Product Information SIMATIC S7-300 Digital Output Module SM 322; DO 16 UC24/48 V X 2 as of Version 3 4 New Digital Output Module Available The S7-300 Digital Output Module SM 322; DO 16 UC24/48 V has been added to the S7-300 family. The order number for this module is 6ES7 322-5GH00-0AB0. This product information includes details about the characteristics and technical specifications of the SM 322; DO 16 UC24/48 V digital output module. Refer to the S7-300 Installation and Hardware Manual for more information about the S7-300 product family. You will also learn:! How to configure digital output module SM 322; DO 16 UC24/48 V Additional Assistance For assistance in answering technical questions, for training on this product, or for ordering, contact your Siemens distributor or sales office. Copyright 2002 by Siemens Energy & Automation, Inc.
Characteristic Features and Technical Specifications of the Digital Output Module SM 322; DO 16xUC24/48 V Order No. 6ES7 322-5GH00-0AB0 Characteristic Features The digital output module SM 322; DO 16 UC24/48 V has the following salient characteristic features:! 16 individually isolated solid state relay outputs! Isolation between channels is 120 V! Switch characteristics: R DS ON is typically 0.25 ohms, and R DS OFF is typically better than 100G ohms! Rated for load voltages up to 48 V AC or DC, and there is no minimum load voltage requirement! Rated for output loads up to 1/2 amp, and there is no minimum load current requirement! Outputs are fully independent, and may be connected in any desired configuration! Outputs may be programmed for substitute or hold last values on PLC stop! Module has parameterization fault and external power loss diagnostics! Suitable for AC solenoid valves, contactors, motor starters, fractional h.p. motors and indicator lights. 2
Terminal Connection Diagram and Wiring Diagram Figure 1 shows the terminal connection diagram and the wiring diagram for the Digital Output SM322; DO 16 UC24/48 V The detailed technical specifications for this digital output module are shown on the following page. 0 1 2 3 4 5 6 7 SM322 DO 16xUC24/48V SF 0 1 2 3 4 5 6 7 X 2 3 4 322 5GH00-0AB0 Channel number Status LEDs -green Byte X Byte (X +1) + 24V L+ M 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 5V BACKPLANE BUS 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 Figure 1 Connection Diagram of Digital Output Module SM 322; DO 16 UC24/48 V 3
Hazardous Location Information Power, input and output (I/O) wiring must be in accordance with Class I, Division 2 wiring methods [Article 501-4 (b) of the National Electric Code, NFPA 70] and in accordance with the authority having jurisdiction. Peripheal equipment must be suitable for the location it is used in. The equipment must be suitable for use in Class I, Div. 2, Groups A, B, C, and D Hazardous Locations and nonhazardous locations only.! Warning Explosion Hazard Substitution of components may impair suitability for Class I, Div. 2 Hazardous Locations. Different or lesser quality components may cause an explosion or other hazardous situation, which could result in death or serious injury, and/or damage to equipment. To avoid potentially hazardous situations, always use the appropriate components.! Warning Explosion Hazard Never disconnect equipment before powering off or before ascertaining that the area is nonhazardous. Disconnecting equipment before powering off or in a hazardous area may cause an explosion, which could result in death or serious injury, and/or damage to equipment. To avoid potentially hazardous situations, always power off equipment and assure that the area is nonhazardous before disconnecting. 4
Dimensions and Weight Dimensions W H D Weight Data for Specific Module Number of output points 16 Length of cable! Unshielded! Shielded Voltage, Currents, Potentials Power rated voltage of the electronics L+! Reverse polarity protection! Power failure bypass Total current of the outputs (per group)! Horizontal configuration Up to 60 C! All other mounting positions Up to 40 C Total current of the outputs (per module)! Horizontal configuration Up to 60 C! All other mounting positions Up to 40 C Isolation backplane bus power supply of the electronics! Between the channels In groups of Permitted potential difference backplane bus power supply of the electronics! Between the outputs of different groups 40 125 120mm approx. 260 g max. 600 m max. 1000 m 24 VDC Yes min. 5 ms max. 0.5 A max. 0.5 A max. 8 A max. 8 A Yes Yes Yes 1 170 VDC, 120 VAC 170 VDC, 120 VAC 170 VDC, 120 VAC Voltage, Currents, Potentials (continued) Insulation tested with backplane bus power supply of the electronics! Between the outputs of different groups Current consumption! From the backplane bus! From the power supply L+ Power dissipation of the module Status, Interrupts, Diagnosis Status Display Diagnostics functions! Group error display Interrupts! Diagnostics interrupt! Diagnosis information can be displayed 1500 VAC 1500 VAC 1500 VAC max. 100 ma max. 200 ma typ. 2.8 W Green LEDs per channel Red LED (SF) Parameters can be Assigned Possible 5
Data for Selecting an Actuator Output Voltage! At signal 1 Output Current! At signal 1 Rated value Permitted surge current (per group)! At signal 0 (leakage current) Output delay (for resistive load)! At 0 to 1! At 1 to 0 External fuse for relay outputs Lamp load Contact protection (internal) Connecting two outputs in parallel! For redundant triggering of a load! To increase performance Triggering a digital input Switch rate! For resistive load! For inductive load accordingtoiec 947--5--1 12 DC/12 AC! For lamp load min. L+ (--0.25 V) 0.5 A max. 1.5 A (for 50 ms) max. 10 ua max. 6 ms max. 3 ms safety fuse, I 2 T: 1A 2 sec, fast acting 1 max. 2.5 W Varistor, 85 V Possible Not possible Possible max. 10 Hz max. 0.5 Hz max. 0.5 Hz Note 1 : Outputs must be fused with a 250 V fast acting fuse (Recommended fuses; Wickman 194-1100 1.1 A and Littelfuse 0217-800 V 800 ma). When installed in a Hazardous Location as defined by the National Electric Code, the fuse must be removable only by use of a tool and the area must be determined to be non-hazardous before removal/replacement. 6
Parameters of the Digital Output Module SM322 DO 16xUC24/48 V Parameter Assignment The type ID of the Digital Output Module SM322 DO16xUC24/48 V is >2FD0. Table 1 and Table 2 shows Data Record numbers for static and dynamic parameters. Table 1 Data Record No. 0 (Static Parameters): Parameter Diagnostics enables Comment Enable interrupt when module fails due to parameter error, hardware fault, or power fault Table 2 Data Record No. 1 (Dynamic Parameters): Parameter Behavior on CPU Stop Hold last value Substitute value output Substitute Value Substitute value Comment Each bit corresponds to an output point This module supports fail-state/substitute value outputs when the CPU transitions from RUN-to-STOP. Status Displays This module contains a green LED per output point to indicate the status of the relay. Additionally, there is a red (SF) LED to indicate the diagnosis state of the module. Diagnosis, Error Handling The assignment of the diagnostic data takes place according to the SM S7300/S7400 System Design Specifications and according to the AS-Besy System Design Specifications. The four bytes of system diagnostics data can be read in the interupt supplementary information, as data record 0 or in the first 4 bytes of data record 1. 7
Data Record Structure Read data record 1 is structured according to Table 3. Table 3 Data Record Structure for SM322 DO 16xUC24/48 V Data Record 1 Byte Address Available Information 0..3 System-specific diagnostics data 4bytes 4 Channel type 72h 5 Diagnostics length per channel in bytes 0 6 Number of channels 16 Contents 7 Channel error vector 0 bit per channel 8..15 Channel-specific diagnostics data 0 byte per channel Table 4 shows system diagnostics for the SM322 DO 16xUC24/48 V module. Table 4 System Diagnostics for SM322 DO 16xUC24/48 V System Diagnostics Byte 1: Specification D0: Module fault Yes D1: Internal error Yes D2: External error Yes D3: Channel error present No D4: External auxiliary supply missing Yes D5: Front connector missing No D6: Module not parameterized Yes D7: Incorrect parameters Yes System Diagnostics Byte 2: D0..D3 Module class 1111 D4: Channel information present No D5: User information present No D6: Diagnostics interrupt from the substitute No D7: Reserve System Diagnostics Byte 3: D0: Memory sub module incorrect/missing No D1: Communications fault No D2: RUN/STOP operating state No D3: Watchdog addressed Yes D4: Internal voltage failure No D5: Battery 1 dead No D6: Entire buffer failure No D7: Reserve 8
Table 4 System Diagnostics for SM322 DO 16xUC24/48 V (continued) System Diagnostics Byte 4: Specification D0: Rack failure No D1: Processor failure Yes D2: EPROM error Yes D3: RAM error Yes D4: DAC error No D5: Fuse failure No D6: Process interrupt lost No D7: Reserve Channel-Specific Diagnostic Byte D0: Parameter setting error No D1: Grounding failure No D2: P short-circuit No D3: M short-circuit No D4: Wire break No D5: Reserve D6: Load voltage missing No D7: Over temperature No 9