SE6104 Control Module

Similar documents
ZN551 Control Module. Technical Instructions

SE6104a Controller. Technical Instructions. Rev. 9/8/2011

Introduction. What is the UC Open controller? Specifications

AppController overview and specifications

AppController overview and specifications

Wiring inputs and outputs... 17

What are the MPC Open XP and MPC Open XPIO expanders?

What are the MPC Open XP and MPC Open XPIO expanders?

UPC Open overview and specifications

BACnet. b3810 Series Local Controllers

Andover ContinuumTM. b3850 Series Terminal Controllers

Specification Sheet For electronically commutated motors

Andover ContinuumTM b3865/866 VAV Controllers with Built-in Actuator

Andover ContinuumTM Infinet II

Andover ContinuumTM Infinet II

Andover Continuum Infinet II i2865/866 VAV Controllers with Built-in Actuator

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3

BACnet. b3867 Terminal Controllers

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

clarity 3 Programmable Controller

Datasheet. ECB-600 and ECx-400 Series. ECB-600 & ECx-400. Overview. Applications. Features & Benefits.

Andover ContinuumTM Infinet II

What is the i-vu XT Router?

ACCESS 9340/9360 Meter Input/Output Module

FX Input/Output (I/O) Modules XM07 and XM14

What is the Carrier ChillerVu?

Introduction. What is a VVT Bypass controller?

DS Type: MAXIM III Controller

Unitary Controller. Features. Description. Technical Specification Sheet Rev. 6, March, 2000

Quick Start Installation Guide

Custom Controller Installation Instructions

Product Manual SZ2141

Introduction. What is a VVT Bypass controller?

EasyIO FW 08VUser Reference

TALON Network Manager- 2 & 6 Express

Siemens BACnet Programmable TEC VAV with Series Fan and 3-Stage Electric Heat Controller

Datasheet ECB /6. BACnet B-ASC 10-Point Programmable Controller. Overview

Lantech. IPES /100TX with 4 PoE Injectors 24~48VDC Industrial Switch. User Manual

MOD-IO9 Modbus Input / Output Modules, Wall Mounted

VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

PM174 PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER. Features

Siemens BACnet Programmable TEC Constant Volume

rcc.1081 Installation Instructions

CONTROL MICROSYSTEMS Analog Output Module. Hardware Manual

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors

PEAK TM. PEAK TM controllers. Mid-Market BAS Smart equipment controllers. HVAC/R controllers

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

NT10 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

ECB-300 Series BACnet B-AAC 18-Point Programmable Controllers

NEUROLOGIC RESEARCH CORPORATION MODEL 2500

AIR HANDLING UNIT CONTROLS

Siemens BACnet Programmable TEC Unit Vent Controller

Datasheet ECB /6. BACnet B-ASC 10-Point Programmable Controller. Overview

HARDWARE GUIDE. Water Loop Controller C1000 Series. Specifications and Operational Guide

DS October MAXIM 1010 Controller

BACnet Flow Controller for Fan Filter Units

Quick Start Installation Guide

2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review...

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

APK INSTALLATION GUIDE

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Quick Start Installation Guide

MOD-RI Room Interface Modules with Modbus

Siemens BACnet Programmable TEC Unit Conditioner Controller

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

Quick Start Guide DDC (2014/02) Subject to change without prior notice Quick Start Guide

ECB-203 Series BACnet B-ASC 14-Point Programmable Controllers

Datasheet. ECB-PTU Series. 1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller

Siemens BACnet Programmable TEC Unit Vent Controller for Smoke Control

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control

MAXIOM. Data Sheet. Lighting Relay Panel. Overview Leverage the Power of BAS Integration

Datasheet. ECB-203 Series. 1/6. BACnet B-ASC 14-Point Programmable Controllers. Overview

LX Series Free Programmable LX-PRG6x0-11 Controllers and LX Series Input/Output (I/O) Extension Modules

EP/2 Installation Instructions

Hardware Installation. Tracer MP581 Programmable Controller CNT-SVN01C-EN

RS-485 FClink Networking Room Thermostats with LCD for Fan Coil Units

MANUAL INSTALLATION. Multi-Variable Monitor. MVM Series. Issue Date: 02/07/ Price Industries Limited. All rights reserved.

UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

TC Compact Series Unitary Equipment Controller

Datasheet. ECB-300 Series. 1/6. BACnet B-AAC 18-Point Programmable Controllers. Overview

THERMOSTATS & CONTROLLERS

LLR-MOD Modbus Light Level and Occupancy Sensor

SORDS ELECTRIC ~ MA7200. Sensorless Vector AC Inverter.

RTD-W Installation Instructions

HARDWARE GUIDE. VAV Zone Controller C1000 Series. Specifications and Operational Guide

XT-9100 Technical Bulletin

CDD Carbon Dioxide Transmitter

Introduction. What is the RTU Open controller?

TAC Xenta 301. Controller, Freely Programmable

PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!

Contents. Appendix - Module Status field descriptions Document revision history... 41

BACnet Terminal Box (VAV) Controller

BACnet MS/TP Interface User s Guide

NB-ASC Family Protocol Implementation Conformance Statement (PICS)

Product Manual SZ2144

BA/BS4S Temperature Sensor Installation & Operating Instructions

TPE 1464 Series Pressure Transducer

Installation & Operation Guide

Transcription:

SE6104 Control Module Technical Instructions What is the SE6104 control module?... 2 Module driver and control program... 2 Specifications... 2 Inputs... 3 Room sensors... 4 Digital outputs... 4 Analog outputs... 4 To mount the SE6104... 4 Wiring for power... 4 To wire for power... 5 To address the SE6104... 5 Wiring for communications... 5 Wiring specifications... 6 To wire the SE6104 for communications... 6 Wiring inputs and outputs... 6 Wiring specifications... 6 To wire inputs and outputs... 7 Downloading memory... 10 To download memory in WebCTRL...10 To assign inputs or outputs to points... 11 Input values...11 Output values...12 Resolution values...12 Offset/Polarity values...13 To use the Auto-Off-On switches...14 To set up the module driver... 14 Driver...14 Device...15 Notification Class #1...15 Common and Specific Alarm...16 Custom Translation Tables...16 To communicate through the local access port... 17 To set up a Local Access connection in WebCTRL...17 Troubleshooting... 17 Formatting the control module...18 LED's...18 Manufacture date...19 Compliance... 19 Automated Logic Corporation 1150 Roberts Blvd. Kennesaw, GA 30144 770/429-3000 Fax 770/429-3001 www.automatedlogic.com 2005 Automated Logic Corporation. All rights reserved throughout the world. Automated Logic Corporation, the Automated Logic logo, WebCTRL, EIKON, BACview, SuperVision, and InterOp are registered trademarks, and Alert is a trademark of Automated Logic Corporation. BACnet is a registered trademark of ASHRAE. All other brand and product names are trademarked by their respective companies.

What is the SE6104 control module? The SE6104 control module controls rooftop Air Handling Units (AHUs). You can mount the SE6104 on or inside the rooftop equipment. Module driver and control program Module driver Maximum number of control programs Maximum number of BACnet objects* * Depends on available memory DRV_SE 1 200 Specifications Power 24 Vac ±10%, 50 60 Hz, 20 VA power consumption (38.4 VA with BACview6 attached) single Class 2 source only, 100 VA or less BACnet port (This port may be labeled CMnet.) Rnet Local Access port LogiStat port Rnet port Inputs For communication with the control module network using ARC156 or MS/TP (9600 bps 76.8 kbps) For system start-up and troubleshooting For LogiStat and LogiStat Plus room sensors. The LogiStat port uses two universal inputs. NOTE The SE6104 does not support the LogiStat Pro. Use an RS Pro on the Rnet port instead. Supports up to four RS Standard sensors and one RS Pro or RS Plus sensor for averaging or high/low select control. The sensors can share the Rnet port with up to 2 BACview6's. NOTE If you use the Rnet port, you cannot connect a LogiStat sensor to the LogiStat port. 10 inputs, configurable for 0 10 Vdc, 0 20 ma, RTD, thermistor, or dry contact, and one LogiStat port. Inputs 1 and 2 are also configurable for pulse counter or timed local override (TLO). NOTE If using a LogiStat or LogiStat Plus, temperature and setpoint adjust inputs replace inputs 9 and 10, making 9 and 10 unavailable. Digital outputs 6 digital outputs, relay contacts rated at 3 A max @ 24 Vac. Configured normally open. Analog outputs Output resolution Microprocessor Memory Real-time clock 4 analog outputs, 0 10 Vdc or 0 20 ma selectable 8 bit D/A High speed 16-bit microprocessor with ARCNET communication co-processor 1 MB non-volatile battery-backed RAM, 1 MB Flash memory, 16-bit memory bus Battery-backed real-time clock keeps track of time in event of power failure SE6104 Control Module Rev. 3/29/2005 2 2005 Automated Logic Corporation

Battery Protection Status indicators Environmental operating range Physical Overall dimensions Mounting dimensions Recommended panel depth Weight BACnet support 10-year Lithium CR2032 battery provides a minimum of 10,000 hours of data retention during power outages Incoming power and network connections are protected by non-replaceable internal solid-state polyswitches that reset themselves when the condition that causes a fault returns to normal. The power, network, analog inputs, analog outputs, and relay output connections are also protected against voltage transient and surge events. LED's indicate status of communications, running, errors, power, and digital outputs -20 to 140 F (-29 to 60 C), 10 90% RH non-condensing NOTE Control modules should be mounted in a protective enclosure. Rugged aluminum cover, removable screw terminal blocks Width: Height: Width: Height: 1 1/2 in. (3.8 cm) 1.2 lbs (0.5 kg) 8 5/16 in. (21.1 cm) 7 in. (17.8 cm) 7 7/8 in. (19.9 cm) 5 in. (12.7 cm) Conforms to the Advanced Application Controller (B-AAC) Standard Device Profile as defined in ANSI/ASHRAE Standard 135-2004 (BACnet) Annex L Listed by UL-916 (PAZX), cul-916 (PAZX7), FCC Part 15-Subpart B- Class A, CE EN50082-1997 Inputs The SE6104 has 10 inputs that accept the following signal types: These inputs... Support this signal type... Description All Thermistor Precon type 2 (10 kohm at 77 F). Input voltages should be from 0.489 Vdc to 3.825 Vdc for thermistors. All Dry contact A 5 Vdc wetting voltage detects contact position, resulting in a 1 ma maximum sense current when the contacts are closed. All 0 5 Vdc 0 10 Vdc The output impedance of a 0 5 Vdc or a 0 10 Vdc source must not exceed 200 Ohms. The input impedance of the SE6104 is approximately 20 kohm. All 0 20 ma The input resistance on the positive () terminal is 250 Ohms. The Aux Power Out terminal is capable of supplying 24 Vdc to a 4 20 ma transducer, but the total current demanded must not exceed 200 ma. If the voltage measured from the Aux Power Out terminal to is less than 18 Vdc, you need to use an external power supply. All RTD 1 kohm at 32 F (0 C). Platinum, Balco, or Copper types. Input voltages should be from 0.6 1.2 V. IN-1, IN-2 Pulse counter Pulse counting up to 20 cycles per second (20 Hz). Minimum On time required for each pulse is 50 msec. SE6104 Control Module Rev. 3/29/2005 3 2005 Automated Logic Corporation

These Support this inputs... signal type... Description IN-1, IN-2 IN-9, IN-10 Timed local override LogiStat LogiStat Plus A momentary contact switch that overrides a schedule and turns equipment on for a defined period of time. The override time added for each push of the button and the maximum allowable On time are software adjustable. IN-9 See Thermistor. IN-10 Setpoint adjust. Input voltages should be from 1.4 3.4 Vdc. NOTE A LogiStat or LogiStat Plus connected to the SE6104 uses IN-9 and IN-10. A LogiStat Pro or an RS room sensor does not use these inputs. Room sensors You can wire an RS Standard, RS Plus or RS Pro to the SE6104's Rnet port. Or you can wire a LogiStat or LogiStat Plus to the SE6104's LogiStat port. See the RS Room Sensors Technical Instructions (http://info.automatedlogic.com) or the LogiStat Sensors Technical Instructions (http://info.automatedlogic.com). NOTE The SE6104 does not support the LogiStat Pro. Digital outputs Analog outputs The SE6104 has 6 digital outputs. You can connect each output to a maximum of 24 Vac. Each output is a dry contact rated at 3 A maximum and is normally open. The SE6104 control module has 4 analog outputs that support voltage or current devices. The controlled device must share the same ground as the control module and have the following resistance to ground: 0 10 Vdc 0 20 ma min 500 Ohms max 800 Ohms To mount the SE6104 Screw the SE6104 into an enclosed panel using the mounting holes provided on the cover plate. Leave about 2 in. (5 cm) on each side of the control module for wiring. Wiring for power CAUTIONS The SE6104 is a Class 2 device (less than 30 Vac, 100 VA). Take appropriate isolation measures when mounting it in a control panel where non-class 2 devices (120 Vac or greater) are present. Do not power pilot relays from the same transformer that powers the SE6104. NOTE You can power several control modules from the same transformer if you maintain the same polarity. SE6104 Control Module Rev. 3/29/2005 4 2005 Automated Logic Corporation

To wire for power 1 Turn off the SE6104 s power to prevent it from powering up before you can verify the correct voltage. 2 Remove power from the 24 Vac transformer. 3 Pull the screw terminal connector from the control module's power terminals labeled and 24 Vac. 4 Connect the transformer wires to the screw terminal connector. 5 Apply power to the transformer. 6 Measure the voltage at the SE6104 s power input terminals to verify that the voltage is within the operating range of 21.6 26.4 Vac. 7 Insert the screw terminal connector into the SE6104's power terminals. 8 Turn on the SE6104's power. 9 Verify that the Power LED is on and the Run LED is blinking. To address the SE6104 You can address the SE6104 before or after you wire the control module for power. 1 If wired for power, turn off the SE6104's power. The control module reads the address each time you turn it on. 2 Using the rotary switches, set the control module's address to match the Address in the control module's Device Properties dialog box in SiteBuilder. Set the Tens (10's) switch to the tens digit of the address, and set the Ones (1's) switch to the ones digit. EXAMPLE If the control module s address is 35, point the arrow on the Tens (10's) switch to 3 and the arrow on the Ones (1's) switch to 5. 10's 1's Wiring for communications The SE6104 communicates using BACnet on the following types of network segments: ARC156 communicating at 156 kbps MS/TP communicating at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps NOTE ARC156 is a unique implementation of the industry standard ARCNET. For a summary of differences between ARCNET and ARC156, see the ARC156 Wiring Technical Instructions (http://info.automatedlogic.com). SE6104 Control Module Rev. 3/29/2005 5 2005 Automated Logic Corporation

Wiring specifications For... Use... Maximum Length ARC156 MS/TP 22 AWG, low-capacitance, twisted, stranded, shielded copper wire* A dedicated 22 AWG to 18 AWG twisted pair wire (EIA-485) 2000 feet (610 meters) 3000 feet (914.4 meters) for 9600 bps, 19.2 kbps, or 38.4 kbps 2000 feet (610 meters) for 76.8 kbps * See the ARC156 Wiring Technical Instructions (http://info.automatedlogic.com). To wire the SE6104 for communications 1 Turn off the SE6104's power. 2 Check the communications wiring for shorts and grounds. 3 Connect the communications wiring to the control module s screw terminals labeled Net, Net -, and Shield. NOTE Use the same polarity throughout the network segment. 4 Set the communication type and baud rate. For... Set DIP switch 4 to... Set DIP switches 1 and 2 to... ARC156 ARC156 N/A. Baud rate will be 156 kbps regardless of the DIP switch settings. MS/TP MSTP The appropriate baud rate. See the MSTP Baud diagram on the control module. NOTE Use the same baud rate for all control modules on the network segment. 5 Turn on the SE6104's power. 6 Verify communication with the network by viewing a module status report in WebCTRL. Wiring inputs and outputs Wire the SE6104's inputs and outputs as follows. Wiring specifications Input wiring Input Maximum length Minimum gauge Shielding 0 5 Vdc 0 10 Vdc 1000 feet (305 meters) 0 20 ma 3000 feet (914 meters) Thermistor Dry contact Pulse counter TLO RTD 1000 feet (305 meters) 100 feet (30 meters) 26 AWG Shielded 26 AWG Shielded 22 AWG Shielded 22 AWG Shielded SE6104 Control Module Rev. 3/29/2005 6 2005 Automated Logic Corporation

Input Maximum length Minimum gauge Shielding RS Room sensor LogiStat 500 feet (152 meters) 100 feet (30 meters) 18 AWG, 4 conductor if a BACview is connected on the Rnet 22 AWG, 4 conductor if Rnet contains only RS room sensors 1 Shielded or unshielded 22 AWG 2 Unshielded 1 See the RS Room Sensors Technical Instructions (http://info.automatedlogic.com). 2 See the LogiStat Sensors Technical Instructions (http://info.automatedlogic.com). Output wiring To size output wiring, consider the following: Total loop distance from the power supply to the control module, and then to the controlled device NOTE Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length. Acceptable voltage drop in the wire from the control module to the controlled device Resistance (Ohms) of the chosen wire gauge Maximum current (Amps) the controlled device requires to operate To wire inputs and outputs 1 Verify that the SE6104's power and communications connections work properly. 2 Turn off the SE6104's power. SE6104 Control Module Rev. 3/29/2005 7 2005 Automated Logic Corporation

3 Connect the input wiring to the screw terminals on the SE6104. 10K ohm thermistor Any input Relay, dry contact Any input 1Kohm RTD Any input V Isolated power supply Vin Out 0-5Vdc 0-10Vdc Any input Vin Out 0-5Vdc 0-10Vdc Any input 2 wire 4-20mA - n/c Any input 3 wire 4-20mA Out Vin Any input 4-20mA 4 wire Out Vin Out- Any input 24Vdc 200mA max NOTES Connect the shield wire to the GND terminal with the ground wire. Use only IN-1 or IN-2 for pulse counter or timed local override. For a loop-powered 4-20 ma sensor, wire the sensor's positive terminal to the terminal on the SE6104's Aux Power Out port. Wire the sensor's negative terminal to an input's terminal. 4 To wire a room sensor to the SE6104, wire each terminal on SE6104's Rnet or LStat port to the terminal of the same name on the room sensor. NOTE If wiring an RS room sensor with shielded wire, connect the shield wire to the GND terminal with the ground wire. SE6104 Control Module Rev. 3/29/2005 8 2005 Automated Logic Corporation

5 Set the appropriate jumpers on the SE6104. To use... For... Any input Aux Power Out port LogiStat Port Thermistor Dry contract 0 5 Vdc 0-10 Vdc 0 20 ma RTD Loop-powered 4-20 ma LogiStat LogiStat Plus LogiStat Pro Set each input's Universal Input Mode Select jumper to the type of signal the input will receive. Set the Select jumper to 5V or 24V as required by the sensor. Set the Stat Select jumper to LogiStat. Rnet Port RS room sensor Set the Stat Select jumper to Rnet to make IN-9 and IN-10 available for use. 6 Connect the digital output wiring to the screw terminals on the SE6104 and to the controlled device. Any DO 24 Vac/dc Motor Any DO Any DO Valve 7 Connect the analog output wiring to the screw terminals on the SE6104 and to the controlled device. Ground Any AO 0-10 V motor 3-wire Hot 24 Vac/dc Any AO 0-20 ma valve 4-wire Hot Ground NOTE Current from the analog outputs can drive a 0 20 ma or 0 10 Vdc device. To use an analog output for this purpose, you may need to add a 1/2 watt resistor in series with the device to achieve the required total resistance which is 800 Ohms for a 0 20 ma device or 500 Ohms for a 0 10 Vdc device. For example, to drive a device that has 400 Ohms of SE6104 Control Module Rev. 3/29/2005 9 2005 Automated Logic Corporation

resistance, wire a 400 Ohm resistor in series with the 20 ma device to achieve 800 Ohms of resistance. 8 Turn on the SE6104's power. Downloading memory Download memory to a control module to: Send control programs, the module driver, editable properties, and schedules to a control module for the first time. The first download takes longer than subsequent downloads. Send changes such as a change to a control program or an upgrade to the module driver. If you change the control module's address, you must download memory again. The SE6104 can store one DRV_SE module driver and one control program. CAUTIONS The control module automatically halts before and restarts after a memory download, causing the shutdown and restart of any equipment controlled by the module. Downloading memory overwrites all control programs in the control module causing it to lose stored data. You download memory from WebCTRL. If your network is complete, you can download from any network browser. If not complete, connect a laptop with a local copy of the system database to the SE6104's local access port. See steps 1 3 of To communicate through the local access port (page 17). To download memory in WebCTRL 1 On WebCTRL's CFG tree, click Download. 2 Select the Memory checkbox. NOTE A memory download includes a Parameters and Schedules download. 3 On the Network tree on the right, select the control module you want to download to. 4 Click Add to add the control module to the Download Items list. 5 Click Download Selected Items. If the download fails, the control module appears in the Failures box. Since this indicates a system problem, do not clear the failure. Locate and resolve the problem, then retry the download. To retry, select the control module in the Failures box, then repeat steps 4 and 5 above. SE6104 Control Module Rev. 3/29/2005 10 2005 Automated Logic Corporation

To assign inputs or outputs to points To use an input or output, you must assign it to its corresponding point in the control program. 1 In WebCTRL's GEO tree, select the equipment controlled by the SE6104. 2 From the menu, select Point Checkout. 3 In the Num field for each point, type the number of the control module's corresponding input or output. For example, if you use DO1 on the SE6104 for the point Fan S/S, type 1 in the Num field for Fan S/S. NOTE Exp (expander number) is 0 for the SE6104. 4 Enter the appropriate values for each input and output in the remaining columns. See Input values, Output values, Resolution values and Offset/Polarity values below. NOTE You can also enter these values in EIKON for WebCTRL. 5 If you have not performed the initial memory download to the SE6104, you must download now so you can verify inputs and outputs. 6 To verify each input's operation, force each sensor to a known value, then compare it to the Value shown on the control program's Point Checkout tool in WebCTRL. 7 To verify each output's operation, lock each output to a known condition on the control program's Point Checkout tool in WebCTRL, then verify that the equipment operates correctly. Input values Input I/O Type Sensor/Actuator Type Min/Max Analog (BAI) 0 5 Vdc 0 5 Volt Linear Full Range Engineering values associated with 0 Vdc (Min) and 5 Vdc (Max) 1 0 10 Vdc 0 10 Volt Linear Full Range Engineering values associated with 0 Vdc (Min) and 10 Vdc (Max) 1 2 10 Vdc 0 10 Volt Linear w/offset, 2 10 Volts Engineering values associated with 2 Vdc (Min) and 10 Vdc (Max) 1 0 20 ma 0 20 ma Linear Full Range Engineering values associated with 0 ma (Min) and 20 ma (Max) 1 4 20 ma 0 20 ma Linear w/offset, 4 20 ma RTD RTD Input Select your RTD type or set up and select a Non- Linear, Custom Table 2 Engineering values associated with 4 ma (Min) and 20 ma (Max) 1 N/A SE6104 Control Module Rev. 3/29/2005 11 2005 Automated Logic Corporation

Input I/O Type Sensor/Actuator Type Min/Max Thermistor Thermistor Select your Thermistor type or set up and select a Non- Linear, Custom Table 2 N/A Pulse to Analog (BPTA) 3 Pulse Counter Counter Input N/A N/A Digital (Binary) (BBI) Dry Contact Dry Contact N/A N/A 1 The sensor reads a value and sends a corresponding signal (Volt, ma, or psi) to the SE6104's physical input. The Analog Input microblock uses the Min and Max values to linearly translate the signal into the engineering value used in subsequent control logic. For example, set Min to 0 and Max to 10 for a 4 20 ma sensor that measures velocity from 0.0 to 10.0 inches/second so that when the input reads 4 ma, the microblock outputs a value of 0. Similarly, when the input reads 8 ma, the microblock outputs a value of 2.5. 2 To set up a custom translation table, see the module driver's Custom Translation Tables properties page in WebCTRL. 3 To use a pulse counter input, you must use the Pulse to Analog Input microblock in EIKON for WebCTRL. Output values Output I/O Type Sensor/Actuator Type Min/Max Analog (BAO) 0 10 Vdc Electrical 0 10 Volt 2 10 Vdc Electrical 0 10 Volt 0 20 ma Electrical 0 20 ma 4 20 ma Electrical 0 20 ma Digital (Binary) (BBO) Relay Relay/Triac Output Linear Full Range Linear w/offset, 2 10 Volts Linear Full Range Linear w/offset, 4 20 ma N/A Engineering values associated with 0 Vdc (Min) and 10 Vdc (Max) 1 Engineering values associated with 2 Vdc (Min) and 10 Vdc (Max) 1 Engineering values associated with 0 ma (Min) and 20 ma (Max) 1 Engineering values associated with 4 ma (Min) and 20 ma (Max) 1 1 The Analog Output microblock uses the Min and Max values to linearly translate its EIKON for WebCTRL wire value into a physical output signal (Volt, ma, or psi) sent from the SE6104 to an actuator. For example, set Min to 0 and Max to 100 for an Analog Output microblock that receives a 0 to 100% open signal from a PID microblock and that controls a 0 10 Vdc actuator so that when the PID signal is 100%, the SE6104 output is 10 Vdc. Similarly, when the PID signal is 50%, the SE6104 output is 5 Vdc. N/A Resolution values Resolution is not particular to a type of input or output, but the module driver handles analog and digital (binary) inputs and outputs differently. To set these values appropriately, you should understand how the module driver uses them. SE6104 Control Module Rev. 3/29/2005 12 2005 Automated Logic Corporation

Resolution Analog Input (BAI) Analog Output (BAO) Digital Inputs and Outputs Notes The driver truncates the microblock's present value according to the resolution. EXAMPLE If the calculated present value is 13.789 and you set the Resolution to 0.1, the control program uses 13.7 for any calculations downstream from the microblock. The driver truncates the wire input value to the microblock before performing any scaling calculations. EXAMPLE If the wire input value is 13.789 and you set the Resolution to 0.1, the microblock uses 13.7 for any scaling calculations. N/A Offset/Polarity values Offset/Polarity is not particular to a type of input or output, but the module driver handles analog and digital (binary) inputs and outputs differently. To set these values appropriately, you should understand how the module driver uses them. Offset/Polarity Analog Input (BAI) Analog Output (BAO) Digital (Binary) Input (BBI) Digital (Binary) Output (BBO) Notes Offset value (positive or negative) adds a fine adjustment to a sensor reading after all scaling for calibration. EXAMPLE If a sensor reads 74.9 F when the actual measured value is 73.6 F, enter an Offset of 1.3 to calibrate the sensor to the measured value. You can use the Offset value (positive or negative) to calibrate an output, but you generally do not need to. If used, the driver adds the offset value to the wire input value before performing any scaling calculations to determine the SE6104's output. Polarity determines the microblock's present value when no signal is received from the equipment. When no signal is received from the equipment, if Polarity is set to: normal present value is off reversed present value is on Polarity determines the SE6104's output based on the control program's signal to the microblock. When the control program's signal to the microblock is on, if Polarity is set to: normal output is on reversed output is off NOTE Regardless of Polarity, the output will be off if the SE6104 loses power. SE6104 Control Module Rev. 3/29/2005 13 2005 Automated Logic Corporation

To use the Auto-Off-On switches You can control a digital output using the Auto-Off-On switch. If switch position is... Normally open output contacts are... Auto Off On Determined by control program Locked open Locked closed The control program can monitor the status of an Auto-Off-On switch and display the status on the control program's Point Checkout page in WebCTRL. The Value of the point monitoring the Auto-Off-On switch shows Off if the switch is set to Auto, and On if the switch is set to Off or On. To monitor an Auto-Off-On switch 1 Insert a BACnet Binary Input microblock in the control program. 2 On the microblock's Properties page in WebCTRL, set the I/O Type field to H-O-A Status Feedback. 3 In the Input Number field, type the number of the output you want to monitor. To set up the module driver After you download the module driver and control program(s) to the SE6104, you may want to change the module driver's properties to suit your application. 1 On WebCTRL's NET tree, click the plus sign () to the left of your SE6104. NOTE Driver properties are on the Driver Properties page and on its children in the tree. 2 Click the page you want to view, then change properties as needed. Driver On this page, you can change the following properties: BACview inactivity timeout and user password. See table below. Module clock synchronization and failure. See table below. Network Input microblock communication properties. BACview Control Overwrite Daylight Saving parameters set in BACview? Keypad inactivity timeout (minutes) Yes Every memory download includes Daylight Saving Time properties from System Settings page and overwrites changes to these properties made from BACview. No Download System Settings page Daylight Saving Time properties during first download. You must make subsequent changes from BACview. (Primarily for OEM use.) End the user session, turn off the backlight, and display the standby screen after this period of inactivity. SE6104 Control Module Rev. 3/29/2005 14 2005 Automated Logic Corporation

Keypad user-level password Module Clock Clock Fail Date and Time Time Synch Sensitivity (seconds) Numeric password user must enter to access system through BACview. Date and time control program uses when module's realtime clock is invalid. TIP Use an occupied date and time (such as a Tuesday at 10 a.m.) so the equipment does not operate in unoccupied mode if the module loses power during occupancy. On a Time Synch signal, update the module clock only if the module time differs from the signal time by more than this value. Device On this page, you can change the following properties: BACnet device object properties for the SE6104 SE6104 network communication Configuration Max Masters and Max Info Frames NOTE The three APDU fields refer to all networks over which the SE6104 communicates. Apply only if the SE6104's parent network is an MS/TP network. Notification Class #1 WebCTRL alarms use Notification Class #1. A BACnet alarm's Notification Class defines: Alarm priority for Alarm, Fault, and Return to Normal states Options for BACnet alarm acknowledgement Where alarms should be sent (recipients) NOTE You may need to set up additional Notification Classes if your system will handle Life Safety alarms or if you need to send certain types of alarms only to an alarm manager other than WebCTRL. Priorities NOTE BACnet defines the following Network message priorities for Alarms and Events. Priority range Network message priority 00 63 Life Safety 64 127 Critical Equipment 128 191 Urgent 192 255 Normal Priority of Off-Normal Priority of Fault Priority of Normal BACnet priority for Alarms. BACnet priority for Fault messages. BACnet priority for Return-to-normal messages. SE6104 Control Module Rev. 3/29/2005 15 2005 Automated Logic Corporation

Ack Required for Off-Normal, Fault, and Normal Recipient List Recipients Recipient Description Recipient Type Recipient Device Object Identifier Process Identifier Issue Confirmed Notifications Requires a control module acknowledgement for each message type. Normally not required. TIP To require operator acknowledgement for an Alarm or Return-to-normal message (stored in the WebCTRL database) change the acknowledgement settings on WebCTRL's Alarm > Enable/Disable tab for an alarm source or an alarm category. The first row in this list is the WebCTRL Server. Do not delete this row. Click Add if you want other BACnet devices to receive alarms. Name that appears in the Recipients table. Use Address (static binding) only for third-party BACnet device recipients that do not support dynamic binding. Type the Device Instance from SiteBuilder (or from the network administrator for third-party devices) in the # field. Change for third-party devices that use a BACnet Process Identifier other than 1. WebCTRL processes alarms for any 32-bit Process Identifier. Select to have a device continue sending an alarm message until it receives delivery confirmation from the recipient. Common and Specific Alarm On these pages, you can change the following control module alarm properties: BACnet alarm object properties Enable/disable Delays NOTE To set up alarm actions for control module generated alarms, see Setting up alarm actions in WebCTRL Help. Module Generated Alarm Description Events Alarm Category and Alarm Template Enable Notification Class Short message shown on WebCTRL's Alarm page or in an alarm action when this type of alarm is generated. See Customizing alarms in WebCTRL Help. Clear these checkboxes to disable Alarm or Return to normal messages of this type from this control module. Do not change this field. Custom Translation Tables On the Custom Translation Table pages, you can edit the tables used to translate raw sensor data to engineering units for inputs associated with Non-Linear, Custom Table sensor/actuator types. SE6104 Control Module Rev. 3/29/2005 16 2005 Automated Logic Corporation

To communicate through the local access port Using a computer and an APT, you can communicate locally with the SE6104 to download memory or to troubleshoot. PREREQUISITES A computer with an RS232 port An APT with cables. See the APT Technical Instructions (http://info.automatedlogic.com). 1 Connect the computer to the APT, and then the APT to the control module. Connect to the control module s Local Access port 9-pin APT cable Rnet adapter cable 8-pin APT cable 2 Set the APT's Mode Select switch to 485. 3 Set the APT's Exec. 4 Relay switch to Network. To set up a Local Access connection in WebCTRL 1 On the CFG tree, select Connections. 2 On the Configure tab, click Add. 3 From the Type drop-down list, select BACnet Local Access. 4 Optional: Edit the Description. 5 Type the computer's Port number where your APT is connected. 6 Set the Baud rate to 115200. 7 Click Accept. 8 On the View tab, click the drop-down arrow next to your device's network Connection, then select BACnet Local Access. 9 Click Accept. 10 On the Configure tab, select BACnet Local Access, then click Start. Troubleshooting If you have problems mounting, wiring, or addressing the SE6104, contact ALC Technical Support. SE6104 Control Module Rev. 3/29/2005 17 2005 Automated Logic Corporation

Formatting the control module If you cannot communicate with a control module after downloading memory to it, as a last resort, you can manually format the control module to erase its memory. 1 Turn off the SE6104's power. Make sure the address switches are not set to 0, 0. 2 Hold down the Format button while you turn the control module s power on. 3 Continue to hold down the Format button until the Error LED stops flashing and turns on, then release the button. 4 Download memory to the SE6104. LED's The LED's on the SE6104 show the status of certain functions. If this LED is on... Power Rx Tx DO# Status is... The SE6104 has power The SE6104 is receiving data from the network segment The SE6104 is transmitting data over the network segment The digital output is active The Run and Error LED's indicate control module and network status. If Run LED shows... And Error LED shows... Status is.. 2 flashes per second Off Normal 2 flashes per second 2 flashes, alternating with Run LED 2 flashes per second 3 flashes, then off 2 flashes per second 4 flashes, then pause Five minute auto-restart delay after system error Control module has just been formatted Two or more devices on this network have the same ARC156 network address 2 flashes per second On Exec halted after frequent system errors or control programs halted 5 flashes per second On Exec start-up aborted, Boot is running 5 flashes per second Off Firmware transfer in progress, Boot is running 7 flashes per second 7 flashes per second, alternating with Run LED 14 flashes per second 14 flashes per second, alternating with Run LED Ten second recovery period after brownout Brownout SE6104 Control Module Rev. 3/29/2005 18 2005 Automated Logic Corporation

Manufacture date When troubleshooting, you may need to know a control module's manufacture date. Obtain the manufacture date from a... Module status report (modstat) Sticker on the back of the main control module board Notes To obtain a modstat in WebCTRL: 1. Select the control module in the NET tree. 2. Press CtrlM. 3. Type modstat. 4. Click OK. The report shows the date under Main board hardware. The first three characters on the sticker show the control module type. The next three characters show the year, month, and day of manufacture. (The month digit is in hexadecimal format.) Compliance This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. CAUTION Changes or modifications not expressly approved by the responsible party for compliance could void the user s authority to operate the equipment. SE6104 Control Module Rev. 3/29/2005 19 2005 Automated Logic Corporation