System Description Advant Controller 31 Intelligent Decentralized Automation System. Notes for Project Planning. ABB Schaltund Steuerungstechnik

Similar documents
AO561 Analog Output Module

Controlesta RCO-Compact

PROFIBUS DP FieldBusPlug PDP21-FBP PROFIBUS DP

AI561 Analog Input Module

DC561, digital input/output module,

DC562, digital input/output module,

TU531, TU532 Terminal Unit

DX561 Digital Input/Output Module

AX522 Analog Input/Output Module

4.7 Digital Input/Output Module 07 DC digital inputs, 8 digital outputs, 8 configurable inputs/outputs, 24 V DC, CS31 system bus

AI531 Analog Input Module

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

Operating Manual Advant Controller 31-S Intelligent Decentralized Automation System

DI561 Digital Input Module

AO523 Analog Input Module

DI572 Digital Input Module

TF501, TF521 Terminal Bases

AX521 Analog Input/Output Module

DC541 Digital Input/Output Module

DA502 Digital/Analog Input/Output Module

4.8 Digital Input/Output Module 07 DC 92 Contents Intended purpose Displays and operating elements on the front panel Electrical connection

DC522 Digital Input/Output Module

DC532-XC, digital input/output module,

CM592 PROFIBUS Communication Module

Universal Motor Controller UMC22-FBP. High-grade Motor Protection and Control

CM597 Ethernet Communication Module

DA502 Digital/Analog Input/Output Module

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

DA502 Digital/Analog Input/Output Module

CI541 PROFIBUS Communication Interface Module

Compact Inductive Proximity Sensor

CM589 PROFINET Communication Module

CI521 Modbus Communication Interface Module

Access Terminal IF-800

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers

DELOMATIC - MULTI-FUNCTION SYSTEM PART 2 INSTALLATION INSTRUCTION

CI542 PROFIBUS Communication Interface Module

Universal Motor Controller UMC22-FBP. Excellent motor protection and control ATEX ABB

ABB i-bus KNX BCI/S Boiler/Chiller Interface

Electronic timer CT-ERD ON-delayed with 1 c/o contact Data sheet

CM579-PNIO PROFINET Communication Module

CD522 Encoder, Counter and PWM Module

Electronic timer CT-VWD Impulse-ON with 1 c/o contact Data sheet

HZS Internal Controller Expansion

AC500. System Description. Scalable PLC for Individual Automation. Hardware

Product Data Sheet. Hochiki 8 Way I/O Card. Features

Hardware Configuration Advant Controller 31-S Safety-Related Automation

IF-80x Outdoor Terminal

CI504 PROFINET Communication Interface Module

CM589 PROFINET Communication Module

ABB i-bus KNX HCC/S Heating/cooling circuit controller

Power Supply HARTING pcon

warning indication issued about 2 weeks before the battery charge becomes critical Real-time clock - with battery back-up Yes

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

Switching relay CT-IRS with 1, 2 or 3 c/o contacts Data sheet

Pluggable interface relays CR-M Miniature relays

Thermocouple Input Module Product Specifications and Installation Data

FBP FieldBusPlug FBP System Accessories

Expansion Module HZS 541-1S

GX SERIES. Cylindrical Compact Inductive Proximity Sensor Amplifier Built-in. Robust enclosure and flexible cable types are also available

Installation Instructions

Power Supply HARTING pcon

genesis TECHNICAL MANUAL Two-Door Controller GEN-045

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet

Cylindrical Compact Inductive Proximity Sensor Amplifier Built-in. panasonic.net/id/pidsx/global

This data sheet is only valid in association with the IL SYS INST UM E user manual.

Two Door Controller GEN-045

Digital I/O Module. Impro (DIO) Digital I/O Module INSTALLATION MANUAL

89SV80/R1200. Mechanical Components. Marshalling rack cubicle with double-sided MTP-Elements. Application. Description. Cubicle

ABB i-bus KNX Weather Unit, 1-fold, MDRC WZ/S , 2CDG110184R0011

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Installation / control / monitoring technique. CANopen PLC IL 5504, IN 5504 minimaster

AC5160 Controller. Fire & Security Products. SiPass integrated

LINETRAXX RCMS150. Residual current monitor type B with integrated measuring current transformers for earthed AC/DC systems (TN and TT systems)

Measurement Systems Datascan Installation and User Guide

Installation / Control / Monitoring Technique

AC500-eCo: your PLC from ABB Unique scalable concept, optimal costs... Change for more!

Installation and Maintenance

Installation / control / monitoring technique. CANopen PLC IL 5504, IN 5504 minimaster

Electronic timer CT-AWS Impulse-OFF with 2 c/o contacts Data sheet

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

Temperature modules. 8 inputs for connection of thermocouple sensors S20-AI-8-UTH

NI REM Remote I/O Overview DATASHEET. Analog Output Module for Remote I/O

MINI-PS AC/10-15DC/8

ABB i-bus KNX Analogue Input, 4-fold, MDRC AE/S , 2CDG110190R0011

Pluggable interface relays and optocouplers CR-P Pcb relays, optocouplers and accessories

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

205 CPU NETWORK ADAPTER F2-UNICON

Wiring Instructions v4

CI501 PROFINET Communication Interface Module

This Datasheet for the IC697CHS790. Rack, 9 Slots, Rear Mount.

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

User s Manual. ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

PHOENIX CONTACT - 11/2007. This data sheet is only valid in association with the IB IL SYS PRO UM E user manual.

Power supply CP-C 24/5.0

BMF400 Input/output module

Connecting a Cisco Input Module

Transcription:

System Description Advant Controller 31 Intelligent Decentralized Automation System Notes for Project Planning ABB Schaltund Steuerungstechnik

Table of contents 1 General instructions for EMC-compatible installation... 1-1 2 Check list for project planning and installation... 1-2 2.1 Planning reserves... 1-2 2.2 Everything firmly attached... 1-2 2.3 Everything correctly set... 1-2 2.4 Laying cables... 1-2 2.5 PE connection... 1-2 2.6 CS31 system bus... 1-3 2.7 Power supplies... 1-3 2.8 Connection of inductive loads to binary outputs... 1-3 2.9 Handling of unused analog inputs (and outputs)... 1-3 2.10 Programming / commissioning... 1-4 Advant Controller 31 / Issued: 10.98 0-1 Contents 5

5 Contents 0-2 Advant Controller 31 / Issued: 10.98

1Notes Systemdaten for Project Planning und Systemaufbau 1 General instructions for EMC-compatible installation Electric and electronical devices have to work correctly on site. This is also valid when electro-magnetic influences affect them in defined and/or expected strength. The devices themselves must not emit electro-magnetic noises. Advant Controller components are developed and constructed so that they have a very high noise immunity. When the wiring and earthing instructions under "System data and system configuration" in volume 2 are met, an error-free operation is given. However, there are applications where high electro-magnetic noises must be taken into due consideration already during the planning phase: e.g. when frequency converters, compressors, small-power pumps (high inductance) or medium-voltage switchgear are mounted nearby. An EMC-compatible earthing concept will also guarantee here an error-free operation. There are three important principles to be especially considered: Keep all connections as short as possible (in particular the earthing conductors) Use large conductor cross sections (in particular for the earthing conductors) Create good and large-sized contacts (in particular for the earthing conductors) - vibration-resistant connections - clean metallic contact areas (remove paint, clean surfaces) - solid plug and screw-type connections - earth cable shields with clips on a well grounded metallic surface, - do not use sheath wires - do not use toothed lock washers under screwed connections wrong bad contact right good contact In special cases, the following hints may be useful: Use filters for power supply units, if they pass too high noises Advant Controller 31 / Issued: 10.98 1-1 Notes for project planning 5

2 Check list for project planning and installation This chapter contains a list of reminders to check whether all of the important items have been taken into consideration during planning and installation. 2.1 Planning reserves Reserve inputs digital/analog for expected extensions Reserve outputs digital/analog for expected extensions Rule of thumb 10...20 % reserve Reserve space in the cabinet for expected extensions 2.2 Everything firmly attached AC31 module firmly plugged on the plug-in base (all screws fastened) 2.3 Everything correctly set Operating modes correctly set on the modules (e.g. DIL switch) Correct input/output terminals on the modules used (e.g. voltage inputs or outputs on the analog modules Adresses correctly set 2.4 Laying cables Power cables (230/400 V) laid out separately from the control cables (24 V, analog signals), whenever possible with a distance of 20 cm or more Sufficient conductor cross sections Sufficient cable insulation / cable shielding Supply lines of the power supply connected to the central units with flanged couplers (e.g. 07 KT 93 with 07 KP 90) - The supply lines are first connected to the central unit (07 KT 93), and then looped to the coupler (07 KP 90), see the descriptions of the coupler. 2.5 PE connection Infeed of earthing potential to the PE bar with large conductor cross section Connection of the PE bar to the mounting steel plate Connection of the switchgear cabinet components to each other Connection of movable switchgear components to PE (doors) PE Faston connection of central units and couplers (see module descriptions) CS31 bus shield to PE Connections between analog cable shields and PE Reference potentials of the output voltages of the power supply units are interconnected and grounded 5 Notes for project planning 1-2 Advant Controller 31 / Issued: 10.98

2.6 CS31 System bus (see also volume 2, system data, system design) Bus line is looped through from module to module no spur lines Bus length (max. 500 m, measure cable length before installation, when necessary) Bus terminating resistors (see system data) Bus terminals (BUS1 to BUS1, BUS2 to BUS2) 2.7 Power supplies All mains voltages of the switchgear cabinet correctly fed in and fused All power supply units correctly fed in and fused Tolerances and load capacities of the power supply units sufficient Ripple of the power supply units low enough Reference potentials of the output voltages of the power supply units are interconnected and grounded 2.8 Connection of inductive loads to binary outputs Inductive DC loads wired with free-wheeling diodes Inductive AC loads wired with snubbers 2.9 Wiring of unused analog inputs (and outputs) Unused analog inputs wired according to module data sheets see also volume 2, chapter 5.2, Analog input modules - to avoid error message, inputs 4-20 ma supplied with at least 4 ma - voltage inputs 0-10 V and/or -10...+10 V connected to Analog GND - to avoid error message, Pt100 inputs wired with 120 Ω - to avoid error message, Pt1000 inputs wired with 1200 Ω - thermocouple inputs short-circuited Analog outputs not overloaded Unused analog voltage outputs left open. Unused current outputs can be short-circuited to Analog GND to e.g. avoid error messages Advant Controller 31 / Issued: 10.98 1-3 Notes for project planning 5

2.10 Programming / commissioning Operating mode of the basic units (master, slave, stand-alone) correctly set (default setting is stand-alone) Software configuration for the modules correctly programmed Program End (PE) exists in the user program FBD/LD and/or extended instructions list translated Program sent to the basic unit Program saved in Flash EPROM Operating mode of the PLC enabled 5 Notes for project planning 1-4 Advant Controller 31 / Issued: 10.98

Printed on chlorine-free bleached paper ABB Schalt- und Steuerungstechnik GmbH Eppelheimer Straße 82 Postfach 10 50 09 D-69123 Heidelberg D-69040 Heidelberg Telephone +49 6221 777-0 Telefax +49 6221 777-111 E-Mail desst.helpline@de.abb.com Internet http://www.abb-sst.de Printed in the Federal Republic of Germany (07.99)