TECH NOTES-307. Integrating RACO Verbatim Gateway with the Allen-Bradley SLC 5/05 Series PLC via Ethernet

Similar documents
TECH NOTES-309. Integrating RACO Verbatim Gateway with the Allen-Bradley ControlLogix Series PLC via Ethernet

TECH NOTES-311. Integrating RACO Verbatim Gateway with the Allen-Bradley CompactLogix PLC via DH485

Modbus RTU Slave Driver is available within the following MicroLogix PLCs

Addendum to Verbatim Gateway Owner's Manual How to configure a Verbatim EtherNet/IP with RSLogix 5000

515RTAAIC Interface Converter

Select Family: MicroLogix 1100 or 1400 Controller

MPU-32 AND FPU-32 TIA-485 NETWORK

Installation and Programming Manual

1. SELECTING NEW PROTOCOLS

Cisco TelePresence Supervisor MSE 8050

Industrial Ethernet Ethernet to Serial Gateways Ethernet to Serial Converters for Modbus, Red lion and other protocols

# Byrne Rd, Burnaby, BC, V5J 3J1, Canada Phone: or

Addendum to Catalyst Owner's Manual How to configure a Catalyst EtherNet/IP with RSLogix 5000

P2 Configuration Guide

EQ-DCM User Manual Revision 1.02 Sep 10, 2013

Lantronix UDS-10 (CoBox) w/sielox Firmware B03.54 or greater Set-up, Installation, and FAQ Notes

C O N T R O L L E R I N F O R M A T I O N S H E E T. Allen-Bradley SLC500 & MicroLogix Series (DF1 BCC Checksum)

RSTC1000 HMI/PLC Design Guide WEB CONTROL PRODUCTS. User Manual FORM NO. L B MTY (81)

Allen-Bradley ONTROLLER NFORMATION HEET. MicroLogix 1000, 1100, 1200, Overview. Communications Cable. PLC Settings

Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter

515RTAENI-N34 Protocol Gateway Product User Guide

ALLEN-BRADLEY MICROLOGIX / SLC500 & EASON 2000 FAMILY

Example 1: Read N7:1, N7:2, N7:3 into IntegersRead[] table, offset for starting index is 2. Fig.1 Source data, MicroLogix 1500.

MicroLogix Ethernet Interface

Advantages for the MicroLogix 1500 Controller (in addition to MicroLogix 1200 controller features)

GW-7472 / GW EtherNet/IP to Modbus RTU/TCP Gateway User Manual

tsh-700 Series User Manual

APNT#1208 GP-Pro EX to Allen Bradley RIO via Gateway. Explore Newer Solutions

Overall Description. Generated by D.J.Withenshaw Date 05/09/2007 Revision A. (Name) only. Page 1 of 7

RTA Gateway N34 Hardware Jumper Configuration

BFR3000 Modbus Router

Gateway for EIP - DF1 Allen-Bradley PLC

TECHNICAL NOTE TNOI38

Replacing the AB 1761-NET-ENI with the MGate EIP3000 to perform an EIP-to-DF1 conversion

EQ7000. User Manual. Rev 1.00

UniStream HMI Panel. Max. current consumption 1.

Power Monitor / Power Monitor 51A. Quick guide to set up a connection with the Power Monitor devices through the Weidmüller Serial/Ethernet Converter

ID8400 Stamper Communications for Firmware Versions 5 and 6

ez80190 Development Kit Quick Start Guide

1210 TM /1040 TM. Features: V1210 Flat Panel. V1040 Classic Panel HMI PLC. Communication

OZONE SWITCH Model OS-6. OS-6 Features

Windows-compatible BASIC Module Interface Software (1747-WINBAS) BASIC Language Modules Catalog Numbers and Specifications

BrewTroller Phoenix. Owners Manual. Updated - March 14, 2016 BREWTROLLER PHOENIX 1

SOFTWARE LICENSE LIMITED WARRANTY

Operating Bulletin MODBUS-RTU. The Fastest Flow Controller Company in the World!

Vision570 TM /560 TM. Color OPLC TM. Color Vision570 TM /560 TM Series Featuring:

QUCM Limitorque Controller

BLH. DXp-40 Interface Manual Allen-Bradley Remote I/O WEIGH SYSTEM TECHNOLOGY. TM014 Rev D 6/1/11 Doc 35105

Device/PLC Connection Manuals

Weather Station Display Software Rev A

MicroLogix Ethernet Interface (ENI)

PLC Driver Manual 2800 & 2900

ProjectorNetTM Adapter Quick Start Guide

Addendum to Verbatim Gateway Owner's Manual. Gateway Ethernet Module Setup. Version 5.0

Standalone Voice/IP Gateway Model MVP110. Proprietary Mode. Quick Start Guide

DataSite Electronic Flow Meter and Remote Terminal Unit

Addendum to Verbatim Gateway Owner's Manual. Verbatim Gateway EtherNet Module Setup. Version 4.0

Recovery Guide for Cisco Digital Media Suite 5.4 Appliances

Allen-Bradley SLC5 Driver Configuration Manual

MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual

QUICK START GUIDE. SMS 2500iX Appliance.

16/24 Port 10/100 Auto-Sensing Dual Speed Ethernet Switch

Installation and Programming Manual. Niobrara Research & Development Corporation P.O. Box 3418 Joplin, MO USA

SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703

Secure Com Port Redirector User Guide

A12B DNP 3.0 SERIAL & ETHERNET (TCP/IP) SCADA INTERFACE

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.

515RTAENI-N34 Protocol Gateway Product User Guide

Serial DHX Driver Help Serial DF1 Protocol Driver for Allen-Bradley Networks

Familiarization with the PLC Trainer and RSLogix 500

EIDX_M Series INSTALLATION GUIDE INTRODUCTION. A Line of Managed Ethernet Switching Hubs

Selecting a Network. Ethernet Network

BACNet Gateway Option

DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for TPSD/A36D Chargers with S2A-205T Option 21P or 57T or 57U. Setup Instructions

Enhanced Programmable Logic Controller Gateway Specification and Technical Data

C-more Micro-Graphic Panel Accessories

Wireless Transducer MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

User Manual Protocol Converter PC-E, Serial to Ethernet (RS232/485 Modbus RTU to Modbus TCP/IP)

Enhanced Programmable Logic Controller Gateway Specification and Technical Data

USER S MANUAL. PH232Ex1. #1 RS-232 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH232Ex1-UM-001 IPEX. (IP Electronix)

DME-N Network Driver Installation Guide for M7CL

Aellius LynX Office Lookup Enhancements

MicroLogix 1000 Programmable Controllers

RS-232/422/485 Over IP Adapter

Programmable Logic Controller Gateway Specification and Technical Data

StoneGate IPS. Hardware Requirements for Version 5.2.0

SCADALink IP100 SCADA Terminal Server QUICK START GUIDE Revision 1.42 June 19, 2012

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL

ALLEN-BRADLEY DF1 INTEGRATION KIT FOR iocontrol USER S GUIDE

User Guide. ewon500 The Configurable Gateway PURPOSE. You have just received your brand new ewon500!

11Mbps Wireless LAN Smart Station Adapter

A36D/TPSD DNP 3.0 & Modbus SCADA INTERFACE

UPS COMMUNICATION Web Card

Ethernet HMi RAC and Gateway Setup Instructions Rev. 09

Serial to Ethernet Converter

Catalyst. Your all-in-one data logging and remote monitoring solution

This guide provides basic information for Unitronics controllers V C30B and V T40B.

3240-D0 Programmable Logic Controller (AB MicroLogix 1100 with Case)

Cisco TelePresence TelePresence Server MSE 8710

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision

Transcription:

TECH NOTES-307 Integrating RACO Verbatim Gateway with the Allen-Bradley SLC 5/05 Series PLC via Ethernet This technical note explains how to interface the RACO Verbatim Gateway system with the Allen-Bradley SLC 5/05 PLC via Ethernet. SLC 5/05 processors provide a 10/100BASE-T or 100 Mbps Ethernet port. This port along with the 1761-NET-ENI allows the Verbatim Gateway to perform its alarm notifications and monitoring functions using the existing wiring to the Allen-Bradley SLC 5/05 PLC as inputs via Ethernet. This technical note is applicable for all Verbatim Gateway models. RACO-supplied components: Verbatim Gateway (any model) 515VAB-ENI cable Allen-Bradley-supplied components: Any model of the SLC 5/05 PLC 1761-CBL-PM02 (RS232 programming cable) 1761-NET-ENI (DF1 to Ethernet protocol converter) Copy of ENI/ENIW Utility software (available free via www.ab.com) Either a crossover Ethernet cable or standard Ethernet cable connected through a Hub / Switch In order to facilitate Ethernet communications, RACO provides a 515VAB-ENI cable that connects the Verbatim Gateway to the 1761-NET-ENI. This cable has the RJ-45 connector required at the Verbatim Gateway end and the 8-pin mini at the other end that connects to Port 2 (RS232) of the 1761-NET-ENI card. Once this cable is connected, only Ethernet related hardware is required.

Communication Setup for the 1761-NET-ENI The 1761-NET-ENI provides Ethernet / IP connectivity to all DF1 full duplex devices. STEP #1 Acquire the 1761-NET-ENI card and the ENI / ENIW Utility program (free download from www.ab.com), both are required. STEP #2 Connect the 1761-CBL-PM02 serial cable. The serial cable connects your PC to the unit via the RS-232 port as illustrated (right). STEP #3 Ethernet port is easily found just below and left of the RS-232 port. STEP #4 The center of the unit contains a blank field available to illustrate your custom configurable IP Address. STEP #5 An external isolated 24vdc power source should be used and wiring terminals can be found at the bottom of the unit. In addition to assigning its own IP address, the ENI / ENIW Utility program maps the DF1 node address of the PLC, as defined in the Verbatim Gateway, to the PLCs IP address. STEP #6 There is a selector below for power. Make sure the switch is in the external position. External power is recommended always. STEP #7 Launch RSLogix software. Once the program is launched, you will observe seven available tabs from which to select. STEP #8 Choose the "Utility Settings'" tab. Select the COM port and baud rate that your PC will be using. TECH NOTES-307 Integrating RACO Verbatim Gateway with the Allen-Bradley SLC 5/05 Series PLC via Ethernet Page 2

STEP #9 Select the "ENI IP Addr" tab. Next, set the 232 Baud Rate to "Auto." Set the IP address of the 1761-NET-ENI. Ensure the ENI series is correct. Provide the "ENI IP Address", "Subnet Mask" and "Gateway" where necessary. STEP #10 Our next step prior to downloading / saving is to map the IP address of your SLC 5/05 to an available NODE / STATION address. Under the "Message Routing" tab, assign a DF1 NODE / STATION number (range from 0 49) to the IP address of your SLC 5/05. In this case we've assigned the node number 2. Now we are complete with the ENI / ENIW configuration utility and we can save and download our application. STEP #11 Observe that there are separate memory areas to save the application, either ENI RAM or ENI ROM. Use the ENI ROM selection. STEP #12 Once you've downloaded your application, you may save and close the Utility. The flashing "Fault" LED on the 1761-NET-ENI indicates an incompatible IP or Subnet. If the "Fault" LED is off following a download, you are now able to proceed. STEP #13 At this point you should also be able to ping the IP Address of your 1761-NET-ENI, and are ready to configure your Verbatim Gateway. TECH NOTES-307 Integrating RACO Verbatim Gateway with the Allen-Bradley SLC 5/05 Series PLC via Ethernet Page 3

Communication Setup for the Verbatim Gateway The following seven-step procedure will configure your Verbatim Gateway to link its Remote Channels (RC) to your PLC addresses over Ethernet highway, via DF1. Once linked, the Verbatim Gateway will monitor RC status and Alarms according to your settings. Connections to the PLC are via the onboard RJ45 port or NET. With the V232 / 485, two NET / ports are provided. NET ID = 1 is dedicated to the DH485 protocol and NET ID = 2 is configurable for either Modbus RTU Master or DF1 (Refer to table #1). TABLE #1 N Protocol Reference Description Nets 0 NONE Device disabled All nets 2 DH485 7.4.2 Allen-Bradley DH485 protocol Net1 V232 / 485 only 3 DF1 7.4.1 Allen-Bradley serial interface 4 5 MODBUSM 7.4.3 Modbus Master Net1 (on VCP only) Net 2 Net1 (on VCP only) Net 2 128 LDL 7.4.5 Local Data Logging May only be used on one device Net1 (on VCP only) Net 2, 4 STEP #1 Protocol Driver (4906) When setting the Protocol, Node Address and Communication parameters, it is good practice to include the NET ID (i.e. 4901, 4903, 4904, 4905 and 4906). Insert the NET ID immediately following the parameter number, as defined below. As per Table #1 above, set the Protocol Driver to DF1 on NET 2. Key in the following: 4906 2 <point> 3 <enter> To read the Protocol Driver for NET 2, key in the following: 4906 2 <enter> STEP #2 Node Address (4905) Choose a unique DF1 NODE address for the Verbatim Gateway. As illustrated above, we ve already selected NODE / STATION 2 for the PLC. DF1 allows NODE addresses to range from 1 64, however, the NET-ENI card can only access 0 49. Therefore a valid range is from 1 49. For example, set the Gateway NODE address to 1 by using code 4905. To set the NODE address of NET 2, key in the following: 4905 1<point> <2> <enter> To read the NODE address of NET 2, key in the following: 4905 1 <enter> STEP #3 Communication Parameters (4901, 4903, 4904) Select the communication parameters. These must match with the driver settings on your PLC. The following communication settings are required to communicate with the 1761-NET-ENI card. BAUD rate = 19200 for 19200 on NET 1, key in the following: 4901 2<point>19200 <enter> Stop Bits = 1 for 1 on NET 2, key in the following: 4903 2<point> 1 <enter> Parity = NONE for NONE on NET 2, key in the following: 4904 2<point> 0 <enter> Parity Definition: 0 = NONE, 1 = ODD, 2 = EVEN, 3 = SPACE, 4 = MARK TECH NOTES-307 Integrating RACO Verbatim Gateway with the Allen-Bradley SLC 5/05 Series PLC via Ethernet Page 4

STEP #4 Confirmations (4900, 4901, 4930, 4946) Step #4 will validate all preceding steps, provided both your serial and Ethernet cabling is in place. To verify successful network communications on NET 2, key in the following: 4930 <point> 2 <enter> To read the BAUD rate for NET 2, key in the following: 4901 2 <enter> To verify that communication settings reflect the above, at NET 2, key in the following: 4900 2<enter> To verify active node addresses on NET 2, key in the following: 4946 2<enter> STEP #5 Set Defaults This step simplifies Channel Configuration (i.e. Step 6). By setting to Default both the NET ID and NODE / STATION address, it is no longer necessary to reference them when setting Channel Configuration. Set the following to DEFAULT. 1 NET ID, used to communicate via DF1 (i.e. 2 ) 2 NODE / STATION address of the target PLC (i.e. "2" as assigned in the NET-ENI / W utility) To change the NET ID to 2, key in the following: 4910 2 <enter> To confirm the NET ID, key in the following: 4910 <enter> To change the PLC NODE / STATION address to 2 of NET 2, key in the following: 4911 2 <enter> To confirm PLC NODE / STATION address, key in the following: 4911 <enter> STEP #6 Channel 1 & 2 Configuration (4501, 4502) Since Verbatim Gateway channels are completely compatible with the logical and I/O addressing scheme for the file structure of the SLC series processors, the table below should look familiar. TABLE #2 Identifier File Type Example O Output O:1.0/0 (SLC500) O:017/10 (PLC5) I Input I:0.1/0 I:013/07 (SLC500) (PLC5) S Status S:2 S:2/0 B Bit B:0 B9:0/1 T Timer T4:0.2 T:0.0/1 C Counter C5:0.2 C10:0.0/1 R Control R6:2.1 R:2/15 N Integer N:1 N:1/0 F Floating Point F:2 (32-bit word) NOTE: Cannot specify 16 or 1-bit points with F file type. D, G, M1, etc All other types Not Supported Table #2 shows the Allen-Bradley-supported address types available to link to Verbatim Gateway channels. Indirect, indexed and symbolic addressing schemes are not supported TECH NOTES-307 Integrating RACO Verbatim Gateway with the Allen-Bradley SLC 5/05 Series PLC via Ethernet Page 5

The two examples below illustrate the link to the PLC data table (via DF1, Table #2) to the Verbatim Gateway channels Example #1 To link B3:0/0 in the PLC to Channel 1 as per the PLC file structure illustrated above, key in the following: 4501 <point> <shift> <B> <3> <shift> <:> <0> <shift> </> <0> <point> <enter> To verify the current address entered, key in 4501<point><enter> To read address value, key in 4001<point><enter>. This will read the actual PLC value assigned to Channel 1. Example #2 To link N7:0 in the SLC PLC to Channel 2 as per our PLC file structure illustrated above, key in the following: 4502 <point> <shift> <N> <7> <shift> <:> <0> <point> <enter> To verify the current address entered, key in 4502<point><enter> To read address value, key in 4002<point><enter>. This will read the actual PLC value assigned to Channel 2. STEP #7 Assignment of Alarm Conditions Having created and tested your Remote Channels in Step #6, you are now able to assign alarm conditions. Channel #1, configured as Discrete, is either ON or OFF. Should this channel be linked to a Failsafe point in the PLC (i.e. ON = NORMAL, OFF = ALARM), we would alarm when OFF. In this case, we would key in 45 01 2. To alarm when ON (i.e. signal is HIGH), key in the following: 45 01 1 To alarm when OFF (i.e. signal is LOW), key in the following: 45 01 2 To read Alarm status for Channel 1, key in: 4001<enter>. Channel #2, configured as Analog, operates within the range from 0 65, 535. Should this channel be linked to a pressure signal in PLC, and the process requires pressure remain within an acceptable level, otherwise ALARM (for example, BELOW 10,000 AND ABOVE 30,000), we would key in the following: To alarm when the analog signal falls below a value, for example 10,000, key in 45 02 5 10000 To read the LOW set point alarm, key in the following: 45 02 5 To alarm when the analog signal rises above a value, for example 30,000, key in 45 02 6 30000 To read the HIGH set point alarm, key in the following: 45 02 6 This document is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this document is not intended to constitute application, design, software or other professional engineering advice or services. Before making any decision or taking any action, which might affect your equipment, you should consult a qualified professional advisor. RACO Manufacturing and Engineering does not warrant the completeness, timeliness or accuracy of any of the data contained in this document and may make changes thereto at any time in its sole discretion without notice. Further, all information conveyed hereby is provided to users "as is." In no event shall RACO Manufacturing be liable for any damages of any kind including direct, indirect, incidental, consequential, loss profit or damage, even if RACO Manufacturing have been advised on the possibility of such damages. RACO Manufacturing and Engineering disclaims all warranties whether expressed or implied in respect of the information (including software) provided hereby, including the implied warranties of fitness for a particular purpose, merchantability, and non-infringement. Note that certain jurisdictions do not countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you. Specifications subject to change without notice. Trade names are trademarks or registered trademarks of their respective companies. RACO MANUFACTURING AND ENGINEERING CO. 1400 62nd Street Emeryville, CA 94608 (800) 722-6999 (510) 658-6713 FAX: (510) 658-3153 www.racoman.com Find us under RACOmann at: www.facebook.com www.twitter.com www.linkedin.com www.youtube.com http://autodialer-info.racoman.com