elion product family emote monitoring and control EC615 Protection of cable feeders with superior fault detection and location
U12 0. 0 kv P 0.00 kw Q 0.00 kvar I2 0 A ESC A 1 15 AN DC IN CONSOE/S1 S2 1 5 1 5 0 1 6 9 6 9 + CONSOE/S1 ø OFF ON 1 Compact and versatile solution for making grids smarter EC615 is a grid automation protection and control relay designed for remote control and monitoring, protection, fault indication, power quality analyzing and automation in medium voltage secondary distribution systems. EC615 is suitable for a wide variety of power distribution networks, which can include distributed power generation, secondary equipment such as medium voltage disconnectors, switches and ring main units. EC615 is a member of the elion product family. The elion family relays have been designed to unleash the full potential of the IEC 61850 standard for communication and interoperability between substation automation devices. Application With EC615, grid reliability is enhanced, ranging from basic, non-directional overload protection to extended protection functionality with power quality analyses. Thus, EC615 meets today s requirements for smart grids and supports the protection of cable feeders in isolated neutral, resistanceearthed, compensated and solidly earthed networks. EC615 is freely programmable with horizontal GOOSE communication, thus enabling sophisticated interlocking functions. The new adaptable standard configurations allow for this relay to be taken into use as soon as the application-specific parameters have been set. EC615 provides superior fault location, isolation and restoration (FI) to lower the frequency and shorten the duration of power outages. EC615 also includes advanced earth-fault detetion methods that can detect developing faults in the network before they cause an outage. EC615 offers a variety of features to enhance grid reliability and functionality. Multiple controllable objects (up to nine objects including one breaker) Sophisticated protection functionality to detect, isolate and restore power in all types of networks Integrated power quality measurement, including voltage dips and swells logging Freely programmable oad profile and event logging Flexible autoreclosing function Six easily manageable setting groups Adaptable standard configurations for rapid commissioning Web-based parametrization tool with download possibility Same configuration tools as for other elion product family relays such as the 615, 620 and 630 series Cyber security features such as audit trail Withdrawable-unit design arge, easy-to-read CD screen with SD, local control and parametrization possibilities with dedicated push buttons for safe and easy operation IEC 60870-5-101/104, DNP3 level 2, Modbus or IEC 61850 with GOOSE messaging communication for high-speed protection, fault isolation and restoration Extendable I/O with IO600 Environmentally-friendly design with ohs compliance Human Machine Interface As a member of the elion product family, EC615 shares the same Human Machine Interface (HMI) look and feel as the other elion family relays. This has the added benefit that once you become familiar with one elion relay, you can use them all. Secondary Switchgear M M I IEC 60780-5-104 One breaker and up to eight load-break switches can be controlled via the relay s front panel HMI or a remote control system. To protect the relay from unauthorized access and to maintain the integrity of information, the relay is provided with a four-level, role-based user authentication system, with individual passwords for the viewer, operator, engineer and administrator levels. The access control system applies to the front panel HMI, embedded Web browser-based HMI and Protection and Control IED Manager PCM600. O EC615 E601 Standardized communication EC615 supports a variety of communication protocols for remote communication, such as IEC 60870-5-101/104, DNP3 level 2 and Modbus, simultaneously also supporting IEC 61850 with GOOSE messaging. 2 emote monitoring and control EC615
Open IA=0A IB=0A IC=0A IG=0. 0A VAB=0.00kV VBC=0. 00kV VCA=0. 00kV 3P=0kW 3Q=0kVAr Configuration System HMI Time Authorization ESC A Function overview Source EC615 Version 1.1 EMOTE MONITING AND CONTO EAY STANDAD CONFIGUATION C POTECTION OCA HMI ASO AVAIABE 3I Master Trip ockout relay 94/86 I2> 46 3I> 51P-1 I2/I1> 46PD 3I> 67-1 3Ith>F 49F 3I>> 51P-2 3I>>> 50P/51P 3I>> 67-2 IEC I O ANSI Close ESC U12 0. 0 kv P 0.00 kw Q 0.00 kvar I2 0 A ESC EF615 A Menu I O - Disturbance recorder - Event log - Fault recorder - elay self-supervision - oad profile - ocal/emote push-button on HMI - ecorded data - User management - Web HMI AND 3I2f> 68 Help Io Io>>> 50N/51N Io>> Io>> 51N-2 67N-2 Yo> 21YN Io> 51N-1 Po> 32N Io> 67N-1 Io> IEF 67NIEF Io>HA 51NHA 3I U 1 U 2 U 3 CONDITION MONITING AND SUPEVISION FUSEF 60 CBCM CBCM PHSVP PHSVP TCS TCM CONTO AND INDICATION 1) COMMUNICATION 0 0 1 1 1 0 0 1 0 1 0 0 1 1 1 0 1 0 1 1 0 1 1 0 1 0 1 0 0 0 1 1 0 1 1 0 0 1 0 Protocols: Master: IEC 61850-8-1 Slave: IEC 101, IEC 104, Modbus, DNP3 evel 2 Interfaces: Ethernet: TX (J-45), FX (C) Serial: Serial glass fiber (ST), S-485, S-232/485 D-sub 9, IIG-B MEASUEMENT Uo> 59G Uo Object Ctrl 2) Ind 3) CB 1 - DC 8 - - I, U, Io, P, Q, E, pf, f - Symmetrical components - imit value supervision - Power Quality functions ES - 8 Analog interface types 1) 1) Check availability of binary inputs/outputs from technical documentation 2) Control and indication function for primary object 3) Status indication function for primary object Current sensor 3 Voltage sensor 3 Current transformer 1 1) Combi sensor inputs with conventional Io input U 1 U 2 U 3 3U< 27 U2> 47O- U1< 47U+ O I 79 ATSABTC ATSABTC PQM3I PQM3I PQM3U PQM3V PQMU PQMV 3U> 59 f>/f<, df/dt 81 PQUUB PQVUB EMAKS oad FOC 21F 6 MAP MAP MVI4 MVI4 8 MV MV 1 SCA4 SCA4 UFS/ 81SH Optional function No. of instances Calculated value Io/Uo Alternative function to be defined when ordering Function overview of EC615 emote monitoring and control EC615 3
Standard configurations 1, 2,... = number of included instances ( ) = optional Software configuration Code EC615 Function IEC 61850 IEC 60617 IEC-ANSI A B C Protection Three-phase non-directional overcurrent protection, low stage PHPTOC 3I> 51P-1 1 1) 1 1) 1 1) Three-phase non-directional overcurrent protection, high stage PHHPTOC 3I>> 51P-2 1 1) 1 1) 1 1) Three-phase non-directional overcurrent protection, instantaneous stage PHIPTOC 3I>>> 50P/51P 1 1 1 Three-phase directional overcurrent protection, low stage DPHPDOC 3I> 67-1 (2) (2) (2) Three-phase directional overcurrent protection, high stage DPHHPDOC 3I>> 67-2 (1) (1) (1) Non-directional earth-fault protection, low stage EFPTOC Io> 51N-1 1 2) 1 2) 1 2) Non-directional earth-fault protection, high stage EFHPTOC Io>> 51N-2 1 2) 1 2) 1 2) Non-directional earth-fault protection, instantaneous stage EFIPTOC Io>>> 50N/51N 1 1 1 Directional earth-fault protection, low stage DEFPDEF Io> 67N-1 (2) (2) (2) Directional earth-fault protection, high stage DEFHPDEF Io>> 67N-2 (1) (1) (1) Transient/intermittent earth-fault protection INTEPDEF Io> IEF 67NIEF (1) (1) () Admittance based earth-fault protection EFPADM Yo> 21YN (3) (3) (3) Wattmetric based earth-fault protection WPWDE Po> 32N (3) (3) (3) Harmonics based earth-fault protection HAEFPTOC Io>HA 51NHA (1) (1) (1) Negative-sequence overcurrent protection NSPTOC I2> 46 2 2 2 Phase discontinuity protection PDNSPTOC I2/I1> 46PD 1 1 1 esidual overvoltage protection OVPTOV Uo> 59G (1) (2) 4) (1) Three-phase undervoltage protection PHPTUV 3U< 27 (3) (3) 3) (3) Three-phase overvoltage protection PHPTOV 3U> 59 (3) (3) 3) (3) Positive-sequence undervoltage protection PSPTUV U1< 47U+ (1) (1) (1) Negative-sequence overvoltage protection NSPTOV U2> 47O- (1) (1) (1) Frequency protection FPFQ f>/f<,df/dt 81 (2) (2) (2) Three-phase thermal protection for feeders, cables and distribution T1PTT 3Ith>F 49F 1 1 1 transformers Three-phase inrush detector INPHA 3I2f> 68 1 1 1 Master trip TPPTC Master Trip 94/86 2 2 2 Multi-purpose protection MAPGAPC MAP MAP 6 6 6 oad-shedding and restoration SHDPFQ UFS/ 81SH (1) (1) (1) Fault locator SCEFFO FOC 21F (1) (1) (1) 4 emote monitoring and control EC615
1, 2,... = number of included instances ( ) = optional Software configuration Code EC615 Function IEC 61850 IEC 60617 IEC-ANSI A B C Power Quality Current total demand distortion CMHAI PQM3I PQM3I (1) (1) (1) Voltage total harmonic distortion VMHAI PQM3U PQM3V (1) (1) (1) Voltage variation PHQVV PQMU PQMV (1) (1) (1) Voltage unbalance VSQVUB PQUUB PQVUB (1) (1) (1) Control Circuit-breaker control CBXCB I O CB I O CB 1 1 1 Disconnector control DCXSWI I O DCC I O DCC 8 8 8 Earthing switch indication ESSXSWI I O ES I O ES 8 8 8 Auto-reclosing DAEC O I 79 (1) (1) (1) Synchronism and energizing check SECSYN SYNC 25-1 - Automatic transfer switch function ATSABTC ATSABTC ATSABTC (1) (1) (1) Condition Monitoring and Supervision Circuit-breaker condition monitoring SSCB CBCM CBCM 2 2 2 Trip circuit supervision TCSSCB TCS TCM 2 2 2 Fuse failure supervision SEQFUF FUSEF 60 1 1 1 Measurement Disturbance recorder DE D DF 1 1 1 Three-phase current measurement CMMXU 3I 3I 1 1 1 Sequence current measurement CSMSQI I1, I2, I0 I1, I2, I0 1 1 1 esidual current measurement ESCMMXU Io In 1 1 1 Three-phase voltage measurement VMMXU 3U 3V 1 2 4) 1 Sequence voltage measurement VSMSQI U1, U2, U0 V1, V2, V0 1 2 4) 1 Three-phase power and energy measurement PEMMXU P, E P, E 1 1 1 Frequency measurement FMMXU f f 1 1 1 oad profile DPMSTA OADPOF OADPOF 1 1 1 1) Is not available when choosing optional directional E/F function 2) Is not available when choosing optional directional O/C function 3) Voltage group B is used in the third (3) instance 4) Voltage group B is used in the second (2) instance Note that all directional protection functions can also be used in non-directional mode. The instances of a protection function represent the number of identical function blocks available in the standard configuration. emote monitoring and control EC615 5
Contact us For more information see the Product Guide or contact us: ABB Oy, Medium Voltage Products Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone: +358 10 22 11 Fax: +358 10 22 41094 www.abb.com/mediumvoltage www.abb.com/substationautomation 1MS757953 C 1.1 Copyright 2015 ABB. All rights reserved.