MOD-IO9 Modbus Input / Output Modules, Wall Mounted

Similar documents
MOD-RI Room Interface Modules with Modbus

LLR-MOD Modbus Light Level and Occupancy Sensor

TER-MOD Active Room Temperature Sensors (Controllers) with Modbus

RHR-MOD Combined Room Temperature and Humidity Sensors (Controllers) with Modbus

CDR Room CO 2 and Temperature Sensor with Modbus

CDR-RH Room CO 2, Temperature and Humidity Sensors (Controllers)

LLR-BAC BACnet MS/TP Light Level and Occupancy Sensor

TER-BAC Room Temperature Sensors (Controllers) with BACnet

MIO12 Intelligent Modbus Input/Output Modules

SRT-50 Slimline Touchscreen Thermostats

FCU-MULTI Modbus Fan Coil Unit Controller

HLS34 Modbus FCU/VAV Controllers installation instructions

MID PRELIMINARY DATA SHEET. RI-D Series. Single Phase Multifunction Energy Meter (MID Certified) MID

PDS2-H Weather Compensator with Modbus Communications

SRT-P50 Series Programmable Touchscreen Thermostats

RCF-230CD. Communicating room thermostat for fan-coil applications with on/off outputs

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

Trident and Trident X2 Digital Process and Temperature Panel Meter

RCF-230CAD. Communicating room controller for fan-coil applications with two analogue V DC outputs

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

Evolution TH. Pre-configured controller with display, clock and communication. Evolution. Applications. TH version. Sensors

Features and Benefits. Certifications

FLTA Wireless Room Transmitter Control Modules

Specification Sheet For electronically commutated motors

Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual.

MCX08M2 Programmable controller

AIAS. Technical description

Communicative controller for VAV systems

Small distributed I/O module

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN

RTD-W Installation Instructions

RCF-230CAD. Room controller with communication for fancoil applications with two analogue V DC outputs

RXTH DUAL ROOM SENSOR / SWITCH

FLTA-KP10 Wireless Receiver/ Control Modules for HRP/LRP

RCF-230CTD. Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater

Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual.

FX Input/Output (I/O) Modules XM07 and XM14

Compact Coded Magnetic Safety Interlock Switch and Control Units

PM174 PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER. Features

DCT 531. Industrial Pressure Transmitter with RS485 Modbus RTU. Stainless Steel Sensor

D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

SX90 Process Controller

Gas Controller System DGC-06

UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

Energy Management Modular DC Energy analyzer Type VMU-E and VMU-X

Intech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual.

12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm)

For full product information, visit Use the SpeedSpec code or scan the QR Code for quick access to the specific web page.

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1

RXTP ROOM TEMPERATURE

MPI-DN, MPI-D MULTICHANNEL ELECTRONIC RECORDER for HART or RS-485/ MODBUS RTU SENSORS

EXD-TEVI Economizer Controller for Tandem Compressors

NEUROLOGIC RESEARCH CORPORATION MODEL 2500

Programmable controller MCX06C

NT10 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx

world class water monitoring series 42

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

The IQ300 wall mount load cell indicator is a precision digital indicator for load cell and strain gauge applications.

Temperature/Process Controllers Manual

Temperature controller Ducted systems

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

IQ21x Series Controllers

Neon pr. ph/ ORP measurement. Applications. Description

FX06 Field Controller

XT-9100 Technical Bulletin

Micro Motion Model 7950 and Model 7951 Signal Converters

BARIX IO12. I/O to RS-485 Modbus converter for commercial interfacing, control and home automation applications PRO D UCT MANUAL. Version: 2.

Millenium II +: general characteristics

ATV340D75N4E variable speed drive - 75kW- 400V - 3 phases - ATV340 Ethernet

DI-917MB/DI-918MB. Heavy-duty 1A solid-state relays provide dependable on/off control of industrial devices. Analog Output Module. Four Analog Outputs

Pre-programmed room controller with display and communication

Displays Transducers. Displays and transducers

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET

CM Series. Most Diverse and Flexible Line of Coded Magnetic Safety Interlock Switches and Controllers. Description. Safety Interlock Switches

High Voltage DC Meter

IntesisBox Modbus Server Panasonic

DL-10. User Manual. RS-485 Remote Temperature and Humidity. English Ver. 1.0, Jul. 2017

s Climatix AHU ext. module 14 I/O POL955.XX/XXX Climatix

USER MANUAL. Modbus IHP24-A IHP24-AF IHP24-B IHP24-BF IHP24-F IHP24-I 1/26

USER GUIDE TEHR LU / TEHR-M

PD765 TRIDENT. Trident Series Process & Temperature Meters.

RC-CDTO. Pre-programmed room controller with display, communication and three-point control

MIC-2 MKII, Multi-instrument DATA SHEET

HIGH-VOLTAGE DC METER

OTB1S0DM9LP I/O distributed module OTB - Modbus non isolated serial link m

Transmitters RHT-WM-485-LCD, RHT-DM-485-LCD and RHT-P LCD

PD765 TRIDENT. Trident Series Process & Temperature Meters.

Controllers for compressor racks with advanced energy saving. PN08 September 2016

Fieldgate SFG500. Technical Information. Intelligent Ethernet/PROFIBUS gateway

APP 700 Technical Specification

Pen Drive USB Datalogger!

USER GUIDE PEL / PEL-M

MXIO. Compact I/O module. Summary. Application Compact I/O module for data acquisition and HVAC control systems. Function

MCX06C Programmable controller

TC-9102 Terminal Controller

SDC-20G/32G Graphics Series Distributed Controller Reference Manual

Transcription:

Product sheet MOD3.9 Type MOD-IO9 MOD-IO9 Modbus Input / Output Modules, Wall Mounted MOD-IO9 and MOD-IO9-AI have been designed to be a compact wall mounted Modbus RTU input and output module. The module has 2 volt-free digital inputs for measurements e.g. for windows, occupancy sensors and so on. The module has 2 digital outputs, Vac triacs switching the plant items on/off. The IO9 modules has 2 inputs for measuring NTC0 temperature, resistive measurements (e.g. light level) or volt-free on/off signals. The IO9-AI models have 2 inputs for measuring 0..0Vdc signals. The three analogue 0..0Vdc outputs complete the compact IO-modules. With the analogue outputs it is possible to control zone valves and other modulating plant equipment. The modules support Modbus RTU communications with most commonly used baud rates and parity settings. Model Type Model Description MOD-IO9 Modbus RTU Digital Input / Output Module, 2DI, 2DO, 2RI, 3AO MOD-IO9-AI Modbus RTU Digital Input / Output Module, 2DI, 2DO, 2AI, 3AO Technical Data Power Supply Power supply Vac/dc -0%/+5% Signal Outputs Analogue Outputs 3 x 0..0V < 5mA; 00k min impedance for % accuracy Digital Outputs 2 x Vac Triacs; 2A maximum; requires Vac Power Supply Signal Inputs Resistive Inputs (MOD-IO9) 2 x Universal NTC0/Resistive/Digital Inputs, 0..50kOhms (NTC0/Volt-Free Digital default, configurable via SW-DCT-USB tool to resistive mode) Voltage Inputs (MOD-IO9-AI) 2 x 0..0Vdc Inputs Digital Inputs 2 x Volt-Free Contact, Impedance <KOhm Pulse Counting: Max 25Hz, Min Pulse Length 20mA (Volatile) Communication Modbus Communications Procotol Modbus RTU Interface RS45; maximum 63 devices ing..63 via a bit switch;..7 via tool / network Communication 9k6/9k2/3k4/57k6 Baud; Parity None/Even/Odd, or 2 Stop Bits (baud rate adjustable through bit switch or network) Connections Terminal Connections Solid and Stranded Cable; 55 Angle for Wiring Maximum Size: 0.05 to.5mm 2 (EN ISO) / 4 to 30 AWG (UL) Rising Clamp: Size 2.5 x.9mm Environmental Conditions Operating Temperature 0 C...+50 C (..22 F) Humidity 0...95%rh (non-cond.) Storage Enquiries: T: 044 40 300 F: 044 40 00 PS MOD3.9 - /5

Temperature Humidity -30 C...+70 C (-22..5 F) 0...95%rh (non-cond.) Standards CE Conformity CE Directive 2004/0/EY EN6000-6-3: 200 (Generic Emission) EN6000-6-: 200 (Generic Immunity). Degree of Protection IP20 Housing Housing Material ABS Plastics, Self Extinguishing Mounting Wall or Junction Box Mounting, RAL900 Pure White Dimensions W6 x H20 x D29mm Weight 0g Wiring Terminals Vac Relay Vac Relay Vac/dc 0 V DO DO2 G Go Digital Output, Vac Triac Digital Output 2, Vac Triac Vac/dc Supply MOD-IO9 Y Analogue Output, 0..0Vdc Y2 Analogue Output 2, 0..0Vdc Y3 Go Analogue Output 3, 0..0Vdc BIT SWITCH 6 Bit Rate A+ RS45 (Modbus) B- RS45 (Modbus) Go RI NTC0/Resistive Input 0..50kOhms/Digital Input 3 (MOD-IO9) Analogue Input, 0..0V (MOD-IO9-AI) DI Digital Input, Volt-Free RI2 NTC0/Resistive Input 2 0..50kOhms/Digital Input 4 (MOD-IO9) Analogue Input 2, 0..0V (MOD-IO9-AI) DI2 Digital Input 2, Volt-Free DO Digital Output; Vac Triac Switching to 0V; max. 2A DO2 Digital Output; Vac Triac Switching to 0V; max. 2A G Vac/dc Power Supply Y 0..0Vdc Analogue Output Y2 0..0Vdc Analogue Output Y3 0..0Vdc Analogue Output A+ RS45 A+ Connection (Modbus) B- RS45 B- Connection (Modbus) RI IO9: NTC0/Resistive Input 0..50kOhms/Volt-Free Digital IO9-AI: 0..0Vdc DI Digital Input; Volt-Free, Max 25Hz, Min Pulse Length 20mS RI2 IO9: NTC0/Resistive Input 0..50kOhms/Volt-Free Digital IO9-AI: 0..0Vdc DI2 Digital Input; Volt-Free, Max 25Hz, Min Pulse Length 20mS Enquiries: T: 044 40 300 F: 044 40 00 Copyright 206 SyxthSense Ltd. All rights reserved - 03/206 PS MOD3.9-2/5

Digital Input Pulse Counting Universal NTC0/ Resistive/Digital Inputs (MOD-IO9) Analogue Inputs (MOD-IO9-AI) Setting Up Modbus and Baud Rate Digital Inputs can be used for pulse counting up to 25Hz, minimum pulse length 20mS. The pulse count is stored in a dedicated register and can be read over the network. It is possible to write to this register to reset the value. NOTE: The pulse count value is not battery backed, and therefore the network master is required to manage the data synchronisation in case of power failure. The universal inputs can be configured to operate as NCT0/Digital Volt-Free inputs or Resistive Inputs. As default the inputs are configured as NTC0/Digital Volt-Free. The maximum measurement range is -0 C to 00 C (-40 F to 22 F). The NTC0/resistive configuration is changed via the Configuration Software using the USB to IO-Module cable. The digital volt-free mode is automatically activated, and separate Modbus registers are available to read the status. The MOD-IO9-AI has 2 x 0..0Vdc inputs. The current status can be read over the Modbus communication network. The Modbus address and the baud rate is normally set through the bit switch. It is also possible to set the address and baud rate over the Modbus communication network. NOTE: The new settings are activated automatically after approx 5 seconds if the bit switch positions have not been moved. In this case the controller reset is applied to activate the new settings. SETTING TRANSMITTER BAUD RATE BAUD RATE BAUD RATE BIT SWITCH 57600 3400 6 Bit Rate BAUD RATE 9200 BAUD RATE 9600 / NETWORK SETTING TRANSMITTER MODBUS ADDRESS The Modbus address is set by using bith switches BIT SWITCH to 6 using binary decoding. Each bitswitch represents the binary value and the address is set by the combination of bit switches. Few examples: 6 Bit Rate MODBUS ADDRESS 2 MODBUS ADDRESS 9 Note: When the baud rate set 9600 via the bit switch it is possible to configure the baud rate via network / tool. Note: To activate the change the transmitter requires power cycle, or software reset via the tool. 6 Note: If all address bit switches are set, then the Modbus address can be set over the Modbus or through configuration tool. 6 Modbus Registers The IO-module supports the following Modbus registers and function codes. The default communication speed is 9600 bps, data bits, Parity None and Stop Bit. The default Modbus Slave address is. The device Parity can be changed between Odd, None and Even. The baud rate is selectable between 9600, 9200, 3400 and 57600 bps. The baud rate speeds can be selected using the built-in bit switch, or over the network if BR and BR2 are set to. The sensor addresses to 63 can be set using the local bit switch, and over the Modbus the adjustable address range is to 7. Please note that Modbus register space is specified from the Modbus master perspective as in the Modbus Application Protocol specification. The Modbus registers for Function Codes 02, 03, 06 and 6 have presentation for both Modbus "address blocks" and for actual Modbus register offsets. For example, the Temperature is read from Modbus register using Function Code 04. Some Modbus masters will require Function Code 04, register to be entered, whereas the others will require register 3000 and Function Code 04. The Modbus addressing starts from the zero Base address. (Some Modbus masters start addressing from, in this case add one to the listed register values). Register Parameter Description Data Type Raw Data Range FUNCTI CODE 0 - READ COILS FUNCTI CODE 05 - WRITE SINGLE COIL FUNCTI CODE 5 - WRITE MULTIPLE COILS 0 Digital Output Override ( Write) 0.. Off - On Digital Output 2 Override ( Write) 0.. Off - On FUNCTI CODE 02 - READ DISCRETE INPUTS 0000 Digital Input Status 0.. Off - On 000 Digital Input 2 Status 0.. Off - On 0002 Digital Output Status 0.. Off - On 0003 Digital Output 2 Status 0.. Off - On 0009 Digital Input 3 Status (MOD-IO9: RI) 0.. Off - On 000 Digital Input 4 Status (MOD-IO9: RI2) 0.. Off - On FUNCTI CODE 04 - READ INPUT REGISTERS 30004 MOD-IO9: Resistive Input Unsigned 6 0...50000 0..50000 Ohms 30005 MOD-IO9: Resistive Input 2 Unsigned 6 0...50000 0..50000 Ohms 30007 Analogue Output Y Unsigned 6 0..000 0..00.0 % 3000 Analogue Output Y2 Unsigned 6 0..000 0..00.0 % Enquiries: T: 044 40 300 F: 044 40 00 Copyright 206 SyxthSense Ltd. All rights reserved - 03/206 PS MOD3.9-3/5

Register Parameter Description Data Type Raw Data Range 30009 Analogue Output Y3 Unsigned 6 0..000 0..00.0 % 3002 MOD-IO9: NTC0 Input (RI in NTC mode; default) 3003 MOD-IO9: NTC0 Input 2 (RI2 in NTC mode; default) Signed 6-400...3020-40.0..302.0 F -40.0..50.0 C Signed 6-400...3020-40.0..302.0 F -40.0..50.0 C 3004 MOD-IO9-AI: Analogue Input Unsigned 6 0...000 0..00.0 % (0..0V) 3005 MOD-IO9-AI: Analogue Input 2 Unsigned 6 0...000 0..00.0 % (0..0V) 3000 Firmware Version Unsigned 6 n/a n/a FUNCTI CODE 03 - READ HOLDING REGISTERS FUNCTI CODE 06 - WRITE SINGLE HOLDING REGISTER FUNCTI CODE 6 - WRITE MULTIPLE HOLDING REGISTERS 40000 Analogue Output Y Override Value Unsigned 6 0..000 0..0.0 V 4000 Analogue Output Y2 Override Value Unsigned 6 0..000 0..0.0 V 40002 Analogue Output Y3 Override Value Unsigned 6 0..000 0..0.0 V 40039 MOD-IO9: Temperature Unit Selection for RI and RI2 in NTC0 Mode Unsigned 6 0.. 0 = Celsius (Default) = Fahrenheit 40050 Modbus Unsigned 6 0..7 See Note 4005 Modbus Baud Rate Unsigned 6 0...3 See Note 2 0..7 (Default ) 0 = 9600 (Default) = 9200 2 = 3400 3 = 57600 40052 Modbus Parity Unsigned 6 0...2 0 = None (Default) = Odd 2 = Even 40053 Stop Bits Unsigned 6 0... 0 = Stop Bit (Default) = 2 Stop Bits 40067 Hold On Delay Setting for Digital Input Unsigned 6..7200..7200 Seconds (s) 4006 Hold On Delay Setting for Digital Input 2 Unsigned 6..7200..7200 Seconds (s) 40070 MOD-IO9: RI Single Point Calibration Signed 6-0,000..0,000 -,000..,000 C, F or Ohms 4007 MOD-IO9: RI2 Single Point Calibration Signed 6-0,000..0,000 -,000..,000 C, F or Ohms 40072 DI Pulse Count Most Significant 6 Bits Unsigned 6 0..6520 0..6520 40073 DI Pulse Count Least Significant 6 Bits Unsigned 6 0..65535 0..655350 40074 DI2 Pulse Count Most Significant 6 Bits Unsigned 6 0..6520 0..6520 40075 DI2 Pulse Count Least Significant 6 Bits Unsigned 6 0..65535 0..655350 4000 Force Reset Unsigned 6 0.. 0 = Normal = Force Reset 400 Non Volatile Memory Update Unsigned 6 0.. Note 3 0 = Normal = Update 4003 Force Factory Defaults Unsigned 6 0.. 0 = Normal = Force Defaults 4004 Force 0..0V Output Calibration Routine Unsigned 6 0.. 0 = Normal = Force Calibration Note. Modbus address can be configured via network only if the bit switches -6 are switched off. Please note if changed over the Modbus, the Non Volatile Memory Updated parameter MUST BE exercised before power cycle or reset. Note 2. Modbus Baud Rate can be configured over the Modbus if bit switches 7 & are in off state (9600). Please note if changed over the Modbus, the Non Volatile Memory Updated parameter MUST BE exercised before power cycle or reset. Note 3. When the settings are changed over the communication bus, the changes for the configuration parameters are not stored in the non-volatile memory automatically. In order to store the changes "Non Volatile Memory Update" is required to be set true. Enquiries: T: 044 40 300 F: 044 40 00 Copyright 206 SyxthSense Ltd. All rights reserved - 03/206 PS MOD3.9-4/5

Dimensions Wall Box Screw Hole Locations 79 64 5 20.50 4 60 5 6 2.7 Enquiries: T: 044 40 300 F: 044 40 00 Copyright 206 SyxthSense Ltd. All rights reserved - 03/206 PS MOD3.9-5/5