A is a power electronics device that behaves as a real battery pack. CINERGIA s is based on a regenerative power supply. When emulating a battery charge, the energy will be injected back to the electrical grid consuming a sinusoidal current with unity power factor and low harmonic distortion. Using a will save space in the laboratory, avoiding safety issues of real batteries and allow a high flexibility in the tests. FUNCTIONAL DESCRIPTION Operation modes: -Constant Voltage (CV) -Static -Dynamic Three channels: The three channels can be configured independently, allowing emulation of different batteries at the same time The three channels can be configured in parallel, emulating one single battery with 3 times the rated current capabilityv Static mode: the emulated battery voltage will depend on the open-circuit voltage and internal charge and discharge virtual resistance. KEY FEATURES 6.75 160 kw 2 Quadrant Power Supply Regenerative up to 100% rated power 1 channel Output: 0 to 750V, 0 to ±555A 3 channels Output: 0 to 750V, 0 to ±A/ch Constant Voltage, Static, and Dynamic modes Dynamic mode: the emulated battery voltage will depend on the State Of Charge, rate of discharge and internal charge and discharge virtual resistance. CINERGIA Pintor Roig i Soler, 10 08916, Badalona, BARCELONA cinergia@cinergia.coop T. +34 934 864 358
CONCEPTUAL SCHEMATIC GRID AC EQUIPMENT UNDER TEST (EUT) BACK-TO-BACK TOPOLOGY Recommended The equipment is formed by two IGBT-based power stages: a grid-side Active Rectifier producing sinusoidal currents with low harmonic distortion and close to unity power factor; and three output converters generating three independent channels. Thanks to the bidirectionality of this topology the test energy can be injected back to the grid. TECHNICAL DIAGRAM AC IN (GRID side) OUT (EUT side) 3P+ N 3CH-COM filter -U -U filter CH1 CH2 CH3 Com_neg Current Drivers x 6 Voltage Drivers x 6 sensor x 2 Current Voltage DSP control CAN DSP control Voltage HMI MODBUS/TCP ETHERNET AC Input is connected to the grid (isolation transformer with neutral is recommended) Output is connected to the Equipment Under Test (EUT) and can be used as: - Independent channels mode: three 2Q channels with a common negative - Parallel channels mode: one 2Q channel (3 times rated current per phase)
USER INTERFACE CABINET Local 3.2 Touchscreen panel Remote Control port: LAN Ethernet with Modbus/TCP protocol. Digital IO port: -4 digital inputs -3 relay outputs -1 Emergency stop Cooling The power supply is air-cooled internally. Mechanical housing The power supplies are housed in compact cabinets with wheels up to 120kVA for easier transportation. Optional analog port: -1 analog input 0-10V -3 analog outputs 0-10V Optional communications: RS485, RS232, CAN, LabView SOFTWARE INTERFACE Windows 7/10 user interface for remote operation and data acquisition. STATIC MODE The battery is emulated through a simplyfied model based on fixed Voc and charge/discharge resistors. Voc Rch Rdisch + Vout - DYNAMIC MODE A model based on battery manufacturer data allows realistic voltage and SOC behaviour. OPERATION AREA: 1/3 CHANNELS 800.0 700.0 600.0 Output voltage (V) 500.0 400.0 300.0 Minimum voltage at rated power 200.0 100.0-1ch mode 0.0-3ch mode 0 3ch mode 1ch mode Output current (A)
RANGE AND SPECIFICATIONS MAGNITUDE VALUE ower (grid side) 7.5kVA-200kVA Input side (GRID side) AC Voltage Rated 3x400Vrms+Neutral+Earth Voltage range +15% / -20 % Rated AC Current Depends on model (see table) 10-290Arms per phase Frequency 48-62Hz THDi (at rated power) <3% Power Factor Typical at rated power 0.99 Configurable by user 0-1 (capacitive/inductive) Efficiency (at rated power) >92% Overload 125% for 10 min / % for 60 s Output side (EUT side) Voltage Channel-Com_neg 20 to 750V ( 60kVA) Channel-Com_neg 40 to 750V (>60kVA) Minimum voltage at rated power1 320V Current Parallel channels mode 0 to ±555A global Independent channels mode 0 to ±A per channel Overcurrent 110% during 1 min Operation Modes Range2 Resolution3 Ripple3 Constant Voltage 5-100% <±0.1% <1% Static 5-±100% <±0.1% <1% Dynamic 5-±100% <±0.1% <1% Response time Rated resistance load 1-5ms (10-90%) General Measurements User interface Input Voltage (Vrms) and Current (Irms) Input and Output Power Output Voltage and Current Temperatures 3.2 Touchscreen Local Control port: 4 digital inputs, 3 relay outputs (Option for AIO) Communication Port: Ethernet (Optionals: RS485, RS232, CAN) Communication Protocol: Modbus/TCP 10-90% (Absolute maximum, without condensation) 5-35 ºC (Absolute maximum) Forced air Over Current, Over Voltage, Shortcircuit, Overtemperature Humidity Temperature Cooling Protections Standards CE Marking Safety EN-62040-1-2, EN-60950-1 : EN-62040-2 1 Below minimum voltage the power is limited by the rated current of the unit. Contact us for further detail 2 Range is related to rated values of each model as defined in table MODELS 3 Resolution and ripple are related to the FS of each model. Contact us for further information.
MODELS REFERENCE 7.5 10 15 20 30 40 50 60 80 100 120 160 200 RATED kva 7.5 10 15 20 30 40 50 60 80 100 120 160 200 kw 6.75 9 13.5 18 27 36 45 54 72 90 108 128 160 GALVANIC ISOLATION (recommended) RATED CURRENT Independent mode Parallel mode 0-750v 0-750v ±10A ±15A ±20A ±25A ±30A ±38A ±47A ±57A ±105A ±130A ±130A ±155A ±A ±30A ±45A ±60A ±75A ±90A ±115A ±140A ±180A ±315A ±390A ±390A ±465A ±555A WEIGHT kg 265 290 290 540 550 DIMENSIONS DxWxH (mm) 770x450x1100 880x590x1320 850x900x2000 REFERENCE RECOMMENDED CIRCUIT BREAKER WEIGHT kg DIMENSIONS DxWxH (mm) IT7.5 IT10 IT15 IT20 IT30 IT40 IT50 IT60 IT80 IT100 IT120 IT160 IT200 Type C - 25A Type C - 25A Type C - 32A Type C - 40A Type D - 80A Type D - 100A Type D - 125A Type D - 160A Type D - 200A Type D - 250A Type D - 315A Type D - 400A Type D - 500A (*) The transformer is delivered in a stand-alone cabinet IP23 174 217 280 381 435 458 514 612 753 Inside the cabinet 595x415x708 (*) 789x490x865 (*) 964x684x1252 (*) 1192x744x1430 (*) OPTIONS Galvanic Isolation (recommended) Isolation monitor Isolated analog inputs RS485, RS232, CAN Labview drivers