XU1-DC DC voltage relay. (June 1998) Manual XU1-DC (Revision New)

Similar documents
XU1-E Earth fault voltage relay. (August 1996) Manual XU1-E (Revision New)

XE2 DC current relay for loss of excitation protection. Manual XE2 (Revision A)

XG2 Generator-/Mains Monitor. Manual XG2 (Revision A)

BN1-400 Mains decoupling relay. (February 2000) Manual BN1-400 (Revision New)

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

MRA1 Trip circuit supervision. Manual MRA1 (Revision A)

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay

MRT1 Test Unit. Manual MRT1 (Revision A)

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet

Switching relay CT-IRS with 1, 2 or 3 c/o contacts Data sheet

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages

Electronic timer CT-ERS.21

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-ERS.12 ON-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AWS Impulse-OFF with 2 c/o contacts Data sheet

Electronic timer CT-ARS.11

Electronic timer CT-SDS.23 Star-delta change-over with 2 n/o contacts

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Three-phase monitoring relay

Electronic timer CT-ERD.12

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

Phase loss monitor CM-PBE Phasemonitor for over and undervoltage CM-PVE Ordering details

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact

Messaging module CP-C MM

02/11/2015

Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

RM4TR31 three-phase network control relay RM4-T - range V

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

Electronic timer CT-AHD.22

Contact protection relay

Electronic timer CT-SDD.22 Star-delta change-over with 2 n/o contacts

Electronic timer CT-ERD ON-delayed with 1 c/o contact Data sheet

Electronic timer CT-ARE OFF-delayed without auxiliary voltage, 1 c/o (SPDT) contact

02/11/2015

Electronic timer CT-VWD Impulse-ON with 1 c/o contact Data sheet

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

08/07/2015

RM4UA33M voltage measurement relay RM4-U - range V V AC

RM4JA01F current measurement relay RM4-J - range ma V AC

02/11/2015

Zelio Control-modular measurement and control relays 1

RTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

TRIO-DIODE/12-24DC/2X10/1X20

RE22R2KMR Off-delay Timing Relay s 10min V AC/DC - 2C/O

RM4JA32MW current measurement relay RM4-J - range A V AC DC

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

RE11RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

MINI MCR-SL-UI-REL(-SP)

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

Arc protection relay. Features Three-phase overcurrent function. Application

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

RM4TA32 three-phase network control relay RM4-T - range V

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC

2C138. Sensitive Earth Fault Relay. Features. Application. Operation

Switching relay CT-IRE with 1 c/o (SPDT) contact

Zelio Control Measurement Relays Multifunction 3-phase supply control relays RM17T 00

Binary output and supervision 520CSD01 Data sheet

RM35TF. Main. Product or component type. Product specific application. Relay monitored parameters 250 V AC 5 A AC

QUINT-BUFFER/24DC/24DC/40

RE8TA31BU industrial timing relay s - type A - 24 V AC/DC, V AC - 1 C/O

RE8YG31BUTQ industrial timing relay s - type Qc - 24 V AC/DC, V AC - 1C/O

RE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

Installation / Control Technique

STEP-PS/1AC/24DC/1.75

RE8YG31BUTQ industrial timing relay s - type Qc - 24 V AC/DC, V AC - 1C/O

Reyrolle Protection Devices. 7SG21 DDB20 Multi Range Digital Setting Time Delay Relay. Energy Management

TU531, TU532 Terminal Unit

Millenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

RE22R2CMR Off-delay Timing Relay s 300h V AC/DC - 2C/O

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

Power Supply HARTING pcon

RM4JA31M current measurement relay RM4-J - range ma V AC

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

RE7RM11BU off-delay timing relay with control contact s - 24 V AC DC - 1OC

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

Power Supply HARTING pcon

DI572 Digital Input Module

Bulletin 817 Thermistor Protection Relay

Miniature Circuit Breakers for Railway Applications

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

RM35UB3. Product data sheet Characteristics. voltage control relay RM35-U - range V AC. Main. Complementary

Arc protection relay. Features Three-phase overcurrent function. Application

RM35TF V AC

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

RE7YA12BU. Main. Contacts type and composition Component name Time delay type. 24 V AC/DC at 50/60 Hz V AC/DCat 50/60 Hz

AI561 Analog Input Module

RM17UB3. Product data sheet Characteristics. voltage control relay RM17-U - range V AC. Main. Complementary

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

Transcription:

XU1-DC DC voltage relay (June 1998) Manual XU1-DC (Revision New)

Woodward Manual XU1-DC GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by Woodward Governor Company is believed to be correct and reliable. However, no responsibility is assumed by Woodward Governor Company unless otherwise expressly undertaken. Woodward 1994-2008 2 TD_XU1-DC_06.98_GB_Rev.New

Manual XU1-DC GB Woodward Contents 1. Applications and features... 4 2. Design... 5 3. Function... 8 4. Operation and settings... 9 4.1 Setting of DIP-switches... 11 4.2 Setting of tripping values... 13 4.3 Communication via serial interface adapter XRS1... 14 5. Relay case and technical data... 15 5.1 Relay case... 15 5.2 Technical Data... 16 6. Order form... 18 TD_XU1-DC_06.98_GB_Rev.New 3

Woodward Manual XU1-DC GB 1. Applications and features Relay XU1-DC of the PROFESSIONAL LINE is a digital re-lay for voltage supervision of DC systems. This relay type is available in three versions. Version 1, type XU1-DC-1, with a nominal voltage range of 100 to 500 V, is mainly used for supervision of DC intermediate circuits, UPS batteries and station batteries. Version 2 and 3, type XU1-DC-2 and XU1-DC-3, with a setting range of 24-60 V, are used for instance for supervision of starter batteries. When compared to conventional protection equipment all relays of the PROFESSIONAL LINE reflect the superiority of digital protection technique with the following features: High measuring accuracy by digital data processing Fault indication via LEDs Extremely wide operating ranges of the supply volt-age by universal wide-range power supply unit Very fine graded wide setting ranges Data exchange with process management system by serial interface adapter XRS1 which can be retrofitted extremely short response time Compact design due to SMD-technology In addition to this the DC voltage relays XU1-DC have the following special features: Rated voltage ranges selectable Separate adjustment of tripping delays for both trip-ping elements possible Different switching hysteresis adjustable The relay types XU1-DC-1 and XU1-DC-2 are provided with two separate tripping elements for under- and overvoltage (U<, U>). The XU1-DC-3 is equipped with two separate tripping elements for undervoltage (U1<, U2<). 4 TD_XU1-DC_06.98_GB_Rev.New

Manual XU1-DC GB Woodward 2. Design Figure 2.1: Connection XU1-DC-1 Figure 2.2: Connection XU1-DC-2 Figure 2.3: Connection XU1-DC-3 TD_XU1-DC_06.98_GB_Rev.New 5

Woodward Manual XU1-DC GB Analog inputs DC voltage is connected to the protection relay via terminals U+ and U-. Auxiliary voltage supply Unit XU1-DC can be supplied from the measuring quantity itself or by secured auxiliary supply. Therefore a DC or AC voltage must be used for unit XU1-DC-1. DC-voltage supply must be used for units XU1-DC-2 and XU1-DC-3. Unit XU1-DC has an integrated wide range power supply. The auxiliary voltage ranges are shown in the margin. 6 TD_XU1-DC_06.98_GB_Rev.New

Manual XU1-DC GB Woodward Contact positions XU1-DC-1 and XU1-DC-2 Figure 2.4: Contact positions of the output relays Contact positions XU1-DC-3 Figure 2.5: Contact positions of the output relays TD_XU1-DC_06.98_GB_Rev.New 7

Woodward Manual XU1-DC GB 3. Function The XU1-DC is provided with one supervision each for overvoltage (U>) and undervoltage (U<); pickup value and time delays of which can be adjusted separately. The DC voltage measured is constantly compared with the set reference values. If these values are not met the respective device (either for over- or undervoltage) trips after elapse of the time delay. Pickup of the supervision circuit, either U> or U<, is indicated by the corresponding flashing LED. Upon trip-ping the flashing light changes to steady light. The XU1-DC-3 is provided with two separately operating undervoltage elements (U1< and U2<) with separately adjustable pickup values and tripping delays. Here it doesn t matter which undervoltage element is adjusted to a lower threshold. The output relay of undervoltage element U1< is an idle-current relay, that of the U2< element is a working current relay. The contact positions for the different operating states are shown in fig. 2.5. If the voltage drops below the set tripping thresholds, the relay trips after elapse of the tripping delay. 8 TD_XU1-DC_06.98_GB_Rev.New

Manual XU1-DC GB Woodward 4. Operation and settings All operating elements needed for setting parameters are located on the front plate of the XU1-DC as well as all display elements. This makes it possible that all adjustments of the relay can be made or changed without disconnecting the unit from the DIN-rail. Figure 4.1: Front plate XU1-DC-1 and XU1-DC-2 Figure 4.2: Front plate XU1-DC-3 TD_XU1-DC_06.98_GB_Rev.New 9

Woodward Manual XU1-DC GB For adjustment of the relay please open the transparent cover as illustrated. Do not use force! The transparent cover has two inserts for labels. Figure 4.3: How to open the transparent cover LEDs LED "ON" is used for the display of readiness for operation (at applied auxiliary voltage Uv). LEDs U> and U< (U1< and U2< at XU1-DC-3) indicate pickup (flashing light) or tripping (steady light). Test push button This push button is used for test tripping of the unit and when pressed for 5 s a check-up of the hardware takes place. Both output relays are tripped and all tripping LEDs light up. 10 TD_XU1-DC_06.98_GB_Rev.New

Manual XU1-DC GB Woodward 4.1 Setting of DIP-switches The DIP-switch block on the front plate of the XU1-DC is used for adjustment of the nominal values and setting of function parameters. DIP-switch OFF ON Functions 1* Un = 100 V Un = 200 V Setting of rated voltage 2* Un = 100 V Un = 400 V 3* Un = 100 V Un = 500 V 4* x 1 s x 10 s multiplier for tu< 5* x 1 s x 10 s multiplier for tu> 6* 1 % 2 % Setting of switching hysteresis 7* 1 % 5 % 8* 1 % 10 % Table 4.1: Adjustment possibilities for the XU1-DC-1 * Only one of the DIP-switches 1-3 or 6-8 shall be in ON position at the same time. DIP-switch OFF ON Functions 1* Un = 24 V Un = 48 V Setting of rated voltage 2* Un = 24 V Un = 60 V 3* 4* x 1 s x 10 s multiplier for tu< 5* x 1 s x 10 s multiplier for tu> 6* 1 % 2 % Setting of switching hysteresis 7* 1 % 5 % 8* 1 % 10 % Table 4.2: Adjustment possibilities for the XU1-DC-2 * Only one of the DIP-switches 1-2 or 6-8 shall be in ON position at the same time. DIP-switch OFF ON Functions 1* Un = 24 V Un = 48 V Setting of rated voltage 2* Un = 24 V Un = 60 V 3* 4* x 0.1 s x 1 s multiplier for tu1< 5* x 0.1 s x 1 s multiplier for tu2< 6* 1 % 2 % Setting of switching hysteresis 7* 1 % 5 % 8* 1 % 10 % Table 4.3: Adjustment possibilities for the XU1-DC-3 * Only one of the DIP-switches 1-2 or 6-8 shall be in ON position at the same time. TD_XU1-DC_06.98_GB_Rev.New 11

Woodward Manual XU1-DC GB Rated voltage The required rated voltage at XU1-DC can be set with the aid of DIP-switch 1-2 or 1-3. It has to be ensured that only one of the two or three DIP-switches is switched on. The following DIP-switch configurations for adjustment of the rated voltage are allowed. Figure 4.4: Adjustment of rated voltage XU1-DC-1 Figure 4.5: Adjustment of rated voltage XU1-DC-2 and XU1-DC-3 Rated voltage chosen too low does not cause destruction of the unit but leads to wrong measuring results which may lead to false tripping. Switching hysteresis By using DIP switches 6-8 the switching hysteresis of the two trip relays can be adjusted to 1%, 2%, 5% or 10% of the tripping values. As for the rated voltage it has to be ensured that only one of the three DIP switches is switched on at a time. The following adjustments of the switching hysteresis for U> and U< or U1< and U2< are possible: Figure 4.6: Adjustment of the switching hysteresis 12 TD_XU1-DC_06.98_GB_Rev.New

Manual XU1-DC GB Woodward 4.2 Setting of tripping values The PROFESSIONAL LINE units have the unique possibility of high accuracy fine adjustments. For this, two potentiometers are used. The coarse setting potentiometer can be set in discrete steps of 10 %. A second fine adjustment potentiometer is then used for continuously variable setting of the final 0-10 %. Adding of the two values results in the precise tripping value. Undervoltage element By using the potentiometer shown on the following figure, the undervoltage element can be adjusted in the range from 50 % to 110 % Un. Example: The requested tripping value to be set is U< (or U1< and U2< at XU1-DC-3) of 86 % Un. To achieve this, the setting value of the potentiometer on the right is simply to be added to the value of the coarse potentiometer. (The arrow of the coarse potentiometer must always be in the middle of the marked bar, otherwise a definite setting value is not possible). Figure 4.7: Adjustment example Undervoltage element The overvoltage trip relay can be adjusted in a range from 90 % to 150 % Un. Setting procedure the same as for the undervoltage trip relay. Time delays The time delays for the undervoltage and overvoltage trip relays can be set in the range from 0-100 s or from 0-10 s at XU1-DC-3 respectively. TD_XU1-DC_06.98_GB_Rev.New 13

Woodward Manual XU1-DC GB 4.3 Communication via serial interface adapter XRS1 Figure 4.8: Communication principle For communication of the units a with superior management system the interface adapter XRS1 is available for data transmission including operating software for our relays. This adapter can easily be retrofitted at the side of relay. Screw terminals simplify its installation. Optical transmission of this adapter makes galvanic isolation of the relay possible. Aided by the software, actual measured values can be processed, relay parameters set and protection functions programmed at the output relays. Information about unit XRS1 in detail can be taken from the description of this unit. 14 TD_XU1-DC_06.98_GB_Rev.New

Manual XU1-DC GB Woodward 5. Relay case and technical data 5.1 Relay case Unit XU1-DC is designed to be fastened with onto a DIN-rail acc. to DIN EN 50022, same as all units of the PROFESSIONAL LINE. The front plate of the relay is protected with a sealable transparent cover (IP40). Figure 5.1: Dimensional drawings Connection terminals The connection of up to a maximum of 2 x 2.5 mm 2 cross-section conductors is possible. For this the transparent cover of the unit has to be removed (see chapter 4). TD_XU1-DC_06.98_GB_Rev.New 15

Woodward Manual XU1-DC GB 5.2 Technical Data Measuring input circuits Rated voltage Un: Power consumption of the voltage circuit: Thermal capacity of the voltage circuit: Auxiliary voltage Rated auxiliary voltage Uv/ Power consumption: DC-2 and DC-3: Common data Dropout to pickup ratio: Resetting time from pickup: Returning time from trip: Minimum response time: 100, 200, 400, 500 V DC (XU1-DC-1) 24, 48, 60 V DC (XU1-DC-2 and XU1-DC-3) 1 VA DC-1 = 750 V DC continuously DC-2 = 90 V DC continuously DC-3 = 90 V DC continuously DC-1: 36-520 V AC (f = 35-78 Hz) or 50-750 V DC/ 4 W (terminals A1-A3) 19-55 V DC / 3 W (terminals A1(L-) and A2(L+)) 11-90V DC / 4 W (terminals A1(L-) and A3(L+)) (Initial operating voltage >12.8 V DC, Relay switches off at <9 V) depending on the adjusted hysteresis <50 ms 200 ms 50 ms Output relay Number of relays: 2 Contacts: 1 changeover contact each for trip relay Maximum breaking capacity: ohmic = 1250 VA/AC or 120 W/DC inductive = 500 VA/AC or 75 W/DC Max. rated voltage: 250 V AC 220 V DC ohmic load Imax. = 0,2 A inductive load Imax. = 0,1 A at L/R 50 ms 24 V DC inductive load Imax. = 5 A Minimum load: 1 W / 1 VA at Umin 10 V Max. rated current: 5 A Making current (16 ms): 20 A Contact life span: 10 5 operations at max. breaking capacity System data Design standards: VDE 0435 T303; IEC 0801 part 1-4, VDE 0160; IEC 255-4; BS 142; VDE 0871 Climatic stress: Temperature range at storage and operation: Climatic resistance class F acc. to DIN 40040 and DIN IEC 68, T.2-3: High voltage test acc. to VDE 0435, part 303 Voltage test: Surge voltage test: High frequency test: -25 C to +70 C more than 56 days at 40 C and 95 % relative humidity 2.5 kv (eff.), 50 Hz - 1 min 5 kv, 1.25/50 µs, 0.5 J 2.5 kv/1mhz 16 TD_XU1-DC_06.98_GB_Rev.New

Manual XU1-DC GB Woodward Electrostatic discharge (ESD) acc. to IEC 0801 part 2: Radiated electro-magnetic field test acc. to IEC 0801 part 3: Electrical fast transient. (burst) acc. to IEC 0801 part 4: Radio interference suppression test acc. to DIN 57871 and VDE 0871: 8 kv 10 V/m 4 kv / 2.5 khz, 15 ms limit value class A Repeat accuracy: 1 % Basic time delay accuracy: 0.5 % or ±25 ms Accuracy of the specific rated values: 0.75 % Temperature effects: 0.02 % per K Mechanical test Shock: class 1 acc. to DIN IEC 255-21-2 Vibration: class 1 acc. to DIN IEC 255-21-1 Degree of protection Front panel: Weight: Mounting position: Relay case material: GL-Approbation: IP40 when the front cover is closed approx. 0.5 kg any self-extinguishing 94657-94HH Parameter Setting range Graduation U< 50-110 % Un continuously variable U> 90-150 % Un continuously variable tu</tu> 0-100 s continuously variable Hysteresis for U> and U< 1, 2, 5, 10 % Table 5.1: Setting ranges and graduation of XU1-DC-1 and XU1-DC-2 Parameter Setting range Graduation U1< 50-110 % Un continuously variable U2< 50-110 % Un continuously variable tu1</tu2< 0-10 s continuously variable Hysteresis for U1< and U2< 1, 2, 5, 10 % Table 5.2: Setting ranges and graduation of XU1-DC-3 TD_XU1-DC_06.98_GB_Rev.New 17

Woodward Manual XU1-DC GB 6. Order form DC voltage relay Rated voltage 100-500 V/DC 24-60 V/DC with two undervoltage elements 24-60 V/DC Technical data subject to change without notice! XU1DC 1 2 3 18 TD_XU1-DC_06.98_GB_Rev.New

Manual XU1-DC GB Woodward Setting-list XU1-DC Project: SEG job.-no.: Function group: = Location: + Relay code: - Relay functions: Date: Setting of parameters at XU1-DC-1 and XU1-DC-2 Function Unit Default settings Actual settings U< Undervoltage tripping % Un 50 U> Overvoltage tripping % Un 90 tu< Time delay for U< s 0 tu> Time delay for U> s 0 DIP switch settings at XU1-DC-1 and XU1-DC-2 DIP-switch Function Default settings Actual settings 1* Setting of rated voltage XU1-DC1 Un = 100 V (24 V) 2* (In brackets XU1-DC2) Un = 100 V (24 V) 3* Setting of rated voltage XU1-DC1 Un = 100 V 4 Multiplier for tu< x 1 s 5 Multiplier for tu> x 1 s 6* Setting of switching hysteresis 1 % 7* Setting of switching hysteresis 1 % 8* Setting of switching hysteresis 1 % *Only one of the DIP-switches 1-3 or 6-8 shall be in ON -position at the same time. Setting of parameters at XU1-DC-3 Function Unit Default settings Actual settings U1< Undervoltage tripping % Un 50 U2< Undervoltage tripping % Un 50 tu1< Time delay for U1< s 0 tu2< Time delay for U2< s 0 DIP switch settings at XU1-DC-3 DIP-switch Function Default settings Actual settings 1* Setting of rated voltage Un = 24 V 2* Setting of rated voltage Un = 24 V 3* 4 Multiplier for tu1< x 1 s 5 Multiplier for tu2< x 1 s 6* Setting of switching hysteresis 1 % 7* Setting of switching hysteresis 1 % 8* Setting of switching hysteresis 1 % *Only one of the DIP-switches 1-3 or 6-8 shall be in ON -position at the same time. TD_XU1-DC_06.98_GB_Rev.New 19

Woodward Manual XU1-DC GB Woodward SEG GmbH & Co. KG Krefelder Weg 47 D 47906 Kempen (Germany) Postfach 10 07 55 (P.O.Box) D 47884 Kempen (Germany) Phone: +49 (0) 21 52 145 1 Internet Homepage http://www.woodward-seg.com Documentation http://doc.seg-pp.com Sales Phone: +49 (0) 21 52 145 635 Telefax: +49 (0) 21 52 145 354 e-mail: kemp.electronics@woodward.com Service Phone: +49 (0) 21 52 145 614 Telefax: +49 (0) 21 52 145 455 e-mail: kemp.pd@woodward.com 20 TD_XU1-DC_06.98_GB_Rev.New