MYRIAD RTU REMOTE TELEMETRY UNITS INSTRUCTION MANUAL

Similar documents
MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

MYRIAD LC1 LEVEL CONTROLLER INSTRUCTION MANUAL

700 SERIES DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

700 SERIES TPC TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

700 SERIES FLOAT OPERATED DUPLEX/TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

Global Water globalw.com. Global Water. Instrumentation, Inc.

MODEL SIB-V245 / V453

Tempco Instruction Manual

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx

POWER SERIES Plus. 3 in 1 AC Voltage. Digital Switchboard Meter. User s Manual IM2493VVV-2

SP6R Level Controller Operation Manual

POWER SERIES Plus Watt-VAR / Watt-Power Factor Digital Switchboard Meter User s Manual IM2492WVPF-1

5504 Thermocouple Analog Input Module

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

Product Description. S&C IntelliNode Interface Module. Table of Contents. Instruction Sheet

POWER SERIES Plus Watt / VAR / Power Factor Digital Switchboard Meter User s Manual IM2493WVP-3

Models beginning with 2M, 2L or 2X. Product Description. Technical Specifications. Installation Instructions. Series 2000 Multiple Meter Units (MMUs)

Global Water Instrumentation, Inc.

Series 8000 RF Signal Switch Solution

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER

Pump-Down Controller MODEL mA Input Scalable 4-20mA Output Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters

Series 8000 RF Signal Switch Solution

LCI User Manual mantracourt.com

AirTest Model CN9000 Series Sensor Controller

Quick Start Guide. ELPRO 105U-L Wireless I/O Receiver Unit. man_105u-l-r_quickstart_v1-8.doc

EX-RC1 Remote I/O Adapter

PWRguard PLUS Spring City Drive Waukesha, WI

XT-9100 Technical Bulletin

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

IO-PT4. Component identification. User safety and equipment protection guidelines. Unitronics Industrial Automation Systems 1

User's Guide. MiniTec TM Series Model MN25 MultiMeter

R & D SPECIALTIES SERIES 100 RO CONTROLLER USERS MANUAL. 2004, by R & D Specialties, Inc. All Rights Reserved.

IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs

Resolver to Digital Expansion Board

Durant Eclipse Series Digital Panel Meters Durant Durant Visit our Web Site at

9500 and 9600 I/O Card Installation Instructions

High Voltage DC Meter

CTS-M5 TOXIC GAS TRANSMITTER/SENSOR INSTALLATION OPERATION AND MAINTENANCE MANUAL. Automation Components, Inc.

IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs

LCI Load Cell Junction Box with Fault Monitor

Trident and Trident X2 Digital Process and Temperature Panel Meter

V E1B Snap-in I/O Module

CONTROL MICROSYSTEMS Differential Analog Input Module. Hardware Manual

Multi-Point Gas Detection and Control System

Standard Options. Model 4100 Position Indicating Meter. Three Phase Motor Control. Positran Transmitter

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

G303 RIO (REMOTE I/O) AND LOW END RTU

ES-600 Ozone Controller Operation Manual

H704-42(H)(E), H704-42/1(H)(E)

ACCESS 9340/9360 Meter Input/Output Module

Operating Instructions VEGAMET 381

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L M O N I T O R E D DEVICE

UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

MICRO SERIES PROCESS DISPLAYS LARGE DIGIT MODELS

BERMAD Irrigation. BIC Wire RTU

The IQ300 wall mount load cell indicator is a precision digital indicator for load cell and strain gauge applications.

Installation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L MONITORED DEVICE

V E2B Snap-in I/O Module

Power Meter PowerMonitor 500

PHASETRONICS. SCR Power Control Specialists. EP1 Series Power Control Single Phase SCR Amps OPERATION & SERVICE MANUAL

Multi-Point Gas Detection and Control System

MODEL 8000MP LEVEL SENSOR

HIGH-VOLTAGE DC METER

Installation & Operation Guide

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

EMS467 Monitoring System. Installation and Operations Manual Section 40

The IQ240 panel mount load cell indicator is a precision digital indicator for load cell and strain gauge applications.

LAUREL. Laureate Digital Panel Meter for Process and Ratiometric Signals ELECTRONICS, INC. Features. Description

Eco Sensors OZONE CONTROLLER Model OS-6 Instructions for Use. General and New Features

Plus-X 300. Installation and Operation Manual

Quick Start Guide. ELPRO 905U-L Wireless I/O Receiver Unit. man_905u-l-r_quickstart_v1.9.doc

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

MP-2000 Dual Channel LVDT/RVDT Readout/Controller

Contents. Temperature & Process Measurement Indicators Setup Guide

FLOW MONITOR & TRANSMITTER

INSTRUCTION MANUAL. Digivac 760 Series. Models 100Led P / P / 29.9" 100Led 760 / SixVac 801 / 760 / 2c 801 Micro

RXTH DUAL ROOM SENSOR / SWITCH

Rotork Fairchild PAX1 Linear Actuator User s Manual

RXTP ROOM TEMPERATURE

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

I/O Expansion Box Installation & Operator s Instruction Manual

CDD Carbon Dioxide Transmitter

NFC110. Flow Computer For Low Pulses FEATURES

SCADAPack. I/O Expansion & Communication Modules

INTRINSICALLY SAFE INSTRUMENTATION FOR HAZARDOUS AREAS

EnCell Battery Cell Monitor

PIECAL 322 Automated Thermocouple Calibrator Operating Instructions. Product Description. Practical Instrument Electronics

DFI 7000 DIGITAL FORCE INDICATOR USER S GUIDE 1.0 INTRODUCTION 2.0 DESCRIPTION. 2.1 Configuration. 2.2 Specifications

OZONE SWITCH Model OS-6. OS-6 Features

Multi-Point Gas Detection and Control System

CONTROL MICROSYSTEMS Analog Input Module. Hardware Manual

Eco Sensors OZONE CONTROLLER Model OS-6 Instructions for Use. General and New Features

Analyzer/Controller. ph/orp HART. Model 54e ph/orp ESSENTIAL INSTRUCTIONS WARNINGS RISK OF ELECTRICAL SHOCK

Installation Instructions

24/7 Sprinkler Monitor. The Ultimate Rain/Freeze Sensor

AUTOMATION. Operator s Manual PG-7. Full Access. Doc Part Rev B, 07/18. Automation Products Group, Inc.

Transcription:

MYRIAD RTU REMOTE TELEMETRY UNITS INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM MYR RTU MANUAL 061314

2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING 8 Dwg #04-26 Analog Input Analog Output Digital Input Digital Output PROGRAMMING AND INITIAL SETUP... 10 Input Range Selection Terminal Block Detail Initial Setup & Programming Overview/Key Description TROUBLESHOOTING & MAINTENANCE.. 19 APPENDIX A 20 WARRANTY 21

3 INTRODUCTION: Remote telemetry units (RTU) are designed to provide monitoring and control of various process parameters between two remote locations. An RTU system consists of two essentially identical Myriad units, one located at each remote location. Connection between the units can be hard wired, spread spectrum radio modem or lease line telephone modem. Communication occurs at 19.2 KB Because of the identical nature of the units they are not known as Master and Slave but rather local and remote. The local unit is whichever one you are in front of with the other being the remote. RTU s have addresses and are factory configured as NODE 1 and NODE 2. Addresses may be changed in the field if required or more RTU s are added to the Network. COMMUNICATION: Communication occurs at 19.2K Baud over any mediums capable of this speed. If a process or status change occurs at a local unit it will be sent to the remote unit and vice versa. For redundancy all data may be sent to the remote unit periodically on a programmable poll rate interval (see SCADA settings). Otherwise data is only sent when a process value or status changes, thus power consumption is kept to a minimum. (A tangible benefit in solar powered systems.) COMMUNICATION FAILURE: Communication failure is of critical importance in telemetry systems. It cannot be assumed that communication is good all of the time. Telephone line failure or atmospheric conditions can occasionally cause temporary breaks in communication between RTU s. In order to constantly monitor communication a timer runs in the local unit whenever the unit is powered. This timer value is sent to the remote unit periodically (Poll Rate 6). If this data does not change for the duration of the Poll Rate, the internal communication fail counter will increase by 1 (see diagrams). When this counter exceeds the COMMFAIL LIMIT (adjustable) a local output will energize to initiate an alarm monitoring device, light, buzzer, autodialer, etc. OPERATION: Mounting and control functions are available on both RTU s. For a detailed overview on input/output relationships see Table 1, attached.

4 MYRIAD RTU1 Input/Output Local RTU to Remote RTU\ NODE 1 Action at Local RTU Digital Input #1 on Digital Input #2 on Digital Input #3 on Digital Input #4 on NODE 2 Action at Remote RTU Solid State Output #1 on Solid State Output #2 on Solid State Output #3 on Solid State Output #4 on Analog Input #1 Read Value on Display Read Value on Display Allows User to Set Values To Turn on Local Relay 1 & 2 Turns on Remote Relay 3 & 4 And Outputs Signal at Analog Output #1 Analog Input #2 Outputs on Analog Output #2 Analog Input #3 Outputs on Analog Output #3 Analog Input #4 Outputs on Analog Output #4 NODE 1 Action at Remote RTU Solid State Output #1 on Solid State Output #2 on Solid State Output #3 on Solid State Output #4 on Digital Input #1 on Digital Input #2 on Digital Input #3 on Digital Input #4 on NODE 2 Action at Local RTU Analog Input #1 Read Value on Display Read Value on Display Allow User to Set Values Turns on Remote Relay 3 & 4 To Turn on Local Relay 1 & 2 And Outputs Signal at Analog Output #1 Outputs on Analog Output #2 Analog Input #2 Outputs on Analog Output #3 Analog Input #3 Outputs on Analog Output #4 Analog Input #4

5 ORDERING INFORMATION: 1/4 DIN Case Wall Mount Nema 4X Sigma Myriad-RTU Sigma Myriad-RTU-N4X SPECIFICATIONS: ANALOG INPUT (4 ea.) Analog, 4/20MA, 0-5V, 1-5V, 0-10VDC, isolated with common negative, +-0.1% accuracy. DIGITAL INPUTS (4 ea.) Digital 10-30V AC or DC, 120 or 240 VAC (requires external resistor). ANALOG OUTPUT: (4ea.) Analog, with common negative 0-20MA, 4/20MA, 0-5V, 0-10V (voltage output requires a resistor). DIGITAL OUTPUTS: (4 ea.) Opto isolated, solid state, open collector, 100MA 30VDC max. RELAY OUTPUTS: (4 ea.) SPDT, Form C 5A Relay DISPLAY: LCD, 128 X 32 pixel bitmapped graphic display LOOP POWER: 24VDC regulated output, 100MA max. 5 USER KEYS: Up, Down, Left, Right, Enter ACCURACY: 0.1% of calibrated span LOCKOUT: User password, user configurable LINEARIZER 20 point programmable for non linear inputs INPUT IMPEDANCE: Voltage 100K, current 100 OHMS POWER: 120VAC (230VAC available)

6 ENVIRONMENTAL: Operating, 0-65 C Storage, -40-80 C R.H., 0-90% non condensing ENCLOSURE: ¼ DIN, ABS plastic 96 X 96 X 150MM FRONT PANEL: Gasketed Nema 4X ACCESS: Chassis & boards remove from front of case. TERMINAL STRIP: (40) Pluggable for ease of wiring 28 16 AWG CONNECTIONS: Removable screw terminal blocks 28 16 AWG wire. CONTROL OUTPUTS: 4 relay outputs, user programmable, SPDT Form C relays 5 AMP. 4 digital outputs, repeat digital inputs. OUTPUT ANNUNCIATION: On board piezo buzzer WATCHDOG CPU ACTIVITY MONITOR PROGRAMMING: Menu based, all parameters and setpoints are user configurable via menu prompts and user keys. The preconfigured screens and pull down sub menus with English prompts assures rapid setup and commissioning. 1 YEAR WARRANTY OPTIONS: 15 Point digital input expander Sigma # DI181 M.V. NET: Network allows RTU s to be connected to radio or telephone modems for remote monitoring SCADA applications. EXPANSION CARDS: Significant expansion is possible via additional control boards and MV networking. (Consult factory for details.)

7 FEATURES: Microprocessor Based Graphic LCD Display 5 Function Keys 20 Point Linearization Isolated 24VDC Sensor Power 4/20MA, 1-5V, 0-5V, 0-10VDC Input 4 Analog Input 4 Analog Output 4 Digital Inputs 4 Digital Outputs 4 Form C Relay Outputs Fully User Programmable in English 2 Ea. RS485 Ports (Programming and SCADA)

8 WIRING DETAIL Inputs/Output see Dwg #04-26! CAUTION All electrical wiring must be in accordance with all local state and national codes that apply. Do not exceed the rated current of the D.C. power supply (100MA) or the form C relay outputs (5A/240VAC resistive). WARNING Hazardous voltages are present within the enclosure. Installation or service should only be carried out by trained personnel.

9

10 PROGRAMMING AND SETUP The Myriad RTU uses plain English menu driven screens for programming setup. After power up the default Main Menu screen will be visible. This screen shows the value of analog input #1 on the local RTU. Process Value of Local RTU Analog Input #1 CPU Status Default Relay Status Engineering Units Fig. 1 Vertical Bar Graph Process Readout Fig. 1 By pressing the buttons the user may view the status of the other 3 analog input unit as follows: LOCAL UNIT ANALOG INPUTS 2,3,4 From the local default screen use the buttons to move to this screen: Shows Value in Percentage of Local Units Analog Input 2,3 & 4 DI Status Indicates that Viewed Data is from the Local Unit This screen provides a way to view the analog and digital inputs of the local unit. If a DI is on it will appear on the screen and will be identified by it s number. After returning to the Main local screen push the enter button to move to the password screen. Enter user selected password (factory default is zero) with the up and down keys, then with arrow buttons, move cursor to next. Press enter to access menu 1. NOTE: Selecting VIEW with the buttons and then pressing ENTER will allow the user to step through all RTU settings without having the ability to change any parameter. Parameter changes may only be carried out after entering the user selected password as described above.

11 REMOTE UNIT STATUS SCREENS To view the status of the Remote unit from the Local unit use the button, while the local default screen is displayed. This will allow selection and viewing as follows: REMOTE DEFAULT SCREEN Value of Remote Unit Analog Input #1 Use to step to: REMOTE UNIT ANALOG INPUTS Shows Status of Remote Units Relay Outputs 1 & 2 Antenna Symbol Flashes When Receiving Data from Remote Shows the Value in % of the Remote Unit Analog Inputs 2, 3, 4 Shows Status of Remote Unit Digital Inputs Indicates that Values are at the Remote This screen shows the analog input values (in percentage) of the remote unit and the status of the digital inputs. If no DI s are indicated then they are not active ( ON ). MENU 1 SCALE Press enter at the Password Screen to access Menu 1 INPUT RANGE SELECTION With the SCALE selection highlighted by the cursor, press ENTER to access the input scale menu.

12 Use the Up/Down arrow buttons to select the desired analog input range. NOTE: INPUT TYPE MUST BE CO-ORDINATED WITH INPUT SELECTOR SWITCH LOCATED ON THE BOTTOM OF THE CIRCUIT BOARD (See Appendix A ). NOTE: If the application is linear between minimum input signal and maximum input signal, i.e. 2 point, then scroll the cursor to NEXT and press ENTER to continue the scaling process. Note on non linear inputs The Myriad RTU offers a 20 point linearizer which allows the user to customize the indicated display for 20 points of input signal. This feature is often used to read volume in a non-linear vessel such as a horizontal tank with domed end caps. a strapping table must be created to allow the display to be linear with the resultant non-linear input signal. If the user required a non-linear display, scroll the cursor to # OF POINTS and use the arrows to select the number of calibration points required, then select NEXT and press ENTER to continue. DECIMAL POINT SELECTOR SCREEN The cursor will be positioned over the decimal count window, use the Up/Down arrow buttons to raise or lower the unit number to the left of the decimal point. (The example shown in this window will change with your selection.) Use the buttons to move the cursor to the number behind the decimal point and the Up/Down buttons to change this selection. Once again the example will change to confirm your selection. Use the buttons to highlight the NEXT selection and press ENTER to access the Input Scale Screen. INPUT SCALING TO ENGINEERING UNITS NOTE: This screen sets what the Myriad RTU displays in its default screen for input 1. The example shown above will display 0.0 units when the input is 4.00 MA. Both the input and the display at that input can be changed for different requirements. A) With the cursor selecting INPUT = 4.00 use the buttons to change the input value for the required displayed value.

13 B) Use the buttons to move the cursor to the display value and the buttons to change the desired display for the previously selected input. Once complete, scroll to SAVE, press ENTER to access INPUT SCALE 2 screen. Follow the steps outlined above to set the values of input and display for input Scale 2. When complete with scale 2, scroll the cursor to the DONE position and press ENTER to move to the ENGINEERING UNITS selection screen. ENGINEERING UNITS SELECTION: When Scale Menu is complete the INPUT TEXT menu is the last menu in the scaling process. This screen allows the selection of several engineering units. With the cursor on the default value as shown, press the buttons to select between FEET OF WATER PSI GALLONS LITERS UNITS Use the keys to select the desired engineering units then with the keys, highlight NEXT and press ENTER to access the display filter screen. DISPLAY FILTER SCREEN When the process is noisy or changing rapidly, a digital filter is provided to slow the display screen from changing rapidly.

14 Use the keys to change the amount of filtering applied to the input signal. O is no filter and 10 is high filter. Once the selection is made select NEXT and press ENTER to return to Menu 1. The scaling process is now complete. MENU 1 ANALOG OUTPUT PROGRAMMING From Menu 1 select AOUT by highlighting with the cursor as previously described. Once selected press ENTER to access the analog output configuration screen. Using the buttons as described previously, select and adjust the values required for the analog output. Both the output value and the display value for that output can be selected. When complete, select NEXT and press ENTER. This will bring up the scaling window for analog output Point 2 which is set as before. When complete, scroll to DONE and press ENTER to return to Menu 1. Analog output #2 is a retransmitted signal and is fixed to the scaling of the analog input. MENU 1 SETPOINTS DIGITAL OUTPUT PROGRAMMING The Myriad RTU has 4 5A SPDT Relay outputs which can be configured to SET (turn on) and RESET (turn off) at a user defined value of the input. From Menu 1 select OUTPUTS and press ENTER.

15 Using the buttons scroll to the value at which the output SETS or turns on, with this value highlighted, use the Up/Down buttons to enter a value of input to activate the output. Scroll down to the RESET point and again change this value to input value which will turn the digital OUTPUT 1 off. NOTE: The internal HORN will sound when the output setpoint is reached. To prevent the horn from sounding, highlight the Y symbol adjacent to the horn symbol and use the Up/Down buttons to change the value to N (NO). This will prevent the horn from sounding when the setpoint is reached. Once all values are selected, scroll to NEXT press ENTER to move to the #2 setpoint screen and proceed as described above. When all setpoints are configured, scroll to EXIT and press ENTER to return to the Main Menu. A second programming menu can be accessed from MENU 1 by selecting NEXT and pressing ENTER. This moves the user to MENU 2. MENU 2 PEAKS The PEAKS feature of the Myriad RTU records the highest and lowest process values of local analog input #1 that have occurred since the last CLR function. With the cursor highlighting PEAKS press the ENTER button to review the PEAK & VALLEY (highest and lowest) values that the Myriad RTU has seen since last reset. MENU 2 SCADA Menu 2 contains a menu item called SCADA. This screen permits adjustment of the parameters affecting communications and general RTU system setup. Use the buttons to highlight the SCADA menu item and press enter. The first parameter is: REMOTE DEC POINT This screen permits a local operator to setup the main screen on the Remote RTU. Setup is identical to that for the local unit (see page 9). Scroll to next and press enter to access the:

16 REMOTE DISPLAY ENGINEERING UNIT Same as main local screen, see example on Page 10. Scroll to next and press enter to access the: ANALOG OUTPUT 1 SOURCE A local unit analog output #1 can be driven from the local units analog input #1 or the remote units analog input #1. With the item highlighted use the buttons to toggle to the desired setup. Select next and then enter to advance to: COMMFAIL OUTPUT If this item is selected to be ON then the local unit solid state output #4 will activate in the case of a communication failure (see introduction). This output will energize if the communication fail counter exceeds it s programmed limit. Use the buttons to toggle this value between ON and OFF. If Off is selected then the local units number 4 solid state output will follow the state of the remote unit s number 4 digital input. Select next and press enter to advance to: SCADA SETTING POLL RATE The factory default poll rate is 60. This setting causes the local RTU to poll the remote RTU once every 60 seconds. This is a safety setting. Data is always updated immediately whenever a process value or status changes. Scroll to next and press enter to access the:

17 SCADA SETTING FAIL LIMIT If the local unit does not detect new data from the remote unit for the duration of the poll rate (previous setting) this will be considered a fault. If this happens more than the number of times defined in the fail limit window (default 3) the commfail output will energize. ONLY WITH COMMFAIL OUTPUT SELECTED TO BE ON. Scroll to next and press enter to access: SCADA SETTINGS NODE NUMBER Either the local RTU or the remote can be node number 1 but the opposite unit must be set to 2 for communication to occur. NOTE: Holding the key and the key at power up sets a unit to NODE 2. NODE 1 is factory default. Select next and press enter to advance to: SCADA SETTINGS CHANGE PASSWORD All access to the programmable functions are password protected. To change the unit s access password, use the Up/Down buttons and enter a new numerical password. CAUTION: ENSURE THAT A RECORD IS KEPT OF THE PROGRAMMED PASSWORD. ACCESS IS RESTRICTED TO ALL PROGRAMMABLE PARAMETERS WITHOUT THE CORRECT PASSWORD. Scroll to exit and press enter to return to the main screen.

18 MENU 2 DIAGNOSTICS Receiving Information from Remote Comm Fail Counter Unit Software Version Transmitting Information to Remote Transmit Buffer is Full This screen will provide useful information regarding the operation of the RTU system. The AI and AO location shows the RAW analog input and output values on this RTU. 400 is approximately 4MA and 2000 is approximately 4.0MA. The IN location shows the status of digital inputs on this RTU. In the example DI #2 and 4 are ON. The OUT location shows the status of the 4 relay outputs. In the example relays 1 and 3 are on. The variables relating to communications are highlighted on the diagram. Press enter to return to the main screen.

19 MAINTENANCE AND TROUBLE SHOOTING MAINTENANCE: The Myriad RTU a digital solid state device which requires no periodic maintenance. Occasional physical checks of the unit should be carried out for physical and mechanical security of mounting, terminal blocks, and electrical wiring. TROUBLE SHOOTING: UNIT LOCKS UP Recycle power to the unit by removing AC power, waiting 10 seconds and reconnecting power. WARNING NOTE: This. should be done by using the user provided circuit breaker or fuse, not by removing the power wires at the terminal block. Serious injury or death can occur if contact is made with the incoming ac power. LCD display goes dim or contrast is poor. Remove power from the unit, release the 2 rear mounting screws and slide the unit forward in it s case approximately 1 inch. On the left side of the circuit board is an adjustable potentiometer. With a small screwdriver adjust this pot to allow alter the contrast to the desired amount. Return the unit to its normal position and secure the rear screws. DISPLAY REMAINS AT ZERO OR SHOWS NO CHANGE -- If the display remains at zero or shows no change but the process is changing, check for D.C. voltage on the loop. With 2 wire (4/20MA) instruments check with a D.C. voltmeter at the level instrument, by disconnecting the level instrument from its terminals (AI1, AIC) and measuring across these terminals with a D.C. voltmeter for the presence of 24VDC. If D.C. voltage is present, reconnect the negative wire of the supply and insert a milliamp meter between the positive wires. The loop should provide a signal between 4 and 20 MA. If no current is present or the current exceeds 20MA consult the level instrument supplier. If D.C. voltage is not present check the user supplied power supply or if using the Myriad supply measure across terminals 24VDC and AIC. If no 24VDC is present consult factory. If 24VDC is present check field wiring between the Myriad and the field device and recheck SCALE functions to ensure correct setup.

20 APPENDIX A SWITCH SELECTION OF ANALOG INPUT RANGES (Factory default 4/20MA). The range dip switches are located on the bottom of the main circuit board. Disconnect power, remove two rear screws, remove terminal strips and slide the entire unit out of its case. Turn the unit upside down to locate the range dip switches. SW1 SW2 INPUT 4 DESCRIPTION 0 0 Ain1 range = 5V 0 1 Ain1 range = 10V 1 0 Ain1 range = 20mA 1 1 Not Used SW3 SW4 DESCRIPTION 0 0 AIn2 range = 5V 0 1 AIn2 range = 10V 1 0 AIn2 range = 20mA 1 1 Not Used SW5 SW6 DESCRIPTION 0 0 AIn3 range = 5V 0 1 AIn3 range = 10V 1 0 AIn3 range = 20mA 1 1 Not Used ON (1) 1 2 3 4 5 6 7 8 EXAMPLE ONLY SW7 SW8 DESCRIPTION 0 0 Ain4 range = 5V 0 1 Ain4 range = 10V 1 0 Ain4 range = 20mA 1 1 Not Used

21 WARRANTY All Sigma Controls, Inc. products are warranted to be free from defective materials and workmanship for one (1) year from date of shipment. Sigma reserves the right to repair or replace at its option any product found to be defective. In no event shall Sigma Controls, Inc. be liable for any consequential, incidental, or special damages and the limit of its liability shall not exceed the purchase price of the supplied equipment. RETURN FOR REPAIR POLICY (WARRANTY/NON-WARRANTY REPAIR) Return status can be determined upon factory inspection of returned equipment. A completed Return Authorization form must accompany all items returned for repair. Repairs will be evaluated as quickly as possible. Cost for nonwarranty repairs will be provided before repairs are initiated and repairs will be completed only after approval by customer. 217 S. Fifth Street, Perkasie, PA 18944 215-257-3412