CSC-150 Busbar Protection IED Product Guide

Similar documents
CSC-150 Busbar Protection IED Technical Application Manual

CSC-121 Breaker Protection IED Product Guide

Relion 611 series. 611 series Type Test Certificate

CSC-150 Busbar Protection IED Technical Application Manual

CSC-211 Multifunction Protection IED Product Guide

Bus Bar Protection Relay B-PRO 4000

Earth-fault Relay SPAJ 110 C. Product Guide

Arc protection relay. Features Three-phase overcurrent function. Application

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

Communication Gateway COM 610. Product Guide

Feeder protection relay SPAA 121 C. Product Guide

Synchro-check relay. Application

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

Arc protection relay. Features Three-phase overcurrent function. Application

TU531, TU532 Terminal Unit

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

CSC-211 Multifunction Protection IED Product Guide

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

Residual overvoltage relay

Transformer Protection Relay

CSC-161 Line Protection IED Product Guide

AO523 Analog Input Module

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

TF501, TF521 Terminal Bases

ekorrps MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Protection Relays PHASE & RESIDUAL OVERCURRENT

TM221M16R controller M IO relay

Table 1 Relay Model and Function

Type VRLTC tap changer

TM221M16TG controller M IO transistor PNP spring

Directional or Non-Directional Earth-Fault Relay REJ 527. Product Guide

Siprotec 7ST61 / 7ST63

PowerLogic power-monitoring units. Power Meter PM500. Technical data sheet 2006

AX522 Analog Input/Output Module

MIC-2 MKII, Multi-instrument DATA SHEET

CM597 Ethernet Communication Module

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET

ekor.rps Multifunctional protection unit Volume 3 of 3: ekor.rps-tpc General instructions IG-150-EN, version 04, 03/10/16 LIB

FL MC 2000E (SM40) LC

CM592 PROFIBUS Communication Module

INGEPAC DA-CU. Control Unit. Data Sheet ZY8932IMA01E 31/03/2016

TM221M32TK controller M IO transistor PNP

CM589 PROFINET Communication Module

Feeder protection relay SPAA 341 C. Product Guide

Relays for Various Protection Applications / 7SV600

AX521 Analog Input/Output Module

AI531 Analog Input Module

DC522 Digital Input/Output Module

CM579-PNIO PROFINET Communication Module

CI504 PROFINET Communication Interface Module

TM221CE24R controller M IO relay Ethernet

DRTS 66. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

Feeder protection relay

DC541 Digital Input/Output Module

Model Number Structure

CM589 PROFINET Communication Module

Substation Automation Products. Line differential protection RED670 Relion 670 series

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

TM221ME32TK controller M IO transistor PNP Ethernet

High impedance protection relay

Multifunction Transducer MT440

CD522 Encoder, Counter and PWM Module

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

This annex is valid from: to Replaces annex dated: Location(s) where activities are performed under accreditation

TM221CE40R controller M IO relay Ethernet

MIC-2 Multi-instrument DATA SHEET

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

GRD130 - FEATURES APPLICATION

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

extending the boundaries of technology evolution of proven technology FEATURES

RT4B-110V/12A RECTIFIER

InteliPro. Protection Relay for Parallel Applications. Technical Specification

MINER-S Station Controller. Substation Automation

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box

Remote I/O RIO600 Product Guide

Published by and copyright 2015 Siemens AG Energy Management Freyeslebenstr Erlangen, Germany

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

High Impedance Protection Relay SPAE010, SPAE011. Product Guide

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

TM221CE40T controller M IO transistor PNP Ethernet

For Transmission, Distribution and Machinery protection.

Tripping Matrix Device 7UW5010. As of Tripping Circuit Management Unit or Non-electric Protection Device. Catalog 1.0. Answers for energy.

PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL

DC532-XC, digital input/output module,

TM241C40U controller M IO transistor NPN

RT4F-110V/25A RECTIFIER

Bulletin 290/291 ArmorStart LT Distributed Motor Controllers Specifications

AI561 Analog Input Module

TM241C24T controller M IO transistor PNP

DRTS 33. The new generation of advanced three phase relay test set

XE2 DC current relay for loss of excitation protection. Manual XE2 (Revision A)

Voltage Transducer UMT516 / MT516

Data Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters.

Transcription:

CSC-150 Busbar Protection IED Product Guide

Version V1.0 Doc. Code: 0SF.492.056(E) Issued Date 201. Copyright owner: Beijing Sifang Automation Co., Ltd. Note: The company keeps the right to perfect the instruction. If equipments do not agree with the instruction at anywhere, please contact our company in time. We will provide you with corresponding service. is registered trademark of Beijing Sifang Automation Co., Ltd. We reserve all rights to this document, even in the event that a patent is issued and a different commercial proprietary right is registered. Improper use, in particular reproduction and dissemination to third parties, is not permitted. This document has been carefully checked. If the user nevertheless detects any errors, he is asked to notify us as soon as possible. The data contained in this manual is intended solely for the IED description and is not to be deemed to be a statement of guaranteed properties. In the interests of our customers, we constantly seek to ensure that our products are developed to the latest technological standards as a result; it is possible that there may be some differences between the hardware/software product and this information product. Manufacturer: Beijing Sifang Automation Co., Ltd.

Overview CSC-150 is selective, reliable and high speed busbar protection IED (Intelligent Electronic Device), with powerful capa- -bilities to cover following applications: For various busbar arrangements, including those listed below: Single Busbar Two Single Busbars connected with bus coupler Two Separate Busbars in 1 CB arrangement Double Busbar Main and Transfer Busbar Double Main and one Transfer Busbar Main and Main/Transfer Busbar For solidly earthed, low impedance earthed or isolated power system Used in a wide range of voltage levels, up to 750kV Communication with station automation system The IED provides reliable busbar differential protection with integrated check zone, short saturation-free time and fast tripping time as well as circuit breaker failure protection and dead zone protection. The wide application flexibility makes the IED an excellent choice for both new installations and retrofitting of the existing installations.. 1

Feature Protection and monitoring IED with extensive functional library, user configuration possibility and expand- -able hardware design to meet with user s special requirements Inter-lock between two CPU modules, avoiding maloperation due to internal severe fault of one module Busbar differential protection (87BB) Low-impedance centralized differ- -ential protection circuit supervision (97FF) Current transformer secondary circuit supervision Self-supervision to all modules in the IED Complete IED information recording: tripping reports, alarm reports, startup reports and general operation reports. Any kinds of reports can be stored up to 2000 and be memorized in case of power disconnection Selective zone tripping Extreme stability against exteral fault, short CT saturation-free time Phase-segraegated measuring system Integrated check zone Bus couplers/disconnetor is defin- -able in busbar scheme A complete protection functions library, include: Busbar differential protection (87BB) Circuit breaker failure protection (50BF) Dead zone protection (50DZ) Voltage transformer secondary Up to three electric /optical Ethernet ports can be selected to communicate with substation automation system by IEC61850 or IEC60870-5-103 proto- -cols Up to two electric RS-485 ports can be selected to communicate with substation automation system by IEC60870-5-103 protocol Time synchronization via network (SNTP), pulse and IRIG-B mode Configurable LEDs (Light Emitting Diodes) and output relays satisfied users requirement Versatile human-machine interface Multifunctional software tool for setting, monitoring, fault recording analysis, configuration, etc. 2

Function Protection functions IEC 61850 IEC 60617 Description ANSI Code Logical Node graphical Name symbol Differential protection Busbar differential protection 87BB PDIF Breaker control function Breaker failure protection 50BF RBRF 3I> BF I 0>BF I 2>BF Dead zone protection 50DZ Secondary system supervision CT secondary circuit supervision VT secondary circuit supervision 97FF Position of circuit breaker, disconnector and other switching devices monitoring Monitoring functions Description Auxiliary contacts of circuit breaker supervision Self-supervision Fault recorder Station communication Description Front communication port Isolated RS232 port for maintaining Rear communication port 0-2 isolated electrical RS485 communication ports, support IEC 60870-5-103 protocol 3

Function 0-3 Ethernet electrical/optical communication ports, support IEC 61850 protocol or IEC 60870-5-103 protocol Time synchronization port, support GPS pulse or IRIG-B code IED software tools Functions Reading measuring value, IED report Setting IED testing Disturbance recording analysis IED configuration Printing 4

Function Application for busbar 50DZ 50DZ 50BF 3I>BF RBRF 50DZ 50BF 3I>BF RBRF 50BF 3I>BF RBRF 87BB PDIF 50BF 3I>BF RBRF 50DZ 50BF 3I>BF RBRF 50DZ MEASUREMENT MONITORING STATION COMMUNICATION Fault recording - RS232/485 - RJ45/FO - IEC61850 - IEC60870-5-103 5

Protection Busbar differential protection (87BB) Busbar differential protection represents the main protection function of the IED. It is characterized by a high measurement accuracy as well as flexible matching to most of busbar configurations. The operation is based on the percentage restraint principle with an extreme stability feature against heavy CT saturation caused by external fault. characteristic is a straight line inclined at 45. Any difference in phase relation of the fault currents leads to a lowering of the fault characteristic. The settable slope, Slope_BDiff is represented as a straight line with corresponding gradient and forms the operating characteristic. The differential current i Diff and the restraining current i Res are calculated in the IED according to following formula. The following definitions are applied for each phase. Operating characteristic Figure 1 illustrates the characteristic of busbar differential protection function. idiff where: n 1, n 2, n n: CT transformation ratios of various feeders connected to the busbar. The IED is informed about these values by user-defined settings I_BDiff K=1 Operating zone K=K_Diff The IED evaluates the differential current and the restraining current at consecutive sampling intervals. The busbar protection would issue a trip command if there are more than (N-2) samples fulfilling following condition in the program observation window: ires Figure 1 Characteristic of busbar differential where: protection i Diff: Busbar differential current i Res: Busbar restraint current I_BDiff: The sensitive threshold of pickup current of busbar differential protection K_Diff: Slope_BDiff, the settable slope of the characteristic If a short circuit occurs on the busbars whereby the same phase relation applies to all infeeding currents, then the fault The above mentioned calculation is performed in relevant bus zones as well as in check zone, respectively. The trip command can be issued only when both the faulty bus zone and the check zone are in operating area. Automatic ratio compensation CT ratios of in a busbar system may be different in various feeders, because the load conditions may be different in the feeders. The IED adjusts CT ratio of all 6

Protection feeders automatically, making the secondary currents fulfilling Krichhoff s current law (KCL). In order to insure the accuracy, the difference of CT ratios among various feeders should not be more than 4 times. Disconnector replica The IED confirms the disconnector status by monitoring the disconnector status contacts. For each disconnector, both the normally open status contact (NO) and normally close status contact (NC) are required. Based on the status of these two contacts, the IED can discriminate error of the contacts and then alarm or/and block the relevant bus zone of differential protection depending on the setting. If blocking protection is selected, the IED would issue an alarm signal and would block the protection. If no blocking is selected, only alarm signal would be issued and the protection would continue to its operation according to the previous healthy state of the disconnector before the contacts error. Circuit breaker status The feeder or coupler circuit breaker status contacts together with disconnector status contacts are used to determine the actual bus connection state for differential current calculation and indication of busbar connection Both normally open status contact and normally close status contact of circuit breakers of all feeders including bus coupler are connected to the IED. Based on the status of these two contacts, the IED can discriminate error of the contacts and then alarm until the error is cleared, and the protection would continue to its operation according the previous healthy state of the breaker before the contacts error. Current transformer open circuit supervision When an open circuit occurs in secondary circuit of current transformers, differential current appears in bus-section selective zones. Further, if the faulty current transformer corresponds to a feeder, differential current would further appear in check zone. The IED detects such a condition and issues respective alarm report. Moreover, it is possible to block busbar differential protection when a CT open circuit is detected. Differential current saturation supervision When an external fault occurs near the busbar, it may lead to current transformer saturation on the faulty feeder. The resulting differential current may cause the protection to maloperate if no measure is taken to detect saturation condition. To cope with the problem, the IED provides a sensitive element to detect current trans- -former saturation according to the wave- -form characteristics of differential and restraining current. In fact, secondary current can be transformed accurately, even by a saturated current transformer, when the current is near zero or at the initial instants of fault. At these instants, the differential current is zero. The IED adopts this characteristic to detect current transformer saturation. The CT saturation free time is only 2 ms. 7

Protection Sequence trip In case of bus coupler with only one CT, when a fault occurs between the CT and bus coupler circuit breaker while the circuit breaker is closed, the IED will trip the bus section near bus coupler circuit breaker instantaneously, and after a fixed time delay, if the bus coupler circuit breaker is opened, the IED will trip the other bus section. The tripping logic is illustrated in Figure 2. The protection operates separately for each feeder and coupler with dedicated settings. Once a circuit breaker operating failure occurs on a feeder/transformer, the bus section which the feeder/transformer is connected with can be selectively isolated by the protection. In addition a transfer trip signal is issued to trip the remote end circuit breaker of the feeder or other transformer windings. Delay trip Instantaneous trip In the event of a circuit breaker failure with a busbar fault, a transfer trip signal is issued to trip the remote end circuit breaker of the feeder. Bus A IFAULT Bus B The current criteria are in combination with three phase current, zero and negative sequence current to achieve a higher security. 2 trip stages (local and surrounding breaker tripping) Related bus zone tripping in second stage Line A1 Legend: Line An Closed CB Line B1 Line Bm Figure 2 Trip logic to clear fault between coupler breaker and its CT Breaker failure protection (50BF) The circuit breaker failure protection is able to detect a failure of the circuit breaker during a fault clearance. It ensures fast back-up tripping of surrounding breakers by tripping relevant bus sections. Transfer trip command to the remote line end in second stage Internal/ external initiation Single/three phase CBF initiation Current criteria checking (including phase current, zero and negative sequence current) Dead zone protection (50DZ) The IED provides dead zone protection to protect the area, between circuit breaker and CT in the case that CB is open. 8

Protection Therefore, by occurrence of a fault in dead zone, the short circuit current is measured by protection relay while CB auxiliary contacts indicate the CB is open. Self-adaptive for bus side CT or line side CT When one bus side CT of feeder is applied, once a fault occurs in the dead zone, the IED trips the relevant busbar zone. Tripping logic is illustrated in Figure 3 Inter trip IFAULT Bus Line1 Line2 LineN Bus Trip Trip Relay IFAULT Legend: Opened CB Closed CB Line1 Line2 LineN Legend: Opened CB Closed CB Figure 3 Tripping logic when applying bus side CT Figure 4 Tripping logic when applying line side CT In case of bus coupler with only one CT, when a fault occurs between the CT and bus coupler circuit breaker while the circuit breaker is opened, the IED will trip the bus section near the bus coupler CT instantaneously. Tripping logic is illustrated in Figure 5. When one line side CT is applied, when a fault occurs in the dead zone, protection relay sends a transfer trip to remote end relay to isolate the fault. Tripping logic is illustrated in Figure 4 9

Protection circuit supervision Line A1 Instantaneous trip Bus A Legend: Line An Opened CB Closed CB IFAULT Line B1 Bus B Line Bm A measured voltage failure, due to a broken conductor or a short circuit fault in the secondary circuit of voltage transformer is detected in the IED. The features of the function are as follows: Symmetrical/asymmetrical VT failure detection 3-phase AC voltage MCB monitoring 1-phase AC voltage MCB monitoring Zero and negative sequence current monitoring Applicable in solid grounded, compensated or isolated networks Auxiliary contacts of circuit breaker and disconnector supervision Figure 5 Tripping logic for fault between coupler breaker and its CT Secondary system supervision Current transformer secondary circuit supervision Open circuited CT cores can cause unwanted operation of differential protec- -tion function. The interruption on CT secondary circuit can be detected by the IED. The IED provides following features: One stage for alarm One stage for block busbar differential protection Each stage can be selected and set separately Voltage transformer secondary The IED is connected with normally open contacts and normally close contacts of circuit breakers and disconnectors. It performs monitoring on the received information to detect any implausible status. If such a wrong status is detected for a disconnector, the IED will announce it after a settable time delay, and continue to operate according to previous healthy state of disconnector contacts. If the blocking function is enabled, the relevant bus zone of the busbar differential protection would be blocked until the wrong status changing to normal. Otherwise, the relevant bus zone of the busbar differential protection would not be blocked. If such a wrong status is detected for a circuit breaker, the device announces it after a settable time delay, and the protection will continue to operate according to previous healthy state of 10

Protection disconnector contacts. 11

Monitoring Self-supervision All modules can perform self- -supervision to its key hardware components and program, as soon as energizing. Parts of the modules are self-supervised in real time. All internal faults or abnormal conditions will initiate an alarm. The fatal faults among them will result in the whole IED blocked CPU module and communication module perform real time inter- -supervision. Therefore communication interruption between them is detected and related alarm will be given CRC checks for the setting, program and configuration, etc. 12

Communication Station communication Overview The IED is able to connect to one or Server or Work Station 1 more substation level systems or equipments simultaneously, through the communication ports with communication protocols supported. (Shown in Figure 6) Server or Work Station 2 Work Station 3 Switch Work Station 4 Net 1: IEC61850/IEC103,Ethernet Port A Switch Net 2: IEC61850/IEC103,Ethernet Port B Switch Switch Switch Gateway or converter Switch Gateway or converter Net 3: IEC103, RS485 Port A Net 4: IEC103, RS485 Port B Figure 6 Connection example for multi-networks of station automation system Note: All four ports can work in parallel Front communication port There is a serial RS232 port on the front plate of all the IEDs. Through this port, the IED can be connected to the personal computer for setting, testing, and configuration using the dedicated Sifang software tool. RS485 communication ports Up to 2 isolated electrical RS485 communication ports are provided to connect with substation automation system. These two ports can work in parallel for IEC60870-5-103. Ethernet communication ports Up to 3 electrical or optical Ethernet communication ports are provided to connect with substation automation system. These two out of three ports can work in parallel for one protocol, IEC61850 or IEC60870-5-103. Communication protocol The IED supports station communication with IEC 61850-8 and IED60870-5-103 protocols. By means of IEC61850, GOOSE peer- to peer communication make it possible that bay IEDs can exchange information to each other directly, and a simple master-less system can be set up for bay and system interlocking and other interactive function. Time synchronization port All IEDs feature a permanently integrated electrical time synchronization port. It can be used to feed timing telegrams in IRIG-B 13

Communication or pulse format into the IEDs via time synchronization receivers. The IED can adapt the second or minute pulse in the pulse mode automatically. Meanwhile, SNTP network time synchronization can be applied. The Figure 7 illustrates the optional time synchronization modes. SNTP IRIG-B Pulse Ethernet port IRIG-B port Binary input Figure 7 Time synchronizing modes 14

Software Tools A user-friendly software tool is offered for engineering, setting, disturbance analysis and monitoring. It provides versatile functionalities required throughout the life cycle of protection IEDs. Its features are as follows: diagrams, vector diagrams, bar charts and data sheet. Device administration in projects with freely configurable hierarchies for any substation and electrical power station topology Intelligent plausibility checks rule out incorrect input Modification, import and export of parameter sets sorted by protection functions, with setting logicality check Precise fault analysis with visualization of fault records in curves, circle Graphical visualization of charac- -teristics and zone diagrams with direct manipulation of the curves Password-protected access for different jobs such as parameter setting, commissioning and controlling (authorized staff only) Testing and diagnostic functions decisive support in the commissioning phase 15

Connection Front plate The whole front plate is divided into zones, each of them with a well-defined 1 functionality: 5 4 CSC-150 2 3 8 6 7 Figure 8 Front plate 1 Liquid crystal display (LCD) 2 LEDs 3 Shortcut function keys 4 Arrow keys 5 Reset key 6 Quit key 7 Set key 8 RS232 communication port 16

AIM AIM AIM AIM BIM BOM COM PSM CPU1 CPU2 AIM AIM AIM PSM BOM BOM BOM BOM BOM BIM BIM BIM BIM BIM BIM BOM BOM BOM BOM BOM PSM BIM Rear terminals Rear plate CAN X21 Test port X14 X13 X12 X11 X4 X3 X2 X1 X20 X19 X18 X17 X16 X15 X10 X9 X8 X7 X6 X5 Figure 9 Rear plate of the main case CAN X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 Figure 10 Rear plate of the auxiliary case. 17

Hardware Modules Analogue Input Module (AIM) The analogue input module is used to galvanically separate and transform the secondary currents and voltages generated by the measuring transformers. CPU Module (CPU) The CPU module handles all protection functions and logic. There are two CPU modules in the IED, CPU1 and CPU2, with the same software and hardware. They work in parallel and interlock each other to prevent maloperation due to the internal faults of one CPU modules. Moreover, the redundant A/D sampling channels are equipped. By comparing the data from redundant sampling channels, any sampling data errors and the channel hardware faults can be detected immediately and the proper alarm and blocking is initiated in time. Communication Module (COM) The communication module performs communication between the internal protection system and external equipments such as HMI, engineering workstation, substation automation system, RTU, etc., to transmit remote metering, remote signaling, SOE, event reports and record data. Up to 3 channels isolated electrical or optical Ethernet ports and up to 2 channels RS485 serial communication ports can be provided in communication module to meet the communication demands of different substation automation system and RTU at the same time. The time synchronization port is equipped, which can work in pulse mode or IRIG-B mode. SNTP mode can be applied through communication port. In addition, a series printer port is also reserved. Binary Input Module (BIM) The binary input module is used to connect the input signals and alarm signals such as the auxiliary contacts of the circuit breaker (CB), etc. Binary Output Module (BOM) The binary output modules mainly provide tripping output contacts, initiating output contacts and signaling output contacts. All the tripping output relays have contacts with a high switching capacity and are blocked by protection startup elements. Each output relay can be configured to satisfy the demands of users. Power Supply Module (PSM) The power supply module is used to provide the correct internal voltages and full isolation between the terminal and the battery system. 18

Hardware Dimension C E A D B Figure 11 8U, 1/1 x 19 main case with rear cover Table 1 Dimension of the main case Legend A B C D E Dimension (mm) 354.8 482.8 267.7 320 450 19

Hardware G E D F C A B Figure 12 Cut-out for the panel mounting of main case Table 2 Dimension of the cut-out for main case panel mounting Legend A B C D E F G Dimension (mm) 450 465 101.6 76.2 101.6 355.6 6.5 20

Hardware D A C B Figure 13 4U, 1/1 x 19 auxiliary case with rear cover Table 3 Dimension of the auxiliary case Legend A B C D E Dimension (mm) 177 482.6 265 320 437.2 E C D A B Figure 14 Cut-out on the panel for auxiliary case Table 4 Dimension of the cutout for auxiliary case panel mounting Legend A B C D E Dimension (mm) 450 465 101.6 178 6.5 21

Connection 22 A. Typical rear terminal diagram X1 CSC-150 Main case a01 I1 b01 a02 I2 b02 a03 I3 b03 a04 I4 b04 a05 I5 b05 a06 I6 b06 a07 I7 b07 a08 I8 b08 a10 I9 b10 a09 b09 a11 b11 a12 b12 X2 a01 I1 b01 b12 X11 a02 BI02 c02 BI03 a04 BI04 c04 BI05 a06 BI06 c06 BI07 a08 BI08 c08 BI09 a10 BI01 BI10 c10 BI11 a12 BI12 c12 BI13 a14 BI14 c14 BI15 a16 BI16 c16 BI17 a18 BI18 c18 BI19 a20 BI20 c20 BI21 a22 BI22 c22 BI23 a24 BI24 c24 BI25 a26 BI26 c26 BI27 a28 BI28 c28 BI29 a30 BI30 c30 a32 c32 BI-COM1(-) BI-COM2(-) Note: 1) The module is same as X1 module. I10 a12 1) a01 I1 b01 b12 a12 X8 a01 I1 b01 a02 I2 b02 a03 b03 a04 b04 a05 b05 a06 b06 a07 b07 a08 b08 a10 b10 a09 UB3 b09 UC3 UA3 a11 b11 a12 b12 UN3 UB1 UC1 UA1 UN1 UB2 UC2 UA2 UN2 X3 a01 I1 b01 b12 a12 X4 a01 I1 b01 b12 a12 X5 a01 I1 b01 b12 a12 X6 1) 1) 1) 1)

Connection CSC-150 main case X12 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 Output relay 01 Output relay 02 Output relay 03 Output relay 04 Output relay 05 Output relay 06 Output relay 07 Output relay 08 Output relay 09 Output relay 10 Output relay 11 Output relay 12 Output relay 13 Output relay 14 Output relay 15 Output relay 16 Power failure alarm relay 1 Power failure alarm relay 2 DC 24V + output DC 24V - output AUX DC + input AUX DC - input Terminal for earthing Terminal for earthing X14 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 X13 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 RS485-2B RS485-2A RS485-1B RS485-1A GPS GPS - GND Ethernet Port 1 - RJ45 Ethernet Port 2 - RJ45 1) Power failure alarm relay 1 Power failure alarm relay 2 DC 24V + output DC 24V - output AUX DC + input AUX DC - input Terminal for earthing Terminal for earthing X15 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 Note: 1) Alternative Ethernet ports are 2 ST optical fiber ports, shown as following. Ethernet Port 1 - ST Ethernet Port 2 - ST 23

Connection CSC-150 main case X16 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 Output relay 01 Output relay 02 Output relay 03 Output relay 04 Output relay 05 Output relay 06 Output relay 07 Output relay 08 Output relay 09 Output relay 10 Output relay 11 Output relay 12 Output relay 13 Output relay 14 Output relay 15 Output relay 16 1) Output relay 01 Output relay 02 Output relay 03 Output relay 04 Output relay 05 Output relay 06 Output relay 07 Output relay 08 Output relay 09 Output relay 10 Output relay 11 Output relay 12 Output relay 13 Output relay 14 Output relay 15 Output relay 16 X20 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 X17 a02 c02 Output relay 01 2) X21 CAN bus cable connector a32 c32 Output relay 16 X18 a02 c02 Output relay 01 2) 1) a32 c32 Output relay 16 X19 a02 c02 Output relay 01 2) Note : 1) The 2 modules are combined into 1 module. a32 c32 Output relay 16 2) The module is same as X16 module. 24

Connection X1 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 X2 a02 c02 CSC-150 auxiliary case BI01 BI02 BI03 BI04 BI05 BI06 BI07 BI08 BI09 BI10 BI11 BI12 BI13 BI14 BI15 BI16 BI17 BI18 BI19 BI20 BI21 BI22 BI23 BI24 BI25 BI26 BI27 BI28 BI29 BI30 BI-COM1(-) BI-COM2(-) BI01 BI02 1) 2) 3) Output relay 01 Output relay 02 Output relay 03 Output relay 04 Output relay 05 Output relay 06 Output relay 07 Output relay 08 Output relay 09 Output relay 10 Output relay 11 Output relay 12 Output relay 13 Output relay 14 Output relay 15 Output relay 16 Output relay 01 Output relay 16 X7 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 X8 a02 c02 a32 c32 a32 c32 X3 a02 c02 a32 c32 X4 a02 c02 a32 c32 X5 a02 c02 a32 c32 X6 a02 c02 BI-COM1(-) BI-COM2(-) BI01 BI02 BI-COM1(-) BI-COM2(-) BI01 BI02 BI-COM1(-) BI-COM2(-) BI01 BI02 BI-COM1(-) BI-COM2(-) BI01 BI02 1) 1) 1) 1) 2) Output relay 01 Output relay 02 Output relay 03 Output relay 04 Output relay 05 Output relay 06 Output relay 07 Output relay 08 Output relay 09 Output relay 10 Output relay 11 Output relay 12 Output relay 13 Output relay 14 Output relay 15 Output relay 16 3) Output relay 01 X9 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 X10 a02 c02 Note : 1) The module is same as X1 module. 2) The 2 modules are combined into 1 module. a32 c32 BI-COM1(-) BI-COM2(-) Output relay 16 a32 c32 3) The module is same as X7 module. 25

Connection X11 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 CSC-150 auxiliary case Output relay 01 Output relay 02 Output relay 03 Output relay 04 Output relay 05 Output relay 06 Output relay 07 Output relay 08 Output relay 09 Output relay 10 Output relay 11 Output relay 12 Output relay 13 Output relay 14 Output relay 15 Output relay 16 BI01 BI02 BI03 BI04 BI05 BI06 BI07 BI08 BI09 BI10 BI11 BI12 BI13 BI14 BI15 BI16 BI17 BI18 BI19 BI20 BI21 BI22 BI23 BI24 BI25 BI26 BI27 BI28 BI29 BI30 BI-COM1(-) BI-COM2(-) X13 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 X12 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 DC 24V + output DC 24V - output AUX DC + input AUX DC - input Terminal for earthing Terminal for earthing Power failure alarm relay 1 Power failure alarm relay 2 CAN bus cable connector X14 26

Connection B. Typical analogue inputs connection for single busbar with line side CTs arrangement Busbar-A CSC- 150 C. Typical analogue inputs connection for single busbar with bus side CTs arrangement Busbar-A CSC- 150 27

Connection D. Typical analogue inputs connection for single busbar with tie disconnector (line side CTs) arrangement Busbar-A Busbar-B CSC- 150 E. Typical analogue inputs connection for single busbar with tie disconnector (bus side CTs) arrangement Busbar-A Busbar-B CSC- 150 28

Connection F. Typical analogue inputs connection for single busbar with tie disconnector and one CT (line side CTs) arrangement Busbar-A Busbar-B CSC- 150 G. Typical analogue inputs connection for two single busbars connected with bus coupler and one CT (line side CTs) arrangement Busbar-A Busbar-B CSC- 150 29

Connection H. Typical analogue inputs connection for two single busbars connected with bus coupler and one CT (bus side CTs) arrangement Busbar-A Busbar-B CSC- 150 I. Typical analogue inputs connection for two single busbars connected with bus coupler and two CTs (line side CTs) arrangement Busbar-A Busbar-B CSC- 150 30

Connection J. Typical analogue inputs connection for two single busbars connected with bus coupler and two CTs (bus side CTs) arrangement Busbar-A Busbar-B CSC- 150 K. Typical analogue inputs connection for one and half breaker arrangement Busbar-A Busbar-B CSC- 150 31

Connection L. Typical analogue inputs connection for double busbar with one coupler CT arrangement Busbar-A Busbar-B CSC- 150 M. Typical analogue inputs connection for double busbar with two coupler CTs arrangement Busbar-A Busbar-B CSC- 150 32

Connection N. Typical analogue inputs connection for main and transfer busbar with two coupler CTs (inside CTs) arrangement Busbar-A Busbar-B CSC- 150 O. Typical analogue inputs connection for main and transfer busbar with two coupler CTs (outside CTs) arrangement Busbar-A Busbar-B CSC- 150 33

Connection P. Typical analogue inputs connection for main and transfer busbar with one coupler CTs (inside CTs) arrangement Busbar-A Busbar-B CSC- 150 Q. Typical analogue inputs connection for main and transfer busbar with one coupler CTs (outside CTs) arrangement Busbar-A Busbar-B CSC- 150 34

Connection R. Typical analogue inputs connection for main and transfer busbar without coupler CTs (outside CTs) arrangement Busbar-A Busbar-B CSC- 150 S. Typical analogue inputs connection for main and main/transfer busbar with inside CTs arrangement Busbar-A Busbar-B CSC- 150 35

Connection T. Typical analogue inputs connection for main and main and/or transfer busbar with outside CTs arrangement Busbar-A Busbar-B CSC- 150 U. Typical analogue inputs connection for double main and transfer busbar with inside CTs arrangement Busbar-A Busbar-B Busbar-C CSC- 150 36

Connection V. Typical analogue inputs connection for double main and transfer busbar with outside CTs arrangement Busbar-A Busbar-B Busbar-C CSC- 150 37

Technical data Frequency Item Standard Data Rated system frequency IEC 60255-1 50 Hz or 60Hz Internal current transformer Item Standard Data Rated current I r IEC 60255-1 1 or 5 A Nominal current range Nominal current range of sensitive CT 0.05 I r to 30 I r 0.005 to 1 A Power consumption (per phase) 0.1 VA at I r = 1 A; 0.5 VA at I r = 5 A 0.5 VA for sensitive CT Thermal overload capability IEC 60255-1 IEC 60255-27 100 I r for 1 s 4 I r continuous Internal voltage transformer Item Standard Data Rated voltage V r (ph-ph) IEC 60255-1 100 V /110 V Nominal range (ph-e) Power consumption at V r = 110 V IEC 60255-27 DL/T 478-2001 0.4 V to 120 V 0.1 VA per phase Thermal overload capability (phase-neutral voltage) IEC 60255-27 DL/T 478-2001 2 V r, for 10s 1.5 V r, continuous Auxiliary voltage Item Standard Data Rated auxiliary voltage U aux IEC60255-1 110 to 250V DC Permissible tolerance IEC60255-1 ±%20 U aux Power consumption at quiescent state Power consumption at maximum load IEC60255-1 IEC60255-1 50 W per power supply module 60 W per power supply module 38

Technical data Inrush Current IEC60255-1 T 10 ms/i 25 A per power supply module, Binary inputs Item Standard Data Input voltage range IEC60255-1 110/125 V DC 220/250 V DC Threshold1: guarantee operation IEC60255-1 154V, for 220/250V DC 77V, for 110V/125V DC Threshold2: uncertain operation IEC60255-1 132V, for 220/250V DC; 66V, for 110V/125V DC Response time/reset time IEC60255-1 Software provides de-bounce time Power consumption, energized IEC60255-1 Max. 0.5 W/input, 110V DC Max. 1 W/input, 220V DC Binary outputs Item Standard Data Max. system voltage IEC60255-1 250V DC / AC Current carrying capacity IEC60255-1 5 A continuous, 30A,200ms ON, 15s OFF Making capacity IEC60255-1 1100 W(DC) at inductive load with L/R>40 ms 1000 VA(AC) Breaking capacity IEC60255-1 220V DC, 0.15A, at L/R 40 ms 110V DC, 0.30A, at L/R 40 ms Mechanical endurance, Unloaded IEC60255-1 50,000,000 cycles (3 Hz switching frequency) Mechanical endurance, making IEC60255-1 1000 cycles Mechanical endurance, breaking IEC60255-1 1000 cycles Specification state verification IEC60255-1 IEC60255-23 IEC61810-1 UL/CSA TŰV 39

Technical data Contact circuit resistance measurement Open Contact insulation test (AC Dielectric strength) IEC60255-1 IEC60255-23 IEC61810-1 IEC60255-1 IEC60255-27 30mΩ AC1000V 1min Maximum temperature of parts and materials IEC60255-1 55 Front communication port Item Number 1 Data Connection Communication speed Max. length of communication cable Isolated, RS232; front panel, 9-pin subminiature connector, for software tools 9600 baud 15 m RS485 communication port Item Data Number 0 to 2 Connection Max. length of communication cable Test voltage 2-wire connector Rear port in communication module 1.0 km 500 V AC against earth For IEC 60870-5-103 protocol Communication speed Factory setting 9600 baud, Min. 1200 baud, Max. 19200 baud Ethernet communication port Item Electrical communication port Data Number 0 to 3 Connection Max. length of communication cable RJ45 connector Rear port in communication module 100m For IEC 61850 protocol 40

Technical data Communication speed 100 Mbit/s For IEC 60870-5-103 protocol Communication speed 100 Mbit/s Optical communication port ( optional ) Number 0 to 2 Connection Optical cable type Max. length of communication cable SC connector Rear port in communication module Multi-mode 2.0km IEC 61850 protocol Communication speed 100 Mbit/s IEC 60870-5-103 protocol Communication speed 100 Mbit/s Time synchronization Mode IRIG-B signal format Item Pulse mode IRIG-B000 Data Connection Voltage levels 2-wire connector Rear port in communication module differential input Environmental influence Item Recommended permanent operating temperature Storage and transport temperature limit Permissible humidity Data -10 C to +55 C (Legibility of display may be impaired above +55 C /+131 F) -25 C to +70 C 95 % of relative humidity IED design Case size Weight Item Data 8U 19inch, Main case 4U 19inch, Auxiliary case 16kg, Main case 5kg,, Auxiliary case 41

Technical Data Product safety-related Tests Item Standard Data Over voltage category IEC60255-27 Category III Pollution degree IEC60255-27 Degree 2 Insulation IEC60255-27 Basic insulation Degree of protection (IP) Power frequency high voltage withstand test Impulse voltage test Insulation resistance IEC60255-27 IEC 60529 IEC 60255-5 EN 60255-5 ANSI C37.90 GB/T 15145-2001 DL/T 478-2001 IEC60255-5 IEC 60255-27 EN 60255-5 ANSI C37.90 GB/T 15145-2001 DL/T 478-2001 IEC60255-5 IEC 60255-27 EN 60255-5 ANSI C37.90 GB/T 15145-2001 DL/T 478-2001 Front plate: IP40 Rear, side, top and bottom: IP 30 2KV, 50Hz 2.8kV between the following circuits: auxiliary power supply CT / VT inputs binary inputs binary outputs case earth 500V, 50Hz between the following circuits: Communication ports to case earth time synchronization terminals to case earth 5kV (1.2/50μs, 0.5J) If U i 63V 1kV if U i<63v Tested between the following circuits: auxiliary power supply CT / VT inputs binary inputs binary outputs case earth Note: U i: Rated voltage 100 MΩ at 500 V 42

Technical Data Protective bonding resistance IEC60255-27 0.1Ω Fire withstand/flammability IEC60255-27 Class V2 Electromagnetic immunity tests Item Standard Data 1 MHz burst immunity test IEC60255-22-1 IEC60255-26 IEC61000-4-18 EN 60255-22-1 ANSI/IEEE C37.90.1 Electrostatic discharge IEC 60255-22-2 IEC 61000-4-2 EN 60255-22-2 Class III 2.5 kv CM ; 1 kv DM Tested on the following circuits: auxiliary power supply CT / VT inputs binary inputs binary outputs 1 kv CM ; 0 kv DM Tested on the following circuits: communication ports Level 4 8 kv contact discharge; 15 kv air gap discharge; both polarities; 150 pf; R i = 330 Ω Radiated electromagnetic field disturbance test Radiated electromagnetic field disturbance test Electric fast transient/burst immunity test IEC 60255-22-3 EN 60255-22-3 IEC 60255-22-3 EN 60255-22-3 IEC 60255-22-4, IEC 61000-4-4 EN 60255-22-4 ANSI/IEEE C37.90.1 Frequency sweep: 80 MHz 1 GHz; 1.4 GHz 2.7 GHz spot frequencies: 80 MHz; 160 MHz; 380 MHz; 450 MHz; 900 MHz; 1850 MHz; 2150 MHz 10 V/m AM, 80%, 1 khz Pulse-modulated 10 V/m, 900 MHz; repetition rate 200 Hz, on duration 50 % Class A, 4KV Tested on the following circuits: auxiliary power supply CT / VT inputs binary inputs binary outputs Class A, 1KV Tested on the following circuits: 43

Technical Data communication ports Surge immunity test IEC 60255-22-5 IEC 61000-4-5 Conduct immunity test IEC 60255-22-6 IEC 61000-4-6 4.0kV L-E 2.0kV L-L Tested on the following circuits: auxiliary power supply CT / VT inputs binary inputs binary outputs 500V L-E Tested on the following circuits: communication ports Frequency sweep: 150 khz 80 MHz spot frequencies: 27 MHz and 68 MHz 10 V AM, 80%, 1 khz Power frequency immunity test IEC60255-22-7 Class A 300 V CM 150 V DM Power frequency magnetic field test IEC 61000-4-8 Level 4 30 A/m cont. / 300 A/m 1 s to 3 s 100 khz burst immunity test IEC61000-4-18 2.5 kv CM ; 1 kv DM Tested on the following circuits: auxiliary power supply CT / VT inputs binary inputs binary outputs 1 kv CM ; 0 kv DM Tested on the following circuits: communication ports DC voltage interruption test Item Standard Data DC voltage dips IEC 60255-11 100% reduction 20 ms 60% reduction 200 ms 30% reduction 500 ms 44

Technical Data DC voltage interruptions IEC 60255-11 100% reduction 5 s DC voltage ripple IEC 60255-11 15%, twice rated frequency DC voltage gradual shut down /start-up IEC 60255-11 60 s shut down ramp 5 min power off 60 s start-up ramp DC voltage reverse polarity IEC 60255-11 1 min Electromagnetic emission test Item Standard Data Radiated emission Conducted emission IEC60255-25 EN60255-25 CISPR22 IEC60255-25 EN60255-25 CISPR22 30MHz to 1GHz ( IT device may up to 5 GHz) 0.15MHz to 30MHz Mechanical tests Item Standard Data Sinusoidal Vibration response test Sinusoidal Vibration endurance test Shock response test Shock withstand test IEC60255-21-1 EN 60255-21-1 IEC60255-21-1 EN 60255-21-1 IEC60255-21-2 EN 60255-21-2 IEC60255-21-2 EN 60255-21-2 Class 1 10 Hz to 60 Hz: 0.075 mm 60 Hz to 150 Hz: 1 g 1 sweep cycle in each axis Relay energized Class 1 10 Hz to 150 Hz: 1 g 20 sweep cycle in each axis Relay non-energized Class 1 5 g, 11 ms duration 3 shocks in both directions of 3 axes Relay energized Class 1 15 g, 11 ms duration 3 shocks in both directions of 3 axes Relay non-energized Bump test IEC60255-21-2 Class 1 45

Technical Data 10 g, 16 ms duration 1000 shocks in both directions of 3 axes Relay non-energized Seismic test IEC60255-21-3 Class 1 X-axis 1 Hz to 8/9 Hz: 7.5 mm X-axis 8/9 Hz to 35 Hz :2 g Y-axis 1 Hz to 8/9 Hz: 3.75 mm Y-axis 8/9 Hz to 35 Hz :1 g 1 sweep cycle in each axis, Relay energized Climatic tests Item Standard Data Cold test - Operation IEC60255-27 -10 C, 16 hours, rated load IEC60068-2-1 Cold test Storage IEC60255-27 IEC60068-2-1-25 C, 16 hours Dry heat test Operation [IEC60255-27 +55 C, 16 hours, rated load IEC60068-2-2 Dry heat test Storage IEC60255-27 +70 C, 16 hours IEC60068-2-2 Change of temperature IEC60255-27 IEC60068-2-14 Test Nb, figure 2, 5 cycles -10 C / +55 C Damp heat static test IEC60255-27 +40 C, 93% r.h. 10 days, rated load IEC60068-2-78 Damp heat cyclic test IEC60255-27 IEC60068-2-30 +55 C, 93% r.h. 6 cycles, rated load CE Certificate EMC Directive Low voltage directive Item Data EN 61000-6-2 and EN61000-6-4 (EMC Council Directive 2004/108/EC) EN 60255-27 (Low-voltage directive 2006/95 EC). 46

Technical Data Functions NOTE: Ir: CT rated secondary current, 1A or 5A; Busbar differential protection (ANSI 87BB) Item Rang or Value Tolerance Differential Current 0.4 Ir to 20.00 Ir ±5% setting or ±0.02Ir Stabilization factor 0.3-0.99 Differential current reset threshold Operating time Reset time 0.1 Ir < 15ms typically at 200% setting < 50ms Breaker failure protection (ANSI 50 BF) Item Rang or Value Tolerance phase current Negative sequence current zero sequence current 0.08 Ir to 20.00 Ir ±3% setting or ±0.02Ir Time delay of stage 1 0.00s to 32.00 s, step 0.01s ±1% setting or +25 ms, at Time delay of stage 2 0.00s to 32.00 s, step 0.01s 200% operating setting Reset time of stage 1 < 20ms Dead zone protection (ANSI 50DZ) Item Rang or Value Tolerance Current 0.08 Ir to 20.00 Ir ±3% setting or ±0.02Ir Time delay 0.00s to 32.00s, step 0.01s ±1% setting or +40 ms, at 200% operating setting VT secondary circuit supervision (97FF) Item Range or value Tolerances Minimum current 0.08Ir to 0.20Ir, step 0.01A ±3% setting or ±0.02Ir Minimum zero or negative sequence current 0.08Ir to 0.20Ir, step 0.01A ±5% setting or ±0.02Ir Maximum phase to earth voltage 7.0V to 20.0V, step 0.01V ±3% setting or ±1 V 47

Technical Data Maximum phase to phase voltage 10.0V to 30.0V, step 0.01V ±3% setting or ±1 V Normal phase to earth voltage 40.0V to 65.0V, step 0.01V ±3% setting or ±1 V 48

Ordering Pre-configure scheme Table 5 Functions and hardware of the pre-configure schemes for transmission network Pre-configure scheme M01 M02 M03 M04 M05 M06 M07 M08 D or A or F G D or A or F G Station arrangement (N1) E or B or E or B or H C H C Voltage level (kv) 230 230 230 230 230 230 230 230 8F+1 8F+1 8F+1 8F+1 16F+ 16F 16F+ 16F+ Number of bay C or C C+1 C/1T 1C or +1C 1C+1 1C/1 1T T 1T T T Busbar differential protection (87BB) 1 1 1 1 1 1 1 1 Breaker failure protection (50BF) 1 1 1 1 1 1 1 1 Dead-zone protection (50DZ) 1 1 1 1 1 1 1 1 CT secondary circuit supervision 1 1 1 1 1 1 1 1 VT secondary circuit supervision (97FF) (1) (1) (1) (1) (1) (1) (1) (1) Analogue input module (10I ) 3 3 3 3 6 6 6 6 Analogue input module (2I+ 9U) (1) (1) (1) (1) (1) (1) (1) (1) CPU modules 2 2 2 2 2 2 2 2 Communication module(with Ethernet interfaces, RS485 interfaces and time 1 1 1 1 1 1 1 1 synchronizing interface) Binary input module (30 BI) 4 4 5 5 8 8 8 8 Binary output modules (16 relays for tripping and initiation) Binary output modules (32 relays for tripping and initiation) Binary output modules (16 relays for signal) 1 1 1 1 2 2 2 2 2 2 2 2 4 4 4 4 1 1 1 1 1 1 1 1 Power supply module 3 3 1 3 3 3 3 3 Programmable LEDs 18 18 18 18 18 18 18 18 Case, 8U,19 1 1 1 1 1 1 1 1 Case, 4U,19 1 1 1 1 1 1 1 1 49

Ordering NOTE: n : Quantity of standard function or standard hardware, n= 1, 2,.; (n) : Quantity of optional function or optional hardware, n= 1, 2,.; N1: Station arrangement: A Single Busbar B Two Single Busbars connected with Coupler C Two Separate Busbars in 1 CB arrangement D Double Busbar E Main and Transfer Busbar F Double Main and one Transfer Busbar with line side CT G Main and Main/Transfer Busbar H Double Main and one Transfer Busbar with bus side CT 50

Ordering Table 6 Functions and hardware of the pre-configure schemes for sub-transmission and distribution network Pre-configure scheme M09 M10 Station arrangement (N1) A, B or C A, B or C Voltage level (kv) 132 132 Number of bay 8F+1C 16F+1C Busbar differential protection (87BB) 1 1 Breaker failure protection (50BF) 1 1 Dead-zone protection (50DZ) 1 1 CT secondary circuit supervision 1 1 VT secondary circuit supervision (97FF) (1) (1) Analogue input module (10I ) 3 6 Analogue input module (2I+ 9U) 1 1 CPU modules 2 2 Communication module(with Ethernet interfaces, RS485 interfaces and time synchronizing interface) 1 1 Binary input module (30 BI) 3 5 Binary output modules (16 relays for tripping and initiation) 1 2 Binary output modules (32 relays for tripping and initiation) 1 2 Binary output modules (16 relays for signal) 1 1 Power supply module 3 3 Programmable LEDs 18 18 Case, 8U,19 1 1 Case, 4U,19 1 1 51

Ordering NOTE: n : Quantity of standard function or standard hardware, n= 1, 2,.; (n) : Quantity of optional function or optional hardware, n= 1, 2,.; N1: Station arrangement: A Single Busbar B Two Single Busbars connected with Coupler C Two Separate Busbars in 1 CB arrangement D Double Busbar E Main and Transfer Busbar F Double Main and one Transfer Busbar with line side CT G Main and Main/Transfer Busbar H Double Main and one Transfer Busbar with bus side CT 52

Ordering Ordering code A. Main case No.1~16 No.17~45 C S C 1 5 0 - L F T Pre-configure Scheme M;N 0~9 0~9 HMI Language (L) note English Russian French Portuguese Spanish 1 2 3 4 5 Rated Frequency (F) 50 Hz 5 60 Hz 6 Station Communication Protocols (T) Ethernet interface:iec61850-8; RS485 interface: IEC60870-5-103 Ethernet interface:iec60870-5-103; RS485 interface: IEC60870-5-103 1 2 Note: Chinese is always offered as default HMI language. 53

Ordering No.1~16 No.17~25 No.26~45 C S C 1 5 0 - A Analogue Input Module (A) Slot 1 10I (1A) 1 10I (5A) 2 Slot 2 10I (1A) 10I (5A) 1 2 x Slot 3 10I (1A) 10I (5A) 1 2 x Slot 4 10I (1A) 10I (5A) 1 2 x Slot 5 10I (1A) 10I (5A) 1 2 x Slot 6 10I (1A) 10I (5A) 1 2 x Slot 7 x Slot 8 2I (1A)+9U 2I (5A)+9U f g x 54

Ordering No.1~25 No.26~37 No.38~45 C S C 1 5 0 - M I O C P Slot 9 CPU Module 1 (M) Dedicated to CSC-150 1 Slot 10 CPU Module 2 (M) Dedicated to CSC-150 1 Slot 11 Binary Input Module (I) 30BI (220V DC), with startup blocking relay 1 30BI (110V DC), with startup blocking relay 2 Slot 12 Binary Output Module (O) 16 relays for tripping 1 Slot 13 Communication module (C) 3 electrical Ethernet ports, 1 RS485 ports, IRIG-B 1 3 electrical Ethernet ports, 1 RS485 ports, Pulse 2 2 electrical Ethernet ports, 2 RS485 ports, IRIG-B 3 2 electrical Ethernet ports, 2 RS485 ports, Pulse 4 2 optical Ethernet ports, 2 RS485 ports, IRIG-B 5 2 optical Ethernet ports, 2 RS485 ports, Pulse 6 Slot 14 Power Supply Module (P) 100V - 250V DC 1 Slot 15 Power Supply Module (P) 100V - 250V DC 1 55

Ordering No.1~37 No.38~45 C S C 1 5 0 - O K Z Binary Output Module (O) Slot 16 & 17 32 relays for tripping 2 Slot 18 & 19 32 relays for tripping 2 Slot 20 16 relays for tripping 1 Case and Front Plate (K) Case: 8U, 19'; Front plate: Medium size LCD; 20 LEDs 1 x Accessories Cable for communication between main case and auxiliary case 1 x 56

Ordering B. Auxiliary case No.1~9 No.10~16 No.17~28 C S C 1 5 0 - Q A I Binary Input Module (I) Slot 1 30BI (220V DC), with startup blocking relay 1 30BI (110V DC), with startup blocking relay 2 Slot 2 30BI (220V DC) 3 30BI (110V DC) 4 Slot 3 30BI (220V DC) 3 30BI (110V DC) 4 x Slot 4 30BI (220V DC) 30BI (110V DC) 3 4 x Slot 5 30BI (220V DC) 30BI (110V DC) 3 4 x Slot 6 30BI (220V DC) 30BI (110V DC) 3 4 x 57

Ordering No.1~16 No.17~28 C S C 1 5 0 - Q A O P I K Z Binary Output Module (O) Slot 7 & 8 32 relays for tripping 2 x Slot 9 & 10 32 relays for tripping 2 x Slot 11 16 relays (with 19 contacts) for signalling 3 Slot 12 Power Supply Module (P) 100V - 250V DC 1 Slot 13 Binary Input Module (I) 30BI (220V DC) 3 30BI (110V DC) 4 Case and Front Plate (K) Case: 4U, 19'; Front plate: Without LCD and LED 2 Accessories (Z) x 58

Address: No.9 Shangdi 4th Street, Haidian District, Beijing, P.R.C. 100085 Tel: +86 10 62962554, +86 10 62961515 ext.8998 Fax: +86 10 82783625 Email:sf_sales@sf-auto.com Website: http://www.sf-auto.com