AlphaNet IDH4 Series DOCSIS Status Monitor for XM2, XM2-HP, and XM2-300HP Series CableUPS. Installation and Quick Start Guide

Similar documents
AlphaNet DM3.0 Series DOCSIS Status Monitor

CableUPS Quick Start Guide

AlphaNet IDH4 for XM2 and XM2-300HP Series DOCSIS Status Monitor. Technical Manual. Effective: March 2015

AlphaNet DSM Series. External DOCSIS Transponder. Technical Manual Model XP-EDH-A. Model XP-EDHEffective: June Alpha Technologies

AlphaGateway SMG-01PE Quick Start Guide

XM360 X-Tractor Troubleshooting

Troubleshooting. Troubleshooting Overview CHAPTER

Installation Instructions

CM500 High Speed Cable Modem User Manual

USM2 Universal Status Monitor 2

AlphaNet DSM Series DOCSIS Status Monitor

GSM-X. Communication module. Quick installation guide. Full manual is available on Firmware version 1.02 gsm-x_sii_en 08/18

CMD-N Arris SG4000 Technical Manual Effective: March 2016

InnoMedia ESBC B. Quick Install Guide. 1

Cisco Cable Manager 1.0

Table of Contents. Introduction

Installation and Configuration Quick Guide R2000. Industrial Dual SIM Cellular VPN Router (2 Eth + 2 SIM) Package Contents

DVG-6008S FXO VoIP Router

CM500 High Speed Cable Modem User Manual

High Speed Cable Modem

High Speed Cable Modem

High Speed Cable Modem

HES-3109 SERIES 9 PORTS 10/100/1000BASE-T MANAGEMENT ETHERNET SWITCH

Royal RVV-500 (B) Retrofit Kit

Liebert MicroPOD 230V

Voice Cable Modem User Manual

Installing the Cisco Unified Videoconferencing 3545 MCU

INDEX. Analog Board Boot and Voltage Test 2 Testing Input Channels 3 Testing Output Channels 4

Cisco UBR-MC20X20V Cable Interface Line Card Quick Start Guide

User Manual. Per Port Monitoring Models

Revision History E F G H J K Revision Description: K > Allegion Rebranding.

High Speed Cable Modem

Energy Management System. Operation and Installation Manual

PT-7728/7828 Quick Installation Guide

Installation and Configuration Quick Guide. R3000 Lite. Industrial Dual SIM Cellular VPN Router (1 Eth + 1 RS RS USB Host)

Series 3700 Screw Terminal Assemblies Installation Instructions

Troubleshooting. Troubleshooting Overview CHAPTER

Industrial Serial Device Server

Connecting a Cisco Output Module

LCD Meter for Model 3051 Pressure Transmitters English Rev. AA

EA500. Installation Instructions Transponder

NexPump Ai Network\Notification Guide

InnoMedia Business VoIP ATA Models

(Cat. No P1) Installation Data

Quick Installation Guide

HYDROTHUNDER WIRING & CIRCUIT INFORMATION C H A P T E R F I V E

XM2-300HP. Technical Manual. XM2-300HP XM2-300CE-HP Effective: March member of The

Installation Guide. Avigilon ACM Embedded Controller

CMD-N GS7000 Technical Manual Effective: May 2016

Voice Cable Modem User Manual

CLIQ.mini Installation and Setup Guide

PS/IO Circuit Board Retrofit

Blue Box BLUE BOX TM LTD PARTS REPLACEMENT GUIDE

Installation Instructions

Cube YY-0420/0430 Technical Instruction

Unpack the package contents and verify that you have the following: Model PA301 Network Card Telephone cable (10 ft) Resource CD

Switched Rack Power Distribution Unit

Installation Note. Removable Hard Disk Drive Upgrade Kit. For All PNA Series RF Network Analyzers. Network Analyzer Model Number

Installation Instructions. Ecast Mojo B75B Motherboard Upgrade Kit Kit #

Keep all manuals as a product component during the life span of the product. Pass all manuals to future users / owners of the product.

NPort W2150A/W2250A Series Quick Installation Guide

Setting Up Your Cisco Unified Videoconferencing 3500 Gateway

AutoScan to MultiScan Replacement Kit

Section. Service & Maintenance. - Core & Hard Disk Drive (HDD) - Amplifier - Monitor - UPS - Dollar Bill Acceptor - Fan Filter G - 1

POWER AVAILABILITY 2U POD USER MANUAL. Power Output Distribution 230 Volt

POWER AVAILABILITY 2U POD USER MANUAL. Power Output Distribution 120 Volt

Part No. P May 4, Business Communications Manager. BCM Imaging Tool User Guide

Quick Start Guide. SEB-710 I/O Expansion board. Introduction

Home automation hub installation and setup guide

Longshine Technologie Europe GmbH

Conettix D6680. Installation Instructions. Ethernet Network Adapter

NA265A. External PCIe 3.0 to GPU Rackmount Enclosure. User Manual

Quick Start Installation Guide

Installation and Configuration Quick Guide R3000. Industrial Dual SIM Cellular VPN Router 2 Eth + 1 RS RS USB Host.

A TCP/IP network CAT 5 cable If the network is faster than 10baseT a switching hub will be needed Static IP address

Regulator Board Installation Instructions for WebPak 3000 Version 1.x Drives

FVT/FVR20D2I1C4E INSTALLATION AND OPERATION MANUAL

NPort S8000 Series Quick Installation Guide

Switched XPDU. 15A Model. User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved.

PoE/FPR Kit for Auto-Sync Time Clock. The Auto-Sync Time Clock is a validated time system with a Web interface and auto discovery.

Application. Contents of Package. Inspect the CyberSwitch upon receipt. The package should contain the following items:

SEI DC-UPS Power Management Package Users Manual

Installation and Configuration Guide

Installation and Configuration Quick Guide. R3000 Quad. Industrial Cellular VPN Router with 4 Ethernet Ports (4 Eth + 1 RS-232/1 RS USB Host)

Hardware Installation Guide Installation (x3350)

EATON Transformer Module

Installing the Cisco ADE 2130 and 2140 Series Appliance Hardware Options

Perle SMI Media Converter Installation Guide

1111 West 35th Street Chicago, IL Customer Support: (773) UPS SNMPWEBCARD

Nighthawk Multi-Gig Speed Cable Modem User Manual

GETTING STARTED WITH YOUR FIBER GUARDIAN

STM-1 Mux SONET/SDH Multiplexer User Manual

3. Install Graphics/PCIe Cards in NA255A 8

Installing and Removing SDRAM and DRAM

Vision OPLC V TR20/V350-J-TR20

Omega 4K/UHD Scaler for HDBaseT and HDMI with USB

EAP110-Outdoor. Installation Guide. 300Mbps Wireless N Outdoor Access Point

CAN YOUR PDU PIVOT? TRUE INNOVATION. ONLY FROM SERVER TECH. Available in Basic, Metered, and Smart PDU models.

PM Series Power Meter

Installation Instructions (KF-2000)

Transcription:

AlphaNet IDH4 Series DOCSIS Status Monitor for XM, XM-HP, and XM-00HP Series CableUPS Installation and Quick Start Guide The AlphaNet IDH4 Series Embedded DOCSIS Transponder allows monitoring of Alpha power supplies through existing cable network infrastructure. Advanced networking services provide quick reporting and access to critical powering information. The IDH4 Series utilizes Simple Network Management Protocol (SNMP) and standard Management Information Bases (MIBs) to provide network status monitoring and diagnostics. A Web interface enables authorized personnel direct access to advanced diagnostics using a common Web browser. No custom software or proprietary cables are required. The transponders can be installed and configured for operation in the XM, XM-HP, or XM-00HP Power Supply. IDH4X DOCSIS Transponder 1 4 5 7 1 1 14 15 1 17 Item LED or Connector Status Behavior Indication 1 ALM/RDY: Alarm and Ready REG: Upstream ranging and registration lock DS: Downstream RF Carrier detection and lock N/A No power or malfunctioning IDH4 Series RED 4 ACT: CPE Activity status 5 LNK: CPE Link status 7 RF Rx/Tx Power Level Indicator COM: AlphaBus communications TRI Steady Blinking Blinking more than Blinking more than Blue Green Red Reset of the IDH4 Series is in process Normal operation Minor Alarm Major Alarm No power, upstream frequency undetermined Power on, downstream locked, upstream frequency ranging, DHCP request in progress CMTS registration completed No power / downstream carrier Power on, downstream carrier frequency searching Downstream carrier lock No Ethernet communications activity Momentary flashes during CPE communications via the Ethernet craft port No Ethernet link Link on Ethernet Craft port No RF detected Rx/Tx Power at a warning level as set within the SCTE-HMS Property Table Rx/Tx RF Power level within tolerance Rx/Tx Power at an alert level as set within the SCTE-HMS Property Table No AlphaBus Communications Momentary flashes - AlphaBus Port communications active 8 9 10 11 18 8 BAT A/B 9 BAT A/B Connector 10 BAT C/D 11 BAT C/D Connector Battery string(s) connected correctly Battery string(s) not connected correctly Battery string(s) connected correctly Battery string(s) not connected correctly 1 RST: Reset buttton 1 ENV: Environmental Control connector 14 TPR: Tamper Switch connector 15 ETH: Ethernet connection 1 RF Connection 17 COM: AlphaBus Communications connector 18 RF, CPE MAC Address label Fig. 1, IDH4X Transponder Front Panel Indicators and Connectors 1

IDH4L DOCSIS Transponder 1 4 5 7 8 9 10 11 1 Item LED or Connector ALM/RDY: Alarm and Ready REG: Upstream ranging and registration lock DS: Downstream RF Carrier detection and lock. Status Behavior Indication N/A No power or malfunctioning transponder RED 4 ACT: CPE Activity status 5 LNK: CPE Link status RF Rx/Tx Power Level Indicator 7 RST: Reset buttton TRI 8 ENV: Environmental Control connector 9 TPR: Tamper Switch connector 10 ETH: Ethernet connection 11 RF Connection Steady Blinking Blinking more than Blinking more than Blue Green Red Transponder reset in process Normal operation Minor Alarm Major Alarm No power, upstream frequency undetermined Power on, downstream locked, upstream frequency ranging, DHCP request pending CMTS registration completed No power / downstream carrier Power on, downstream carrier frequency searching Downstream carrier lock No Ethernet communications activity Momentary flashes during CPE communications via the Ethernet Craft port No link Link on Ethernet Craft port No RF detected Rx/Tx Power at a warning level as set within the SCTE- HMS Property Table Rx/Tx RF Power level within tolerance Rx/Tx Power at an alert level as set within the SCTE-HMS Property Table Fig., IDH4L Transponder Front Panel Indicators and Connectors

Overview CAUTI! For units in service, backup battery power will not be available during this procedure. IDH4 Series installation and setup is comprised of three basic steps: 1. Configuring the Network: Provisioning the DHCP Server with the transponder s MAC Address and assigning it a DOCSIS Configuration File.. Setting Options: The IDH4 Series is designed for out-of-the-box, "plug and play" operation, but non-default settings such as SNMP trap destination addresses may be required for the Network Management System (NMS). SNMP trap addresses can be set automatically via the DOCSIS Configuration File per RFC 49, while IDH4 Series proprietary options may be set through type-11 TLV entries. The SCTE-HMS and Alpha MIBs may need to be compiled into a MIB browser before it can be used to monitor or set transponder and power supply parameters. Refer to the IDH4 for XM and XM-HP Technical Manual (Alpha p/n 74-57-B-001) for details.. Installation: Installation of the IDH4 Series into the power supply, connecting the RF Cable, battery sense wire harnesses (IDH4X only), Environmental, Tamper switch, Ethernet, and verifying operation. These steps can be performed independently of one another. However, configuring the network prior to field installation will allow the installation to be verified while personnel are still on-site. Performing field installation before network configuration and before the installation can be verified, might result in additional field service calls to correct mistakes. IDH4X Installation / Replacement Procedure in XM and XM-HP Power Supplies 1. Before removing the Inverter Module (IM), verify the power supply device address is correct. The power supply device address must not be set to zero and no two power supplies monitored by a single IDH4 Series can have the same address. Power supplies must have 1,,, 4 or 5 as an address. To verify the power supply s address, go to the LCD display on the inverter module and enter the "Setup" menu. Scroll to the "Device Address" menu item and verify the device address is set to something other than 0 (Zero).. Switch the power supply s battery breaker. With the battery breaker in the position, the power supply will not go into inverter mode.. Unplug all Inverter Module connections (e.g. battery cable, remote temperature sensor). 4. Loosen the Inverter Module thumbscrews and slide the inverter module out just enough to disconnect the ribbon cable. Disconnect the ribbon cable. 5. Slide the Inverter Module out of the power supply.

IDH4X Installation / Replacement Procedure in XM and XM-HP Power Supplies, continued. If the Inverter Module is equipped with a communication module, remove it by loosening the two Phillips captive screws. 7. Plug the supplied 18-pin jumper into the header on the back of the IDH4 Series circuit board. Disconnect here Captive Screws Fig., Inverter Module Ribbon Cable Fig. 4, Captive Screw Locations To prevent damage to the IDH4X, do not reuse the existing 18-pin connector. Instead, use the jumper supplied with the transponder. Fig. 5, Installing 18-pin Jumper (Alpha p/n 540-8-19) Fig., Connecting the Transponder to the Inverter Module 8. Line up the 18-pin jumper with the header on the Inverter Module and connect the unit to the Inverter Module. 9. Fasten the IDH4 Series to the Inverter Module by tightening the two captive screws. It is recommended that the screws be tightened alternately, a few turns at a time so the transponder aligns in parallel to the Inverter Module. 10. Reinstall the Inverter Module and reconnect the ribbon cable. Make front panel connections (tamper, temperature sensor, battery sense, RF etc.). 11. If not yet done, record the cable modem MAC address from the front of the unit and report it to the network manager for network provisioning. For Dual IP applications, the CPE MAC address should also be recorded. 4

IDH4L Installation / Replacement Procedure in XM-00HP Power Supplies 1. Before removing the Inverter Module (IM), verify the power supply device address is correct. The power supply device address must not be set to zero and no two power supplies monitored by a single IDH4 Series can have the same address. Power supplies must have 1,,, 4 or 5 as an address. To verify the power supply s address, go to the LCD display on the inverter module and enter the "Setup" menu. Scroll to the "Device Address" menu item and verify the device address is set to something other than 0 (Zero).. Switch the power supply s battery breaker. With the battery breaker in the position, the power supply will not go into inverter mode.. Unplug all Inverter Module connections (e.g. battery cable, remote temperature sensor). Inverter Module Thumbscrews Power Supply Battery Breaker Fig. 7, Removing the Inverter Module from the Power Supply 4. Loosen the Inverter Module thumbscrews. 5. Slide the Inverter Module out of the power supply.. Loosen the two Phillips captive screws to remove the IDH4L sheet metal from the Inverter Module. Captive Screw Captive Screw Fig. 8, Removing the IDH4L Sheet Metal from the Inverter Module 5

IDH4L Installation / Replacement Procedure in XM-00HP Power Supplies, continued 7. Plug the supplied 18-pin jumper into the header on the Inverter Module. To prevent damage to the IDH4L, do not reuse the existing 18-pin connector. Instead, use the jumper supplied with the transponder. Fig. 9, Installing 18-pin Jumper (Alpha p/n 540-581-19) 8. Attach the IDH4L to the sheet metal with the supplied - screws. 9. Line up the 18-pin jumper with the header on the Inverter Module and connect the unit to the inverter module. Fig. 10, IDH4L Attached to Sheet Metal Fig. 11, IDH4L Inverter Module Connection 10. Fasten the IDH4L to the Inverter Module by tightening the two captive screws. It is recommended that the screws be tightened alternately, a few turns at a time so the transponder aligns in parallel to the Inverter Module. 11. Reinstall the Inverter Module and make front panel connections (tamper, temperature sensor, battery, RF, etc.). 1. If not yet done, record the cable modem MAC address from the front of the unit and report it to the network manager for network provisioning. For Dual IP applications, the CPE MAC address should also be recorded.

Connecting the RF Drop CAUTI! Install a grounded surge suppressor (Alpha P/N 1-08-10 or equivalent). Connect the RF drop according to the diagram below. The RF drop must have a properly installed ground block in the power supply enclosure. Recommended downstream RF level is 0 dbmv. Connect any other front panel connections at this time (e.g. battery strings, tamper switch). Grounded Surge Protector (See Caution Above) RF Cable to Headend Fig. 1, Connecting the RF Drop ECM to SCM Interface (Alpha P/N 704-709-0) Linked CableUPS Serial Interface Cards IDH4X in Primary XM AlphaBus Cable (Alpha P/N 875-190-0 for ', -1 for 9', - for 18', - for 5') A S Y S C O M A B S Y S C O M B Environmental connection Ethernet connection RF connection Generator (ECM) A C Battery Sense Wire Harness A B C Comm Port System Port Battery Sense Connections Connections Connections with more than one power supply Fig. 14, System Interconnection Diagram Each power supply must have a unique address. Refer to Intelligent CableUPS technical manual (Alpha p/n 017-805-B0), or the IDH4 Series Transponder Technical Manual (Alpha p/n 74-57-B) for additional information. 7

Total Power Solutions Initial Startup and Test / Returning the Unit to Service 1. Plug the power supply into the AC outlet.. Switch battery breaker.. The IDH4 Status LEDs will all blink in unison upon initial power up. The RDY LED will then begin blinking steadily indicating normal processor activity. 4. Verify the DS and REG LEDs are on solid. This verifies the Communications Module has registered an IP address on the network. 5. Verify the RF LED is solid Green, indicating Upstream and Downstream Power is within the default specified range and the Upstream RF Power is below the recommended +50 dbmv.. Verify no XM / XM-HP / XM-00HP alarms are active. RF Power Default Values LED Color Rx Range (dbmv) Tx Range (dbmv) Green +10 to -10 0 to +50 Blue +15 to +10 and -10 to -15 +50 to +55 Red >+15 and <-15 >+55 Test Connection Table 1, RF Power Default Values With the IDH4 Series Transponder used in conjunction with the XM-HP power supply, network connectivity can be verified via the smart display. For other power supply models, verify the network status via the Ethernet port. Connect a computer s network port to the transponder s Ethernet port using a standard network cable. Launch an Internet browser and enter 19.18.100.1 into the Address. The transponder will return the Web page shown below. The General Configuration page shown below will appear and display connectivity, power levels, and power supply status information such as alarms, output voltage, output current, and individual battery voltages. System Name, System Location, System Contact and Common Logical ID may be edited on this page; when prompted for a User Name and Password, use "Alpha" and "AlphaGet". Alpha Technologies Inc. 77 Alpha Way Bellingham WA 98 USA Tel: +1 0 47 0 Fax: +1 0 71 49 Alpha Technologies Ltd. 7700 Riverfront Gate Burnaby BC V5J 5M4 Canada Tel: +1 04 4 5900 Fax: +1 04 4 1 Alpha Technologies Europe Ltd. Twyford House, Thorley Bishop s Stortford, Hertfordshire CM 7PA United Kingdom Tel: +44 179 501110 Fax: +44 179 59870 Fig. 15, Initial Web Page (data values shown for illustration purposes only) Alpha Technologies GmbH Hansastrasse 8 D 911 Schwabach Germany Tel: +49 91 79889 0 Fax: +49 91 79889 1 AlphaTec Ltd. 9 Saint Andrews Street Suite 101 Andrea Chambers 07 Limassol Cyprus Tel: +57 5 7575 Fax: +57 5 59595 AlphaTEK ooo Khokhlovskiy Pereulok 1 Stroenie 1 Office 40 10908 Moscow Russia Tel: +7 495 91 1854 Fax: +7 495 91 149 Alpha Technologies Suite 190, Tower 1 Canton Road, Kowloon Hong Kong, China Tel: +85 7 8 Fax: +85 199 7988 Alpha Technologies Alpha reserves the right to change specifications without notice. 014 Alpha Technologies Inc. All Rights Reserved. member of The Group TM Alpha is a registered trademark of Alpha Technologies. For more information visit www.alpha.com