Thermistor motor protection relay CM-MSS.41

Similar documents
Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Thermistor motor protection relay CM-MSS.21

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Thermistor motor protection relays CM-MSS.32 and CM-MSS.33

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Thermistor motor protection relay CM-MSS.11

Thermistor motor protection relay CM-MSS.41

Thermistor motor protection relays CM-MSS.32 and CM-MSS.33

Thermistor motor protection relay CM-MSS.31

Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages

Electronic timer CT-ERS.12 ON-delayed with 1 c/o (SPDT) contact

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact

Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts

Electronic timer CT-SDS.23 Star-delta change-over with 2 n/o contacts

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

Electronic timer CT-SDD.22 Star-delta change-over with 2 n/o contacts

Electronic timer CT-ARE OFF-delayed without auxiliary voltage, 1 c/o (SPDT) contact

Switching relay CT-IRE with 1 c/o (SPDT) contact

Messaging module CP-C MM

Electronic timer CT-ERS.21

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

Electronic timer CT-ARS.11

Electronic timer CT-ERD.12

Three-phase monitoring relay

Electronic timer CT-AHD.22

Power supply CP-E 48/1.25 Primary switch mode power supply

Redundancy unit CP-A RU

Power supply CP-D 12/2.1 Primary switch mode power supply

Power supply CP-E 24/0.75 Primary switch mode power supply

RTU500 series Data Sheet Power Supply CP-E 24/2.5

Power supply CP-E 24/10.0 Primary switch mode power supply

Contact protection relay

Buffer module CP-B 24/20.0, ultra-capacitor based Accessory for power supplies (e.g. switch mode power supplies CP range)

Redundancy unit CP-D RU Accessory for CP range power supplies (e.g. switch mode power supplies CP-D range)

Boxed interface relays and optocouplers R600 Boxed slim relays, optocouplers and accessories

Switching relay CT-IRS with 1, 2 or 3 c/o contacts Data sheet

Pluggable interface relays CR-P Pcb relays

Power supply CP-C 24/5.0

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet

Pluggable interface relays and optocouplers CR-P Pcb relays, optocouplers and accessories

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet

Pluggable interface relays CR-M Miniature relays

Accessories for pluggable interface relays CR-P Sockets

Electronic timer CT-AWS Impulse-OFF with 2 c/o contacts Data sheet

Power supply CP-C 24/5.0

Electronic timer CT-ERD ON-delayed with 1 c/o contact Data sheet

Electronic timer CT-VWD Impulse-ON with 1 c/o contact Data sheet

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

RE22R2KMR Off-delay Timing Relay s 10min V AC/DC - 2C/O

Control elements. Fine adjustment. Status indication. 24 V DC typ. 0,25 W / 0,25 VA. 24 V DC typ. 0,03 W / 0,09 VA. 0,15 3 s. 0,5 10 h.

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

RE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

RE22R2CMR Off-delay Timing Relay s 300h V AC/DC - 2C/O

MINI-PS AC/10-15DC/8

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

VEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA

RM22LA32MR Level control relay RM22-L V AC/DC - 2 C/O

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

TU531, TU532 Terminal Unit

Electronic timers CT range

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

RTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.

RE22R2QTMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

TRIO-DIODE/12-24DC/2X10/1X20

DI572 Digital Input Module

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

VEO. V2ZS V AC/DC Art.Nr.: V2ZS20P V AC/DC Art.Nr.: TECHNICAL DATA

Bulletin 817 Thermistor Protection Relay

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

VEO. V2UF230V10 Art.Nr.: TECHNICAL DATA

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

PHOENIX CONTACT Features

PHOENIX CONTACT - 07/2006

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

TF501, TF521 Terminal Bases

DC561, digital input/output module,

AO523 Analog Input Module

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

DC562, digital input/output module,

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

AI561 Analog Input Module

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

DI561 Digital Input Module

DX561 Digital Input/Output Module

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1

QUINT-BUFFER/24DC/24DC/40

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

ABB i-bus KNX HCC/S Heating/cooling circuit controller

Accessories for pluggable interface relays CR-P, CR-M Pluggable function module

PHOENIX CONTACT - 01/2007

Output Voltage* (nom.)(adjustable)

Accessories for pluggable interface relays CR-U Pluggable function modules

02/11/2015

02/11/2015

Transcription:

Data sheet Thermistor motor protection relay CM-MSS.41 The thermistor motor protection relay CM-MSS.41 monitors the winding temperature of motors and protects them from overheating, overload and insufficient cooling. The device is available with two different terminal versions. You can choose between the proven screw connection technology (double-chamber cage connection terminals) and the completely tool-free Easy Connect Technology (push-in terminals). 2CDC 251 013 V0014 Characteristics 1 measuring circuit Test / Reset button Auto, manual or remote reset configurable Short-circuit monitoring of the sensor circuit, configurable Dynamic interrupted wire detection Non-volatile fault storage, configurable Easy configuration via DIP switches LEDs to distinguish between different failure causes Overvoltage protected supply and measuring inputs Increased interference immunity acc. to EN 62061 with evaluation criterion "Fail-Safe" According to the latest version of the product standard IEC 60947-8 Screw connection technology or Easy Connect Technology available Housing material for highest fire protection classification UL 94 V-0 Tool-free mounting on DIN rail as well as demounting 22.5 mm (0.89 in) width Approvals A UL 508, CAN/CSA C22.2 No.14 C GL R EAC K E CCC I Marks a b CB scheme ATEX CE RCM Order data Type Rated control supply voltage Output contacts Connection technology Order code CM-MSS.41P 24-240 V AC/DC 2 c/o (SPDT) contacts Push-in terminals 1SVR740712R1200 CM-MSS.41S Screw terminals 1SVR730712R1200

Connection technology Maintenance free Easy Connect Technology with push-in terminals Type designation CM-xxS.yyP Approved screw connection technology with double-chamber cage connection terminals Type designation CM-xxS.yyS 2CDC 253 026 F0011 2CDC 253 025 F0011 Push-in terminals Tool-free connection of rigid and flexible wires with wire end ferrule according to DIN 46228-1-A, DIN 46228-4-E Wire size: 2 x 0.5-1.5 mm², (2 x 20-16 AWG) Easy connection of flexible wires without wire end ferrule by opening the terminals No retightening necessary One operation lever for opening both connection terminals For triggering the lever and disconnecting of wires you can use the same tool (Screwdriver according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in)) Constant spring force on terminal point independent of the applied wire type, wire size or ambient conditions (e. g. vibrations or temperature changes) Opening for testing the electrical contacting Gas-tight Double-chamber cage connection terminals Terminal spaces for different wire sizes: fine strand with/without wire end ferrule: 1 x 0.5-2.5 mm² (2 x 20-14 AWG), 2 x 0.5-1.5 mm² (2 x 20-16 AWG) rigid: 1 x 0.5-4 mm² (1 x 20-12 AWG), 2 x 0.5-2.5 mm² (2 x 20-14 AWG) One screw for opening and closing of both cages Pozidrive screws for pan- or crosshead screwdrivers according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in) Both the Easy Connect Technology with push-in terminals and screw connection technology with double-chamber cage connection terminals have the same connection geometry as well as terminal position. 2 - Thermistor motor protection relay CM-MSS.41 Data sheet

Functions Operating controls 1 Test / Reset button Reset - only possible if measured value < switch-on resistance 2 Indication of operational states with LEDs U: green LED - Status indication of control supply voltage V Control supply voltage applied F: red LED - Fault message R: yellow LED - Status indication of the output relay 1 3 DIP switches (see DIP switch functions) 2CDC 251 013 V0014 2 3 Application / Monitoring function The thermistor motor protection relay CM-MSS monitors the winding temperature and thus protects the motor from overheating, overload and insufficient cooling in accordance to the product standard IEC 60947-8, control units for built-in thermal protection (PTC) for rotating electrical machines. Operating mode The thermistor motor protection relay CM-MSS.41 is used to monitor the temperature of motors or generators equipped with PTC resistor sensors type A. The sensors are built-in into the motor windings, measuring the motor heating. In case of an increase of the temperature in the motor, the resistance of the PTC sensors will increase as well. If the motor heatsup excessively (>2.83 kh) the output relays de-energize and the corresponding LED displays the overtemperature. A short circuit and an interrupted wire within the sensor circuit can also be detected. A reset is only possible after cooling down of the motor (<1.1 kh) or after a wire interruption or a short circuit within the sensor circuit has been removed. A reset after tripping can be done manually with the Test / Reset button, externally with a push button between S1 and T2, or automatically by jumpering S1 and T2. By pressing the front-face combined Test / Reset button a system test routine is executed. Short-circuit detection x If a short circuit is detected between the two lines of a sensor circuit, the output relays de-energize and the LEDs will display the specific error code. Dynamic interrupted wire detection During the operation the device is permanently monitoring the measuring circuit. If the resistance in the measuring circuit rises, the device distinguishes if there is an overtemperature or an interrupted wire. Then the output relays de-energize. Data sheet Thermistor motor protection relay CM-MSS.41-3

Test function The test function is only possible when there is no fault. By pressing the front-face combined Test / Reset button or by jumpering S1-T2 a system test routine is executed. If S1-T2 are jumpered for the automatic reset, the test function can only be executed by pressing the Test / Reset button. After starting the test routine the output relays de-energize. They remain de-energized until control input S1-T2 is closed or a reset is executed. Fault storage f, reset function The fault storage is designed as non-volatile (remanent). This means that after switch-off and return of the control supply voltage the device returns to the state it was prior to the switch-off. If prior to the interruption of control supply voltage there was no fault, the device restarts automatically after re-applying control supply voltage. If there was a fault prior to the interruption, reset can be made manually by the Test / Reset button or externally by remote reset between S1-T2. With deactivated fault storage reset can be made manually by the Test / Reset button, automatically by jumpering S1-T2 or externally by remote reset between S1-T2. Depending on the configuration of DIP switch 1, there are several possibilities of resetting the device, as shown in the picture. DIP switch 1 e f S1 T2 1.) Front 2.) Remote 3.) A1-A2 1.) Front 2.) Remote S1 T2 S1 T2 1.) Front 2.) A1-A2 1.) Auto- Reset 1.) Front 2CDC 252 036 F0214 Electrical connection A1 11 21 T2 T1 T1 A1 11 21 A1 A2 Control supply voltage 11 12/14 1st c/o (SPDT) contact 21 22/24 2nd c/o (SPDT) contact S1 T2 (jumpered) Automatic reset T1 T2 Measuring circuit S1 ϑ T2 A2 12 14 22 24 24 22 S1 14 12 A2 2CDC 252 019 F0014 Connection diagram CM-MSS.41 4 - Thermistor motor protection relay CM-MSS.41 Data sheet

DIP switches ON OFF (default) DIP switch 4 DIP switch 3 DIP switch 2 DIP switch 1 y Short-circuit detection de-activated x Short-circuit detection activated e Non-volatile fault storage de-activated f Non-volatile fault storage activated Indication of operational states LEDs, status information and fault messages Operational State U: LED green F: LED red R: LED yellow Absence of control supply voltage OFF OFF OFF No fault V OFF V Short circuit V Y OFF Interrupted wire V Z OFF Overtemperature V V OFF Test function X OFF OFF Fault rectified but not confirmed V 1) X Change of configuration not confirmed V OFF X Control supply voltage not within the tolerance range X V OFF Internal fault 2) OFF W W Internal fault 2) X X X 1) Depending on the fault 2) Restart the device. If after restart the same fault is indicated, replace the device Data sheet Thermistor motor protection relay CM-MSS.41-5

Function diagrams A1-A2 2830 Ω 1100 Ω R [Ω] 19 Ω 12 Ω Test / Reset button S1-T2 11-14 / 21-24 11-12 / 21-22 1 Tripping caused by overtemperature 2 Control supply voltage interrupted 3 Test (outputs are switched off) 1 2 5 3 5 4 5 4 Short-circuit in sensor circuit 5 Reset (resets fault) - manually with front-face Test / Reset button or - externally by a remote reset between terminal S1-T2 2CDC 252 041 F0214 Manual or remote reset (= non-volatile fault storage) A1-A2 2830 Ω 1100 Ω R [Ω] 19 Ω 12 Ω Test / Reset button S1-T2 11-14 / 21-24 11-12 / 21-22 1 2 3 4 1 Tripping caused by overtemperature 2 Control supply voltage interrupted 3 Test (outputs are switched off) 4 Short-circuit in sensor circuit 2CDC 252 042 F0214 Auto reset (= no fault storage) 6 - Thermistor motor protection relay CM-MSS.41 Data sheet

Example of application Circuit diagram V+ A1 11 21 T1 M 3~ µc t T2 24 22 V- Test / Reset S1 A2 14 12 2CDC 252 015 F0014 Data sheet Thermistor motor protection relay CM-MSS.41-7

Technical data Data at T a = 25 C and rated values, unless otherwise indicated Input circuit Supply circuit Rated control supply voltage U s A1-A2 24-240 V AC/DC Rated control supply voltage U s tolerance -15...+10 % Rated frequency 15-400 Hz Typical current / power consumption 24 V AC/DC 33 ma / 0.55 VA 220-240 V AC 11 ma / 1.6 VA Electrical insulation between supply circuit and measuring circuit yes Power failure buffering time 20 ms Measuring circuit / Sensor circuit T1-T2 Number of sensor circuits 1 Sensor type PTC type A (DIN/EN 44081, DIN/EN 44082) Max. total resistance of sensors connected in series, cold state < 750 h Overtemperature monitoring switch-off resistance (relays de-energize) 2.83 kh w 1% switch-on resistance (relays energize) 1.1 kh w 1% Short-circuit detection configurable switch-off resistance (relays de-energize) <12 h switch-on resistance (relays energize) >19 h Interrupted wire detection switch-off resistance (relays de-energize) dynamic switch-on resistance (relays energize) not available Non-volatile fault storage configurable Test function yes Maximum voltage in sensor circuit 1.33 kohm 2.5 V 4 kohm 3.7 V y kohm 5.5 V Maximum current in sensor circuit 3.7 ma Maximum sensor cable length 2 x 100 m at 0.75 mm ², 2 x 400 m at 2.5 mm ² Accuracy within the rated control supply voltage tolerance 0.50 % Accuracy within the temperature range 0.01 %/K Repeat accuracy (constant parameters) on request Reaction time of the safety function <100 ms Hardware fault tolerance (HFT) 0 Control circuit S1 - T2 Control function manual reset yes auto reset adjustable remote reset adjustable Maximum no-load voltage (S1-T2 open) 5.5 V Max. current (S1-T2 jumpered) 0.6 ma Maximum cable length 2 x 100 m at 0.75 mm ², 2 x 400 m at 2.5 mm ² User interface Indication of operational states Control supply voltage U LED green Relay status R LED yellow Fault message F See LEDs, status information and fault messages on page 5 Operating controls Test / Reset front-face button Configuration of DIP switch 1 non-volatile fault storage DIP switch 2 short-circuit detection 8 - Thermistor motor protection relay CM-MSS.41 Data sheet

Output circuit Kind of output 11-12/14 relay, 1st c/o (SPDT) contact 21-22/24 relay, 2nd c/o (SPDT) contact Operating principle closed-circuit principle Contact material AgNi alloy, Cd free Rated operational voltage U e (IEC/EN 60947-1) 250 V AC Minimum switching voltage / Minimum switching current 24 V / 10 ma Maximum switching voltage / Maximum switching current See Load limit curves on page 12 Rated operating current I e (IEC/EN 60947-5-1) AC-12 (resistive) at 230 V 4 A AC-15 (inductive) at 230 V 3 A DC-12 (resistive) at 24 V 4 A DC-13 (inductive) at 24 V 2 A AC Rating (UL 508) utilization category (Control Circuit Rating Code) B 300 maximum rated operational voltage 250 V AC maximum continuous thermal current at B 300 4 A maximum making/breaking apparent power at B 300 3600/360 VA Mechanical lifetime 30 x 10 6 switching cycles Electrical lifetime at AC12, 230 V AC, 4 A 0.1 x 10 6 switching cycles Maximum fuse rating to achieve short-circuit protection n/c contact 10 A fast-acting n/o contact 10 A fast-acting General data MTBF on request Duty time 100 % Dimensions (W x H x D) product dimensions 22.5 x 85.6 x 103.7 mm (0.89 x 3.37 x 4.08 in) packaging dimensions 97 x 109 x 30 mm (3.82 x 4.29 x 1.18 in) Weight Screw connection technology Easy Connect Technology (push-in) net weight 0.141 kg 0.130 kg gross weight 0.167 kg 0.157 kg Mounting DIN rail (IEC/EN 60715), snap-on mounting without any tool Mounting position any Minimum distance to other units vertical 10 mm (0.394 in) if switching current > 2 A horizontal 10 mm (0.394 in) if switching current > 2 A Material of housing UL 94 V-0 Degree of protection housing IP50 terminals IP20 Electrical connection Screw connection technology Easy Connect Technology (push-in) Wire size fine strand with(out) wire end ferrule 1 x 0.5-2.5 mm² (1 x 20-14 AWG) 2 x 0.5-1.5 mm² (2 x 20-16 AWG) 2 x 0.5-1.5 mm² (2 x 20-16 AWG) rigid 1 x 0.5-4 mm² (1 x 20-12 AWG) 2 x 0.5-2.5 mm² (2 x 20-14 AWG) 2 x 0.5-1.5 mm² (2 x 20-16 AWG) Stripping length 8 mm (0.32 in) Tightening torque 0.6-0.8 Nm (5.31-7.08 lb.in) - Wire end ferrule according to DIN 46228-1-A, DIN 46228-4-E Data sheet Thermistor motor protection relay CM-MSS.41-9

Environmental data Ambient temperature ranges operation -25 C...+60 C storage -40 C...+85 C Damp heat, cyclic (IEC/EN 60068-2-30) 6 x 24 h cycle, 55 C, 95 % RH Climatic category (IEC/EN 60721-3-3) 3K5 (no condensation, no ice formation) Vibration, sinusoidal (IEC/EN 60255-21-1) Class 2 Shock (IEC/EN 60255-21-2) Class 2 Isolation data Rated insulation voltage U i Supply circuit / Measuring circuit 1) 300 V AC (IEC/EN 60947-1, IEC/EN 60664-1) Supply circuit / Output circuits 300 V AC Measuring circuit 1) / Output circuits 300 V AC Output circuit 1 / Output circuit 2 300 V AC Rated impulse withstand voltage U imp Supply circuit / Measuring circuit 1) 4 kv / 6 kv (IEC/EN 60947-1, IEC/EN 60664-1) Supply circuit / Output circuits 4 kv / 6 kv Measuring circuit 1) / Output circuits 4 kv / 6 kv Output circuit 1 / Output circuit 2 4 kv Basic insulation (IEC/EN 60664-1) Supply circuit / Measuring circuit 1) 600 V AC Supply circuit / Output circuits 600 V AC Measuring circuit 1) / Output circuits 600 V AC Output circuit 1 / Output circuit 2 300 V AC Test voltage, routine test Supply circuit / Measuring circuit 1) 2.5 kv, 50 Hz, 1 min. (IEC/EN 60255-27, IEC/EN 61010-1) Supply circuit / Output circuits 2.5 kv, 50 Hz, 1 min. Measuring circuit 1) / Output circuits 2.5 kv, 50 Hz, 1 min. Test voltage, type test Supply circuit / Measuring circuit 1) 6 kv / 1.2-50 µs (IEC/EN 60255-27) Supply circuit / Output circuits 6 kv / 1.2-50 µs Measuring circuit 1) / Output circuits 6 kv / 1.2-50 µs Output circuit 1 / Output circuit 2 6 kv / 1.2-50 µs Protective separation Supply circuit / Measuring circuit 1) yes, up to 300 V (IEC/EN 61140, IEC/EN 50178) Supply circuit / Output circuits yes Measuring circuit 1) / Output circuits yes Output circuit 1 / Output circuit 2 no Pollution degree (IEC/EN 60664-1) 3 Overvoltage category (IEC/EN 60664-1) III 1) Potential of measuring circuit = Potential of control circuit Standards Product standard IEC/EN 60255-1; IEC/EN 60947-8 Low Voltage Directive EMC directive ATEX directive RoHS directive 2006/95/EC 2004/108/EC 94/9/EC 2011/65/EC 10 - Thermistor motor protection relay CM-MSS.41 Data sheet

Electromagnetic compatibility Interference immunity to IEC/EN 61000-6-1, IEC/EN 61000-6-2 electrostatic discharge IEC/EN 61000-4-2 Level 3, 6 kv contact discharge, 8 kv air discharge radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3, 10 V/m (1 GHz), 3 V/m (2 GHz), 1 V/m (2.7 GHz) electrical fast transient / burst IEC/EN 61000-4-4 Level 3, 2 kv / 5 khz surge IEC/EN 61000-4-5 Level 3, Installation class 3, supply circuit and measuring circuit 1 kv L-L, 2 kv L-N conducted disturbances, induced by radio-frequency IEC/EN 61000-4-6 Level 3, 0.15-80 MHz, 10 V, 80 % AM (1kHz) fields voltage dips, short interruptions and voltage variations IEC/EN 61000-4-11 Class 3 harmonics and interharmonics IEC/EN 61000-4-13 Class 3 Additional interference immunity according to product standard EN 60255-1 (reference on EN 60255-26_2011) radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 10 V/m (80 MHz - 3 GHz) conducted disturbances, induced by radio-frequency fields IEC/EN 61000-4-6 10 V at stated frequencies damped oscillatory waves IEC/EN 61000-4-18 Signal lines, symmetric coupling: 1 kv peak voltage Power supply, asymmetric coupling: 2.5 kv peak voltage, Increased interference immunity acc. to EN 62061 for safety with the evaluation criterion IEC/EN 61000-6-1, IEC/EN 61000-6-2 "Fail-Safe" against electrostatic discharge IEC/EN 61000-4-2 Level 3, 6 kv contact discharge, 8 kv air discharge radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3, 20 V/m (1 GHz), 6 V/m (2 GHz), 3 V/m (2.7 GHz) electrical fast transient / burst IEC/EN 61000-4-4 Level 3, 4 kv / 5 khz surge IEC/EN 61000-4-5 Level 3, Installation class 3, supply circuit and measuring circuit 2 kv L-L, 4 kv L-N conducted disturbances, induced by radio-frequency IEC/EN 61000-4-6 Level 3, 10 V fields voltage dips, short interruptions and voltage variations IEC/EN 61000-4-11 Class 3 harmonics and interharmonics IEC/EN 61000-4-13 Class 3 Interference emissions IEC/EN 61000-6-3, IEC/EN 61000-6-4 high-frequency radiated IEC/CISPR 22, EN 55022 Class B high-frequency conducted IEC/CISPR 22, EN 55022 Class B high-frequency radiated Germanischer Lloyd increased requirements in the emergency call frequency band Data sheet Thermistor motor protection relay CM-MSS.41-11

Technical diagrams Load limit curves V V 300 200 V V 300 200 100 80 60 50 40 30 100 80 60 50 40 30 20 10 0.1 0.2 0.5 1 2 4 6 10 I A 2CDC 252 194 F0205 20 10 0.1 0.2 0.5 1 2 4 6 10 I A 2CDC 252 193 F0205 AC load (resistive) DC load (resistive) 1.0 0.9 Switching cycles F 0.8 0.7 0.6 250 V resistive load 0.5 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 cos ϕ 2CDC 252 192 F0205 Switching current [A] 2CDC 252 148 F0206 Reduction factor F for inductive AC load Contact life time / number of operations N 220 V 50 Hz 1 AC, 360 operations/h 12 - Thermistor motor protection relay CM-MSS.41 Data sheet

Dimensions in mm and inches 113.4 4.47 105.9 4.17 22.5 0.89 85.6 3.37 103.7 4.08 2CDC 252 009 F0011 Accessories in mm and inches 22.5 0.89 8 0.32 4.8 0.19 6.5 0.256 62.5 2.461 60 2.362 70 2.756 10 11.5 0.394 0.453 20 0.787 2CDC 252 008 F0010 22.2 0.874 4T22 19.9 0.783 7.85 0.309 2CDC 252 020 F0011 68 2.68 front to back 110.5 4.31 2CDC 252 010 F0011 ADP.01 Adapter for screw mounting MAR.12 Marker label for devices with DIP switches COV.11 Sealable transparent cover Further documentation Document title Document type Document number Electronic products and relays Technical catalogue 2CDC 110 004 C02xx Operating and installation instructions CM-MSS.41 Instruction manual 1SVC 730 650 M0000 You can find the documentation on the internet at http://new.abb.com/low-voltage/products/epr/monitors/thermistor-motor-protection-relays CAD system files You can find the CAD files for CAD systems at http://abb-control-products.partcommunity.com/portal/portal/abb-control-products -> Low Voltage Products & Systems -> Control Products -> Electronic Relays and Controls -> Thermistor Motor Protection Relays. Data sheet Thermistor motor protection relay CM-MSS.41-13

Contact us ABB STOTZ-KONTAKT GmbH P. O. Box 10 16 80 69006 Heidelberg, Germany Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-mail: info.desto@de.abb.com You can find the address of your local sales organisation on the ABB home page http://www.abb.com/contacts -> Low Voltage Products and Systems Document number 2CDC 112 216 D0201 (12/2014) Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2014 ABB All rights reserved