Awareness of the Situation

Similar documents
Small Generator Interconnection System Impact Study Report. Completed For Q0047

Sacramen Sacr t amen o t Municipal Utility Dis t Dis rict t SMUD May Ma 10,

Generation Interconnection Impact Study Report. For. Interconnection Customer Q0022

Chapter 2 State Estimation and Visualization

Testing of Real Time Power System Control Software

STCP 04-3 Issue 005 Real Time Data Provision

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

Automate and Preserve Electromechanical Relay Investment Part 3 of 3 Using the Bitronics 70 Series to Improve Remote Monitoring and Control

1. Project Description

Lecture 5 Substation Automation Systems. Course map

Amsterdam 27 September 2017 David MacDonald

Automation Services and Solutions

ELG4125: System Protection

Automation in Large Urban Power Distribution System. Dr. K Rajamani CENTRAL TECHNICAL SERVICES, RELIANCE ENERGY LIMITED, MUMBAI

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Using the Bitronics 70 Series to Improve Local Monitoring and Control

Transmission Infrastructure Investment & Development in Vietnam

IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS

Benefits, offering and references

Real Time Monitoring of

Solutions for transmission network management

AUTOMATION OF POWER DISTRIBUTION USING SCADA

MINER-S Station Controller

Smart Distribution Technology

Veesta World Co. V-SCADA2000 Product Series. The cross platform SCADA system

DS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication

Multi-Vendor Data Concentration of 7000 Distribution Devices to Facilitate Asset Optimization

Network Configuration Document Selection for New Substations Framework

Technology Live Workshop

Jehanpour Ranjkesh, Integrator Partner Seminar 2012 Station level product news Automation Controller COM600

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Lecture 6 Substation Automation Systems

Generator Interconnection Impact Study Report Pamlico County, NC 200 MW Wind Farm Queue #281

Data Concentration of 7000 Distribution Devices to Facilitate Asset Optimization with the PI System

POWER SYSTEM SECURITY CONCEPTS

Blueprint Data Center

SWITCHYARD SYSTEM BC1-SS-11-SD TRAINING SYSTEM DESCRIPTION NRG ENERGY, INC. BIG CAJUN 1

Interconnection Feasibility Study Report GIP-IR377-FEAS-R1

IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO

IEEE PES Swiss Chapter Workshop: Microgrids Evolution and Integration in Modern Power Systems

Busbar protection REB 670

Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure

A Current Based, Communication Assisted High Speed Protection System to Limit Arc Energy. Patrick Robinson Altelec Engineering

Automated Approach to Generate Customized Reports Based on Relay Setting Files Stored in a Database

Evolution of Control for the Power Grid

XXXX. Bear Creek Hydro Generation Project. Interconnection Facilities Study

ELECTRICAL, INSTRUMENTATION & CONTROL SYSTEMS

Blackout 101. Dr. B. Don Russell Texas A&M University. Dr. Bruce Wollenberg University of Minnesota. Mr. John McDonald KEMA, Inc.

Configuration and Interoperability Guide for IEC for the SEL-751 Feeder Protection Relay. July 10, 2015

ABB Surge Arresters Contribution to Power Quality Line Side Protection

Grid Automation Controller COM600 How it fits into the Smart Grid?

Making the Right Choices In Lightning & Surge Arrestors Some Basics:

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A

Design Guidelines for SCADA & DSA

IDS SAS. Station Automation System for Complex Applications

IEC Test Equipment Requirements

Advanced Monitoring Solutions for Critical Electric Power Transmission & Distribution Assets

Hybrid STATCOM / SVC Workgroup 15 th May 2014

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

IEC Interoperability Document for:

User Manual. KE-Relay or KD-Relay Profibus DPV0 Communication Module. Page 1 / 18. KE-PROFI-DP0 Version (NE_NC-KE-PROFI-DP0_MAN_01_10_FN04)

IMP/ 001 / 014 Policy for the Protection of Distribution Networks

A Case Study: SCADA Implementation in KPTCL

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

5800 Series Non-IntelliTEAM Universal Automatic Switch Control PG&E SCADA Points List

Bus Bar Protection Relay B-PRO 4000

Landsnet-Icegrid. Requirements for protection and control systems. Principles for the Icelandic power transmission network.

Plats för bild på PST2291 med solpanel och en person

SOUTH TEXAS ELECTRIC COOPERATIVE, INC.

Numerical Protective and Management Relays

DISTRIBUTION FEEDER FAULT ANALYSIS TILLAMOOK PEOPLE S UTILITY DISTRICT

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES

TFS 2100 Traveling Wave Fault Location System

EDS SCADA NUMBERING SYSTEM

Non-conventional instrument transformers Advanced GIS substations with IEC LE process bus

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

March 4, Mona Substation Line position & assoc relaying, communications & metering

TENGIZ PROJECT - FIELD SUBSTATION REPLACEMENT

October 05, ECE 421 Session 12. Utility SCADA and Automation. Presented by: Chris Dyer

SPM Series. Plug-in Surge Protection

Mehta Tech, Inc. TRANSCAN IED For Multi-Function, Multi-Speed Recording

Protection, Automation, and Bay Control System. Advanced feeder protection and complete substation bay control in one economical system

Distribution Substations Relaying

SIGUARD System for Phasor Data Processing

Shabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India

Concept of Automation in Management of Electric Power Systems Richard Joseph, Nerey Mvungi

MV NETWORK AUTOMATION IN THE TOWN OF MILLION - ZAGREB (CROATIA)

MV NETWORK AUTOMATION IN THE TOWN OF MILLION - ZAGREB (CROATIA)

Real-time Power System Operation. Energy Management Systems. Introduction

Concept White Paper. Concepts for Proposed Content of Eventual Standard(s) for Project : Real-Time Monitoring and Analysis Capabilities

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

B O N N E V I L L E A D M I N I S T R A T I O N B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

SCADA Training - T&D Automation

FAULT DETECTION ISOLATION AND RESTORATION ON THE FEEDER (FDIR): PICK YOUR TECHNOLOGY

EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES

NewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application

IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO

PG&E Transmission Interconnection Handbook

DRAFT Risks and Mitigations for Losing EMS Functions

Transcription:

17/11/21 Situational Awareness UPDEA - Workshop Awareness of the Situation 25,623 Alarms in 8 ours 53 Alarms / min (average) 8% Are consequential Things 1 to keep in mind during a disturbance - Analog data is 19 not Feb reported 26 in - time h with - the 8h state am data 9 Controls are issued but the feedback is very slow 8 Control staff are no longer aware of the situation. 7 Communications protocol (IEC687-5-11) 6 SCADA data base design 5 4 DEVICE AMP Z KV MVA MW TAP PANEL 3 2 1 : :34 :59 1:25 1:5 2:15 2:4 3:5 3:31 3:57 4:23 4:48 5:13 5:38 6:3 6:28 6:53 7:18 7:43 1

17/11/21 State Alarming to Process Alarming 4 kv Arnot 4 kv Simplon 22 kv 132 kv 3 MVA in 3 min. 9 7 Customer Items 27 / 15:3: to keep in mind that will ARNOT cause SIMPL2 a blackout: MVA IG 425 42 ALARM The trip limit is 5% above the 9 degree limit. 27 / 16::22 ARNOT SIMPL2 MVA IG ++ 45 44 ALARM Don t have predictive analysis tools No Rate-of-change alarm processing. No consequential analysis warning No warnings of when it could trip. Alarm Questions Customer ow much knowledge do Control Staff have of the situation? Address of a state change there is no context. No information - only data! Why 2 separate messages? Why not 1 message with all the event Information e.g. 27 / 15:3: ARNOT_SIMPL1 - Trip - ARC - Trip, - Main 1, Zone 1, White phase, - Impedance Earth Fault - 35 km from Arnot - Tripped 3 phase - Locked out Permanent Fault - 32 MVA Loss at 42 kv - DR indicates lightning strike on White phase 2

17/11/21 Electricity Production Namibia Botswana Zimbabwe Windhoek T Transmission Gaboronetransports the electricity to Distribution Pretoria Johannesburg South Africa T Maputo Mbabane Swaziland Generation makes the electricity T P Lesotho Distribution then sells the electricity to the customer N Cape Town Electricity production is a continuous process but we do not P monitor it as such. SCADA Master data base SCADA Substation Device Type Device Real Time alarming is done on this side Point Point Analog Analog Counter Power Application Substn (Network Model) CB Line Bus KV XF Un PAS Prediction tools State Estimation Short-circuit analysis Contingency analysis Voltage VAr dispatch Violation alarming is kept on this side X 3

17/11/21 Monitoring Problems Processes are never static - they are always changing Problems : a 2 Rate-of-change b Load / Truck b d a d t 1 Limit Exceeded a Result : We do not predict the future but we can ands up who recognise this. 4

17/11/21 Adding Situational Awareness Reactive Monitor the Rate-of-Change of the Process Variables. Proactive 5 6 minutes Trip Limit igh ++ igh 1. Temperature 2. Megawatts 3. Megavars 4. Kilo Volts Add Consequential Analysis - (New) Combine PAS tool outputs Add predictive warnings to SCADA 2 4 3 Customer 4 1 1 3 Customer Designing for a Disturbance (1) SCADA Master SCADA Master Philosophy Front Ends use the Containerise bay and station substation state to filter data the alarms Messages are automatically suppressed based on bay state Event data from both ends of a line is combined Bay states Station Bay Venus Bay State Substation State VT 1 2 12 4 32 16 12 Substation Philosophy Bays report their state to the station bay following a change The In station classical state systems is a function each of the point bay is and reported busbar states The station bay decides what is sent to the SCADA Master Update individually messages to are the sent SCADA to all bays master. on the same busbar A Dead Bus automatically sets the alarm suppression flag. 1 message is sent to the control staff for dead busses Include the protection, analog data and what happened 5

17/11/21 Summary Change the: Substation data base to Object Oriented structure Master station data base to support Object Orientation Communications protocol to allow for containerisation Allow Ad hoc messages from RTU Dynamic alarm suppression at Master based on bay state Provide Situations Awareness identification areas using colour Consequential Analysis tool to SCADA tool box Protocol Conversion Dual Front End Computers RTU ost I/O X.21 Designing for a Disturbance (2) EMS Back End Computers SCADA Database SCADA Substation philosophy : Each status and analog values is reported individually to the SCADA master The physical bay structure is modelled in SCADA VT 1 2 12 4 32 16 12 Primary Plant input via the RTU 6

17/11/21 SCADA Bay model Master Station Philosophy Each physical Bay is modelled in SCADA including the substation and region bays. All tele-metered state changes are defined as log only. No messages are sent directly to the control staff from the station. All incoming status and analog value are used to update the bay state only. Level 3 : Network and region Modelling Level 2 : Sub-station Modelling The station state is a function of the bays and busbar states. The bays send messages to update the Station bay state. The station object updates the bay states based on the overall station state. Level 1:Bay Modelling Designing for a Disturbance (3) Alarming The station bay sets flags that decides what alarm data is sent to the control staff by the bays. See example on next slide. The station bay generates and sends messages that are common to the station. For local bay events the bay generates and sends bay related messages For line events the alarm data is combined from both bays to create a single line alarm message A Dead Bus automatically sets the alarm suppression flag. All alarm messages include the protection, analog data and explain what happened 7

17/11/21 Primary versus Consequential 8% of alarms are consequential Battery Charger Battery DC Fail condition Battery Fail Alarm (Primary) Bay DC Fail indication Bay 1 (Consequential) Alarm Log Alarm Log 1314 Bay 1 DC Fail Alarm 13h14 1314 Battery Bay DC 2 DC output Fail Alarm fail alarm 1314 Bay 3 DC Fail Alarm Bay 2 System Activity Log Bay 3 1314 Bay 1 DC Fail Alarm 1314 Bay 2 DC Fail Alarm 1314 Bay 3 DC Fail Alarm Summary Change the: Substation data base to Object Oriented structure Master station data base to support Object Orientation Containerisation is performed at the Master Station Allow Bays to generate alarm messages All alarms are defined as log only at Master Provide Situations Awareness identification areas using colour Consequential Analysis tool to SCADA tool box 8

17/11/21 Situational Awareness Problem identification ighlight problem areas in colour on the display Sequential Analysis Rate of change Contingency Analysis VSAT Indicate the cause and effect and number of possible incidents in a possible event Identify time to Trip Identify consequences of Trfr 2 trip and reasons for tripping. Identify local voltage changes and risks Consequential Analysis Identify Time to Trip (Trfr 4) Identify size of Load loss and number of customers affected Adding Situational Awareness Scenario : Trfr 2 has reported an oil temperature high alarm note red line. Since we measure the actual temperature and can predict, based on the current, when the transformer will trip, i.e. how much time we have before it will trip. Contingency Analysis calculated how much load will be carried by transformer 4 if trfr 2 trips. Contingency Analysis also predicts that trfr4 will also trip on overload. We can also predict how long it will take before trfr 4 trip based on the new load, With VSAT we can estimate the resulting voltage collapse risk if both transformers trip. We can also calculate the total load loss and the number of customers that will be affected. 9

17/11/21 1) ighlight problem area in colour on the display 2) Indicate the cause and effect and number of possible incidents in a possible event 3) ighlight second problem area in a different colour. Include time to trip and consequences. Sequence = 2 of 2 Trip Time = + 2 Interruption = 15 + j55 Reason = Amps Customers = 6 VSAT = No threat Sequence = 1 of 2 Trip Time = + Interruption = 76 + j26 Reason = C Customers = VSAT = No threat Questions 1