DRAFT. Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters. 1.0 Introduction DANGER. 1.1 Related Documents

Similar documents
Conext CL-60 Inverter Firmware Upgrade Process

Conext TM ComBox USB Application Note - copy_settings

Application Note on Modifying Disconnect Settings for Xantrex GT Series Single Phase Inverters and Conext TX Series Inverters

Using the AUX Port on the Conext XW+ to Connect to a Generator or the Grid

Conext TM ComBox USB Application Note reset_logs.lux, reset_logs_cfgs.lux

Modbus Map: Conext System Control Panel (SCP) Device

Modbus Map: Automatic Generator Start (AGS) Device

Modbus Map: System Control Panel (SCP) Device

Application Note: Using Modbus With the Conext CL Series. Important Safety Instructions

Modbus Map: Conext MPPT Device

Modbus Map: MPPT60 Device

Conext EasyConfig Tool

SERVICE BULLETIN DEPARTMENT OF COMPLIANCE VEHICLE SAFETY AND RECALL MANAGEMENT BUILDING N MAIN ST MIDDLEBURY, INDIANA

Version 3.00 User s Guide

Conext ComBox Communication and Monitoring Device

Conext CL-60 EasyConfig Tool

Conext ComBox Communication and Monitoring Device

Technical Note: XW/Conext XW+

Galaxy Shore Connection 500 kva. Operation 04/

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems

Lightning and Surge Protection for PV Systems

PowerLogic High Density Metering System 1-Meter Enclosure

Solar Combiner Enclosure

CEM M-RS485 INSTRUCTION MANUAL (M014B A)

Conext ComBox. Installation and Configuration Manual.

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

ATS22D75S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

DECK All-In-One Enclosure. Quick Installation Guide for Field Installers

CPCI-PS24 24V-Power Supply

SDM120 SERIES. SDM120 series User Manual. Single phase two wire DIN rail energy meter (One module)

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating Instructions 05/2010 SINAMICS

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)

PanelView Plus/VersaView CE Terminals and Display Modules

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating instructions 03/2011 SINAMICS

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

Industrial Media Converters

PRO-1250D CT MID DIN rail three phase four wire energy meter.

ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/ V(7.5kW)

ATS22C11S6U soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100h

Operating instructions. Standstill monitor A / / 2011

PRO1 V21.xxx series MID DIN rail single phase two wire energy meter

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

Digital ac/dc (24V) Input Module

ATS22C41Q soft starter-ats22-control 220V-power 230V(110kW)/ V(220kW)

Quick Installation Guide for Field Installers

XPSMCMx Fieldbus Expansion Modules Instruction Sheet (Original Language)

Please read these instructions carefully before installing This will ensure an easy start and a great first customer experience with TS4 installation

Industrial 5-Port Fast Ethernet Switches. with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541. PoE Model: KSD-541-HP. Installation Guide

String monitoring with CMS - Circuit monitoring system Increased productivity and improved maintenance of PV systems

TU531, TU532 Terminal Unit

ATS22D47S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

VRp Three-Phase Precision AC Voltage Regulator

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

BCM2 Series Branch Circuit Monitors Quick Setup Guide

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER!

P3-SCM. General Specifications

Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) SIMATIC. S7-1500/ET 200MP Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) Preface

PowerLogic ION7550 RTU option

ATS22D88S6U. ATS22D88S6U soft starter-ats22-control110v-power 208V(25hp)/230V(30hp)/460V(60hp)/575V(75hp) Product data sheet Characteristics.

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

TM241CE24T controller M IO transistor PNP Ethernet

Operating instructions Evaluation system for flow sensors VS / / 2013

Installation Instructions

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions IO-Link master CabinetLine AL19xx

ATS22C17Q. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

Ethernet/DALI Interface 2 DALI Lines

Serial Communication Converters & Adapters Instruction Manual

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW)

Acti 9 Communication System

TM241CE40R controller M IO relay Ethernet

TN-5308 Quick Installation Guide

FAQ about Drives Technology

NI REM Remote I/O Overview DATASHEET. Bus Coupler for Remote I/O

PM Series Power Meter

INSTALLATION, OPERATION & MAINTENANCE CRFF Series Wall Control Console. ECM Motors. ACC1-25 (Part # ) Revision:

LMC058LF42 compact base - 42 I/O - 24 V DC supply

INJ-24A Series Quick Installation Guide

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

Lightning Protection and Grounding Guidelines

XTM1250SA DIN rail three phase four wire LCD display energy meter

Telcordia GR-1089-CORE Issue 4 Topics Primary Protection

User Manual Digital Input Module

hdpv.org Ampt Communications Unit Installation Manual D

ATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW)

LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual

FLEX Ex Spring Clamp Terminal Base

INTERNATIONAL STANDARD

Quick Start Guide Elinx ESW100 Series. 5 and 8 port Unmanaged Ethernet Switch

Zener Barriers Bulletin 937Z

Digital encoder interface module 5/12/24 V DANGER

NTS-protect. Description of GPS antenna and NTS time server connection via system lightning protector system /NTS-3000, NTS-4000, NTS-5000/

MINI-PS AC/10-15DC/8

PRO2DM DIN rail single phase two wire energy meter

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

User Manual HMI Linkbox HL01 DP/MPI

Conext ComBox - Custom Data Logging

TF501, TF521 Terminal Bases

Transcription:

Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters AP-XC-025 Revision B 1.0 Introduction DANGER RISK OF ELECTRIC SHOCK, EXPLOSION, ARC FLASH, AND FIRE This Application Note is in addition to, and incorporates by reference, the relevant product manuals for the Schneider Electric Conext Core XC Series Grid-Tied Photovoltaic Inverters. Before reviewing this Application Note you must read the relevant product manuals. Unless specified, information on safety, specifications, installation, and operation is as shown in the primary documentation received with the product. Ensure you are familiar with that information before proceeding. Failure to follow these instructions will result in death or serious injury. Most Conext Core XC Series Grid-Tied Photovoltaic Inverters communicate using Modbus/RS485 connections to a monitoring and control system that is located in the same photovoltaic (PV) box as the inverter. This arrangement provides isolation for the inverter electronics. Occasionally the inverter communication lines are routed outside of the boundary of a PV box and connected to devices such as array boxes. If fiber optic cables are used to carry the signals between the boxes, isolation can be maintained. If copper wiring is used to carry the signals, however, the wiring may conduct power surges (from lightning or ground differentials between nodes) back into the inverter. This Application Note explains the communication cabling requirements for Conext Core XC Series inverters at sites where the inverter is connected to devices outside of the PV box via copper wiring. It also provides recommendations for the type of surge protection and describes how to wire the surge protection devices. 1.1 Related Documents Modbus over Serial Line Specification and Implementation Guide, version 1.02, Modbus.org, December 2006. Conext Core XC Series Installation and Planning Manual (document number 990-4613) IEC 61000-4-5. Electromagnetic compatibility (EMC) Part 4-5: Testing and measurement techniques Surge immunity test. 2nd edition. International Electrotechnical Commission, 2005. ANSI/ TIA/ EIA-485-A-1998 Electrical Characteristics of Generators and Receivers for Use in Balanced Digital Multipoint Systems

2.0 Safety In the Conext Core XC Series, the Modbus/RS485 circuits are to be connected only to external Modbus/RS485 circuits that are Safety Extra-Low Voltage (SELV). SELV is a common designation that refers to a circuit in which the voltages within the circuit and from the circuit to ground have values that are not a shock hazard, under both normal and single fault conditions. This is achieved by the design of the circuits, and by maintaining protective separation (fault-tolerant insulation and isolation) between the SELV circuits and all hazardous voltage circuits, both within the inverter and in the installation. HAZARD OF ELECTRIC SHOCK 3.0 Surge Protection Design DANGER Connect only to Safety Extra Low Voltage (SELV) circuits. The circuits provided for use with external communications and control equipment are designed to provide isolation from neighboring hazardous circuits within the inverter. The communications and control circuits within the Conext Core XC Series are floating from ground and are classified as SELV. They must be connected only to other SELV circuits in a manner which maintains all the circuits within SELV limits and prevents ground loops. Separate conduit entries must be provided for the communications and control circuits and the PV circuits and all AC circuits. Physical and electrical separation of the communications and control circuits from non-selv electrical circuits must be maintained both within the inverter and external to the inverters. Failure to follow these instructions will result in death or serious injury. The surge protection system described in this Application Note is intended for connecting Conext Core XC Series inverters to a Modbus/RS485 network that may contain other devices including, but not limited to, supervisory control and data acquisition (SCADA) systems, other inverters, combiner boxes, and so on. NOTICE EQUIPMENT DAMAGE The protection needs of devices other than Conext Core XC Series inverters on a Modbus/RS485 network that uses copper wiring must be considered individually. Failure to follow these instructions may result in equipment damage. The recommended surge protection design is shown in Figure 1. 2 AP-XC-025 Revision B

. Figure 1 Conext Core XC Series communication system, showing surge protection design AP-XC-025 Revision B 3

3.1 Inverter Connections The Modbus/RS485 connectors in the Conext Core XC Series are located at S43 and S44 on the communications (CMX) board on the left wall of the DC cabinet, (see Figure 2). S43 and S44 Figure 2 Modbus/RS485 connectors The details of the Modbus connections are shown in Figure 3. Figure 3 Modbus connection details The shield of the RJ45 male connector must be connected to the cable shield (drain). Do not connect the RJ45 connector shield to the signal common. 4 AP-XC-025 Revision B

3.2 System Cable Shield and Signal Common Grounding NOTICE 3.3 Surge Protector RISK OF EQUIPMENT DAMAGE The signal common and the cable shield must each be connected directly to protective ground and at one point only for the entire bus. Failure to follow these instructions may result in equipment damage. The signal common must be connected directly to the protective ground and must be connected at one point only for the entire bus. In general, this connection point is on the master device or on its tap. The cable shield must be connected directly to the protective ground and must be connected at one point only for the entire bus. The shield drain wire must not be used as a signal common. In the system diagram shown in Figure 1 on page 3, the preferred point of connection of the cable shield and signal common to the protective grounding is at the SCADA device. To achieve the highest level of surge protection, install the surge protector near the point where the copper wiring exits the PV box and minimize the length of wiring between the surge protector and the Conext Core XC Series inverter that is being protected on the Modbus/RS485 network. The surge protector must be connected so that the Line Side faces the unprotected environment (outdoor cabling), as shown in Figure 4. Figure 4 Surge protector connections The following surge protectors have been tested and are approved for operation with Conext Core XC Series inverters when configured as shown in Figure 1 on page 3: B&B Electronics Model HESP4DR: DIN Rail Mounted Data Line Surge Suppressor B&B Electronics Model 485HESP: RS485 High-Energy Surge Protector (panel mounted) These devices offer three stage surge protection of 6 kv as per IEC 61000-4-5. AP-XC-025 Revision B 5

3.3.1 Connection Details The surge protector must be connected as follows: Equipment Side: To inverter Line side: To outdoor environment Grounding The grounding cable should be kept as short as possible and the ground should be close to the inverter to minimize noise. The cable shields from the two cables must be connected to provide continuity. Do not connect the cable shield to the surge protector ground. Figure 5 shows a typical surge protector wiring (B&B Electronics Model HESP4DR). Figure 5 Surge protector wiring example 6 AP-XC-025 Revision B

3.4 Common Mode Choke Communication lines may have common mode noise if a ground potential difference exists between different nodes of the RS485 network. When the communication quality is affected, a common mode choke can be used to reduce the noise impact. Figure 6 shows a typical common mode choke. 3.4.1 Guidelines Figure 6 Common mode choke Loss of data due to an increase in the common mode voltage can also be more significant if multiple surge arresters are used on one RS485 network (for example, between the PV box and the array boxes). Common mode chokes can reduce these effects. It is not possible to specify a single common mode choke device that will ensure proper performance for every scenario because the magnitude and effect of the common mode noise varies depending on the particular details of an installation. The following sections provide general guidelines for the use of a common mode choke. Placement Within the System Place the common mode choke between the Line Side of the surge protector and the cable coming from the outdoor environment (see Figure 5). This reduces the possibility of loss of communication between the inverters and the rest of the nodes on the Modbus/RS485 chain. Winding Wind the entire communication cable, including the shield, through the core of the common mode choke. Core Type and Turns The core type and the number of turns depend on the details of a particular installation. For example, in a test setup the Fair-Rite part number 2643803802 core was found to be effective for link distances from 0 m to 330 m. AP-XC-025 Revision B 7

3.5 Cabling A 1.5 pair cable that is suitable for an EIA-485/Modbus/RS485 application is illustrated in Figure 7. The illustrated cable is Belden 3106A Multi-Conductor - EIA Industrial RS485 PLTC/CM. Figure 7 Cable example To properly select a cable, the system designer must consider factors such as local codes, environmental conditions (such as temperature), location (such as cable tray vs direct burial), and the requirements for other equipment connected on the Modbus/RS485 network. Many cables meet the recommendations of the EIA-485 standard, including the shielded Cat 5 cable used in Ethernet network installations. For more information please refer to the Modbus and EIA-485 standards (see Related Documents on page 1). Copyright 2014 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Exclusion for Documentation UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER (A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION; (B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S RISK; AND (C) REMINDS YOU THAT IF THIS DOCUMENTATION IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION WHICH IS POSTED AT www.schneider-electric.com. Date: May 2014 Revision: Revision B Document Number: AP-XC-025 Contact Information www.schneider-electric.com For other country details please contact your local Schneider Electric Sales Representative or visit the Schneider Electric website at: http://www.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page 8 AP-XC-025 Revision B