Bus Protection Application Challenges

Similar documents
Bus Bar Protection Applications Seminar

Redundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc

System Protection and Control Subcommittee

Busbar protection REB 670

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements

Distributed bus protection application in a platform for process bus deployment in the SMART SUBSTATION

We will discuss two types of loss-of-potential (LOP) logic during this presentation:

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation

An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems

ELG4125: System Protection

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

KEY BENEFITS APPLICATIONS FEATURES

SPECIAL CONSIDERATION OF FEEDER PROTECTION FOR BREAKER-AND-A-HALF CONFIGURA- TIONS. G. Steynberg

A Current Based, Communication Assisted High Speed Protection System to Limit Arc Energy. Patrick Robinson Altelec Engineering

Deploying Digital Substations: Experience with a Digital Substation Pilot in North America. Harsh Vardhan, R Ramlachan GE Grid Solutions, USA

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

Numerical Protective and Management Relays

PRC Coordination of Protection Systems for Performance During Faults

MiCOM Agile P746. Grid Solutions. Key Benefits. Numerical Busbar Protection. A Combination of Speed, Security and Selectivity. About MiCOM P40 Agile

ABB Data Center Forum 2017

1. Project Description

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Network Configuration Document Selection for New Substations Framework

Effective commissioning of bus bar protection systems using a dynamic simulation in the field

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers

BREAKER FAILURE PROTECTION

Siprotec 7ST61 / 7ST63

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection

Redundant Bus Protection Using High-Impedance Differential Relays

Utility Implements Communications- Assisted Special Protection and Control Schemes for Distribution Substations

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

Standard Development Timeline

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

SEL Time-Domain Link (TiDL ) Technology

Substation Automation Products. Line differential protection RED670 Relion 670 series

Implementing the protection and control of future DC Grids

FS Series PV Modules Reverse Current Overload

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure

AUTOMATED TESTING OF BUSBAR DIFFERENTIAL PROTECTION USING A SYSTEM-BASED APPROACH. Christopher Pritchard, Florian Fink

MiCOM P521. Fast Feeder Differential Protection

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection

Zone-Selective Interlocking Field Testing and Commissioning

Important Considerations in Testing and Commissioning Digital Relays

MODERN COST-EFFICIENT DIGITAL BUSBAR PROTECTION SOLUTIONS

MiCOM P521. Fast feeder differential protection

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Lecture 5 Substation Automation Systems. Course map

FP-5000 Feeder Protection

F6150. Power System Simulator For Testing Protection Relays and Schemes.

GE Energy Connections Grid Solutions MMLZ. Technical Data Sheet Auxiliary Modules. Publication reference: MMLZ/EN TDS/B

SE-701 MANUAL GROUND-FAULT MONITOR

p. 1 p. 9 p. 26 p. 56 p. 62 p. 68

User Manual. AQ-F215 Simulator

IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS

STEP OUT OF THE ARC FLASH HAZARD ZONE

Power Systems Communications Implementation of IEC61850 in a Substation Environment

Smart Grid Protection through Self-Healing

EDR-3000 Eaton Distribution Relay

Products Portfolio. Pole mounted Vacuum Recloser

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

USE CASE 13 ADAPTIVE TRANSMISSION LINE PROTECTION

Lessons Learned in Static VAR Compensator Protection

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

WHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION. Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District

www. ElectricalPartManuals. com .Basler Electric BE1-878 HIGH IMPEDANCE BUS DIFFERENTIAL RELAY ADVANTAGES ADDITIONAL INFORMATION APPLICATION Page2

MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

Integrating Monitoring and Diagnostic Equipment on Aging Transformers

Branch Procedure. Document No. Issue No. : : 29/06/ /06/2021 (Supersedes CEOP8012, Generation Connection: Protection Guidelines, Issue 4.

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS

This webinar brought to you by the Relion product family

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK

Relays for Various Protection Applications / 7SV600

IMP/ 001 / 014 Policy for the Protection of Distribution Networks

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection

RMS Product Presentation

750/760 Feeder Management Relay Instruction Manual

SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality,

SIPROTEC 5 Application Note. Breaker-and-a-half solutions. SIP5-APN-002, Edition 2.

Packaged Solutions. Grid Solutions. Value Added Solutions for Protection, Control and Automation Applications. Flexible and Expandable

FP5000. Refer to for the latest information on this constantly evolving product

Catching Falling Conductors in Midair Detecting and Tripping Broken Distribution Circuit Conductors at Protection Speeds

FP-5000 Series Multi-functional Microprocessor-based Feeder Protective Relay

Auxiliary Units for 7SR23 High Impedance Protection Energy Management

IED (Intelligent Electronic Device)

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection

DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830

Spectra RMS Circuit Breakers with microentelliguard Trip Units

PUBLIC SERVICE OF NEW HAMPSHIRE. Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System

VIP 40/45 VIP 400/410

Protection relays.

SIPROTEC 5 V7.8 Protection, automation and monitoring for digital substations

Transcription:

Bus Protection Application Challenges KN Dinesh Babu - Megger JC Theron, Lubomir Sevov GE Grid Solutions 2017 Texas A&M Protective Relay Conference

Content Introduction Application Challenges Increase Security with Supervising Elements Open CT Detection Monitoring Isolator Positions Detection of External Faults Engineering Experience of Complex Bus Protection Schemes End Fault Protection Schemes Conclusions

Challenges to Bus Zone Protection High fault current levels can: Damage equipment from mechanical stress on busbars Lead to CT saturation Cause high levels of arc flash Mal-operation of bus protection has significant impact Loss of customer loads may damage customer assets Detrimental impact on industrial processes System voltage levels stability may be adversely impacted

Challenges to Bus Zone Protection Many different bus topologies Many switchyard configurations possible Many different CTs possible Single bus, double bus, main and transfer bus, breakerand-a-half, etc. Buses may reconfigure at any time Different components may be connected/disconnected to a bus Switching invoking bus reconfiguration occurs from different sources Bus Protection Must be Dependable and Secure, With Emphasis on Security

Additional Security for The Bus Differential Zone No matter reliability, any relay may fail. For bus applications, any MTBF never high enough Consider securing the application against reasonable contingencies CT problems, AC wiring problem Problems with aux. switches for breakers, isolators DC wiring problems involving the Dynamic Bus Replica Failure of relay hardware (single current input channel, single digital input) Security above and beyond inherent security mechanisms in IEDs CT Saturation Detector Directional (Phase) Comparison Isolator monitoring

External Check Zone Principle: Develop independent copy of differential current for entire bus regardless of dynamic zones for individual bus sections Use the check zone to supervise the tripping zone(-s) Use independent CTs / CT cores if possible to guard against CT and wiring problems Use independent relay current inputs to guard against relay problems Alarm on spurious differential Guards against: CT problems and AC wiring problems Malfunctioning of auxiliary 52/89 contacts for breakers and isolators DC wiring problems for dynamic bus replica Failures of current inputs

Application of Overcurrent Check Zone External check zone can be configured as unrestrained zone that (ideally) uses separate CTs or CT cores IOC function can be configured to operate on the externally summated currents (from different IED or Inputs) For external zone, CTs summed for this overcurrent must: Have identical CT ratios or matching transformers are required Be of same type Make use of three ground CT inputs (IG) and Ground IOC or unused 3- phase bank & Phase IOC elements as check zone

Application of Overcurrent Check Zone 87B phase A supervised by IOC1 phase A; the IOC responds to the externally formed differential current Three-phase trip command

External IED Check Zone Equivalent Bus Zone Use two different CTs / CT cores Place the supervising zone in a different chassis Strong security bias, practically a 2-out-of-2 independent relay scheme Use fail-safe output to substitute for the permission if the supervising relay fails / is taken out of service

External IED Check Zone External Voltage Supervision Place the supervising voltage inputs in a different IED Guards against relay problems and bus replica problems Does not need any extra ac current wiring Use fail-safe output to substitute for the permission if the supervising relay fails / is taken out of service

Open CT Detection CT problems and AC wiring problems challenge security of Bus Protection Secondary open CT must be identified hazardous overvoltage (Safety) Multifunctional IEDs calculating sequence components (I2) capable to detect Phase Segregated IEDs can t calculate sequence components (Centralized schemes) Alternative: use CT Trouble/Low Diff, Breaker status and Current Supervision. Implemented in Centralized 400kV & 220kV schemes

Monitoring Isolator Positions Reliable Isolator Closed signals needed for Dynamic Bus Replica In simple applications, a single normally closed contact sufficient For maximum security: Use both N.O. (89a) and N.C. (89b) contacts Alarm for non-valid combinations (open-open, closed-closed) Inhibit switching operations until bus image is recognized Optionally block 87B operation from Isolator Alarm Each isolator position signal determines: Circuit currents to be included in the differential calculations Circuit breakers to be tripped ZONE 1 ZONE 2

Typical Isolator Connections

Isolator Switching Sequence Time of Open/Close of 89a/89b must be adjusted to ensure current of circuit included when Isolator closes 89a/89b close indication must be just before circuit current flowing through Isolator; not after 89a/89b open indication must be just after Isolator interrupted current

Isolator Switching Sequence Importance Eg. 1 ZONE 3=CHECK ZONE L7 ZONE 1=BUS1 ISO31 CB1-2 L8 ZONE 2=BUS2 ISO10 ISO11 ISO13 ISO14 ISO16 ISO17 ISO19 ISO20 ISO22 ISO23 ISO25 ISO32 ISO26 ISO28 ISO29 CB4 CB5 CB6 CB7 CB8 CB9 CB10 ISO12 F4 ISO15 F5 ISO18 F6 ISO21 F7 ISO24 F8 ISO27 L1 ISO30 L2 What happens when an AG fault occurs on Bus 2 during transition of F7 from Bus 1 to Bus 2 with both Isolators Iso19 and Iso20 closed?

Isolator Switching Sequence Importance Eg. 2 ZONE 3=CHECK ZONE L7 CB1-2 ZONE 1=BUS1 ISO31 L8 ZONE 2=BUS2 ISO8 ISO10 ISO11 ISO13 ISO14 ISO16 ISO17 ISO19 ISO20 ISO22 ISO23 ISO25 ISO26 ISO32 ISO28 ISO29 CB4 CB5 CB6 CB7 CB8 CB9 CB10 F3 ISO12 F4 ISO15 F5 ISO18 F6 ISO21 F7 ISO24 F8 ISO27 L1 ISO30 L2 What happens when an Internal AG fault occurs on feeder F7 with bypass Isolator Iso21 closed? Zone 2 Disabled Only Active Protection Breaker Fail Backup O/C

Detection of External Faults Bus configuration could require large CT ratio differences: Main power feeders large CT ratio Load/small generation feeders low CT ratio s Hence, I2 due to F2 will be significantly larger than I1 due to F1 General recommendation: increase CT ratio Load/small generation feeder CT sized for load and not system fault condition; Hence, significant CT saturation can occur due to I2

External Faults: CT Saturation Detection CT saturation detection in some IEDs counts on Differential vs Restraining current trajectory Expect trajectory to move from t0 to t1, then to t2 This is possible with at least 2ms saturation-free current

External Faults: Extreme CT Saturation Detection CT saturation below in less than 2.5ms at 50Hz CT saturation too fast to guarantee secure CT saturation detection

External Faults: CT Saturation Alternative General recommendation: Increase CT ratio Not economical feasible Increased CT ratio impacts local feeder protection sensitivity Alternative: use very fast current magnitude detection faster than 87B Conventional current detection based on DFT too slow slower than 87B Time domain sample-based overcurrent (3 5ms reaction) faster than 87B Comparison between full cycle Fourier (Green) and Fast OC Mag Det (Red) Fast OC Mag Detection used to supervise 87B on external faults

Engineering Experience : Complex Buses (1) Complex bus arrangements (Double bus with 2 transfer busses) can have Main Bus operated as Transfer Bus 4 Zones plus 2 check zones Complex operational procedures to facilitate maintenance requirements Traditionally very complex operational procedures required on Bus Protection (Main Bus to act as Aux Bus) to maintain protection security Very unreliable operations achieved if not followed in detail misoperations With a low impedance IED bus replica bus protection, this is eliminated.

Engineering Experience : Complex Buses (2) Fault at F1 detected as Bus 2 fault trips all Bus 2 Breakers. However fault in Bus 1 hence not cleared since seen as external fault Normally cleared by Breaker Failure unacceptable time delay End Fault used for accelerated tripping (40ms) normal circumstances Delayed tripping logic (150ms) added from Bus 1 OR Bus 2 trip in event breaker contacts or wiring failed.

End Fault Protection: Changing the Zone contract CB CT Over-trip spot for bus protection Over-trip between CB and CT when CB is open When CB is open, current must be removed from 87B calculation contracting 87B zone to CB This exposes this small part of the power system to uncleared faults until cleared by backup protection, but

End Fault Protection: Changing the Zone CB Blind spot for bus protection CT But A blind spot is created when the bus zone contracted to the CB End Fault Protection is required to trip remote circuit breaker(s) for this fault

End Fault Protection (EFP) CB CT Instantaneous overcurrent enabled when associated CB is open to cover blind spot between CB and line-side CT Pickup delay must be long enough to ride-through ramp down of current interruption (1.3 cycles max) EFP sends transfer trip to remote end of circuit/ps component End Fault Protection must be inhibited from Manual Close command Most Bus Protection IEDs (Centralized and De-centralized) do have EFP

Conclusions Power systems are evolving; hence the need that Bus Protection should follow Bus Protection must remain very dependable and secure Low Impedance most suitable for new application challenges Six application challenges, with implemented changes, covered where conventional Bus Protection falls short

Thank You Questions?