Adding a token to a user Select add token and user if prompted by keypad select reader Menu 120 Select door/s that the user will have access to (if applicable) Menu 145 Select areas that the user will belong to Menu 141 Adding a keyfob Enable the receiver - Select option 4 bosch serial receiver Menu 350 Select add keyfob and select user, then enter 9 digit code Menu 130 Select areas that the user will belong to Menu 141 Adding a Fingerprint Select add a fingerprint Menu 180 Select door/s that the user will access to(if applicable) Menu 145 Select area's that the user will belong to Menu 141 Setting up a door for access only Assign user to a door/s Menu 145 Untick reader area control Menu 614 Assign reader/keypad to a door assignment Menu 617 Set output to required function (e.g. 60 Door) Menu 411 Select event assignment (door Name) Menu 412 Select output polarity (e.g. Open one shot low = 4) Menu 413 Set time parameter for the output (e.g. 10sec) Menu 414 Set any options required for the output Menu 415
Setting up a door & User with arm, disarm & badging required Assign user to a door/s Menu 145 Select reader & enable all on & disarming allowed. Menu 612 Select reader and enable reader badging (& egress if required) Menu 614 Select reader and enable reader area control Menu 614 Assign reader/keypad to a door assignment Menu 617 Set output to event type 60 Door Menu 411 Select event assignment (door Name) Menu 412 Select output polarity (e.g. Open one shot low = 4) Menu 413 Set time parameter for the output (e.g. 10sec) Menu 414 Set any options required for the output Menu 415 Setting up a door with D.O.T.L triggering an output Select options for reader/keypad (e.g.; arm/disarm/part) Menu 612 If required Select reader badging & reader area control Menu 614 Assign reader/keypad to a door assignment Menu 617 Set output to required function (e.g. 60 Door) Menu 411 Select event assignment (door Name) Menu 412 Select output polarity (e.g. Open one shot low = 4) Menu 413 Set time parameter for the output (e.g. 10sec) Menu 414 Set any options required for the output Menu 415 Select a zone for D.O.T.L function in pulse count ( 13 ) Menu 313 Set D.O.T.L time frame in pulse count time Menu 314 Select the door the the D.O.T.L will work with Menu 315 Set report route in Menu 316 Set alarm condition if required for door forced Menu 423 Select output type 61 D.O.T.L alarm Menu 411 Select the door the D.O.T.L is operating on Menu 412 Set output polarity for the output. Menu 413 Set time parameter for the output Menu 414 Select output options for the output Menu 415
Access control with time zones Assign user to a door/s Menu 145 Assign user to a time zone (e.g. time zone 2) Menu 144 Assign reader/keypad to a door assignment Menu 617 Select options for reader/keypad (e.g.; arm/disarm/part) Menu 612 If required Select reader badging Menu 614 Set output to required function (e.g. 60 Door) Menu 411 Select event assignment (door Name) Menu 412 Select output polarity (e.g. Open one shot low = 4) Menu 413 Set time parameter for the output (e.g. 10sec) Menu 414 Set any options required for the output Menu 415 Select door options in Menu 423 Select name for time zone Menu 750 Set time frame that the user will have access (e.g. 9am-5pm) Menu 751 Set the days that the time zone will be active Menu 752 Access control with door auto open/close Assign user to a door/s Menu 145 Assign reader/keypad to a door assignment Menu 617 Select options for reader/keypad (e.g. arm/disarm/part) Menu 612 If required Select reader badging Menu 614 Set output to required function (e.g. 60 Door) Menu 411 Select event assignment (door Name) Menu 412 Select output polarity (e.g. Open one shot low = 4) Menu 413 Set time parameter for the output (e.g. 10sec) Menu 414 Set any options required for the output Menu 415 Select unlock time zone for door (e.g. time zone 2) Menu 422 Select door options in Menu 423 Select name for time zone 2 Menu 750 Set the unlock time period for the door Menu 751 Set the days that the time zone will be active Menu 752
Using outputs with time zones Select desired output & select event type 58 time zone Menu 411 Select output event assignment (e.g. time zone 2) Menu 412 Select output polarity Menu 413 Select output time parameter Menu 414 Select time zone and set time frame for that time zone Menu 751 Select the days of the week that the time zone will operate Menu 752 Operating a door with a single digit code Set user pin length to 0 ( 0 = variable ) Menu 150 Set user 10 pin code to 5 Menu 112 Set user 10 Area assignment to no area Menu 141 Set output 5 to event type 56-follow pin Menu 411 Set output 5 to 10 in event assignment-( 10 =this user ) Menu 412 Set output 5 to 4 = ( normally open one shot low ) Menu 413 Set output 5 to 000 000 005 000 ( 5 seconds ) Menu 414 Enable output 5 to display status message Menu 415 To open door press 5 and ok. Setting up an Request to exit zone. Select zone and set to Display only ( 14 ) Menu 311 Select an area for the zone Menu 312 Select the door that the zone belongs to. Menu 315
Communications setup Tx 1 used for the e.g. Contact ID Select Tx 1 and set to contact id (default is C.I.D) Menu 540 Enter account number per area Menu 220 Enter base station numbers Menu 511 Test report period Menu 592 Test report route Menu 594 Open/close route Menu 222 Report route(per zone) Menu 316 Status route (system events E.g. low battery, ac fail) Menu 543 Emergency route (keypad fire, panic, medical) Menu 544 Contact ID using GSM Select Tx 1 and set to GSM contact id (default is C.I.D) Menu 540 Enter Account number per area Menu 220 Enter base station numbers Menu 511 Test report period Menu 592 Test report route Menu 594 Open/close route Menu 222 Report route (per zone) Menu 316 Status route (system events E.g. low battery, ac fail) Menu 543 Emergency route (keypad fire, panic, medical) Menu 544
SMS Select Tx 1 and set to sms Menu 540 Enter mobile phone numbers in Menu 511 Test report period Menu 592 Test report route Menu 594 Open/close route Menu 222 Report route (per zone) Menu 316 Status route (system events E.g. low battery, ac fail) Menu 543 Emergency route (keypad fire, panic, medical) Menu 544 SMS using GSM Select Tx1 and set to GSM SMS (12) Menu 540 Enter mobile numbers in Menu 511 To use SMS commands to control the system enter the mobile number/s that you will be sending the command from. Menu 656 Test report period Menu 592 Test report route Menu 594 Open/close route Menu 222 Report route per zone Menu 316 Status route (system events E.g. low battery, ac fail) Menu 543 Emergency route (keypad fire, panic,medical) Menu 544 Domestic dial Default panel to domestic dial (only effects comms programming) Menu 703 Enter phone numbers in Menu 511
Commonly used locations Home area Menu 613 Home area only Menu 612 Add token Menu 120 Add key fob Menu 130 Display area icons Menu 615 Enable Bosch R.F receiver (option 4) Menu 350 Turn off part arm via key fob Menu 622 Turn off audible key fob panic Menu 622 Zone array Menu 301 Operate output manually Menu 401 Output array Menu 402 Panel tamper options Menu 360 Lan scan Menu 602 E.O.L value Menu 340 Disable dialler Menu 521 Service interval Menu 292 Monitor default pin Menu 770 First to open/last to close Menu 771 Rf beep volume Menu 742 Test report time Menu 591 Test report period Menu 592 Test route Menu 594 Time/date Menu 710 Speaker beeps via key fob Menu 213 Strobe flash via key fob Menu 215 Set chime zones Menu 303 Chime mode Menu 206 Chime mode on ( Press and hold the 4 key) to toggle or use Menu 205 Zone silent alarm Menu 318 Invert zone seal Menu 318
Zone test on exit Menu 318 Service mode Menu 708 Start direct link Menu 505 Dial number test Menu 595 History log Menu 702 System trouble Menu 701 Open close after alarm Menu 214 Cancel reports Menu 214 Battery test Menu 791 Open/close reports (per user) Menu 142
System Components Keypads CP050B night arm station CP150B External vandal resistant keypad (large) CP151B External vandal resistant keypad (slim) CP700B Graphic white (non prox) CP701B Graphic white with prox CP710B Graphic black (non prox) CP711B Graphic black with prox Readers PR109B Internal LAN prox reader (black) PR110B Internal LAN prox reader (white) PR111B External LAN prox reader (black) PR112B External LAN prox reader (white) PR116B External LAN Smart Card reader (white) PR115B External LAN Smart Card reader (black) PR114B Internal LAN Smart Card reader (white) PR113B Internal LAN Smart Card reader (black) CM728B Bio metric reader (black) CM729B Bio metric reader (white) Prox credentials PR200 ( Grey token ) PR201 ( Black token with keyring ) PR260 ( clam shell prox card ) PR250 ( ISO prox card ) Smart card credentials PR301 ( Smart card token with keyring ) PR350 ( ISO Smart card ) PR365 ( Adhesive smart card sticker )
System Components Expansion modules CM101B voice module CM195B Multi RF receiver interface CM704B 8/16 zone input expander CM705B universal expansion module CM707B piggy back zone input expander (used with CM705B) CM710B 4 way relay output module CM720B 1 amp power supply module CM743B GSM/GPRS 2G plug on module CM751B TCP/IP interface module CM760B Real time clock module CM797B LAN isolator module Accessories SW500B Solution link software SW501B Site manager software ( customer software ) CM900 Direct link cable CM901 Firmware upgrade cable CM255 Default key module (one time use only) CM940B 6 way programmable relay card. (Can be separated into single cards )