R & D SPECIALTIES SERIES 100 RO CONTROLLER USERS MANUAL. 2004, by R & D Specialties, Inc. All Rights Reserved.

Similar documents
ROC-4. icontrols. Reverse Osmosis System Controller Documentation

PSA200 User s Manual

ICM 400. Three Phase Voltage Monitor with Reset Switch. Low cost line voltage protection for 3-phase motor systems

User Guide. Control Box. RoscoLED TM.

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

MPP1700 User s Manual

Tornado F-5. Motor Backspin Detect Relay And Probe For F-5 Motor Controller

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

AirPro Surveyor 2 Manual

MICROtrac MICROPROCESSOR BASED WATER TREATMENT CONTROLLER. Installation and Operation Manual

User s Guide. OM-CP-PRHTEMP2000 Pressure, Humidity and Temperature Data Logger with LCD

CO2 Controller Operating Instructions Models: RAD-0501, RAD-0501A, RAD-0501E 1. Product Description

Digital Lighting Systems, Inc. PD216. Two Channel Dimmer and Switch Packs PROTOCOL USER'S MANUAL. PD216-UM Rev. E - 02/03

Manual. NanoTron Dual Timer. Installation Maintenance Repair Manual

700 SERIES DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL

HVPS-C. High Voltage Power Supply. HVPS-C. Package Contents: Sold Separately. Table of Contents:

FA-2448 SIX POSITION Filter Wheel

PMDX-105. I/O Option Riser Board User s Manual. Document Revision: 1.1 Date: 7 September 2004 PCB Revision: PCB-443A

INSTRUCTION MANUAL. ph/mv CONTROLLER/RECORDER

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

Digital Lighting Systems, Inc.

AGRI-COVERTM REMOTE CONTROL INSTRUCTIONS

Manual. Water Vend Controller Model ESDI WARNING! ELECTRICAL SHOCK HAZARD! AUTHORIZED PERSONNEL ONLY. EXPOSED 120 VAC ON CIRCUIT BOARD

MAXIMA+ Series Rotary Level Indicator

STATUS Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free

87421/22A Power Supply. Operating and Service Manual

Seven Channel Remote Control

Woolich Racing. USB ECU Interface User Guide

ACLD Channel Opto-isolated Digital Input Board

MAXIMA + Series ROTARY LEVEL CONTROL

MYRIAD LC1 LEVEL CONTROLLER INSTRUCTION MANUAL

Instruction Manual. M Pump Motor Controller. For file reference, please record the following data:

MAXIMA + Series ROTARY LEVEL CONTROL

FX-2 Control Board ASY-360-XXX Setup and Configuration Guide

Eco Sensors OZONE CONTROLLER Model OS-6 Instructions for Use. General and New Features

Model CD-AW. Infrared Environmental CO2 Sensor. Operator's manual

ES-600 Ozone Controller Operation Manual

AUTOMATION. Operator s Manual. PG5 Digital Pressure Gauge

MICRO GROW GREENHOUSE SYSTEMS, INC

MPP200 User s Manual

Xxxxx Xxxxxx Bridge / Strain Gauge Data Logger

Remote Relay Controller LC40, LC41 and LC42 Series Owner s Manual

INSTRUCTION MANUAL IM253 R0. AquaStart COMBINATION SOFT STARTERS START-UP MANUAL

Zonit μats TM Users Guide μats1-lv Version 1.2

PCM-7140 Pulsed Current Source Operation Manual

BrewTroller Phoenix. Owners Manual. Updated - March 14, 2016 BREWTROLLER PHOENIX 1

Xxxxx Xxxxxx DC Voltage Data Logger

Quad-Relay Delay Switch (QRDS) User Manual (v1.0)

Eco Sensors OZONE CONTROLLER Model OS-6 Instructions for Use. General and New Features

I/O Expansion Box Installation & Operator s Instruction Manual

USER S MANUAL ENTITY. Energy Meter TRINITY. Entity Operational Manual

EverPump Wireless Pump control system

TD 600 Thermo-Fastprinter

Suretrol Manufacturing Inc. MA052X-2. Kiln Controller User's Manual

PIM-Mini Pulsed Current Source Operation Manual

700 SERIES TPC TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

OZONE SWITCH Model OS-6. OS-6 Features

Xxxxx Xxxxxx OM-CP-QUADVOLT. OM-CP-OCTVOLT 8-Channel Low Level DC Voltage Data Logger. 4-Channel Low Level DC Voltage Data Logger INSTRUCTION SHEET

G2M Control Board Installation and Operations Manual

212iL Rev. 1.1

700 SERIES FLOAT OPERATED DUPLEX/TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

AirTest Model CN9000 Series Sensor Controller

Digital Lighting Systems, Inc.

Carefree-Security. Installation and programming instructions 1050A. Owner s Manual

B2800 FLOW MONITOR. - For Liquid Meters - PROGRAMMING & INSTALLATION MANUAL Simplified Version

EMS. Electrical Management System. Progressive Industries Incorporated Morrisville, North Carolina

AC4G-D User s Manual

Mold Control Systems, Inc.

Digital Lighting Systems, Inc. PD405-DMX. Four Channel Dimmer and Switch Packs. DMX512 compatible. PD405-DMX-24DC DMX512 4 x 5 Amps Dimmer Pack

ANT CNTR DC ALRM LNB RX DC ALRM +18V OFF

PD10. Pulse Divider Instructions PROUDLY MADE IN THE USA

Pump-Down Controller MODEL mA Input Scalable 4-20mA Output Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters

Digital Lighting Systems, Inc. CD400-DMX DMX512 Four Channel Dimmer and Switch module

AUTOMATION. Operator s Manual PG-5. Full Access. DOC Rev. A1 3/10

PDC-X Digital Controller

EASON TECHNOLOGY. IO8 & IO24 Break-Out Module

GARNET. SEELEVEL II TM Tank Monitor INSTRUMENTS LTD. Model 709 Owner s Manual IMPORTANT OPERATOR INFORMATION DATE INSTALLED: SERIAL NUMBER:

Installation Instructions

OPERATING AND SERVICE MANUAL. Universal Interface Device 47

INSTALLATION INSTRUCTIONS

User's Manual Sound Level Alert Model SL130

RE-82 RACK MOUNT DIMMER OWNERS MANUAL. 8 X 2400Watts. Revision /29/2007

Series RMA Hot Runner Controller Setup and Operation Manual

USER MANUAL CCHP-6000-XX 6kJ/s Capacitor Charging Power Supply

BTU-4D/BTU-4D-I Digital Temperature Unit & Sensors. Installation and Operation Manual

TM0-1 AMPLIFIER / CONDITIONER MODULE OPERATORS MANUAL. Transducer Techniques R

Installation and Operation Guide

Installation and Operation Guide for PD5200 and PD5300 Automatic Transfer Switch

I/O SIGNAL CONDITIONER

Hybrid AC Driver [GCNC-1110]

PMDX-108-Output. 8-Channel Isolated Output Board for PC parallel port pins 2-9. User s Manual

SD1306. Speed Dome IP Camera. Quick User Guide

MONITOR Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free

MICRO GROW GREENHOUSE SYSTEMS, INC ZEVO DR., SUITE B-1, TEMECULA, CA PHONE (951) FAX

MicroVision Timer MICROPROCESSOR TIMER CONTROLLER. Installation Operation Manual Rev.F Page 1 of 30

Secured Series: Hub Plus Kit Single Door Controller Package Installation Manual

Global Water Instrumentation, Inc.

QuickTouch (QT4) Owner s Manual

DCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies

FNet Repeater Installation & Operator s Instruction Manual

Transcription:

R & D SPECIALTIES 2004, by R & D Specialties, Inc. All Rights Reserved. No part of this document may be copied or reproduced in any form or by any means without the prior written permission of R & D Specialties. R & D Specialties makes no warranties with respect to this documentation. Information in this document is subject to change without notice. R & D Specialties shall not be held liable for technical or editorial errors or omissions that may appear in this document; nor for incidental or consequential damages resulting from the furnishing, performance, or use of this document. R & D SPECIALTIES SERIES 100 RO CONTROLLER Document: Series 100 Released: June 2012 R & D Specialties 9918 W. I-20 Midland, Texas USA 79706 432 561-5707 Fax 432 561-5696 www.rdspec.com E-mail rdspec@rdspec.com USERS MANUAL i

LIMITED WARRANTY R & D Specialties warrants to the original purchaser that the products it manufactures will be free from defects in material and workmanship for a period of twelve months from the date of shipment on parts and ninety days on labor. Some non R & D Specialties manufactured resale items may have warranty periods less than twelve months. R & D Specialties obligation under this warranty is limited exclusively to the repair or replacement of any product that R & D Specialties finds to be defective. Items returned for warranty consideration must have a return authorization number and be properly packaged, shipped prepaid and insured. This warranty is valid only when the products are properly installed, maintained and used for the purpose for which they were designed. Misuse, neglect, damage, accident, improper repair, or modification not authorized in writing by R & D Specialties will void this warranty. There are no warranties, expressed or implied, including the implied warranties for merchantability or fitness for a particular purpose that extend beyond the limited warranty expressly stated above. R & D Specialties liability to any purchaser of its products, whether in contract or in tort, and whether arising out of warranties, representations, instructions, installations, or defects from any cause, will be limited exclusively to repairing or replacing the product or any part thereof under the conditions set out above. TABLE OF CONTENTS INTRODUCTION 1 SPECIFICATIONS 1 FRONT PANEL CONTROLS AND INDICATORS 2 INSTALLATION 3 Physical Installation 3 Terminal Strip, Jumper and Adjustment Locations 3 Power Wiring 3 Pump and Valve Relay Outputs 3 RO Pump Wiring 3 Inlet and Flush Valve Wiring 3 TDS Cell Installation and Wiring 4 Switch Inputs 4 Pressure Fault Switch 4 Pretreat Switch 4 Tank Full Switch 4 SYSTEM OPERATION 6 General Operation 6 Display and Status Indicators 6 RO Start Delay 7 Pressure Fault 7 PF Auto Reset/PF Retry 7 Tank Full 7 Pretreat Lockout 8 Membrane Flush 8 Water Quality Display 8 Water Quality Setpoint 9 Calibration 9 TROUBLESHOOTING 10 System Inoperative 10 Inlet Valve Will Not Operate 10 ii iii

RO Pump Will Not Operate 10 No Flush or Not Flushing Correctly 10 No or Incorrect TDS Reading 10 FIGURES AND TABLES Figure 1 - Front Panel Controls and Indicators 2 Figure 2 - Terminal Strip, Jumper Locations 5 INTRODUCTION The R & D Specialties Series 100 controller is a state of the art control system for commercial and industrial reverse osmosis systems. The Series 100 combines features that have not previously been available in one compact unit. The Series 100 is a microprocessor controlled system that can monitor pressure and level switches. A TDS monitor/controller with adjustable limit is an integral part of the Series 100. The Series 100 displays system status and sensor and switch input status using a status LED and a 3 digit LED display. SPECIFICATIONS Power: 120/240 VAC -15+10%, 50/60Hz, 6Watts Environment: -22 F to 140 F, 0-95% RH, noncondensing Enclosure: 7.6" X 4.6" X 2.4" (193mm X 117mm X 61mm) Table 1 - Display and Status Indicators 6 Table 2 - Flush Jumpers 8 Display: 3 digit red LED Front Panel: Overlay with LED window, status LED, water quality LED, power and setpoint switches Switch Inputs, Dry Contact: Pressure fault Pretreat lockout Tank full Relay Outputs: RO pump relay 120/240VAC, 1HP Inlet valve relay 120/240VAC, 5A Flush valve relay 120/240VAC, 5A Relays supply same output voltage as board power(120 or 240 VAC) 20A maximum total load for all outputs. * Based on a service factor of 1.0 Cell: TDS cell with 3 digit display, range: 0-1000PPM. Wetted parts ABS and 316SS, 3/4" NPT, 300 PSI max. iv 1

FRONT PANEL CONTROLS AND INDICATORS INSTALLATION LED DISPLAY STATUS LED WATER QUALITY LED POWER KEY SETPOINT KEY SP CAL Figure 1 - Shows status of system and water quality. - Shows operating status of unit. - Green if OK, Red if above limit. - Places controller in operating or standby mode. - Places display in mode to display current setpoint - Setpoint adjustment screw. - Calibration adjustment screw. 2 Physical Installation Mount the Series 100 in a convenient location on the RO equipment using the integral mounting flanges. Terminal Strip and Jumper Locations Refer to figure 2 for the location of all terminal strips, connectors and jumpers. Figure 2 also shows a sample wiring diagram for the controller. NOTE: All terminals on the board are labeled. Power Wiring CAUTION: Before applying power to the unit, verify that the voltage jumpers are configured correctly for the voltage that will power the unit. The voltage jumpers are located below the transformer. For 120VAC operation, there should be a wire jumper installed between J1 and J3 and a second wire jumper installed between J2 and J4. For 240VAC operation, a single wire jumper should be installed between J3 and J4. AC power for the unit is connected to terminal strip P1. Connect the ground wire of the AC power to P1-1(GND). For AC power with a neutral and hot wire, the hot wire connects to P1-2(L1) and the neutral wire connects to P1-3(L2). For AC power with 2 hot wires, either wire can connect to L1 and L2. Pump and Valve Relay Outputs The Series 100 supplies relay outputs to control the RO pump and solenoid valves. NOTE: The relays output the same voltage as the AC power to the board. If the pump and solenoids operate on different voltages, a contactor will need to be supplied to operate the pump. RO Pump Wiring The RO pump connects to P1-4( L1) and P1-5(L2) RO pump terminals. This output can operate 120/240VAC motors up to 1HP directly. For motors larger than 1HP or for 3 phase motors, this output can be used to operate a contactor. Inlet and Flush Valve Wiring The inlet and flush valves must operate at the same voltage as supplied to the board. These outputs can supply 5A maximum and are not designed to operate pump motors directly. If these outputs are to be used to operate a boost or flush pump, the output should be used to operate a contactor. The inlet valve connects to P1-6(L1) and P1-7(L2) inlet terminals. The flush valve connects to P1-8(L1) and P1-9(L2) flush terminals. 3

TDS Cell Installation and Wiring For accurate TDS readings, the cell should be installed in a tee fitting where a continuous flow of water passes over the cell and no air can be trapped around the cell. The cell is connected with 5 wires to terminal strip P3. Connect each colored wire to the terminal labeled with the same color. Switch Inputs Switch inputs are connected to P2. The connections for these inputs are not polarity sensitive and can be connected to either terminal. The switch inputs should be dry contact closures only. CAUTION: Applying voltage to these terminals will damage the controller. The switches can be either normally open or normally closed, but all switches must be the same. If the controller is set for normally open switches, all switches must be open for the unit to run. If the controller is set for normally closed switches, all switches must be closed for the unit to run. NOTE: J10 selects normally open or normally closed operation. When J10 is in the A position, the unit is configured for normally open switches. When J10 is in the B position, the unit is configured for normally closed switches. Pressure Fault Switch On systems where a low feed pressure shut down is required, a feed pressure switch can be connected to the pressure fault input of P2. If a high pump pressure shut down is required, a high pressure switch can be connected to this input. If both low feed pressure and high pump pressure shut down are required, both switches can be connected to this input. Both switches must be either normally open or normally closed to operate properly. Pretreat Switch In systems with pretreatment, a pretreat lockout switch can be connected to the pretreat input of P2. This switch should operate when the pretreatment device is out of service. NOTE: The output from the pretreatment device must be a dry contact and must not supply voltage. Tank Full Switch Connecting a tank full switch to the tank full input of P2 can cause the unit to shut down for a tank full condition. J9 selects a short or long tank full restart. Figure 2 4 5

SYSTEM OPERATION General Operation The unit has 2 modes of operation, a standby mode and an operating mode. In the standby mode, the unit is effectively off. All outputs are turned off and the display shows OFF. In the operating mode, the unit operates automatically. All inputs are monitored and the outputs are controlled accordingly. Pressing the Power key will toggle the unit from standby to operate or from operate to standby. If power is removed from the unit, when power is reapplied, the unit will restart in the mode it was in when power was removed. Display and Status Indicators The display is a 3 digit display. System operating status, the TDS reading and the TDS setpoint are shown on this display. A red/green LED indicates the system status in conjunction with the display. Refer to Table 1 for the description of the operation of the display and LED. CONDITION DISPLAY STATUS LED RO OFF OFF RO START DELAY - - - RO OPERATING TANK FULL FUL STEADY GREEN TANK FULL RESTART FUL SLOW FLASH GREEN PRETREAT LOCKOUT FLUSH PL FLS PRESSURE FAULT PF FLASHING RED PF AUTO RESET PF PF AUTO RETRY PF STEADY RED Table 1 6 RO Start Delay When the controller is placed in the operating mode or restarts from a shut down condition, the inlet valve will open and a 5 second time delay will start. During the delay, - - - will show on the water quality display. After this delay, the RO pump will start. The water quality display will now show the current water quality. The status lamp will show steady green. Pressure Fault If the pressure fault input is active for 2 seconds, a pressure fault condition will occur. This will cause the controller to shut down. PF will show on the water quality display and the status lamp will flash red. To clear the pressure fault, press the power key twice. PF Auto Reset/PF Retry With J8 in the A position, the power must be cycled using the Power key to clear a pressure fault shut down. A PF auto reset function is enabled by placing J8 in the B position. When a pressure fault occurs with the PF auto reset enabled, the controller will automatically reset after a 60 minute delay and the controller will start. If the pressure fault has cleared, the controller will continue to run. If the pressure fault condition is still active, the controller will again shut down for the pressure fault condition and the auto reset cycle will repeat. During the auto reset delay, the water quality display will show PF and the status lamp will be off. A PF retry function is enabled by placing J8 in the C position. When a pressure fault occurs with the PF retry enabled, the controller will shut down for 30 seconds and then attempt to restart. If the pressure fault is still active, the controller will shut down for 5 minutes and then attempt to restart. If the pressure fault is still active, the controller will shut down for 30 minutes and attempt to restart. If the pressure fault is still active, the controller will lockout for the pressure fault. During the retry delays, the water quality display will show PF and the status lamp will be a steady red. If during one of the retries, the controller is able to start and run continuously for 10 seconds, the retry function is reset. If a pressure fault occurs, the PF retry cycle will repeat from the beginning. When J8 is in the D position, both the PF auto reset AND the PF retry functions are enabled. If a pressure fault condition occurs, the PF retry function will operate as described above. If the retry function locks out, the PF auto reset function will operate as described above. The PF retry and PF auto reset functions will continue in a 30 second, 5 minute, 30 minute and 60 minute cycle until the pressure fault condition clears. Tank Full If the tank full input is active for 5 seconds, the controller will shut down for a tank full condition. The water quality display will show FUL. When the tank full condition clears, the unit will restart after the selected restart delay. The delay is selected with J9. With J9 in the A position, the restart delay is 2 seconds. With J9 in the B position, the restart delay is 15 minutes. Position A is normally used with tank level switches that have a large span. During the restart time, the status lamp will flash green. 7

Pretreat Lockout If the pretreat lockout input is active for 2 seconds, the controller will shut down for a pretreat lockout condition. The water quality display will show PL. When the pretreat lockout condition clears, the unit will restart. Membrane Flush A flush function can be enabled using J11 and J12. When a flush is initiated, the flush valve will operate and the flush will last 5 minutes. The flush can occur when a tank full condition occurs or every 24 hours, depending on the jumper settings. The inlet valve can be open or closed and the RO pump can be on or off, depending on the jumper settings. Refer to Table 2 for the jumper settings. Water Quality Setpoint The water quality setpoint can be adjusted from 0-999. If set to 999, the water quality lamp will always remain green. To set the water quality setpoint, press the Setpoint key. The display will alternate between the setpoint and SP. Use a small screwdriver to adjust the SP adjustment to the desired setpoint value. Press the Setpoint key to return the display to the water quality display. Calibration To adjust the calibration of the water quality, measure the water with a meter calibrated to a known standard. Using a small screwdriver, adjust the CAL adjustment to get the correct reading on the display. J11 J12 FLUSH TYPE INLET RO PUMP A A NONE A B TANK FULL OPEN ON A C TANK FULL CLOSED ON B A TANK FULL OPEN OFF B B TANK FULL CLOSED OFF B C 24 HOUR OPEN ON C A 24 HOUR CLOSED ON C B 24 HOUR OPEN OFF C C 24 HOUR CLOSED OFF Table 2 Water Quality Display The water quality display shows the current water quality when the controller is operating normally and status messages when the controller is shut down. The water quality display is 0-999PPM. If the water quality is above 999, the display will show ^ ^ ^. If the water quality is below the setpoint, the water quality lamp will be green. If the water quality is above the setpoint, the water quality lamp will be red. 8 9

Troubleshooting CAUTION: Hazardous voltages are present when power is applied to the controller. Pressing the Power key DOES NOT remove these voltages. The power must be disconnected from the power source. When connecting or disconnecting any wiring to the unit, be sure the power is turned off at the disconnect or breaker. Refer to figure 2 for the location of components. NOTE: If fuse F1 is blown, none of the outputs will operate. If fuse F2 is blown, the controller will be inoperative. System Inoperative Is the water quality display lit? If no, check fuse F2 located below the transformer. If the fuse is OK, use a voltmeter to verify that power is applied to power terminals L1 and L2. If power is applied to the power terminals and the above checks are OK, the board may be defective and should be replaced. If no power is applied to the board, check the power wiring to the controller. Inlet Valve Will Not Operate Is the controller off? If no, are any shut down conditions active? If no, is the inlet LED, I2 lit? If no, replace the board. If yes, check fuse F1. If bad, replace the fuse. If it is OK, check the inlet terminals for power. Is there power? If no, replace the board. If yes, check the valve and valve wiring. RO Pump Will Not Operate Is the controller off? If no, are any shut down conditions active? If no, is the RO LED, I1 lit? If no, replace the board. If yes, check fuse F1. If bad, replace the fuse. If it is OK, check the RO pump terminals for power. Is there power? If no, replace the board. If yes, check the pump motor and motor wiring. No Flush or Not Flushing Correctly Verify that the flush jumpers, J11 and J12 are set correctly. No or Incorrect TDS Reading Is the sensor wired correctly? If no, correct wiring. Is the sensor installed as described in the installation section? If no, install correctly. Is unit calibrated correctly? If no, recalibrate. Disconnect green and white wires of sensor from P3. Does reading show 0? If no, replace board. If yes, reconnect wires and remove sensor from piping and dry. Does reading show 0? If no, replace sensor. If yes, short pins of sensor. Does reading show ^ ^ ^? If no, replace board. 10