UPS Operating Modes: A Global Standard. A White Paper from the Experts in Business-Critical Continuity

Similar documents
Powering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM

Data Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM

Securely Deliver Remote Monitoring and Service to Critical Systems. A White Paper from the Experts in Business-Critical Continuity TM

Tel: AC Power for Business-Critical Continuity TM

Liebert IntelliSlot Relay Card

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

APMTM UPS 18kW - 90kW The Flexpower Technology for mission critical applications

Hipulse-U UPS 80kVA - 500kVA Utmost Reliable Power Solution for Critical Business Applications

Common Mode Noise The Often Neglected Tenth Power Problem

10 kva 3/1 15 kva 3/1 20 kva 3/1 10 kva 3/3 15 kva 3/3 20 kva 3/3 30 kva 3/3 40 kva 3/3 UOUS SERV WARRANTY

Liebert APM The Compact Row-Based UPS With Flexpower Technology TM 30kW - 300kW. AC Power For Business-Critical Continuity

Liebert APM UPS The Industry s Highest Energy Efficiency In A Row-Based, On-line UPS. AC Power For Business-Critical Continuity

THE NEW SHAPE OF NETWORK POWER PROTECTION

Smart Solutions Intelligent, Integrated Infrastructure for the Data Center

Liebert THE NEW SHAPE OF NETWORK POWER PROTECTION. UPStation GXT 2U. An On-Line UPS With Proven Reliability,

Liebert NXr Series 15KVA to 90KVA (208V/220V) AC Power for Business-Critical Continuity

Hospital IT and Facilities Special Report Top concerns in the hospital include budget, power requirements

Liebert NX - Next Generation UPS for protecting your Business Critical Systems. AC Power Systems for Business-Critical Continuity

Trinergy from 200 to 1600 kw. High Power Modular Scalable UPS With Three Dynamic Functioning Modes

Liebert LM Series. Continuous Protection For Your Business. Surge Protection For Business-Critical Continuity

Chloride Trinergy from 200 to 1200 kw

Liebert. APM from 30 to 300 kw. The Compact Row Based UPS With FlexPower Technology

The Power of Modularity

SmartAisle Intelligent, Integrated Infrastructure Using Row-based Building Blocks. Solutions For Business-Critical Continuity

Liebert Load Bus Sync Extender/Adapter for Dual Bus UPS

Liebert NX, kva/kw UPS Maximum Efficiency in a transformer-free, High Efficiency, Scalable On-line UPS EFFICIENCY. AVAILABILITY.

Liebert Nfinity. A Powerful UPS Solution For Small To Medium Data Centers. AC Power For Business-Critical Continuity

Liebert LM Series Surge Protective Device Continuous Protection For Your Business. Surge Protection For Business-Critical Continuity

Liebert STS2/PDU, Static Transfer Switch 2/Power Distribution Unit. A Streamlined Package For Power Distribution And Source Switching

Liebert exm UPS kva/kw Efficient, Flexible Power Optimized for Midsize Applications FLEXIBLE. ECONOMICAL. INTELLIGENT

Liebert Precision Power Center

Liebert. NXC from 10 to 200 kw. Compact and Reliable Power in a Fully Integrated Packaged Solution

ENERGY STAR for Data Center Products: UPS plus Servers, Storage, and more April 24, 2012

The Different Types of UPS Systems

SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up. Solutions For Business-Critical Continuity

Liebert APM from kw. The Compact Row-Based UPS With FlexPower Technology TM

Liebert. EXL UPS 800 and 1200kVA Single Module and Multi-Module Systems

Liebert NXC. 10 to 40kVA Compact and Reliable Power in a Fully Integrated Packaged Solution

Liebert : The Right Cooling For IT Environments

UPS series PROTECT C. / C.R. Double conversion UPS with true sine wave - output

02 Why Does My IT Infrastructure Need a UPS?

IP Telephony. Contact Centers. Mobility. Services Avaya Overview Brochure

UPS PRO MODERNÍ DATOVÁ CENTRA. Rastislav Smatana AC Power Sales Manager CZ&SK

Liebert NX from 30 to 60 kw. AC Power for Business-Critical Continuity

Liebert MicroPOD 230V

Modular UPS S KVA

Liebert. EXS from 10 to 20 kw. Optimized and integrated three-phase UPS solution with high efficiency power protection

A Dell Technical White Paper Dell

Liebert NXC from 10 to 200 kva

PRODUCT PRESENTATION PROTECT 1. April 2012 DATA&IT, SBU C-UPS, PM/SR

PRODUCT PRESENTATION PROTECT C (6-10kVA) DATA & IT, C-UPS

The Different Types of UPS Systems

SmartMod Intelligent, Integrated Infrastructure for the Data Center

Liebert GXT MT kva

APMTM UPS 30kW - 300kW The Compact Row-Based UPS With Flexpower Technology

Liebert APM. The Compact, Row-Based UPS with Flexpower Technology 30kW - 300kW

Liebert NX Series. 30kVA to 200kVA. AC Power for Business-Critical Continuity TM

Liebert 80-eXL from 100 to 1200 kw. Enhanced Design and Improved Efficiency

Socomec Netys PR RT U P S TOWER / RACK MOUNT

Tech Byte 25: UPS Systems - Key To Ensuring Business Continuity - Part 1

LP 33 Series UPS. Digital Energy. GE Digital Energy

ADDRESSING CHALLENGES TO POWERING SMALL TO MIDSIZE IT SPACES

PRODUCT PRESENTATION PROTECT D.1000 D.3000 APRIL 2012 DATA&IT, SBU C-UPS, PM/SR

How Power Problems Affect PLC Reliability

ITA2 UPS 5-20kVA Compact, Efficient & Robust UPS For Critical Applications

ITA2 UPS 5-20kVA Compact, Efficient & Robust UPS For Critical Applications

Liebert NXr Series 30kVA to 160kVA. AC Power for Business-Critical Continuity TM

MGE Galaxy /30/40/60/80/100/120 kva. The recommended power protection for all critical applications.

SmartOnline SVTX Series 3-Phase 380/400/415V 30kVA 27kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option

Liebert APM The Compact Row-Based UPS With Flexpower Technology TM 30kW - 300kW. AC Power For Business-Critical Continuity

Dirty Power... A Guide to Surge Suppression & Filtering. Surge & Signal Protection for Business-Critical Continuity. EmersonNetworkPower.

GXT 2U Configuration Program

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity

Maximum Efficiency UPS Protection in an Intelligent, Low TCO Design Liebert exl UPS kVA, Single Module and Multi-Module Systems

Two-Stage Power Distribution: An Essential Strategy to Future Proof the Data Center

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability

SCALABLE, FAULT TOLERANT, INDUSTRIAL PROTECTION

DATA CENTER TRANSFORMATION: THE IMPACT OF EMERGING POWER ARCHITECTURES ON TODAY S DATA CENTERS

Liebert NX. UPS For Small And Medium Business. AC Power For Business-Critical Continuity

EP Series II UPS 230 V

SERIES 610 LOAD BUS SYNC

Liebert NX Series. 30kVA to 200kVA. AC Power For Business-Critical Continuity

Liebert NXC from 10 to 60kVA

CRITICAL INFRASTRUCTURE ASSESSMENTS

Liebert 80-eXL from 160 to 500 kw. Enhanced Design and Improved Efficiency

Chloride CROSS Rack 16 A, 32 A and 63 A

Liebert. ITA2 TM UPS 5-20kVA Compact, Efficient & Robust UPS For Critical Applications

Z8 G4 Site Prep Guide Table of contents

Specifying your exact choice of power supply: alternatives to full customization

Liebert EXL TM S kw to 1200 kw. Enhanced Design and Improved Efficiency

Current Trends in UPS Technology. Voltages

MODULAR UPS SYSTEM KVA

Liebert APM. The Compact Row-Based UPS With FlexPower Technology TM. AC Power for Business-Critical Continuity

LEVELUPS T3. SERIES kva ONLINE UPS 3:3 PHASE VFI TYPE. Highest Reliability and Robust Protection for Industrial Loads

GE Critical Power. Single Phase UPS Overview. 1 Gabriele Andrighetti

SmartRow Solution Intelligent, Integrated Infrastructure for the Data Center

Technical Data Sheets Uninterruptible Power Supply LP11 Series UPS kva

MUST900 Modular UPS. Datacenter & servers. Internet centers. Local Area Networks (LAN) Telecommunication devices. Emergency application

Power and Cooling Design Guidelines for Network Access Rooms. A White Paper from the Experts in Business-Critical Continuity TM

Transcription:

UPS Operating Modes: A Global Standard A White Paper from the Experts in Business-Critical Continuity

Executive Summary UPS terminology is a complex subject, often made more confusing by the competing marketing claims of various manufacturers. This can make it difficult for specifiers and owners to understand and evaluate the options provided by competing vendors. The North American industry should consider the approach and terminology developed by the IEC. The IEC has defined UPS types based on the relationships and dependencies (or lack thereof) between input and output voltage and frequency. This paper explains these terms and discusses the capabilities and limitations of the various classifications. Areas of confusion There are two areas where confusion seems to be most prevalent: 1. The meaning of the terms on-line and conversion when describing a UPS topology. 2. The power conditioning capabilities of energy saver or Eco modes of operation. The primary motivation for clarifying this terminology is to make sure that the specified solution is actually capable of addressing the problems that it is intended to solve or prevent. For example, the terms on-line and conversion (as in double conversion ) were historically used to describe and identify a UPS that converted incoming AC to DC and then back to AC, eliminating the largest range of power problems in the process. It was unusual for a manufacturer to highlight the fact that their UPS might be single conversion as this was considered to be a lower standard of performance, particularly in large threephase application. With the growing focus on energy efficiency, users have been demanding and manufacturers have been offering energy saver or Eco modes as a way to reduce energy consumption. These have gained acceptance as server power supply units (PSU s) have evolved with wider tolerances for input voltage levels and longer ridethrough capability, as measured by the ITI (formerly CBEMA) curve. The confusion arises as to the effectiveness of these modes in providing clean power to the critical load and controlling issues that could be reflected back to the source, including input current harmonics and load power factor issues. These are issues which the new power supply designs do not always solve and in some cases will exacerbate. In broad terms, there are two possible modes that can be considered high efficiency : 1. The load will be supported through the UPS bypass with NO interaction with the incoming mains (other than battery charging). This is typically referred to as an off-line or standby topology or mode; 2. The load can also be supported through the UPS bypass but the inverter can provide some level of power conditioning (and this can range from basic voltage regulation to active filtering of load-generated harmonics); This range of capabilities is typically referred to as line interactive topology or mode. It is important to understand exactly which mode is offered and how that is controlled so that the specifier and user s expectations and requirements are properly met. 1

As a starting point, it may be useful to review the range of common power issues and the traditional solutions which have been offered. Available solutions There are several solutions presently available in the market to condition and improve the energy supply quality to the load: UPS Transient Voltage Surge Suppressor (TVSS) Static transfer switches Series active filters Parallel active filters Hybrid active filters (series and parallel) The electrical supply quality depends on several types of disturbances that can be briefly summarized in the following categories: Harmonics and inter-harmonics Voltage fluctuations and flickers Voltage dip (sag) and interruptions Voltage imbalance Power frequency variations DC components Other disturbances include, notching, electric noise, and inducted low frequency voltage and oscillatory transients. Typical electrical disturbances 2

The latter three solutions based on active filters are typically used to compensate all of the disturbance categories, except voltage interruptions and frequency variations, within certain limits and with high efficiency. When considering the common electrical disturbances seen earlier on page 2, the UPS in its double conversion configuration, is the only one to date capable of compensating for all of the possible electrical disturbances. The UPS is indeed capable of supplying high quality voltage to the load both during the presence of large voltage amplitude fluctuations and also during total power supply interruptions. The latter can be achieved with local energy storage devices, such as batteries or flywheels. The double conversion UPS is certainly a leading solution, its only drawback is that it consumes a higher amount of energy in continuously converting input AC power to DC power and then back to AC for output to the loads. Figure 1. Parallel active filter for harmonics, PF, and transient compensation. Operating modes defined by IEC 602040-3 How the IEC definitions bring clarity. The IEC has identified three UPS topologies in its standard #62040-3. These are defined by the relationships and dependencies (or lack thereof) between input and output voltage and frequency characteristics. a). VFI Voltage and Frequency of the Output are Independent of Input Voltage and Frequency this is only possible if the they are generated independently, as in a double conversion mode or topology. b). VFD Voltage and Frequency of the Output are Dependent on the Input. This is true if there is no voltage regulation or independent generation of the output, which identifies a standby or offline mode. There can be some passive filtering, but no active power correction. c). VI Voltage of the Output is Independent of Input (Frequency In = Out). This is descriptive of line interactive mode or topology All of these are predicated on the ability of the UPS to maintain these relationships within a specified range without resorting to battery power. By defining these relationships in this way, the focus is on WHAT the UPS actually does (and therefore, what problems it can address) as opposed to HOW it actually achieves the result. Thus, competing methods of achieving these results can be evaluated by the specifier or end user, knowing that they are actually comparing apples to apples. 3

VFI operation IEC 62040-3 VFI is the double conversion mode which provides the highest level of power conditioning. It protects the load from all types of electrical network disturbances using a greater amount of energy. Efficiency at full load with the latest transformer-free technology is over 94%. Manual Bypass Static Bypass Rectifier Power Interface Inverter Output VI operation IEC 62040-3 VI compensates only the main disturbances such as mains sags and swells. In enhanced mode, this can also address issues such as load THDi and load PF. The energy used is derived from the use of the inverter as an active filter giving all the necessary reactive power. In a typical condition this mode will have an efficiency of between 96 and 98%, depending on the load type (e.g. non-linear, linear, etc.) and the input mains conditions. Manual Bypass Batteries Static Bypass Rectifier Power Interface Inverter Output Figure 2. New transformer-free VFI UPS (double conversion) VFD operation Batteries This mode may be used when the need for conditioning is non-existent and allows energy flow to pass through the bypass line. In this case efficiency reaches 99%. Figure 4. New transformer-free VI UPS with active filter compensating the mains or load disturbances. Manual Bypass Static Bypass Rectifier Power Interface Inverter Output Batteries Figure 3. New transformer-free VFD UPS 4

Using the inverter as an active filter An enhanced version of a VI UPS allows compensation of most of the disturbance categories seen on page 2, except voltage interruptions and frequency variations, within certain limits while continuing to maintain a high efficiency. This can be achieved given that the active filter uses less power than double conversion to compensate disturbances. The good news, in this case, is that the active filter does not need to be an extra, bulky component added to the UPS since an IGBT inverter controlled by appropriate technology can function as an active filter. This is possible, because the inverter itself is idle when the UPS is in high efficiency mode, making it possible to use the inverter both in series and parallel. Manual Bypass Inverter as a series active filter: the current of the active filter will have a shape intended to compensate the bypass line voltage in order to be able to remain inside the tolerance limits. This is possible by adding a series inductance that adds a small line impedance for the active voltage compensation by interacting with the current of the active filter generated by the inverter. Proportional to the current generated for the compensation of disturbances, power losses will be greater than those experienced on the high efficiency bypass line, but in any case will be less than those which occur in the double conversion mode. If this is then incorporated with the use of the latest transformer free technology in the same UPS, it becomes evident that this UPS offers the highest possible efficiency while maintaining tight standards of power quality. Static Bypass Rectifier Power Interface Inverter Output Batteries Figure 5. Enhanced VI UPS technology. The UPS is configurated to automatically compensate some disturbances on the network by using the IGBT inverter as an active filter that can be both configured as a parallel or series active filter, while the load is supplied through the static bypass line. Inverter as a parallel active filter: the inverter will work as a current controlled generator, generating a current that compensates the reactive and harmonic content of the load. 5

Conclusion The definitions developed by the IEC to identify the various operating modes (or topologies) of UPS s can eliminate much of the confusion emanating from various manufacturers terms and feature brand names, enabling the specifier and user to make better informed choices. These definitions provide objective benchmarks for comparing the expected power quality performance of competing offerings in high efficiency operating modes. As energy efficiency becomes more and more critical, the specifier and customer will be better able to understand and select the best solution for their applications. 6

Emerson Network Power 1050 Dearborn Drive P.O. Box 29186 Columbus, Ohio 43229 800.877.9222 (U.S. & Canada Only) 614.888.0246 (Outside U.S.) Fax: 614.841.6022 EmersonNetworkPower.com Liebert.com While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. 2010 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. All names referred to are trademarks or registered trademarks of their respective owners. Liebert and the Liebert logo are registered trademarks of the Liebert Corporation. Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. 2010 Emerson Electric Co. SL-24653-R10-10 Printed in USA Emerson Network Power. The global leader in enabling Business-Critical Continuity. EmersonNetworkPower. com AC Power Embedded Computing Outside Plant Racks & Integrated Cabinets Connectivity Embedded Power Power Switching & Controls Services DC Power Infrastructure Management & Monitoring Precision Cooling Surge Protection