Easy Start Guide. Parker SSD Drives 650 Series Frequency Inverter available from Parker.InverterDrive.com

Similar documents
Bosch Rexroth EFC3610 Frequency Inverter. Easy Start Guide L1 L2 L3 (+) B U V W

Mitsubishi D700-SC Frequency Inverter. Easy Start Guide. The Mitsubishi D700-SC Frequency Inverter range is available to order from inverterdrive.

LS M100 Frequency Inverter Easy Start Guide

EQ5 SERIES Quick Start Guide for Constant Torque Applications

Power Connections: Basic Wiring:

TECO L510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

ETM MD100 Drive System 1/2HP (370W) User Manual. Table of Contents. Drive Features

Unidrive M200, M201 (Frame 1 to 4) Quick Start Guide

890 Quickstart Manual

890 Quickstart Manual

Status line The top line of the LCD display shows the basic status information of the drive.

650 Series AC Drive Frame 1, 2 & 3

Unidrive M400 (Frame 1 to 4) Quick Start Guide

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Revision 1.10

AF-600 FP TM Fan & Pump Drive. (230V to 60HP, 460/575V to 125HP Operating Instructions

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

INSTALLATION AND OPERATION MANUAL KBDF SERIES

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Installation & Operating Instructions

GV3000/SE 230 VAC 1-20 HP General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.04

Firmware Manual - EC Series Drives

890 Quickstart Manual 890CS/CD (Common Bus) Drives Frames B, C & D

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Revision 2.00

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC

WARNING NOT ZTC Controls Ltd

Optidrive Applications Support Library

Digistart. Soft starters for 3 phase induction motors 7.5 to 800kW (18 to 1600A) 200V, 400V, 575V, 690V

COMBIMASTER 411 & MICROMASTER 411

IP55 Quick Start Up Guide

Installation and Operating Instructions

IM-pAC. Getting Started Guide. AC variable speed drive for 3 phase induction motors from 0.25kW to 4kW, 0.33hp to 5hp. Model sizes A, B and C

Delta C200 Series AC Drives

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors

QD:CT Plus & QD:VT Installation and Operating Instructions

SIMOCODE 3UF Motor Management and Control Devices

IM-pAC. Getting Started Guide. AC variable speed drive for 3 phase induction motors from 0.25kW to 4kW, 0.33hp to 5hp. Model sizes A, B and C

Quick Start Guide For GVX9000 AF Drives

AC Variable Speed Drive

LiquiFlo AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.4

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Installation & Operating Instructions

MODBUS TCP MODULE INSTRUCTIONS. for use with WSIQ2/WSE

Basic Drive Programming PowerFlex 755 Basic Start Up

Contents. Temperature & Process Measurement Indicators Setup Guide

Universal Motor Controller UMC22-FBP. High-grade Motor Protection and Control

INSTALLATION AND OPERATION MANUAL KBMK SERIES. Adjustable Frequency Drives for 1/8 HP thru 1 HP 3-Phase AC Motors Rated VAC, 50/60 Hz

Installation & Operation Manual KBVF SERIES. Chassis / IP-20 AC Drives

OptiDrive Advanced Technical Manual

ABB Micro drives. User s manual ACS255 drives ( hp) (115V-480V Variants)

Quick start commissioning guide. Unidrive SP. Positioning Solution. Part number : 3773 en / c

IP20 Easy Start Up Guide

Experiment #2 PLC Input Output Wiring Methods. OBJECTIVES After successfully completing this laboratory, you should be able to:

SIAC-PS 3G SIGNAL ISOLATOR WITH POWER SUPPLY (PART NO. 8890) INSTALLATION INSTRUCTIONS

SECTION VARIABLE FREQUENCY DRIVES

690+ Series AC Drive Frame B, C, D, E & F

Basic control panel. Features. Control panels 75

User Guide. IP20 & IP66 (NEMA 4X) AC Variable Speed Drive. Installation and Operating Instructions. 1 Quick Start Up kW (0.

Instruc on Manual. Series S3. Industrial Inverter IP20 IP66

lnvertek Drives.com ct,ve ELECTRICAL SUPPLIERS LTD

P216. Condenser fan speed controller. Product bulletin. Features

Variable Speed Drives

BlueWave ~ Intelligent Energy Control. Installation and User Manual for BW2/C and BW3/C versions. Quick Guide

Macro Guide. Affinity. Model sizes 1 to 6. Building Automation HVAC/R drive. Part Number: Issue: 1.

Optidrive Applications Support Library

Important Safety Notice

QUICK REFERENCE GUIDE

Motor Controllers AC Variable Frequency Drives Type Variflex 3 RVLF Advance

User Guide. IP20 & IP66 (NEMA 4X) AC Variable Speed Drive kW V

GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000

BACnet Flow Controller for Fan Filter Units

SED2 Variable Frequency Drives Startup, Operation, and Maintenance Manual

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Issue 06

REACTIVE ENERGY REGULATORS

SED2 Variable Frequency Drives with Electronic (E) Bypass Options

SK CU4-ECT-C Part number:

Motor Controllers Variable Frequency AC Drives Type VariFlex 2 RVCF

Motor Controllers AC Variable Frequency Drives Type Variflex 3 RVLF Advance

FREQUENCY CONVERTER FC101 (QUICK GUIDE)

Profinet Module. User Manual. Contents

Parameter displayed menu (SUP)

SINAMICS IOP. Intelligent Operator Panel. Operating Instructions February 2009 SINAMICS

GS400. Electronic Auto-Ranging DIN Panel Mounted Positioner

SK CU4-EIP-C Part number:

VARMECA 20. Variable speed motors and geared motors. Parameter setting manual. This manual is to be given to. the end user CDC -VMA 20

VariFlex 2 - RVEF Series

SK CU4-PNT-C Part number:

60131/2 Te ESC ENT RUN ESC ENT RUN ESC ENT RUN ESC ENT RUN ESC ENT RUN. stop reset FWO REV. stop reset FWO REV. stop reset FWO REV. stop reset FWO REV

PHASE MONITOR RELAYS Product Summary

PSU. User s manual. Rev. 0

User Guide VLT Parallel Drive Modules

For Classroom Use Only! Flying Start PowerFlex 755 AC Drives

PART 1: GENERAL PART 2: PRODUCT. Effective: 12/29/10 Page 1 of 6 FECA-TE-104D

Zenith DS9000 Dispensing System

4100 and 4100/R Controllers

Quick Start Guide Cutler-Hammer SVX9000 Drives from Eaton Corporation CONTENT STEP 1 Keypad Operation Overview STEP 2 Standard Wiring Diagrams and

RTK3 Logic Controller User Manual Revised

Q9 ASD LOW VOLTAGE DRIVE

Specifications N Termination Voltage Range Current Consumption, Max. Type Number Termination. Voltage Range. Sinking Sensor Current

SSW06. Soft Starters.

Operating Instructions

Operating and Maintenance Instructions

SENSORLESS VECTOR CONTROL

Transcription:

Parker SSD Drives 650 Series Frequency Inverter available from Parker.InverterDrive.com This guide is intended to compliment the user manual provided by the manufacturer. It is provided as a basic introduction to the product for Inverter Drive Supermarket customers. It should not be used as a replacement for the manual issued by the manufacturer. This product is not a safety device. All safety considerations including but not limited to Emergency Stop provision should be assessed separately and are outside the scope of this guide. v1.0 20110321

Contents Page 1 Page 2 Page 3 Page 4 Page 5 Contents Power and Motor Connections (Single ) Power and Motor Connections (Three ) Motor Connections - Star and Delta Parameters - Overview Parameters to set before use Page 6 Page 8 Page 10 Page 11 Page 12 Page 13 Page 14 Page 15 How to set Boost - Parameter P13 How to set a Parameter value How to Operate the Inverter (Local mode) How to switch from Local (keypad) control to Remote (terminal) control and back How to connect and configure a Potentiometer for remote speed control How to connect and configure a Run/Stop switch How to connect and configure a Fwd/Rev switch How to Reset the Inverter to Factory Defaults Page 1

1. Power and Motor Connections (Single ) Before commencing, confirm that the Inverter and all cables are completely isolated from the power supply, have been isolated for at least 5 minutes and that the motor is not turning. TH1A TH1B Motor Connect TH1A and TH1B terminals to the motor thermistor if available. If the motor does not have thermistor protection, short TH1A and TH1B as shown. The Inverter will not operate if TH1A and TH1B are not connected. Earth Live Neutral Earth RL1A RL1B TH1A TH1B L1 L2/N M1/U M2/V M3/W 10 9 8 7 6 5 4 3 2 1 I/O Terminal Block Fit the cable clamp to the power cable and attach motor cable to power cable securely. Motor Power Notes: Important: The illustration above is based on frame size 1 models (0.25kW - 0.75kW). The terminal layout for sizes 2 and 3 (1.1kW - 2.2kW) is slightly different. The order of the three phases determines the direction the motor turns. Use screened SY cable between the Inverter and Motor to minimise electromagnetic interference. Ensure the motor cable screen is earthed at the motor end. Page 2

2. Power and Motor Connections (Three ) Before commencing, confirm that the Inverter and all cables are completely isolated from the power supply, have been isolated for at least 5 minutes and that the motor is not turning. TH1A TH1B Motor Connect TH1A and TH1B terminals to the motor thermistor if available. If the motor does not have thermistor protection, short TH1A and TH1B as shown. The Inverter will not operate if TH1A and TH1B are not connected. Power Motor Earth Earth RL1A RL1B TH1A TH1B L1 L2/N L3 DC+ DBR M1/U M2/V M3/W 10 9 8 7 6 5 4 3 2 1 I/O Terminal Block Fit the cable clamp to the power cable and attach motor cable to power cable securely. Motor Power Notes: The illustration above is based on frame size 2 models (0.37kW - 2.2kW). The terminal layout for size 3 (3kW - 7.5kW) is slightly different. The order of the three motor phases determines the direction the motor turns. The order of the three power phases is unimportant. Important: Use screened SY cable between the Inverter and Motor to minimise electromagnetic interference. Ensure the motor cable screen is earthed at the motor end. Page 3

3. Motor Connections - Star and Delta Dual voltage induction motors typically include terminal boxes with six points. The points can be connected together with links in one of two ways to suit one of the two rated voltages. The two ways of connecting the links are shown below. These are known as Star (the higher voltage) or Delta (the lower voltage). The selection of Star or Delta is not optional and must match the supply voltage. Dual voltage motor nameplates include symbols to represent voltage and full load current in each configuration. Delta is represented by a triangle and star by a Y (Wye). Link Link STAR Earth Screen DELTA Earth 3.1 Motor connected in STAR (or Wye): For safety purposes, Star (shown opposite) is the default configuration for new motors and is sometimes known as two at one side. Only two links are required for Star. Double-up the links if changing from Delta to allow the motor to be changed to back in future. The order of the three phases determines the direction the motor turns. Note that the cable screen and earth are connected together at the earth terminal. 3.2 Motor connected in DELTA: The link configuration is shown in the illustration opposite and is sometimes referred to a three-a-breast. The order of the three phases determines the direction the motor turns. Note that the cable screen and earth are connected together at the earth terminal. Screen Page 4

4. Parameters - overview The Inverter contains a number of settings which can be changed to tailor it for use in a wide range of applications. These settings are known as parameters. Parameters are typically referred to by code or number (eg. P6 = Motor Full Load Current) with a description available in the manual. 5. Parameters to set before use Set the following parameters to allow the 650 to run in standard mode with Run, Stop and Speed Control from the keypad. Parameter Description How to set P2 Maximum Speed in Hz Default is 50 or 60 depending on region. Set at 50 for 50Hz motor. P3 Minimum Speed as % of P2 Default is 0. Set to 0 for most applications. P6 Motor Current in Amps Set to match motor nameplate - eg. 4.7 P7 Base Frequency in Hz Default is 50. Change to 60 for 60Hz motor only - otherwise set at 50. P13 Fixed Boost (%) See section 6 for details of how to correctly set this value. The parameters contain critical information essential to the correct operation of the Inverter. Therefore, they should at least be checked by the user before it is operated for the first time. The parameters listed in section 5 are intended to provide a starting point to allow for basic operation of the 650 Inverter. See section 7 to learn how to set a parameter value. 5.1 Parameters to check and values to set If any of the parameters have been changed previously, follow the procedure in section 13 to reset the Inverter to Factory Defaults. Page 5

6. How to set Boost - Parameter P13 Boost is an important parameter to set to get the best possible motor performance. Correctly set, it significantly improves torque at lower speeds. However, it is not relevant for Fan and Centrifugal Pump applications. The procedure involves running the motor offload at it s rated speed and making a note of output current. The motor is then run at 10% speed and P13 adjusted to ensure that the output current is the same in both cases. 6.1 How to determine Motor no-load current by operating the 650. 6.1.1 Set speed to 100% and start the motor. Motor no-load current can only be determined with the motor running off-load. Decouple the motor from the machine before beginning! Use the up key to increase speed to 100% (50Hz or 60Hz depending on motor) and press the green button to start the motor. Once the motor is running at 100%, proceed to the next step. 6.1.2 Press M to open the menu. Press and hold the M button until the display shows diag as illustrated. Press M again to open the diagnostics (diag) menu. 6.1.3 Use the up and down keys to locate output current. Output current can be identified by the letter A on the top right as shown. Make a note of this value. It is Motor no-load current in Amps. Leave the motor running and continue to the next step overleaf. Page 6

6.2 How to use Motor no-load current to set Boost correctly. 6.2.1 Reduce motor speed to 10%. Press the E (escape) key twice to return to the speed display. Then press and hold the down key to reduce the speed from 100% to 10%. Once the motor is running at 10%, proceed to the next step. 6.2.2 Use the diagnostics menu to find output current. Press and hold the M button until the display shows diag as before. Press M again to open the diagnostics menu. Use the up and down keys to locate output current as before. If the current value shown is more than motor no-load current, the Boost value in P13 will need to be reduced. If it is less, P13 will need to be increased. 6.2.3 Locate parameter P13 and change as required. From the output current display in the previous step, press E to return to diag then up and down to locate par as shown. Press M to open the parameter list then up and down to locate P13. Press M again to edit it. 6.2.4 Change P13, save and check output current. Use the up and down keys to increase or decrease the value of P13 as necessary. Press E to save and E to return to par, then E again to return to the speed display. Repeat step 6.2.2 to check output current. If it matches motor no-load current Boost is set correctly and the motor can be stopped using the red button. If the output current does not match, repeat steps 6.2.3 and 6.2.4 until it does. All content, including but not limited to graphics, text and procedures copyright The Inverter Page 7

7. How to set a Parameter value 7.1 Press and hold the M (Menu) key for 1 second. This example demonstrates the steps required to set parameter 6 (P6) which is motor full-load current. From the speed reference screen (shown in the illustration opposite), press and hold the Menu key for approximately 1 second to access the menu. 7.2 Press the up key to move from Diagnostics to Parameters. The display shows diag to indicate that the currently selected menu option is diagnostics. Press the up key to select the parameter menu. The display will show par to indicate that this has been selected. 7.3 Press the Menu key to access the parameter list. When the display shows par, press the Menu key to access the parameter list. 7.4 The Parameter List The display shows P1 to indicate that Parameter 1 is currently selected. Use the up and down keys to navigate through the list of available parameters. For this example, select P6 (motor full-load current). Press the Menu key to modify the parameter value. Page 8

7.5 Use the Menu, up and down keys to change the value. Press the Menu key to select the first digit. The selected digit will flash to indicate that it can be changed. Use the up and down keys to increase or decrease the value. Press the Menu key again to move through each digit from right to left. Continue to press Menu to cycle back to the first digit. 7.6 Press the E (Escape) key to return to the Parameter List. Press the Escape key to return to the parameter list. The previously selected parameter number is shown. Use the up and down arrows to select a different parameter and press the Menu key to modify as before. Press the Escape key again to return to the Parameter menu as shown in 7.3. 7.7 Press the Escape key to return to the speed reference screen. When the display shows par, press the Escape key to return to the initial screen. 7.8 The initial screen The drive is now back at the speed reference screen. Page 9

8. How to operate the Inverter (Local mode) 8.1 Use the up and down keys to set the required speed. The display will change to show the current speed reference in percent. 8.3 Press the green button to start the motor. Press the green button firmly to start the motor. The motor will accelerate to the speed set in 8.1 (above) in the time defined by parameter P4. Motor speed can be changed whilst the motor is running by pressing and holding the down key (slower) or up key (faster). When the motor is running, the shaft-end symbol on the left side of the screen will rotate. 8.4 Press the red button to stop the motor. The red button will stop the motor. The time taken (in seconds) to stop the motor is determined by parameter P5. Page 10

9. How to switch from Local (keypad) control to Remote (terminal) control and back 9.1 Press and hold the stop button. When the drive is in Local control mode a small hand symbol is shown on the right side of the display. Press and hold the stop button to switch the Inverter from Local control via the keypad to Remote control via the IO terminals. Keep the stop button held down. 9.2 LOC is displayed. The display shows LOC and each letter disappears one at a time whilst the Inverter switches to remote control. Keep the stop button held down. 9.3 The display shows rdy. Once the process is complete the display shows rdy (ready) and the stop button can be released. If the display immediately switches back to local control (ie. the hand symbol is still visible) a run signal is present. Check the IO terminals and disable the run signal before attempting this procedure again. 9.4 To switch back to Local control. Press and hold the stop button as before to switch back to local control. The display will show LOC with each letter appearing in sequence as the Inverter switches to local control. Keep the stop button held down. Once the process is complete a hand symbol appears on the right side of the display. The stop button can now be released. Page 11

10. How to connect and configure a Potentiometer for remote speed control If the up and down speed control buttons on the keypad are unsuitable for the application, a remote Potentiometer can be used instead. This provides the benefit of allowing motor speed to be controlled from a more convenient location such as a cabinet door (if the 650 is cabinet-mounted) or on the machine itself. A Potentiometer of 10kOhm rating should be used. The number of turns depends on the application but both single turn and ten turn Potentiometers are available from The Inverter Drive Supermarket at InverterDrive.com. 10.1 Connecting the Potentiometer SY Cable 650 I/O Terminal Block 10 9 8 7 6 5 4 +10V 3 2 AIN1 1 0V To use a external potentiometer, the Inverter must be set to operate in Remote mode - see section 9 for details. A wiring diagram is shown in the illustration opposite. The most important connection at the Potentiometer end is the centre terminal or wiper. The wiper will output a variable voltage between 0 and 10 volts and should be connected to terminal 2 (AIN1) at the Inverter end. It is this voltage which provides the speed signal with 0V being slowest and 10V fastest. The default speed at 0V is 0%. To change this, edit parameter P3. 1 2 3 Screen to Earth Terminal on Cable clamp 10kOhm Potentiometer The default speed at 10V is 50Hz or 60Hz depending on region. To change this, edit parameter P2. If the rotation of the Potentiometer is the opposite to that required (ie. turn anticlockwise to increase speed instead of clockwise) reverse connections +10V and 0V. Use shielded SY cable between Potentiometer and Inverter and ensure that the cable screen Page 12

11. How to connect and configure a Run/Stop switch The default settings of the Inverter enable Run/Stop operation via the red and green buttons on the keypad. If this is unsuitable for the application, a remote Run/Stop switch can be used instead. Note that once this procedure is complete, the Run/Stop buttons on the keypad can no longer be used. 11.1 Connecting the Run/Stop Switch 650 I/O Terminal Block 10 9 8 7 6 DIN1 +24V To use a external Run/Stop switch, the Inverter must be set to operate in Remote mode - see section 9 for details. A wiring diagram is shown in the illustration opposite. 5 4 3 2 1 When terminal 7 (DIN1) receives 24V (ie. when the circuit with terminal 6 (+24V) is complete), Run is enabled and motor will turn. Conversely, when it receives 0V (ie. when the circuit with +24V is broken), Run is disabled and the motor will stop. This behaviour is known as a Digital Input, hence Digital Input 1 (DIN1). Screen to Earth Terminal on Cable clamp SY Cable Switch Any +24V DC signal connected to DIN1 will cause the Inverter to run. This can be useful if an external source such as a PLC is controlling the Inverter. If the +24V DC signal is external, a connection to +24V is not required. Use shielded SY cable between Potentiometer and Inverter and ensure that the cable screen is earthed at the cable clamp on the Inverter as shown opposite. Note that although 2 core SY cable is shown in the illustration opposite, multi-core SY cable can be used if several digital inputs are to be used. Page 13

12. How to connect and configure a Fwd/Rev switch The default settings of the Inverter enable Run/Stop operation via the red and green buttons but do not allow forward and reverse rotation to be selected via the keypad. Section 11 explains how to enable remote Run/Stop via a external switch. This section extends the functionality added in section 11 to include a Forward/Reverse switch as well. 12.1 Connecting the Fwd/Rev Switch 650 I/O Terminal Block F R SY Cable 10 9 8 DIN2 7 6 +24V 5 4 3 2 1 Screen to Earth Terminal on Cable clamp Switch To use a external Fwd/Rev switch, the Inverter must be set to operate in Remote mode - see section 9 for details. A wiring diagram is shown in the illustration opposite. Note that this switch should be used in conjunction with a Run/Stop switch as described in section 11. When the switch is in position F (forward), the circuit between terminal 8 (DIN2) and terminal 6 (+24V) is incomplete and the motor direction is set to forward. When the switch is in position R (reverse), the circuit between DIN2 and +24V is complete and the motor direction is set to reverse. This behaviour is known as a Digital Input, hence Digital Input 2 (DIN2). Any 24V DC signal from an external source such as a PLC connected to DIN2 will set the direction of rotation. Use shielded SY cable between the switch and Inverter and ensure that the cable screen is earthed as described in section 11. Page 14

13. How to reset the Inverter to Factory Defaults 13.1 Power-on with up and down keys pressed With the power supply to the drive off, press and hold the up and down arrow keys and switch the power supply on. 13.2 Release up and down keys when data is displayed. When the display flashes data, release the up and down keys. Press the E (Escape) key to continue. 13.3 Drive initialises The display briefly shows init to indicate that the drive is initialising. 13.4 Reset complete Once the reset is completed the display shows the speed reference screen (as shown in the illustration opposite) and the drive is ready. Note that the hand icon indicates that the drive is in local mode (control via keypad only). See section 9 for more information regarding Local and Remote control modes. Page 15

14. Notes Page 16