Fixed setpoint (binary coded decimal (BCD)) 1 Local/remote 5 DC brake enable 9 External trip Disable additional freq setpoint 99 Enable BICO parameterization Signals above 4 V are active, signals below 1.6 V are inactive. Parameters MICROMASTER 40 6SE6400-5BA00-0BP0 5