Installation Instructions IN Allen-Bradley 1397 460-to-230V Conversion Kit Cat. Nos. 1397-FC030 1397-FC075 What This Option Provides The 460-to-230V Conversion Kit provides (2) replacement fuses that are used to convert a 460VAC input drive to a 230VAC input drive at half the horsepower rating of the 460V drive. When converted to a 230VAC input drive, the following drive rating reductions will apply. 460V AC Input 230V AC Input Nominal Rating Nominal Rating HP kw 1 Code HP kw 1 Code 3 (2.2) B003 1.5 (1.2) A001 5 (3.7) B005 2 (1.5) A002 7.5 (5.5) B007 3 (2.2) A003 10 (7.5) B010 5 (3.7) A005 15 (11) B015 7.5 (5.5) A007 20 (15) B020 10 (7.5) A010 30 (22) B030 15 (11) A015 40 (30) B040 20 (15) A020 50 (37) B050 25 (18.5) A025 60 (45) B060 30 (22) A030 75 (56) B070 40 (30) A040 100 (75) B100 50 (37) A050 125 (93) B125 60 (45) A060 150 (112) B150 75 (56) A075 1 kw ratings are based on rated input voltage. Where This Option Is Used This option may be used with all 3-150HP/460V 1397 Drives. 460V Drive Rating 230V Drive Rating Catalog Number HP (kw) HP (kw) 1397-FC030 3-60 (2.2-45) 1.5-30 (1.2-22) 1397-FC075 75-150 (56-112) 40-75 (30-56)
2 1397 460-to-230V Conversion Kit Installation! ATTENTION: Electric Shock can cause injury or death. Remove all power before working on this product. The drive is at line voltage when connected to incoming AC power. Before proceeding with any installation or troubleshooting activity, disconnect, lock out, and tag all incoming power to the drive. Verify with a voltmeter that no voltage exists at terminals L1, L2 and L3 on the drive input power terminal block. 3-60HP/460V Drive Installation 1 Remove and lock-out all incoming power to the drive. Replace fuses 4FU & 5FU with the (2) fuses included with the kit 4FU 5FU Control Transformer Set for 460V AC Input Line H4 H2 610273 07-08- H3-030RD 1966 H1 2 Reconnect the drive control transformer for 230VAC input operation. Control Transformer Set for 230V AC Input Line H4 H2 610273 07-08- H3 H1-030RD 1966
1397 460-to-230V Conversion Kit 3 Installation (continued) 75-150HP/460V Drive Installation 1 Remove and lock-out all incoming power to the drive. Replace fuses 4FU & 5FU with the (2) fuses included with the kit. 4FU 5FU 610273 07-08- H1 H3 Control Transformer Set for 460V AC Input Line -030RD 1966 H2 H4 2 Reconnect the drive control transformer for 230VAC input operation. 610273 07-08- H1 H3 Control Transformer Set for 230V AC Input Line -030RD 1966 H2 H4
230 V BULLETIN 1397 M/N 1397-B003R 1.5/3.0HP INPUT 230/460VAC 10A 3PH 50/60HZ OUTPUT 240/500VDC 7A DC FIELD 150/300VDC 10A SHORT CIRCUIT RATING 5000A I/M 1397-5.0 W/D 30371-23 FOR 230V OPERATION, SEE I/M SERIAL NO. 01PE400977 V 004 WY MADE IN U.S.A. 230 V BULLETIN 1397 M/N 1397-B003R 1.5/3.0HP INPUT 230/460VAC 10A 3PH 50/60HZ OUTPUT 240/500VDC 7A DC FIELD 150/300VDC 10A SHORT CIRCUIT RATING 5000A I/M 1397-5.0 W/D 30371-23 FOR 230V OPERATION, SEE I/M SERIAL NO. 01PE400977 V 004 WY MADE IN U.S.A. 4 1397 460-to-230V Conversion Kit Installation (continued) 3 Peel the 230V label from the fuse shipping bag. Place it next to the drive nameplate label as shown. 3-60HP/460V Drive Installation 230 V BULLETIN 1397 M/N 1397-B003R 1.5/3.0HP INPUT 230/460VAC 10A 3PH 50/60HZ OUTPUT 240/500VDC 7A DC FIELD 150/300VDC 10A SHORT CIRCUIT RATING 5000A I/M 1397-5.0 W/D 30371-23 FOR 230V OPERATION, SEE I/M SERIAL NO. 01PE400977 V 004 WY MADE IN U.S.A. 75-150HP/460V Drive Installation 230 V BULLETIN 1397 M/N 1397-B003R 50/100HP INPUT 230/460VAC 154A 3PH 50/60HZ OUTPUT 240/500VDC 180A DC FIELD 150/300VDC 15A SHORT CIRCUIT RATING 42000A I/M 1397-5.0 W/D 30372-23 FOR 230V OPERATION, SEE I/M SERIAL NO. 01PE777777 V 004 WY MADE IN U.S.A.
1397 460-to-230V Conversion Kit 5 Setup To reconfigure a drive for 230VAC operation, the following parameters must be reset. Important: Depending upon the application, additional parameter adjustments may be required. If additional options are installed, different parameter settings may be required. Perform the Start-Up and Adjustment procedure in the 1397 User Manual to verify all parameter settings. Motor Armature Amps P.045 [Motor Arm Amps] Reset to match the motor s nameplate armature Amps. Motor Armature Volts P.046 [Motor Arm Volts] Reset to match the motor s nameplate armature voltage. Nominal AC Input Voltage P.051 [Motor AC Volts] Reset to match the nominal AC line RMS voltage.
6 1397 460-to-230V Conversion Kit Notes
1397 460-to-230V Conversion Kit 7 Notes
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support you can find technical and application notes, sample code, and links to software service packs. You can also visit our Support Center at https://rockwellautomation.custhelp.com/ for software updates, support chats and forums, technical information, FAQs, and to sign up for product notification updates. In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/services/online-phone. Installation Assistance If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running. United States or Canada 1.440.646.3434 Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local Rockwell Automation representative. New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures. United States Outside United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process. Please contact your local Rockwell Automation representative for the return procedure. Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/. Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 Publication 1397-5.16 - August 2013 Supersedes Publication 1397-5.16 - September 1997 Copyright 2013 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.