PSM 505. Inform IT Power System Monitoring. Stand-alone Fault Analysis and Evaluation Tool. Technical Data. Introduction.

Similar documents
THE INTEGRATED TESTING SOLUTION

Terminal tool box CAP 540*1.2

Relay configuration and setting tool package

User s Manual CAP 531*1.5 Configuration and Programming tool

IDM DATA ACQUISITION SYSTEM

MV Process Application Library LIB 510. Product Guide

Relay Product Engineering Tools

Relay setting toolbox

Communicate IT Software module DR-COM. Buyer s Guide

SPECIAL CONSIDERATION OF FEEDER PROTECTION FOR BREAKER-AND-A-HALF CONFIGURA- TIONS. G. Steynberg

DRAN-VIEW Power Quality Browser (v.6) QuickStart and Reporting Skills Course: TS-DB-DV6 (PQS204)

Power Products. Protection and Control IED Manager PCM600 Product Guide

Quick Start Guide PCM600 for Relion 650/670 Series

Logger Pro 3. Quick Reference

RecordGraph Template Application Note

SPRECON-E Display Editor

Distribution Management System Open++ Opera v.3.3. User Manual

Open Excel by following the directions listed below: Click on Start, select Programs, and the click on Microsoft Excel.

What s New in Version 14 of ASPEN OneLiner/ Power Flow

SequencePro Data Analysis Application. User Guide

LIB 500 Base & LIB 510 Introduction Operator s Manual

Mirasys N series. Network Video Recorder Quick Guide

Desktop Studio: Charts

Aurora Multi-image System Control Software. User Manual

Process Eye Professional. Recall

Manual SmartGraph for Humlog 10

EZCT-2000 Software. VERSION 2.x USER'S MANUAL

Desktop Studio: Charts. Version: 7.3

Distribution Management System Open++ Opera v.3.2. User Manual

Virtual MODELA USER'S MANUAL

PowerView for the EnergyPro

Desigo Insight Operating the management station, V5 User s guide, Volume 2

Tutorial Base Module

ACS Plant Operating Software

AQ7932 OTDR Emulation Software Operation Manual

Electromechanical Systems Simulation Software (LVSIM -EMS)

USB Instruments EasyLogger for PS40M10 "Swordfish" Help

POWERSTUDIO USER MANUAL 3 / 4

IML-RESI F-Series. Electronic. F-Tools F-Tools Pro. Manual. Issued

User s Manual. CW500Viewer IM CW500-61EN. 2nd Edition

BusinessObjects Frequently Asked Questions

Operating Instructions / User manual. IRSoft. Version 2.0. Documentation software for ERSA Rework Systems. ERSA GmbH

Testing and Diagnostics

Substation Automation Products. Line differential protection RED670 Relion 670 series

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Multichannel Data logging

Starting Excel application

Topaze Guided Session #2

TFS 2100 Traveling Wave Fault Location System

Enerscope-3S Studio. User Manual. Windows Software for Consulting and Analysing Data collected by Enerscope-3S Power Analyzer.

Technical Documentation Version 7.3 Output

Impress Guide. Chapter 11 Setting Up and Customizing Impress

WAProtector Power System Wide Area Monitoring Protection and Control

METS methane sensor SOFTWARE MANUAL UNDERWATER SENSORS FOR DISSOLVED GASES

USE CASE 13 ADAPTIVE TRANSMISSION LINE PROTECTION

Yukon Visual T&D HMI/SCADA

AEMLog Users Guide. Version 1.01

Impress Guide Chapter 11 Setting Up and Customizing Impress

Real-time visualization for detecting and solving power system challenges

Smart Tool Suite. Documentation. Users Manual. Version 1.0

F U E L C E L L S U P E R V I S O R H 2

DOWNLOAD KIT CYCLOCOMPUTER INTRODUCTION. Download unit & Download Software [e-train Data Ver.3] for Windows 98/ME/2000/XP

Fig. A. Fig. B. Fig. 1. Fig. 2. Fig. 3 Fig. 4

Nintex Reporting 2008 Help

LINAX Series Videographic Recorders

Multiscan. RASCAN-4 PC Software USER'S GUIDE. ver RSLab

F6150. Power System Simulator For Testing Protection Relays and Schemes.

Microsoft Excel 2007

Dranetz s industry leading power analysis software provides professional reports and analysis to all users COMPATIBLE INSTRUMENTS

41126 Cognento (MODENA) Italy Via Bottego 33/A Tel: +39-(0) Internet: Fax: +39-(0)

InkZone2Optim. Page 1/11

Chapter 2 State Estimation and Visualization

LIB 500 Event List Operator s Manual

GRID/PRSHT/MU320/EN/1.2014/GBR/1894 ALSTOM All rights reserved.

Summary I Minimum system requirements...2

FLEXIBLE SOLUTIONS FOR THE ENERGY INDUSTRY

AEMLog users guide V User Guide - Advanced Engine Management 2205 West 126 th st Hawthorne CA,

LIB 510 Measurement Reports 2 Operator s Manual

Instruction Manual A1. GE Digital Energy

Tutorial 3: Using the Waveform Viewer Introduces the basics of using the waveform viewer. Read Tutorial SIMPLIS Tutorials SIMPLIS provide a range of t

POWER WORLD LAB MANUAL

*Note that LL Studio can also work in Stand-alone mode with an SD card.

Operating Manual. Windows Operating Software GSOFT 3050 as of version 3.0. for Handheld Instruments GMH 3000 / GMH 5000 / GHMsilverline

ArtDMX DMX control software V1.4

Introduction to MS Office Somy Kuriakose Principal Scientist, FRAD, CMFRI

Avigilon Control Center Web Client User Guide

Bus Bar Protection Relay B-PRO 4000

VANGUARD LOAD TAP CHANGER ANALYZER (LTCA) VERSION 2.xx SOFTWARE MANUAL. LTCA-10, LTCA-40, WRM-10P, WRM-40, TRM-20, TRM-40, TRM-203, and TRM-403

USER INTERFACING FOR AN AUTOMATED CIRCUIT BREAKER MONITORING AND ANALYSIS

testo Comfort Software Professional 4 Instruction manual

Day : Date : Objects : Open MS Excel program * Open Excel application. Select : start. Choose: programs. Choose : Microsoft Office.

DL160 Datalogger Software Guide

Woodward USB WIC1-PC3. WI-Soft2 Parameterisation and Diagnosis Software. (Revision A)

OPERATION MANUAL. MV-410HS Layout Editor. Version higher. Command

DIAGNOSTICS PN# / / FSP

2010 by Microtek International, Inc. All rights reserved.

SCREEN RECORDER KD-Series TYPE

Mehta Tech, Inc. TRANSCAN IED For Multi-Function, Multi-Speed Recording

14 July Ver CRView V3 User Guide. 1 P a g e

Transcription:

Page 1 Issued: July 2003 New Data subject to change without notice Introduction High-voltage transmission and distribution networks are the backbone of modern power generation and distribution systems. Faults on the transmission system are prone to cause severe economic losses. Protection engineers apply to analyze all generated disturbance records, making good use of the highly flexible evaluation and calculation features. This leads to a better understanding of complex effects in the network, weak spots in the network are detected and settings are accurately adjusted or protection diagrams improved, which in the long-term results in a decreasing number of faults. Therefore higher reliability of the network is achieved. belongs to the software suite "Power System Monitoring". The package described in this Data Sheet is intended for the stand-alone use on a PC or laptop to evaluate single disturbance records manually. User benefits Viewed in the long-term, increases the reliability of the power network and minimizes the damage resulting from faults in transmission and distribution systems and in power generation systems. This can be achieved using the strong and user-friendly analyzing functions of. Calculations can easily be programmed using the point-and-click icons. Related disturbance records can be merged and many other functions can be applied to analyze disturbance records. Using this information the protection engineer will uncover secondary effects in the power system and may optimize the settings of his assets, which results in a more robust power network. PSM is a scalable solution allowing a stepby-step implementation and integration into the existing power network. This allows a very flexible system investment. A installation can be connected to a PSM 500 server, which provides fully automatic collection and evaluation of disturbance records from all connected fault recorders and protection devices in a network of a utility.

User Application benefits (cont d) The stand-alone application can be used to evaluate disturbances recorded in the following devices: Dedicated disturbance recorders such as Indactic 650 from ABB Integrated disturbance recorders of protection devices manufactured by ABB 3rd party dedicated disturbance recorders 3rd party integrated disturbance recorders generated from protection devices. can handle various standard and proprietary file formats of the disturbance recording, for example: ABB Indactic EVE format ABB REVAL format COMTRADE file format IEEE C37.111-1991 COMTRADE file format IEEE C37.111-1999. The system can run on Microsoft Windows 2000 or Windows P computer for evaluation and analysis of faults in the following areas: Distribution, transmission and subtransmission levels Power supply of industrial plants and the auxiliary supply of power plants Power generation systems, generator-, transformer- and transmission protection systems. Software module and feature overview The PSM software consists of different functional modules. These modules are combined in different ways to build big PSM systems described in the referenced brochure [1] and in detail in the Data Sheets [2] and [3]. The stand-alone fault analysis application consists of three modules shown in the graphical representation in Fig. 1 and described below. Fig. 1 Software modules of is available in three variants. The "Expert" variant allows full functionality with highest performance. RelView variant The RelView variant is the basic entry level of. The functionality comprises the display/view of the fault records and analog and digital signals. Professional variant The Professional variant provides advanced functionality in addition to the features available in the RelView variant. Fault location and power analysis calculations are possible as an example. Expert variant The Expert variant is an advanced extension of the Professional variant with in-depth analysis, time calculation and animation features. Page 2 ABB Switzerland Ltd, Utility Automation Systems

Table 1: Key features of the stand-alone fault analysis tool dependent on the RelView, Professional and Expert versions Features RelView Professional Expert E_wineve workplace E_navigate Phasor display: Overlaying phasors with impedance settings of RE.2/316 Phasor display: Animation Merging of two disturbance records Time calculations using the time formula editor Manual "One-Terminal Fault Location" (OTFL) Manual "Two-Terminal Fault Location" (TTFL) Power analysis calculations using the formula editor Phasor display: Viewing of signals as symmetrical components Phasor display: Displaying the locus of voltages, currents and impedances Phasor display: Displaying voltages, currents and impedances Manual saving of file in COMTRADE format Oscillography viewing of disturbance records Viewing of the configuration of the PSM system Changing the configuration of the PSM system for authorized users The module E_navigate This module is used to configure PSM with static information about the power grid, which is represented by substation lines and feeders. Also the secondary devices and the mapping of measured signals and power lines are configured with this module. It provides the following key features: Easy navigation because of tree structure with expandable nodes Stations can be combined to regions Devices are grouped into stations Aside from the tree structure graphical panes exist in addition A freely configurable background can be added to every pane Pull-down menus for any tree node and icon Freely configurable comments appearing when the mouse pointer crosses an icon User authentication based on the Windows user group concept Different authentication levels for viewing or changing the configuration. The graphical view of the communication network and a tree-structured view of all recording devices simplify navigation. Devices are grouped in stations. For big installations it might be helpful to group stations in regions. The tree structure is also displayed on graphical panes. An overview with all substations is displayed on one pane. For every region and substation there is a separate pane, where the devices and substation icons can be arranged in any way desired. In addi- ABB Switzerland Ltd, Utility Automation Systems Page 3

Software The module module and E_navigate feature overview (cont d) (cont d) tion a bitmap background can be added to every pane, which provides additional information for the user. Pull-down menus containing all relevant commands are available for every node in the tree node and also for every icon in the graphical pane just by a right mouse click. The authentication is based on a strict user management of the Windows operating system. This allows high security against unwanted access to PSM data. This module is installed on the PSM central server and also on all PSM station servers. It is especially needed for stand-alone disturbance record evaluating installations without network connection to a PSM server. Fig. 2 E_navigate to configure PSM The module E_wineve workplace The module called "E_wineve Workplace" contains a viewer with a large number of useful features for the display of disturbance records. Interactively different algorithms for fault location can be applied, and strong interactive evaluation tools enable the user to perform an in-depth post-mortem analysis of disturbance records. Oscillography visualization After opening a disturbance record file analysis, support is given by means of: a simultaneous display of several disturbance records in different windows a cursor line able to be positioned to a numeric time value, whereby the corresponding values of the signals are updated zooming in/out the interesting part of a display by expanding the amplitude and/or time axis a free arrangement of all signals or composing of several signals on one time axis, e.g. all voltages on the same horizontal axis. signals able to be hidden and inserted later on selection of the color for each analog and digital signal. Page 4 ABB Switzerland Ltd, Utility Automation Systems

For every configured device the user may store up to ten different individual layout settings, containing for example, the preferred amplitude size and axis height, zoom values and hidden signals. Supported file formats E_wineve is able to handle various standard and proprietary file formats of the disturbance recordings. Files can be opened, displayed and evaluated for the following file formats: ABB Indactic EVE format ABB REVAL format COMTRADE file format IEEE C37.111-1991 COMTRADE file format IEEE C37.111-1999. The files may be saved and optionally converted into all mentioned formats except for the ABB REVAL file format. Fig. 3 Curve representation of a disturbance record Merging of two disturbance record files The merge function allows the combination of data for the same fault recorded by different acquisition units. This results in a new data set with selected measurements from an extended area that can be used for further analysis by additional functions, such as power analysis calculation and fault location. Merging of different recorded fault data for in-depth analysis Automatic synchronization of both data sets, i.e. the time axes of both data sets are made to correspond exactly within <0.1 ms with regard to the event e.g. in a 1½ breaker scheme Merging on the basis of the discontinuity of a "common" analog signal in both files ABB Switzerland Ltd, Utility Automation Systems Page 5

The module E_wineve workplace (cont d) Free selection of signals to be combined Saving of the new combined data set for further processing is possible in the supported file formats. Manual fault location E_wineve has integrated high-end fault location algorithms producing accurate results even for high-impedance short circuits between lines or for line-to-earth faults. Line parameters entered by the user are utilized for the fault location calculation. After a fault location algorithm has been applied, the results are presented in the form of a "Short fault report", an easy to read onepage report containing all facts. The algorithms have the following features: Calculation of the loop impedance of the faulted line Correct interpretation of short circuits to earth, two- or three-phase short circuits and symmetrical or asymmetrical lines Parallel lines are considered by the fault location algorithms. One-terminal fault location The accuracy of the fault location is dependent on the fault resistance and is typical better than 3.5% of the distance to the fault, considering one disturbance record from one line terminal. Two-terminal fault location This algorithm uses disturbance records recorded in different substations connected to both ends of a faulty line. Combining the information of both disturbance records, the fault location is calculated with an improved accuracy. It would be a simple way to implement a "two-terminal fault location", calculating the average value of the result of using a one-terminal location algorithm applied from both line ends. But the twoterminal fault location algorithm developed by the utility TVA (Tennessee Valley Authority) together with ABB is much more advanced. This algorithm combines samples from both disturbance records initally and therefore minimizes line parameter uncertainties and source impedance influence bound to change a quite a lot in case of a fault. The typical accuracy of a "two-terminal fault location algorithm is 1% of the line length Fig. 4 Two-terminal fault location algorithm applied to disturbance records provided by a customer. OTFL means One-Terminal Fault Location, TTFL means Two-Terminal Fault Location. The yellow arrow symbolizes the real fault location. Example from a customer Line length OTFL from A OTFL from B TTFL Real distance 139.0 km 28.3 km 104 km 29.6 km from A 109.4 km from B 30.6 km from A 108.4 km from B Page 6 ABB Switzerland Ltd, Utility Automation Systems

Two-terminal fault location details Before E_wineve applies the two-terminal fault location algorithm to two DR files, it checks the following three conditions: The fault is on the same line and phase, referenced in the disturbance records The fault type seen from both sides is equal The trigger time of both files differs by less than some seconds. The two-terminal fault location algorithm has the following limitation in the actual PSM V1.5 version: The fault recorder has to be configured with the same sampling rate on both line ends. Short fault report The information printed out in the "short report" (see Fig. 5) is the following: General information about the fault event - Name of the acquisition unit recording the disturbance - Number of the acquisition devices - Date and time of the disturbance record - Information of the line name and line length - The complete directory path and name of the disturbance fault record - Duration of the fault record Information regarding the trigger, which causes the record - Type of trigger Information regarding the disturbance and location of the fault - Fault type - Fault duration - Impedance at the fault in the polar and Cartesian format - Distance to the fault. Fig. 5 Short Fault Report Power analysis calculations The power analysis calculation can be used to derive useful data for in-depth fault analysis by means of additional calculations and the combination of recorded signals. For example, the analysis of the harmonics provides a measure of the quality of a voltage. It also permits the calculation of the effective short-circuit power, which has resulted in damage to the switching elements, using the measured short-circuit currents and voltages. The loop impedance as a function of time (impedance and phase angle) derived from the sequence of the voltage and current is another possible calculation. Sum, difference, multiplication and division and average of input signals Pre-programmed function for the calculation of - RMS values - impedance and power vectors - harmonic contents - frequency deviation Formula editor, on-line syntax check, and test execution of the calculation program Linking the stored calculation for automatic execution. ABB Switzerland Ltd, Utility Automation Systems Page 7

The module E_wineve workplace (cont d) Fig. 6 Power analysis calculation functions Phasor display The new, combined phasor and impedance display dialog is a powerful tool to analyse voltage and current measurements as part of an opened disturbance record. It shows the results of the phasor and impedance calculations (with complex algebra) in a polar chart and in a numerical data table. The polar chart may be printed and the calculated results saved in a text file for further examination with other tools (e.g. Microsoft Excel). For certain relay types, the impedance calculation results may be superimposed with the line or distance protection zones after importing the corresponding relay parameter file. Functions of the phasor display E_wineve provides the following different views to display analog signals in the phasor display: Showing all voltages and currents of a selected line in the phasor diagram Displaying a freely arranged combination of analog signals in the phasor diagram Showing the impedances of a line in the polar chart (phase-to-phase and phase-toearth impedances) Displaying the locus of the phasors (voltages, currents or line impedances) related to a freely selectable time interval Page 8 ABB Switzerland Ltd, Utility Automation Systems

Exporting the values of a selected time interval to a text file for further examination with other tools (e.g. Microsoft Excel) Calculation of symmetrical components for three-phase systems. Fig. 9 Apparent line impedance. Sample markers are enabled Fig. 7 The phasors of the voltages and currents together with the locus in the phasor display Fig. 10 Symmetrical components of voltages and currents, captured in the "full screen mode" Fig. 8 The same as in Fig. 7, in addition the green-coloured voltage phasor remains constant Easy-to-use features of the phasor display Certain features are designed to increase the user-friendliness of the tool and to support the user with expressive screen shots for documentation issues or further analysis: Zooming in and out the graphical polar chart Hiding and re-displaying signals Enlarging the polar chart to the complete screen size Direct printing of charts Displaying sample points, which point out big dynamics of signals. ABB Switzerland Ltd, Utility Automation Systems Page 9

The module E_wineve workplace (cont d) Expert features of the phasor display E_wineve provides two special features for experts working in the protection fields: Phasor animation Overlaying the impedance view with the zone settings of a distance protection relay. The integrated animation tool visualizes the dynamic behaviour of the voltage and current measurements. Thereby the movement of the phasors and the composition of the loci are shown in a short animation. In addition the numerical data table is updated after each simulation step and the cursor in the curve representation is moved over the corresponding time interval. If a distance protection relay is involved in a line trip, it is also very helpful to overlay the impedance view of the disturbance record with the zone settings of the relay. The version V1.5 of PSM supports this feature for the RE.316*4 devices only. Fig. 11 Locus of the impedance of one phase after a phase-to-earth fault. The curve is overlaid with the zone settings of a distance protection relay. Page 10 ABB Switzerland Ltd, Utility Automation Systems

License handling The functions of PSM are license-protected. Every PSM installation requires a software key, which is bound to the PC hardware. In order to get the required license key, install all modules of PSM you are interested in. Start the module E_wineve or E_com and fill in the license request form. The form may be found under the menu "Options"; click "License...". After pressing OK your license request file will be generated. Send the file, named "PSMLicense.req", via e-mail to SA-LEC-Support@ch.abb.com and you'll get the software key, which enables the ordered functions. Alternatively you can send us the request file on a diskette. In case the e-mail and mail service do not work you can send the requested file via fax using a simple text editor such as Notepad for opening and printing. Please mention the order or project number in the e-mail or fax. Fig. 12 The method of getting the license key, which is required to enable the modules and functions of PSM Technical requirements PSM runs on the listed Windows operating system and has the following requirements on the PChardware. Table 2: Technical requirements to be able to use the stand-alone application Minimum requirements on the used hardware Intel Pentium III or equivalent recommended 256 MBytes RAM, 512 MBytes recommended 20 GBytes hard disk CD-ROM drive Keyboard, mouse Monitor resolution: 1024 by 768 pixels with 65535 colours. Operating system Microsoft Windows 2000 Professional with service pack 3 at minimum Microsoft Windows P. ABB Switzerland Ltd, Utility Automation Systems Page 11

Ordering Technical information requirements (cont d) can be ordered in different functional versions described in "Table 1: Key features of the stand-alone fault analysis tool dependent on the RelView, Professional and Expert versions". In addition the customer may choose between a single-user license and a multiuser license. A single-user license means that the software runs only on one PC. In case of a multi-user license the customer can install the software on ten different PCs. All manuals are available as *.pdf files on the installation CD. The manuals can be ordered as one complete folder containing the module manuals for E_database, E_wineve, E_com and E_navigate. Table 3: Ordering numbers for all variants of the stand-alone fault analysis and evaluation tool Description SW variant License type Ordering number Software installation CD all all 1MRB260035R0099 License key RelView Single-user 1MRB260035R0001 Professional Single-user 1MRB260035R0011 Professional Multi-user 1MRB260035R0012 Expert Single-user 1MRB260035R0021 Expert Multi-user 1MRB260035R0022 30-day trial license key Expert Single-user On request: SA-LEC-Support@ch.abb.com Table 4: Ordering information for printed manuals Printed documentation Language Ordering information Operating instructions English 1MRB520378-Uen Other relevant documents [1] Inform IT Power System Monitoring, brochure 1KHA-000829-SEN [2] Inform IT Power System Monitoring Central Server, Station Server PSM 500, PSM 501 [3] Inform IT Power System Monitoring Workplaces PSM 510, PSM 511, PSM 530, PSM 550 1MRB520355-Ben 1MRB520375-Ben [4] Substation Monitoring System SMS530 1MRB520268-Ben ABB Switzerland Ltd Utility Automation Systems Brown-Boveri-Strasse 6 CH-5400 Baden/Switzerland Tel. +41 58 585 77 44 Fax +41 58 585 55 77 E-mail: substation.automation@ch.abb.com www.abb.com/substationautomation Copyright 2003 ABB. All rights reserved Printed in Switzerland (0307-800-0)