Watts and Volt-Amps: Powerful Confusion

Similar documents
Reliability Models for Electric Power Systems

Effect of UPS on System Availability

The Different Types of UPS Systems

A Scalable, Reconfigurable, and Efficient High Density Data Center Power Distribution Architecture

Calculating Total Power Requirements for Data Centers

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

> Executive summary. Implementing Energy Efficient Data Centers. White Paper 114 Revision 1. Contents. by Neil Rasmussen

The Different Types of AC Power Connectors in North America

Rack Powering Options for High Density

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

Improving Rack Cooling Performance Using Blanking Panels

Electrical Efficiency Measurement for Data Centers

Rack Powering Options for High Density

Impact of Leading Power Factor on Data Center Generator Systems

The Different Types of UPS Systems

Specification of Modular Data Center Architecture

Virtualization and consolidation

Data Center Projects: Establishing a Floor Plan

HP Power Calculator Utility: a tool for estimating power requirements for HP ProLiant rack-mounted systems

Calculating Power for Cisco StackPower and the Cisco Catalyst 3750-X Series Switches

Preventing Data Corruption in the Event of an Extended Power Outage

1. Micro Drive Load sharing application note

E f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; V D C p o w e r f e e d s o l u t i o n

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN

Residential/Commercial/Industrial

Back-UPS RS 550 Installation & Operation

Installation and Operation Back-UPS Pro BR700G-TW

APC APPLICATION NOTE #114

HarmonicGuard Series Bus-Applied Active Harmonic Filter Quick Start Unit Software Setup

G5 PDU Installation Guide

Deploying High-Density Zones in a Low-Density Data Center

PAS 9406/AMP ENGINEERING SPECIFICATION

Server Technology Inc.

Data Center Projects: Standardized Process

Cooling Strategies for Ultra-High Density Racks and Blade Servers

MEMORANDUM SUBJECT: APPROVED POWER STRIPS AND SURGE PROTECTORS

OPERATOR S MANUAL ATE 1/2 RACK POWER SUPPLY AUTOMATIC TEST EQUIPMENT MODEL

DC Energy, Efficiency Challenges

Midwest Energy, Inc. Distributed Generation Interconnection Expedited & Standard Process Application

HP Uninterruptible Power Supplies Overview

Medium Voltage Metal-Enclosed Thyristor-Switched Harmonic Filter Banks

Universal AC Input, 12 V0.35A Output, 4.2 Watt Non-isolated Power Supply

Spring Test 5 due 4/26/2013

OPERATOR S MANUAL ATE 1/2 RACK POWER SUPPLY AUTOMATIC TEST EQUIPMENT MODEL

INSTRUCTION MANUAL RA 60 SERIES RACK ADAPTER RA 60, RA 62, AND RA 63. 1) This manual is valid for the following Model and associated serial numbers:

Specifying Data Center IT Pod Architectures

Data Center Facility Project. Robert Bunger Schneider Electric

Ultrathin & High Power µmodule Regulators Are Ideal for Communications Systems

Medium Voltage Metal-Enclosed Power Capacitor Banks

Rapidus Power Factor Controller

APC by Schneider Electric Elite Data Centre Partner

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

Electrical Efficiency Measurement for Data Centers

Highly Efficient Power Protection for High Density Computing Applications

Knowledge base No. 002

Top Microsystems Proprietary Specification P/N: P6301H N1F SK SPECIFICATION P/N: P6301H N1F

Part Numbers SNAP-IT-EMU1

OPERATOR S MANUAL BOP (M) (D) 100W, 200W, 400W BIPOLAR POWER SUPPLY

for Power Energy and

Stalking the Elusive and Somewhat Strange PV System

Deploying High Power to IT Equipment Racks

Implementation considerations for cabling supporting remote powering

Powering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM

SLI 15 Inverter Series Data Sheet 1500 Watt, 1U Compact Inverters

Configurable power distribution

Avoiding Costs From Oversizing Datacenter Infrastructure

Installation and Operation Manual Back-UPS BR900G-RS

Installation and Operation Back-UPS Pro 900

Power and Cooling for Ultra-High Density Racks and Blade Servers

Data Centre Solutions Expertly Engineered APC Management Software

INSTRUCTION MANUAL RA 55 RACK ADAPTER RACK ADAPTER FOR MST SERIES POWER MODULES

Sinexcel. Static Var Generator (SVG) Installation Guide

Maximise Data Center Value

Application of TileFlow to Improve Cooling in a Data Center

ELECTRICAL SUPPLY TROUBLESHOOTING QUICK GUIDE SAFETY PRECAUTIONS

BOP QUICK START GUIDE 100W, 200W, 400W. KEPCO An ISO 9001 Company. BIPOLAR OPERATIONAL POWER SUPPLY I INTRODUCTION

APC Back-UPS - Floor Style

Impact of High Density Hot Aisles on IT Personnel Work Conditions

Modular Systems: The Evolution of Reliability

RE-82 RACK MOUNT DIMMER OWNERS MANUAL. 8 X 2400Watts. Revision /29/2007

SECTION VARIABLE FREQUENCY DRIVES

Schneider Electric Data Center Software

Speaker Selectors Models SSW-L4 EX and SSW-L6 EX. User Manual. SSW-L4 EX (bottom) and SSW-L6 EX (top)

Marine User Guide. USBT202 Series High Power USB Charging Port

Installation and Operation Back-UPS Pro 900

Model 160. Model 186. Model 247. Surge Protective Devices. Installation & Operation Manual. Model 160. Model 186. Model 247 (EDCO RM-CX06-16R)

RL Line/Load Reactors

Data Center Temperature Rise During a Cooling System Outage

Rack Power Distribution. Rack power distribution offerings for entry-level networking equipment and high-density server and blade environments

Deploying High Power to IT Equipment Racks

Symmetra PX. Symmetra PX 48kW Scalable from 16kW to 48kW. Modular, Scalable, High-Efficiency Power Protection for Data Centers

Benefits of Limiting MV Short-Circuit Current in Large Data Centers

Who Needs Remote Power Management for Power Distribution, Power Measurement and Power Control of 48 VDC Equipment?

Systems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development

DCIM Data Center Infrastructure Management

ASCO 920 Remote Control (RC) Switches

Table 1 shows all the different variations of output modules available.

SUN3 LED REV

Medium Voltage Metal-Enclosed Harmonic Filter Systems

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Transcription:

Watts and Volt-Amps: Powerful Confusion White Paper 15 Revision 1 by Neil Rasmussen Click on a section to jump to it > Executive summary This white paper helps explain the differences between watts and VA and explains how the terms are correctly and incorrectly used in specifying power protection equipment. Contents Introduction 2 Background 2 Watts may not equal VA 2 The power rating of the UPS 2 Examples where a sizing problem can occur 3 How to avoid sizing errors 3 Conclusion 4 Resources 5

Introduction This note helps explain the differences between watts and VA and explains how the terms are correctly and incorrectly used in specifying power protection equipment. Many people are confused about the distinction between the watt (W) and volt-amp (VA) measures for UPS load sizing. Many manufacturers of UPS and load equipment add to this confusion by failing to distinguish between these measures. Background The power drawn by computing equipment is expressed in watts or volt-amps (VA). The power in watts is the real power drawn by the equipment. Volt-amps are called the "apparent power" and are the product of the voltage applied to the equipment times the current drawn by the equipment. Both watt and VA ratings have a use and purpose. The watt rating determines the actual power purchased from the utility company and the heat loading generated by the equipment. The VA rating is used for sizing wiring and circuit breakers. The VA and watt ratings for some types of electrical loads, like incandescent light bulbs, are identical. However, for computer equipment the watt and VA ratings can differ significantly, with the VA rating always being equal to or larger than the watt rating. The ratio of the watt to VA rating is called the "Power Factor" and is expressed either as a number (i.e., 0.7) or a percentage (i.e. 70%). Watts may not equal VA All information technology equipment including computers uses an electronic switching power supply. There are two basic types of computer switching power supplies, which are called 1) Power Factor Corrected (PFC) supplies or 2) capacitor input supplies. It is not possible to tell which kind of power supply is used by inspection of the equipment, and this information is not commonly provided in equipment specifications. PFC supplies were introduced in the mid 1990 s and have the characteristic that the watt and VA ratings are equal (power factor of 0.99 to 1.0). Capacitor input supplies have the characteristic that the watt rating is in the range of.55 to.75 times the VA rating (power factor of 0.55 to 0.75). All large computing equipment such as routers, switches, drive arrays, and servers made after about 1996 uses the PFC supply and consequently for this type of equipment the power factor is 1. Personal computers, small hubs, and personal computer accessories typically have capacitor input supplies and consequently for this type of equipment the power factor is less than one, and is ordinarily in the range of 0.65. Larger computer equipment made prior to 1996 also typically used this type of power supply and exhibited a power factor less than one. The power rating of the UPS UPS have both maximum watt ratings and maximum VA ratings. Neither the watt nor the VA rating of a UPS may be exceeded. It is a de-facto standard in the industry that the watt rating is approximately 60% of the VA rating for small UPS systems, this being the typical power factor of common personal computer loads. In some cases, UPS manufacturers only publish the VA rating of the UPS. For small UPS designed for computer loads, which have only a VA rating, it is appropriate to assume that the watt rating of the UPS is 60% of the published VA rating. APC by Schneider Electric White Paper 15 Rev 1 2

Related resource APC White Paper 26 Hazards of Harmonics and Neutral Overloads For larger UPS systems, it is becoming common to focus on the watt rating of the UPS, and to have equal watt and VA ratings for the UPS, because the watt and VA ratings of the typical loads are equal. For a further discussion of the issues of power factor of larger systems and data centers, see APC White Paper 26, Hazards of Harmonics and Neutral Overloads. Examples where a sizing problem can occur Example 1: Consider the case of a typical 1000 VA UPS. The user wants to power a 900 W heater with the UPS. The heater has a watt rating of 900 W and a VA rating of 900 VA with a power factor of 1. Although the VA rating of the load is 900 VA, which is within the VA rating of the UPS, the UPS will probably not power this load. That is because the 900 W rating of the load exceeds the watt rating of the UPS, which is most likely 60% of 1000 VA or around 600 W. Example 2: Consider the case of a 1000 VA UPS. The user wants to power a 900 VA file server with the UPS. The file server has a PFC power supply, and so has a watt rating of 900 W and a VA rating of 900 VA. Although the VA rating of the load is 900 VA, which is within the VA rating of the UPS, the UPS will not power this load. That is because the 900 W rating of the load exceeds the watt rating of the UPS, which is 60% of 1000 VA or 600 W. How to avoid sizing errors Using the APC UPS Selector can help avoid these problems, as the load power values are verified based on the equipment specified. Also, the selector ensures that neither the watt nor VA ratings are exceeded. Equipment nameplate ratings are often in VA, which makes it difficult to know the watt ratings. If using equipment nameplate ratings for sizing, a user might configure a system, which appears to be correctly sized based on VA ratings but actually exceeds the UPS watt rating. By sizing the VA rating of a load to be no greater than 60% of the VA rating of the UPS, it is impossible to exceed the watt rating of the UPS. Therefore, unless you have high certainty of the watt ratings of the loads, the safest approach is to keep the sum of the load nameplate ratings below 60% of the UPS VA rating. Note that this conservative sizing approach will typically give rise to an oversized UPS and a larger run time than expected. If optimization of the system and an accurate run time are required, use the APC UPS Selector. APC by Schneider Electric White Paper 15 Rev 1 3

Conclusion Power consumption information on computer loads is often not specified in a way that allows simple sizing of a UPS. It is possible to configure systems that appear to be correctly sized but actually overload the UPS. By slightly over sizing the UPS compared with the nameplate ratings of the equipment, proper operation of the system is ensured. Over sizing also provides the side benefit of providing additional UPS backup time. About the author Neil Rasmussen is the Senior VP of Innovation for APC, which is the IT Business Unit of Schneider Electric. He establishes the technology direction for the world s largest R&D budget devoted to power, cooling, and rack infrastructure for critical networks. Neil holds 14 patents related to high efficiency and high density data center power and cooling infrastructure, and has published over 50 white papers related to power and cooling systems, many published in more than 10 languages, most recently with a focus on the improvement of energy efficiency. He is an internationally recognized keynote speaker on the subject of high efficiency data centers. Neil is currently working to advance the science of high-efficiency, high-density, scalable data center infrastructure solutions and is a principal architect of the APC InfraStruXure system. Prior to founding APC in 1981, Neil received his bachelors and masters degrees from MIT in electrical engineering, where he did his thesis on the analysis of a 200MW power supply for a tokamak fusion reactor. From 1979 to 1981 he worked at MIT Lincoln Laboratories on flywheel energy storage systems and solar electric power systems. APC by Schneider Electric White Paper 15 Rev 1 4

Resources Click on icon to link to resource Hazards and Harmonics of Neutral Overloads APC White Paper 26 APC White Paper Library whitepapers.apc.com APC TradeOff Tools tools.apc.com Related reading For further reading on the subject of power factor as it relates to non-linear loads, consult the following: IEEE Guide to Harmonic Control and Reactive Compensation of Static Power Converters (IEEE Std 519-1981) The Institute of Electrical and Electronics Engineers, Inc., 345 E 47th Street, New York, NY 10017 Guideline on Electrical Power for ADP Installations (FIPS PUB 94 September 21, 1983) U.S. Dept. of Commerce, National Technical Information Service, 5285 Port Royal Road, Springfield, VA 22161 Contact us For feedback and comments about the content of this white paper: Data Center Science Center, APC by Schneider Electric DCSC@Schneider-Electric.com If you are a customer and have questions specific to your data center project: Contact your APC by Schneider Electric representative APC by Schneider Electric White Paper 15 Rev 1 5